GT 25 / 40 / 50 / 60 / 75 / 90 / 120A
                                     SOLID STATE RELAYS WITH ANALOG CONTROL




Main applications                                                                          Main features
• Plastics extrusion lines                                                                 • Command input from analogue voltage
  and injection moulding                                                                     or current signal or potentiometer.
  machines                                                                                 • Switching at voltage zero crossing.
• Polymerization plant for                                                                 • Partialization of wave train power with
  synthetic fibre production                                                                 dynamically optimized time cycle.
• Rubber moulding                                                                          • Antiparallel double SCR
  machinery                                                                                • 2 led for supply indication, “ON” state,
• Driers for ceramics and                                                                    1 optional LED for load interrupt alarm
  components for the                                                                       • 4000V isolation between input circuit
  building industries                                                                        and power output
• Chemical and                                                                             • MOV (varistor)
  pharmaceutical industries                                                                • Optional monitoring of interrupted load
• Industrial electric furnaces                                                             • DIN rail mounting (standard);
• Food processing plants                                                                     Panel mounting (optional)



PROFILE                                      is settable with trimmer and yellow LED       TECHNICAL DATA
The GT family of solid-state relays has      signal, with voltage-free contact, normally
been designed with the aim of providing      open.                                         General features
very accurate control of the load thanks     The GT solid-state relay has a green          Category of use AC1
to an analog control input, in voltage at    LED to indicate the presence of the           Nominal voltage
0…5V; 0…10V or in current at                 24Vac power supply and a red LED to           - 480Vac (max. range 24...530Vac)
0…20/4…20mA or a potentiometer (from         indicate the switching based on the           Nominal frequency: 50/60Hz
1KΩ to 10 KΩ).                               analog control input signal.
                                                                                           Non-repetitive voltage: 1200Vp
                                                                                           Zero switching voltage: ≤ 20V
The electronic design ensures that the       The LED signal will be continuous (off at
                                                                                           Voltage drop at nominal current ≤
cycle time for proportioning the power is    minimum, on at maximum) at the ends of        1.4Vrms
automatically optimized.                     the scale, pulsing for intermediate           Power factor = 1
Il numero di periodi che il GT fornisce al   values.
carico (“treni d’ onda”) per un certo        The units offer optional accessoires for      Control inputs
valore di segnale di ingresso, è calcolato   panel mounting, fuses and fuseholders,
in modo da essere il minimo possibile,       current transformer, isolation                Voltage: 0...5Vdc, 0...10Vdc
pur mantenendo la precisione                 transformers.                                 (impedance ≥100KΩ)
necessaria.                                  Use the relè with an opportune heatsink       Current: 0...20mA, 4...20mA
The number of cycles that the GT             (see section accessories).                    (impedance 125Ω)
supplies to the load (wave trains) for a                                                   Potentiometer: da1K a 10KΩ
given input signal is calculated to be the                                                 (auto-fed by GT)
minimum possible to maintain the
necessary accuracy.                                                                        OUTPUTS
The GT can be used in three phase
systems, using master-slave control                                                        GT 25 (SCR version)
architecture in which the control signal                                                   Nominal currents of the device with
drives only one GT (master) and this unit
                                                                                           opportune heatsink in continuous
                                                                                           work: 25A
supplies the synchronized signals to the
                                                                                           Non-repetitive overcurrent t=20 ms:
other slaves. Two GS modules can also                                                      400A
be used as slaves (logic control).                                                         I2t for blowout: ≤ 645A2s
A load interrupt control option (HB) is                                                    dV/dt critical with output deactivated:
available without having to use an                                                         1000V/µs
external current transformer; alarm limit
GT 40 (SCR version)                       Options:                                 Installation notes
Nominal currents of the device with       Interrupted HB load alarm.               - The heat sink must be grounded.
opportune heatsink in continuous          Controls the load by measuring           - The device must be protected by an
work: 40A                                 current on a shunt inside the device.    appropriate high-speed fuse (accessory).
Non-repetitive overcurrent t=20 ms:       The alarm limit is set with a multirev   - Protect the solid state relay by using an
600A                                      monorev trimmer.                         appropriate heat sink (accessory).
I2t for blowout: ≤ 1010A2s
                                          The alarm output is obtained by          The heat sink must be sized according to
dV/dt critical with output deactivated:
1000V/µs                                  means of a solid state relay.            room temperature and load current (see
                                          The contact is normally open (max.       the technical documentation).
GT 50 (SCR version)                       30V, 150mA, conduction resistance        - Procedure for mounting on heat sink:
Nominal currents of the device with       15Ω).                                    The module-heat sink contact surface
opportune heatsink in continuous                                                   must have a maximum planarity error of
work: 50A                                 Thermal features                         0.05mm. and maximum roughness of
Non-repetitive overcurrent t=20 ms:                                                0.02mm. The fastening holes on the
                                          GT 25
1150A                                     Junction temperature:    ≤ 125°C         heat sink must be threaded and counter-
I2t for blowout: ≤ 6600A2s                Rth junction/case:       ≤ 1.25 K/W      sunk.
dV/dt critical with output deactivated:   Rth junction/ambient:    ≤ 12 K/W        Attention: spread 1 gram of
1000V/µs                                                                           thermoconductive silicone (we
                                          GT 40
                                          Junction temperature:    ≤ 125°C         recommend DOW CORNING 340
GT 60 (SCR version)
Nominal currents of the device with       Rth junction/case:       ≤ 0.65 K/W      HeatSink) on the dissipative metal
                                          Rth junction/ambient:    ≤ 12 K/W        surface of the module.
opportune heatsink in continuous
work: 60A                                                                          The surfaces must be clean and there
                                          GT 50
Non-repetitive overcurrent t=20 ms:                                                must be no impurities in the
                                          Junction temperature:    ≤ 125°C
1150A                                     Rth junction/case:       ≤ 0.35 K/W      thermoconductive paste.
I2t for blowout: ≤ 6600A2s                Rth junction/ambient:    ≤ 12 K/W        Alternately tighten the two fastening
dV/dt critical with output deactivated:                                            screws until reaching a torque of 0.60
1000V/µs                                  GT 60                                    Nm for the M4 screws and 0.75 Nm for
                                          Junction temperature:    ≤ 125°C
                                          Rth junction/case:       ≤ 0.35 K/W      the M5 screws.
GT 75 (SCR version)                       Rth junction/ambient:    ≤ 12 K/W        Wait 30 minutes for any excess paste to
Nominal currents of the device with                                                drain.
opportune heatsink in continuous          GT 75                                    Alternately tighten the two fastening
work: 75A                                 Junction temperature:    ≤ 125°C
                                                                                   screws until reaching a torque of 1.2 Nm
Non-repetitive overcurrent t=20 ms:       Rth junction/case:       ≤ 0.3 K/W
                                          Rth junction/ambient:    ≤ 12 K/W        for the M4 screws and 1.5 Nm for the M5
1300A
I2t for blowout: ≤ 8000A2s                                                         screws.
                                          GT 90                                    We advise you to randomly check for
dV/dt critical with output deactivated:
                                          Junction temperature:    ≤ 125°C         proper installation by dismantling the
1000V/µs                                  Rth junction/case:       ≤ 0.3 K/W
                                          Rth junction/ambient:    ≤ 12 K/W        module to make sure there are no air
GT 90 (SCR version)                                                                bubbles under the copper plate.
Nominal currents of the device with       GT 120
opportune heatsink in continuous          Junction temperature:    ≤ 125°C         Limits of use
work: 90A                                 Rth junction/case:       ≤ 0.25 K/W      • dissipation of thermal power of device
Non-repetitive overcurrent t=20 ms:       Rth junction/ambient:    ≤ 12 K/W        with restrictions on temperature of
1500A                                     Solid State Relay Dissipated Power       installation site.
I2t for blowout: ≤ 11200A2s               Calculation                              • requires exchange with outside air
dV/dt critical with output deactivated:   Singol-phase static relay                or an air conditioner to transfer
1000V/µs                                  Pds = 1.4 * IRMS [W]                     dissipated power outside the panel.
                                          IRMS = singol phase load current         • installation restrictions (distances
GT 120 (SCR version)                                                               between devices to guarantee dissipation
Nominal currents of the device with       Heatsink thermal resistance
                                          Calculation                              by natural convection).
opportune heatsink in continuous
                                          Rth = (90°C - T.amb. max) / Pd           • max. voltage limits and derivative
work: 120A (complete with fan and
standard thermostat).                     where Pd = dissipated power              of transients in line, for which the
Non-repetitive overcurrent t=20 ms:       T.amb.max = max air temperature inside   solid state unit has internal protection
1500A                                     the electrical cabinet.                  devices (depending on model).
I2t for blowout: ≤ 11200A2s               Use a heatsink with thermal resistance   • presence of dispersion current
dV/dt critical with output deactivated:   inferior to the calculated one (Rth).    < 3mA for SCR version GS
1000V/µs                                                                           < 4mA for TRIAC version GS
                                          Ambient conditions                        (max. value with rated voltage
Isolation                                 • Working temperature: 0 to 80°C.        and junction temperature of 125°C).
Rated isolation voltage input/output:     • Max. relative humidity: 50% at 40°C
4000Vac                                   • Max. installation altitude:
                                            2000m asl
Power supply:                             • Pollution level: 3
24Vac ±10%, 50/60 Hz                      • Storage temperature: -20..85°C
Absorption: 1.5VA
Max. isolation voltage: 300Vdc
WORKING TYPOOLOGY

 “Zero crossing” with variable cycle time

 Examples of the operation of the GT for different values of the input drive signal and the consequent different cycle times
 (100msec and 40msec respectively).


                        Example of input at 20% = 2V (IN 0-10V) or 4mA (IN 0-20mA)
             V
                        V=Voltage across load




                                                 100msec




                        Logic output control for GT


             V          Example of input at 50% = 5V (IN 0-10V) or 10mA (IN 0-20mA)
                        V=Voltage across load




                             40msec




 GT thermal protection



                            Control
                            input
                                    ON
                                 OFF
                                                                                             t

                                           Red LED       Red LED
                                           ON            Thermal alarm

                                                                                             t
                                                V = Load voltage




                                                                                             t

                                                       Thermal protection
                                                       activation
FACEPLATE DESCRIPTION


                                Synchronism signal for             - control signal
                                Master/Slave connection                 + control signal
                                          Alarm output                       Reference voltage for potentiometer power supply (+ 10V)
                         (solid state relay, HB option)
                                                                                      24 Vac 50/60 Hz power terminal




                   Green LED (power on),
                   Red LED (GT running)
                                                    a
    Red LED (thermal alarm), yellow LED
         (load interrupt alarm, HB option)
                                                    b
            Monorev trimmer for minimum             c                                            Dip switch for selection of input signal
                calibration of input signal                                                      (S1, S2, S3)
                                                             d e         f
  Monorev trimmer for calibration of load
               interrupt (HB) alarm limit           g                                            Monorev trimmer for maximum
                                                                                                 calibration of load signal

                           LINE connection                                                       LOAD connection




              Reference connection of 230V line voltage                        Reference connection of 480V line voltage (HB option
                    (HB option with 150V to 300V load)                         with 300V to 530V load)




CALIBRATION PROCEDURE OF THE INPUT SIGNAL

 The solid-state power unit, Gt, is supplied factory calibrated for 0..5V, 0..10V, 0..20mA, 4..20mA, 10Kohm potentiometer.
 Minimum and maximum values are adjusted with two monorev trimmers (d,e).
 Input signal type is selected with the adjustment f dip switches (S1,S2,S3).



              Control signal                 Dip Switch Position
                                                                         e            V/mA           V/mA         f       Rin
                                                                                      In             In          S1-S3
                                          S1            S2     S3            96%                           On
                                                                                                    0-5V                 100KΩ
                                                                             82%                           Off
              0...5Vdc                   OFF         OFF       ON
                                                                                                    0-10V                100KΩ
              0...10Vdc                   ON         OFF       ON
                                                                         d                          0-20mA               125Ω
              0...20mA                   OFF         ON        ON            18%
                                                                             4%                     4-20mA
              4...20mA                   OFF         ON       OFF                                                        125Ω
                                                                                             T




 Minimum adjustment trimmer (d) turned fully counterclockwise sets the start conducting limit at 4% of the signal; turned fully
 clockwise, the minimum conducting limit is set at 18% of the input signal.
 Maximum adjustment trimmer (e) turned fully clockwise sets the full conducting limit at 96% of the signal; turned fully
 counterclockwise, the full conducting limit is set at 82% of the input signal.
CALIBRATION PROCEDURE OF THE INTERRUPTED LOAD ALARM

The interrupted load alarm function enables the GT to diagnose a variation of the load current (compared to a set limit),
distinguishing it from one caused by a change in grid voltage. You therefore have to bring the grid voltage to the appropriate
terminals ("h" for 150V to 300V, "i" for 300-530 V).
The alarm activates (relay closed and yellow alarm LED on) when the current, during the conduction of the device, falls below
a preset level that may be adjusted using the trimmer on the faceplate.

Calibration procedure (refer to the faceplate description drawing)
1) Use the adjustment system (or a calibrator) in order to supply the maximum signal (100% conduction or thered “ON” LED
    always illuminated). As an alternative, you can configure the GT to 0-10 V DC input configuration and connect terminals 5
    and 6.
2) Use a current sensing pliers to check that the load current is at rated level.
3) Turn alarm limit adjustment trimmer (g) fully clockwise. Check that yellow alarm LED (b) turns on.
4) Slowly turn trimmer (g) counterclockwise until the alarm LED turns off.
5) Turn the trimmer counterclockwise another 1/10 of a turn (1 notch on the scale).
   In this way, the alarm limit is set below 10% of the rated load current.

N.B:
the partial load break alarm function operates with power partialization exceeding 15%. For partializations below 20%, tripping
times increase due to the reduced load activation time. For correct operation of the option, the load current has to exceed 30%
of rated current for the GT.




Notes on use of the GT with the digital On/Off control

- The logic control signal has to be connected with the correct polarities to terminals 4 and 5 of the analog input.
- Turn minimum adjustment trimmer (d) fully counterclockwise and maximum adjustment trimmer (e) fully clockwise.
- Set the 3 dip switches (f) to off.




For applications with a very short work cycle, you can drive the solid state group by means of the Master/Slave signal by
driving it with a digital signal (OFF = 0 V dc; ON = from 4 V dc to 10 V dc)




Inhibiting the GT

You can inhibit operation of the GT by means of the Master/Slave signal.
To inhibit, connect control signal - (4) with the synchronism signal for Master/Slave connection (3).




Notes on use of the GT in Master/Slave configuration

The GT can be used as a master to drive other solid state groups (slaves). With Master/Slave signal (3), you can drive up to 9
GTs (see connection examples for GT solid state power relays with three-phase load). You can also use a GT to drive GS solid
state power relays (maximum of 2), as shown in the connection diagrams for GT/GS solid state power relays with three-phase
load (attention: the HB option cannot be used for a three-phase application with neutral).
DIMENSIONS AND CUT-OUT

                                             GT 25 - 40 - 50 - 60 - 75 - 90 - 120A

                                                                  60 mm




                                              L2              i                 h         L1
                                             Load          Line                Line      Line
                                                          480 V               230 V

                                                               0..10V
                                                                                g Alarm Adj
                                                                                f Input selection
                                                                0..5V
                                                                                e Max Adj
                                                              4..20mA           d Min Adj
                                                              0..20mA           c Reset Alarm


                                                                                                         Accessory LAB-1

                                                          GT 25A/480 Vac
                      100mm




                                                              AC1 50/60 Hz




                                                                              AL

                                                                        PWR                  ON


                                                                    Analog                   Alarm
                                                                     Input      Master        Out
                                             24 Vac     +10 Vdc
                                             Supply       Out                   Slave    30 Vdc/ac

                                         8          7     6        5      4        3     2       1


Depth 34 mm.   Weight 200gr.

 TEMPLATE DIMENSIONS


                                                                  60 mm
                               26 mm
                               47.5 mm




                                                                                                     100 mm
CONNECTION EXAMPLES

 Single-phase connection with optional monitoring of interrupted load (command input from analog signal or potentiometer)

                 Ground


                 Neutral
                 Phase




                                                                                                Load




                                                                                                                                                                                               Fuse
                                                                                                            L2                         i                           h                L1
                                                                                                           Load                Line                               Line             Line
                                                                                                                              480 V                              230 V

                                                                                                                                       0..10V
                                                                                                                                                                   g Alarm Adj
                                                                                                                                                                   f Input selection
                                                                                                                                       0..5V
                                                                                                                                                                   e Max Adj
                                                                                                                                  4..20mA                          d Min Adj
                                                                                                                                  0..20mA                          c Reset Alarm




                                                                                                                                      GT 25A/480 Vac
                                                                                                                                           AC1 50/60 Hz




                                                                       24Vac 1,5VA
                       Controller
                                                                                                                                                             AL
      Digital output
            0-20mA                                                                                                                                      PWR                            ON

            4-20mA
           0-10Vdc                                                                                         24 Vac           +10 Vdc
                                                                                                                                                Analog
                                                                                                                                                 Input             Master
                                                                                                                                                                   Slave
                                                                                                                                                                                       Alarm
                                                                                                                                                                                        Out
                                                                                                           Supply             Out                                                  30 Vdc/ac
             0-5Vdc                                                                                    8            7         6                 5        4             3           2       1




                                                                                                                                                                                                                                       Relay output - Alarm
                                                       Potentiometer                                                                                                                                                                   (solid state relay)




 Star or delta three-phase connection without neutral, with control of two phases.

                            Phase R
                            Phase S
                            Phase T

                            Ground
                                                                                                                                                                                Fuse




                                                                                                                                                                                                                                                             Fuse




                                          Star connection              Three-phase connection
                                                                                                                    L2              i                     h           L1                              L2              i                 h           L1
                                                                                                                   Load          Line                    Line       Line                             Load          Line                Line       Line
                                                                                                                                480 V                   230 V                                                     480 V               230 V


                                                                                                                                       0..10V
                                                                                                                                                          g Alarm Adj                                                  0..10V
                                                                                                                                                                                                                                         g Alarm Adj
                                                                                                                                                          f Input selection                                                              f Input selection
                                                                                                                                        0..5V                                                                           0..5V
                                                                                                                                                          e Max Adj                                                                      e Max Adj
                                                                                                                                      4..20mA             d Min Adj                                                   4..20mA            d Min Adj
                                                                                                                                      0..20mA             c Reset Alarm                                               0..20mA            c Reset Alarm




                                                                                                                                      GT 25A/480 Vac                                                                  GT 25A/480 Vac
                                                                                                                                        AC1 50/60 Hz                                                                      AC1 50/60 Hz




                                                                                  24Vac 1,5VA                                                           AL                                                                            AL

                                                                                                                                                    PWR                 ON                                                       PWR                  ON
                                                   Controller
                                                                                                                                            Analog                      Alarm                                                Analog                   Alarm
                                                                                                                                             Input        Master         Out                                                  Input      Master        Out
                                                                                                                   24 Vac     +10 Vdc                                                                24 Vac     +10 Vdc
                                                                                                                   Supply       Out                       Slave        30 Vdc/ac                     Supply       Out                    Slave    30 Vdc/ac

                                                                                                               8          7       6        5        4        3      2       1                    8          7     6         5     4        3      2      1




                                      Digital output
                                            0-20mA                     Potentiometer
                                            4-20mA
                                           0-10Vdc
                                             0-5Vdc



                                                       Relay output - Alarm
                                                       (Solid state relay)
CONNECTION EXAMPLES

 Three-phase star connection with neutral.
                 Phase R

                 Phase S

                 Phase T

                 Neutral


                 Ground




                                                                                                                                           Fuse




                                                                                                                                                                                                                                                        Fuse




                                                                                                                                                                                                                                                                                                                                               Fuse
                                                                                     L2               i                   h          L1                                               L2                     i                       h            L1                                 L2               i                       h          L1
                                                                                    Load          Line                   Line      Line                                              Load                Line                       Line        Line                                Load          Line                       Line      Line
                                                                                                 480 V                  230 V                                                                           480 V                      230 V                                                         480 V                      230 V


                                                                                                      0..10V
                                                                                                                          g Alarm Adj                                                                        0..10V                     g Alarm Adj                                                   0..10V
                                                                                                                                                                                                                                                                                                                              g Alarm Adj
                                                                                                                          f Input selection                                                                                             f Input selection                                                                     f Input selection
                                                                                                       0..5V                                                                                                  0..5V                                                                                    0..5V
                                                                                                                          e Max Adj                                                                                                     e Max Adj                                                                             e Max Adj
                                                                                                     4..20mA              d Min Adj                                                                         4..20mA
                                                                                                                                                                                                                                        d Min Adj                                                    4..20mA                  d Min Adj
                                                                                                     0..20mA              c Reset Alarm                                                                     0..20mA                     c Reset Alarm                                                0..20mA                  c Reset Alarm




                                                                                                     GT 25A/480 Vac                                                                                         GT 25A/480 Vac                                                                           GT 25A/480 Vac
                                                                                                          AC1 50/60 Hz                                                                                           AC1 50/60 Hz                                                                     Carico  AC1 50/60 Hz




                                                              24Vac 1,5VA                                               AL                                                                                                         AL                                                                                       AL

                                                                                                                   PWR                 ON                                                                                 PWR                       ON                                                             PWR                     ON
                           Controller
                                                                                                               Analog                  Alarm                                                                          Analog                        Alarm                                                      Analog                      Alarm
                                                                                                                          Master        Out                                       24 Vac                                             Master          Out                         24 Vac                                       Master        Out
                                                                                    24 Vac     +10 Vdc          Input                                                                               +10 Vdc            Input                                                                   +10 Vdc          Input
                                                                                                                                                                                  Supply                                                                                         Supply
                                                                                    Supply       Out                      Slave    30 Vdc/ac                                                          Out                            Slave       30 Vdc/ac                                       Out                          Slave    30 Vdc/ac

                                                                                8          7     6         5        4        3     2       1                                     8          7           6         5            4        3       2       1                       8          7     6         5            4        3     2       1




              Digital output
                    0-20mA                        Potentiometer
                    4-20mA
                   0-10Vdc
                     0-5Vdc



                               Relay output - Alarm
                               (solid state relay)


 Three-phase connection (triangle or star) without neutral, with control of two phases using one GT in Master configuration
 and one GS in Slave configuration.


                    Phase R
                    Phase S

                    Phase T

                    Ground
                                                                                                                                                                                                                             Fuse



                                                                                                                                                                                                                                                                    Fuse




                                  Star connection                 Three-phase connection
                                                                                                                                                    L2                 i                        h                  L1
                                                                                                                                                   Load                                                          Line                                        Line                                    Load
                                                                                                                                                                   Line                      Line
                                                                                                                                                                  480 V                     230 V


                                                                                                                                                                       0..10V
                                                                                                                                                                                                g Alarm Adj
                                                                                                                                                                                                f Input selection
                                                                                                                                                                        0..5V
                                                                                                                                                                                                e Max Adj
                                                                                                                                                                      4..20mA                   d Min Adj
                                                                                                                                                                      0..20mA                   c Reset Alarm




                                                                                                                                                                      GT 50A/480 Vac                                                                                       GS 50A/480 Vac
                                                                                                                                                                                                                                                                             AC1 50/60 Hz
                                                                                                                                                                           AC1 50/60 Hz




                                                                              24Vac 1,5VA                                                                                                  AL                                                                                          AL

                                                                                                                                                                                                                                                                                       ON
                                                 Controller                                                                                                                           PWR                            ON


                                Digital output                                                                                                     24 Vac
                                                                                                                                                   Supply
                                                                                                                                                                +10 Vdc
                                                                                                                                                                  Out
                                                                                                                                                                                Analog
                                                                                                                                                                                 Input          Master
                                                                                                                                                                                                Slave
                                                                                                                                                                                                                     Alarm
                                                                                                                                                                                                                      Out
                                                                                                                                                                                                                  30 Vdc/ac
                                                                                                                                                                                                                                                                                       6÷32Vcc
                                                                                                                                                                                                                                                                                       ON/OFF Control

                                      0-20mA                                                                                                   8            7     6         5          4            3            2        1


                                      4-20mA
                                     0-10Vdc
                                       0-5Vdc                       Potentiometer




                                                    Relay output - Alarm
                                                    (solid state relay)
CONNECTION EXAMPLES

  Three-phase star connection with neutral using one GT in Master configuration and two GSs in Slave configuration.



            Phase R
            Phase S

            Phase T

            Neutral


            Ground




                                               Load




                                                                                                                                   Fuse




                                                                                                                                            Fuse




                                                                                                                                                                                Fuse
                                                                             L2                i                   h          L1
                                                                            Load                                            Line          Line                       Load      Line                      Load
                                                                                            Line                  Line
                                                                                           480 V                 230 V

                                                                                               0..10V
                                                                                                                   g Alarm Adj
                                                                                                                   f Input selection
                                                                                                0..5V
                                                                                                                   e Max Adj
                                                                                              4..20mA              d Min Adj
                                                                                              0..20mA              c Reset Alarm




                                                                                                                                                   GS 50A/480 Vac                      GS 50A/480 Vac
                                                                                              GT 50A/480 Vac
                                                                                                                                                    AC1 50/60 Hz                         AC1 50/60 Hz
                                                                                                   AC1 50/60 Hz




                                                       24Vac 1,5VA                                               AL                                          AL                                  AL

                                                                                                            PWR                 ON                           ON                                  ON
                          Controller
                                                                                                        Analog                  Alarm
                                                                                                         Input     Master        Out                          6÷32Vcc                             6÷32Vcc
                                                                            24 Vac       +10 Vdc
                                                                                                                   Slave                                      ON/OFF Control                      ON/OFF Control
         Digital output                                                 8
                                                                            Supply
                                                                                     7    6
                                                                                           Out
                                                                                                    5       4         3
                                                                                                                            30 Vdc/ac

                                                                                                                            2      1

               0-20mA
               4-20mA
              0-10Vdc
                0-5Vdc                 Potentiometer




TABLE OF TERMINALS AND CONDUCTORS

                          CONTROL TERMINAL                                                                       POWER TERMINAL                                                       GROUND TERMINAL •

         Contact Type of pre-               Max section. ** Contact Type of pre-                                                                   Max section. **               Contact                           Max section. **
Size     area       isolated terminal        conductor      area       isolated terminal                                                           conductor                     area                               conductor
          (WxD)                              tightening      (WxD)                                                                                 tightening                     (WxD)                             tightening
         screw type                            torque       screw type                                                                               torque                      screw type                           torque
25/40A   6,3x9            Eye/fork              2.5mm2               16x18                         Eye/fork                                                  50mm2             14x16                             50mm2
50/60A    M3              tip                0.6Nm Max                M6                                                                                    3.5-6 Nm            M5                           1.8-2.5Nm
75-90A   6,3x9            Eye/fork              2.5mm2               16x18                         Eye/fork                                                  50mm2             14x16                            50mm2
          M3              tip                0.6Nm Max                M6                                                                                    3.5-6 Nm            M5                            1.8-2.5 Nm
120A     6,3x9            Eye/fork              2.5mm2               16x18                         Eye/fork                                                  50mm2             14x16                            50mm2
          M3              tip                0.6Nm Max                M6                                                                                    3.5-6 Nm            M5                            1.8-2.5 Nm

(**) The max. sections specified refer to unipolar copper wires isolated in PVC.
• Note: For the ground terminal, you have to use an eye wire terminal.
    (WxD) = Width x depth



ACCESSORIES


 A wide range of accessories is available (including fuses and fuse holders, supports for fastening DIN bar, ID
 plates, thermostats, current transformers and isolation transformers). To choose accessories, see the section
 "Solid state relays - Accessories."
ORDER CODE

                                                         GT                           /       480       -


             Model
                                     GT


             Nominal current
             25Aac                  25
             40Aac                  40
             50Aac                  50
             60Aac                  60
            75Aac                   75
             90Aac                  90
            120Aac                  120



             Nominal voltage
             480Vac                 480


             Load interrupt
             (HB) option
             Without option           0
             With load
                                      1
             interrupt option




           Please contact GEFRAN personnel for information on availability of codes.

                                                                               •WARNINGS


      !      WARNING: this symbol indicates danger.
 Before installation, please read the following advices:
 • follow the indications of the manual scrupulously when making the connections to the instrument.
 • use a cable that is suitable for the ratings of voltage and current indicated in the technical specifications.
 • if the instrument is used in applications where there is risk of injury to persons and damage to machines or materials, it is essential that it is used with
 an auxiliary alarm device.
 It is advisable to verify frequently that the alarm device is functional even during the normal operation of the equipment.
 • The instrument must NOT be used in environments where there could be the presence of dangerous atmospheres (inflammable or explosive).
 • During continuous operation, the heatsink may reach 100°C and remain at a high temperature due to thermal inertia even after the device is switched
 off. Therefore, DO NOT touch the heat sink or the electrical wires.
 • do not operate on the power circuit untless the main supply is disconnected.
 • DO NOT open the cover if device is “ON”!
 (use the holes in the cover for eventual re-calibration).
 Installation:
 • connect the device to the ground using the proper ground terminal.
 • the power supply wiring must be kept separate from that of inputs and outputs of the instrument; always check that the supply voltage corresponds to
 that indicated on the instrument cover.
 • evitare la polvere, l’ umidità, i gas corrosivi, le fonti di calore.
 • keep away from dust, humidity, corrosive gases and heat sources.
 • The connection cable must be shorter than 3 meters if the current transformer is used.
 Maintenance: Check the correct operation of the cooling fans at regular intervals; clean the ventilation air filters of the installation at regular intervals.
 • Repairs must be performed only by specialized or appropriately trained personnel. Cut off power to the device before accessing internal parts.
 • Do not clean the box with solvents derived from hydrocarbons (trichloroethylene, gasoline, etc.). Using such solvents will compromise the mechanical
 reliability of the device. To clean external plastic parts, use a clean cloth wet with ethyl alcohol or water.
 Technical service : GEFRAN has a technical service department. Defects caused by use not conforming to the instructions are excluded from the
 warranty.


GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice


               In conformity to ECC 89/336/CEE and 73/23/CEE with reference to standards:
               CEI-EN 61000-6-2 (immunity in industrial enviroment)- EN 50081-1 (emission in residential enviroment) - CEI 17-38 and further modification




                                 GEFRAN spa via Sebina, 74 - 25050 Provaglio d’Iseo (BS)
                                 Tel. 03098881 - fax 0309839063 - Internet: http://www.gefran.it                                                 cod. GT - 09/03

More Related Content

What's hot

Datasheet sensor temperatura mcp9700
Datasheet sensor temperatura mcp9700Datasheet sensor temperatura mcp9700
Datasheet sensor temperatura mcp9700ADELIUS
 
High Precision ADC Display
High Precision ADC DisplayHigh Precision ADC Display
High Precision ADC Displaysaneeshforu
 
Cataloge schneider contactor ct-dienhathe.vn
Cataloge schneider contactor ct-dienhathe.vnCataloge schneider contactor ct-dienhathe.vn
Cataloge schneider contactor ct-dienhathe.vnDien Ha The
 
Advanced motion controls az10a20ddc
Advanced motion controls az10a20ddcAdvanced motion controls az10a20ddc
Advanced motion controls az10a20ddcElectromate
 
244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdfBarlomax
 
ELECTRICAL PROJECT ABSTRACT-Embedded pic microcontroller based motor protecti...
ELECTRICAL PROJECT ABSTRACT-Embedded pic microcontroller based motor protecti...ELECTRICAL PROJECT ABSTRACT-Embedded pic microcontroller based motor protecti...
ELECTRICAL PROJECT ABSTRACT-Embedded pic microcontroller based motor protecti...ASHOKKUMAR RAMAR
 

What's hot (16)

Lpc662
Lpc662Lpc662
Lpc662
 
Ua741
Ua741Ua741
Ua741
 
Datasheet sensor temperatura mcp9700
Datasheet sensor temperatura mcp9700Datasheet sensor temperatura mcp9700
Datasheet sensor temperatura mcp9700
 
High Precision ADC Display
High Precision ADC DisplayHigh Precision ADC Display
High Precision ADC Display
 
Triac 2 n6073a
Triac 2 n6073aTriac 2 n6073a
Triac 2 n6073a
 
Cataloge schneider contactor ct-dienhathe.vn
Cataloge schneider contactor ct-dienhathe.vnCataloge schneider contactor ct-dienhathe.vn
Cataloge schneider contactor ct-dienhathe.vn
 
Datasheet 3
Datasheet 3Datasheet 3
Datasheet 3
 
Advanced motion controls az10a20ddc
Advanced motion controls az10a20ddcAdvanced motion controls az10a20ddc
Advanced motion controls az10a20ddc
 
244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf
 
Acs712
Acs712Acs712
Acs712
 
Tle4904 343973
Tle4904 343973Tle4904 343973
Tle4904 343973
 
P700; 75-150A Programmable Power Controller
P700; 75-150A Programmable Power ControllerP700; 75-150A Programmable Power Controller
P700; 75-150A Programmable Power Controller
 
ELECTRICAL PROJECT ABSTRACT-Embedded pic microcontroller based motor protecti...
ELECTRICAL PROJECT ABSTRACT-Embedded pic microcontroller based motor protecti...ELECTRICAL PROJECT ABSTRACT-Embedded pic microcontroller based motor protecti...
ELECTRICAL PROJECT ABSTRACT-Embedded pic microcontroller based motor protecti...
 
Datasheet of TPC8014
Datasheet of TPC8014Datasheet of TPC8014
Datasheet of TPC8014
 
1 n4148 1n4448
1 n4148 1n44481 n4148 1n4448
1 n4148 1n4448
 
acarlen
acarlenacarlen
acarlen
 

Similar to DC 340 HS Compound Reco in relays - Project Sales Corp

Dold earth leakage indicator
Dold earth leakage indicatorDold earth leakage indicator
Dold earth leakage indicatorSony Gunawan
 
Dold earth leakage indicator
Dold earth leakage indicatorDold earth leakage indicator
Dold earth leakage indicatorSony Gunawan
 
Advanced motion controls azbh40a8
Advanced motion controls azbh40a8Advanced motion controls azbh40a8
Advanced motion controls azbh40a8Electromate
 
Advanced motion controls azxb25a8
Advanced motion controls azxb25a8Advanced motion controls azxb25a8
Advanced motion controls azxb25a8Electromate
 
Advanced motion controls azxbe6c20
Advanced motion controls azxbe6c20Advanced motion controls azxbe6c20
Advanced motion controls azxbe6c20Electromate
 
K49 Controller
K49 ControllerK49 Controller
K49 ControllerJoseph
 
Cdvr service manual renr7941-00 _ sis - caterpillar
Cdvr   service manual   renr7941-00 _ sis - caterpillarCdvr   service manual   renr7941-00 _ sis - caterpillar
Cdvr service manual renr7941-00 _ sis - caterpillarOtorongosabroso
 
IGBT Based Static Voltage Regulator
IGBT Based Static Voltage RegulatorIGBT Based Static Voltage Regulator
IGBT Based Static Voltage RegulatorKirk Patel
 
Advanced motion controls zb6a6
Advanced motion controls zb6a6Advanced motion controls zb6a6
Advanced motion controls zb6a6Electromate
 
Advanced motion controls azxb8a8
Advanced motion controls azxb8a8Advanced motion controls azxb8a8
Advanced motion controls azxb8a8Electromate
 
Mc 33078n op amp dual lo noise
Mc 33078n op amp dual lo noiseMc 33078n op amp dual lo noise
Mc 33078n op amp dual lo noisevakumtube
 
Advanced motion controls azbh20a8
Advanced motion controls azbh20a8Advanced motion controls azbh20a8
Advanced motion controls azbh20a8Electromate
 
Advanced motion controls azxb15a8
Advanced motion controls azxb15a8Advanced motion controls azxb15a8
Advanced motion controls azxb15a8Electromate
 
Advanced motion controls azbh10a20
Advanced motion controls azbh10a20Advanced motion controls azbh10a20
Advanced motion controls azbh10a20Electromate
 
Tp series 1-6 k va
Tp series 1-6 k vaTp series 1-6 k va
Tp series 1-6 k vaelsy-ups
 

Similar to DC 340 HS Compound Reco in relays - Project Sales Corp (20)

Dold earth leakage indicator
Dold earth leakage indicatorDold earth leakage indicator
Dold earth leakage indicator
 
Dold earth leakage indicator
Dold earth leakage indicatorDold earth leakage indicator
Dold earth leakage indicator
 
Ad598
Ad598Ad598
Ad598
 
Advanced motion controls azbh40a8
Advanced motion controls azbh40a8Advanced motion controls azbh40a8
Advanced motion controls azbh40a8
 
Acs712 datasheet
Acs712 datasheetAcs712 datasheet
Acs712 datasheet
 
Advanced motion controls azxb25a8
Advanced motion controls azxb25a8Advanced motion controls azxb25a8
Advanced motion controls azxb25a8
 
Advanced motion controls azxbe6c20
Advanced motion controls azxbe6c20Advanced motion controls azxbe6c20
Advanced motion controls azxbe6c20
 
K49 Controller
K49 ControllerK49 Controller
K49 Controller
 
Cdvr service manual renr7941-00 _ sis - caterpillar
Cdvr   service manual   renr7941-00 _ sis - caterpillarCdvr   service manual   renr7941-00 _ sis - caterpillar
Cdvr service manual renr7941-00 _ sis - caterpillar
 
IGBT Based Static Voltage Regulator
IGBT Based Static Voltage RegulatorIGBT Based Static Voltage Regulator
IGBT Based Static Voltage Regulator
 
Advanced motion controls zb6a6
Advanced motion controls zb6a6Advanced motion controls zb6a6
Advanced motion controls zb6a6
 
Acs712 sensor-arus
Acs712 sensor-arusAcs712 sensor-arus
Acs712 sensor-arus
 
Pt4115 e
Pt4115 ePt4115 e
Pt4115 e
 
Advanced motion controls azxb8a8
Advanced motion controls azxb8a8Advanced motion controls azxb8a8
Advanced motion controls azxb8a8
 
Riello master-industrial-ups-datasheet
Riello master-industrial-ups-datasheetRiello master-industrial-ups-datasheet
Riello master-industrial-ups-datasheet
 
Mc 33078n op amp dual lo noise
Mc 33078n op amp dual lo noiseMc 33078n op amp dual lo noise
Mc 33078n op amp dual lo noise
 
Advanced motion controls azbh20a8
Advanced motion controls azbh20a8Advanced motion controls azbh20a8
Advanced motion controls azbh20a8
 
Advanced motion controls azxb15a8
Advanced motion controls azxb15a8Advanced motion controls azxb15a8
Advanced motion controls azxb15a8
 
Advanced motion controls azbh10a20
Advanced motion controls azbh10a20Advanced motion controls azbh10a20
Advanced motion controls azbh10a20
 
Tp series 1-6 k va
Tp series 1-6 k vaTp series 1-6 k va
Tp series 1-6 k va
 

More from Project Sales Corp

PSC Dropped Objects Prevention Guidebook.pdf
PSC Dropped Objects Prevention Guidebook.pdfPSC Dropped Objects Prevention Guidebook.pdf
PSC Dropped Objects Prevention Guidebook.pdfProject Sales Corp
 
Managing Suspended Loads Presentation- 2024
Managing Suspended Loads Presentation- 2024Managing Suspended Loads Presentation- 2024
Managing Suspended Loads Presentation- 2024Project Sales Corp
 
PSC Gulf FZCO Dubai - Global Sourcing Now Made Easy
PSC Gulf FZCO Dubai - Global Sourcing Now Made EasyPSC Gulf FZCO Dubai - Global Sourcing Now Made Easy
PSC Gulf FZCO Dubai - Global Sourcing Now Made EasyProject Sales Corp
 
PSC Ropes Soaps Dopes Guidebook 2024.pdf
PSC Ropes Soaps Dopes Guidebook 2024.pdfPSC Ropes Soaps Dopes Guidebook 2024.pdf
PSC Ropes Soaps Dopes Guidebook 2024.pdfProject Sales Corp
 
PSC India Workplace Safety Guidebook 2024
PSC India Workplace Safety Guidebook 2024PSC India Workplace Safety Guidebook 2024
PSC India Workplace Safety Guidebook 2024Project Sales Corp
 
PSC India - Rig Spares Supplied - Examples .pdf
PSC India - Rig Spares Supplied - Examples .pdfPSC India - Rig Spares Supplied - Examples .pdf
PSC India - Rig Spares Supplied - Examples .pdfProject Sales Corp
 
PSC Supplier Partners List 2024 - Global
PSC Supplier Partners List 2024 - GlobalPSC Supplier Partners List 2024 - Global
PSC Supplier Partners List 2024 - GlobalProject Sales Corp
 
PSC SPECIALITY LUBRICANTS GUIDEBOOK 2024
PSC SPECIALITY LUBRICANTS GUIDEBOOK 2024PSC SPECIALITY LUBRICANTS GUIDEBOOK 2024
PSC SPECIALITY LUBRICANTS GUIDEBOOK 2024Project Sales Corp
 
PSC India Sealing Compounds Guidebook 2024
PSC India Sealing Compounds Guidebook 2024PSC India Sealing Compounds Guidebook 2024
PSC India Sealing Compounds Guidebook 2024Project Sales Corp
 
PSC Guide-it SlingGrab Hand Safety Tools
PSC Guide-it SlingGrab Hand Safety ToolsPSC Guide-it SlingGrab Hand Safety Tools
PSC Guide-it SlingGrab Hand Safety ToolsProject Sales Corp
 
GasGrab - Project Report on Cylinder Lifting and Benefits with GasGrab
GasGrab - Project Report on Cylinder Lifting and Benefits with GasGrabGasGrab - Project Report on Cylinder Lifting and Benefits with GasGrab
GasGrab - Project Report on Cylinder Lifting and Benefits with GasGrabProject Sales Corp
 
Man-Made-Mineral-Fibre-MMMF-Filter-Masks from PSC.pdf
Man-Made-Mineral-Fibre-MMMF-Filter-Masks from PSC.pdfMan-Made-Mineral-Fibre-MMMF-Filter-Masks from PSC.pdf
Man-Made-Mineral-Fibre-MMMF-Filter-Masks from PSC.pdfProject Sales Corp
 
PSC TASK SPECIFIC GLOVE GUIDE-BOOK (3).pdf
PSC TASK SPECIFIC GLOVE GUIDE-BOOK  (3).pdfPSC TASK SPECIFIC GLOVE GUIDE-BOOK  (3).pdf
PSC TASK SPECIFIC GLOVE GUIDE-BOOK (3).pdfProject Sales Corp
 
PSC Hands-Free Safety Tools 2023
PSC Hands-Free Safety Tools 2023PSC Hands-Free Safety Tools 2023
PSC Hands-Free Safety Tools 2023Project Sales Corp
 
PSC Hands-Free Safety Range 2023.pdf
PSC Hands-Free Safety Range 2023.pdfPSC Hands-Free Safety Range 2023.pdf
PSC Hands-Free Safety Range 2023.pdfProject Sales Corp
 

More from Project Sales Corp (20)

PSC Dropped Objects Prevention Guidebook.pdf
PSC Dropped Objects Prevention Guidebook.pdfPSC Dropped Objects Prevention Guidebook.pdf
PSC Dropped Objects Prevention Guidebook.pdf
 
Managing Suspended Loads Presentation- 2024
Managing Suspended Loads Presentation- 2024Managing Suspended Loads Presentation- 2024
Managing Suspended Loads Presentation- 2024
 
PSC Gulf FZCO Dubai - Global Sourcing Now Made Easy
PSC Gulf FZCO Dubai - Global Sourcing Now Made EasyPSC Gulf FZCO Dubai - Global Sourcing Now Made Easy
PSC Gulf FZCO Dubai - Global Sourcing Now Made Easy
 
PSC Ropes Soaps Dopes Guidebook 2024.pdf
PSC Ropes Soaps Dopes Guidebook 2024.pdfPSC Ropes Soaps Dopes Guidebook 2024.pdf
PSC Ropes Soaps Dopes Guidebook 2024.pdf
 
PSC India Workplace Safety Guidebook 2024
PSC India Workplace Safety Guidebook 2024PSC India Workplace Safety Guidebook 2024
PSC India Workplace Safety Guidebook 2024
 
PSC India - Rig Spares Supplied - Examples .pdf
PSC India - Rig Spares Supplied - Examples .pdfPSC India - Rig Spares Supplied - Examples .pdf
PSC India - Rig Spares Supplied - Examples .pdf
 
PSC Supplier Partners List 2024 - Global
PSC Supplier Partners List 2024 - GlobalPSC Supplier Partners List 2024 - Global
PSC Supplier Partners List 2024 - Global
 
PSC SPECIALITY LUBRICANTS GUIDEBOOK 2024
PSC SPECIALITY LUBRICANTS GUIDEBOOK 2024PSC SPECIALITY LUBRICANTS GUIDEBOOK 2024
PSC SPECIALITY LUBRICANTS GUIDEBOOK 2024
 
PSC India Sealing Compounds Guidebook 2024
PSC India Sealing Compounds Guidebook 2024PSC India Sealing Compounds Guidebook 2024
PSC India Sealing Compounds Guidebook 2024
 
PSC Guide-it SlingGrab Hand Safety Tools
PSC Guide-it SlingGrab Hand Safety ToolsPSC Guide-it SlingGrab Hand Safety Tools
PSC Guide-it SlingGrab Hand Safety Tools
 
GasGrab - Project Report on Cylinder Lifting and Benefits with GasGrab
GasGrab - Project Report on Cylinder Lifting and Benefits with GasGrabGasGrab - Project Report on Cylinder Lifting and Benefits with GasGrab
GasGrab - Project Report on Cylinder Lifting and Benefits with GasGrab
 
MOTORS IN STOCK.pdf
MOTORS IN STOCK.pdfMOTORS IN STOCK.pdf
MOTORS IN STOCK.pdf
 
RING GASKETS IN STOCK.pdf
RING GASKETS IN STOCK.pdfRING GASKETS IN STOCK.pdf
RING GASKETS IN STOCK.pdf
 
Man-Made-Mineral-Fibre-MMMF-Filter-Masks from PSC.pdf
Man-Made-Mineral-Fibre-MMMF-Filter-Masks from PSC.pdfMan-Made-Mineral-Fibre-MMMF-Filter-Masks from PSC.pdf
Man-Made-Mineral-Fibre-MMMF-Filter-Masks from PSC.pdf
 
PSC TASK SPECIFIC GLOVE GUIDE-BOOK (3).pdf
PSC TASK SPECIFIC GLOVE GUIDE-BOOK  (3).pdfPSC TASK SPECIFIC GLOVE GUIDE-BOOK  (3).pdf
PSC TASK SPECIFIC GLOVE GUIDE-BOOK (3).pdf
 
PSC Hands-Free Safety Tools 2023
PSC Hands-Free Safety Tools 2023PSC Hands-Free Safety Tools 2023
PSC Hands-Free Safety Tools 2023
 
PSC Hands-Free Safety Range 2023.pdf
PSC Hands-Free Safety Range 2023.pdfPSC Hands-Free Safety Range 2023.pdf
PSC Hands-Free Safety Range 2023.pdf
 
Stock - Filters.pdf
Stock - Filters.pdfStock - Filters.pdf
Stock - Filters.pdf
 
Stock - Ballasts.pdf
Stock - Ballasts.pdfStock - Ballasts.pdf
Stock - Ballasts.pdf
 
Stock - Junction Boxes.pdf
Stock - Junction Boxes.pdfStock - Junction Boxes.pdf
Stock - Junction Boxes.pdf
 

Recently uploaded

The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024christinemoorman
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMRavindra Nath Shukla
 
Catalogue ONG NUOC PPR DE NHAT .pdf
Catalogue ONG NUOC PPR DE NHAT      .pdfCatalogue ONG NUOC PPR DE NHAT      .pdf
Catalogue ONG NUOC PPR DE NHAT .pdfOrient Homes
 
RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechNewman George Leech
 
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...noida100girls
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxAndy Lambert
 
DEPED Work From Home WORKWEEK-PLAN.docx
DEPED Work From Home  WORKWEEK-PLAN.docxDEPED Work From Home  WORKWEEK-PLAN.docx
DEPED Work From Home WORKWEEK-PLAN.docxRodelinaLaud
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation SlidesKeppelCorporation
 
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyThe Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyEthan lee
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Roland Driesen
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Servicediscovermytutordmt
 
M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.Aaiza Hassan
 
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurVIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurSuhani Kapoor
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayNZSG
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessAggregage
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni
 
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Lviv Startup Club
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdfRenandantas16
 

Recently uploaded (20)

The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024
 
Forklift Operations: Safety through Cartoons
Forklift Operations: Safety through CartoonsForklift Operations: Safety through Cartoons
Forklift Operations: Safety through Cartoons
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSM
 
Catalogue ONG NUOC PPR DE NHAT .pdf
Catalogue ONG NUOC PPR DE NHAT      .pdfCatalogue ONG NUOC PPR DE NHAT      .pdf
Catalogue ONG NUOC PPR DE NHAT .pdf
 
RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman Leech
 
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptx
 
DEPED Work From Home WORKWEEK-PLAN.docx
DEPED Work From Home  WORKWEEK-PLAN.docxDEPED Work From Home  WORKWEEK-PLAN.docx
DEPED Work From Home WORKWEEK-PLAN.docx
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
 
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyThe Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Service
 
M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.
 
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurVIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
 
Nepali Escort Girl Kakori \ 9548273370 Indian Call Girls Service Lucknow ₹,9517
Nepali Escort Girl Kakori \ 9548273370 Indian Call Girls Service Lucknow ₹,9517Nepali Escort Girl Kakori \ 9548273370 Indian Call Girls Service Lucknow ₹,9517
Nepali Escort Girl Kakori \ 9548273370 Indian Call Girls Service Lucknow ₹,9517
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 May
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for Success
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.
 
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
Yaroslav Rozhankivskyy: Три складові і три передумови максимальної продуктивн...
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
 

DC 340 HS Compound Reco in relays - Project Sales Corp

  • 1. GT 25 / 40 / 50 / 60 / 75 / 90 / 120A SOLID STATE RELAYS WITH ANALOG CONTROL Main applications Main features • Plastics extrusion lines • Command input from analogue voltage and injection moulding or current signal or potentiometer. machines • Switching at voltage zero crossing. • Polymerization plant for • Partialization of wave train power with synthetic fibre production dynamically optimized time cycle. • Rubber moulding • Antiparallel double SCR machinery • 2 led for supply indication, “ON” state, • Driers for ceramics and 1 optional LED for load interrupt alarm components for the • 4000V isolation between input circuit building industries and power output • Chemical and • MOV (varistor) pharmaceutical industries • Optional monitoring of interrupted load • Industrial electric furnaces • DIN rail mounting (standard); • Food processing plants Panel mounting (optional) PROFILE is settable with trimmer and yellow LED TECHNICAL DATA The GT family of solid-state relays has signal, with voltage-free contact, normally been designed with the aim of providing open. General features very accurate control of the load thanks The GT solid-state relay has a green Category of use AC1 to an analog control input, in voltage at LED to indicate the presence of the Nominal voltage 0…5V; 0…10V or in current at 24Vac power supply and a red LED to - 480Vac (max. range 24...530Vac) 0…20/4…20mA or a potentiometer (from indicate the switching based on the Nominal frequency: 50/60Hz 1KΩ to 10 KΩ). analog control input signal. Non-repetitive voltage: 1200Vp Zero switching voltage: ≤ 20V The electronic design ensures that the The LED signal will be continuous (off at Voltage drop at nominal current ≤ cycle time for proportioning the power is minimum, on at maximum) at the ends of 1.4Vrms automatically optimized. the scale, pulsing for intermediate Power factor = 1 Il numero di periodi che il GT fornisce al values. carico (“treni d’ onda”) per un certo The units offer optional accessoires for Control inputs valore di segnale di ingresso, è calcolato panel mounting, fuses and fuseholders, in modo da essere il minimo possibile, current transformer, isolation Voltage: 0...5Vdc, 0...10Vdc pur mantenendo la precisione transformers. (impedance ≥100KΩ) necessaria. Use the relè with an opportune heatsink Current: 0...20mA, 4...20mA The number of cycles that the GT (see section accessories). (impedance 125Ω) supplies to the load (wave trains) for a Potentiometer: da1K a 10KΩ given input signal is calculated to be the (auto-fed by GT) minimum possible to maintain the necessary accuracy. OUTPUTS The GT can be used in three phase systems, using master-slave control GT 25 (SCR version) architecture in which the control signal Nominal currents of the device with drives only one GT (master) and this unit opportune heatsink in continuous work: 25A supplies the synchronized signals to the Non-repetitive overcurrent t=20 ms: other slaves. Two GS modules can also 400A be used as slaves (logic control). I2t for blowout: ≤ 645A2s A load interrupt control option (HB) is dV/dt critical with output deactivated: available without having to use an 1000V/µs external current transformer; alarm limit
  • 2. GT 40 (SCR version) Options: Installation notes Nominal currents of the device with Interrupted HB load alarm. - The heat sink must be grounded. opportune heatsink in continuous Controls the load by measuring - The device must be protected by an work: 40A current on a shunt inside the device. appropriate high-speed fuse (accessory). Non-repetitive overcurrent t=20 ms: The alarm limit is set with a multirev - Protect the solid state relay by using an 600A monorev trimmer. appropriate heat sink (accessory). I2t for blowout: ≤ 1010A2s The alarm output is obtained by The heat sink must be sized according to dV/dt critical with output deactivated: 1000V/µs means of a solid state relay. room temperature and load current (see The contact is normally open (max. the technical documentation). GT 50 (SCR version) 30V, 150mA, conduction resistance - Procedure for mounting on heat sink: Nominal currents of the device with 15Ω). The module-heat sink contact surface opportune heatsink in continuous must have a maximum planarity error of work: 50A Thermal features 0.05mm. and maximum roughness of Non-repetitive overcurrent t=20 ms: 0.02mm. The fastening holes on the GT 25 1150A Junction temperature: ≤ 125°C heat sink must be threaded and counter- I2t for blowout: ≤ 6600A2s Rth junction/case: ≤ 1.25 K/W sunk. dV/dt critical with output deactivated: Rth junction/ambient: ≤ 12 K/W Attention: spread 1 gram of 1000V/µs thermoconductive silicone (we GT 40 Junction temperature: ≤ 125°C recommend DOW CORNING 340 GT 60 (SCR version) Nominal currents of the device with Rth junction/case: ≤ 0.65 K/W HeatSink) on the dissipative metal Rth junction/ambient: ≤ 12 K/W surface of the module. opportune heatsink in continuous work: 60A The surfaces must be clean and there GT 50 Non-repetitive overcurrent t=20 ms: must be no impurities in the Junction temperature: ≤ 125°C 1150A Rth junction/case: ≤ 0.35 K/W thermoconductive paste. I2t for blowout: ≤ 6600A2s Rth junction/ambient: ≤ 12 K/W Alternately tighten the two fastening dV/dt critical with output deactivated: screws until reaching a torque of 0.60 1000V/µs GT 60 Nm for the M4 screws and 0.75 Nm for Junction temperature: ≤ 125°C Rth junction/case: ≤ 0.35 K/W the M5 screws. GT 75 (SCR version) Rth junction/ambient: ≤ 12 K/W Wait 30 minutes for any excess paste to Nominal currents of the device with drain. opportune heatsink in continuous GT 75 Alternately tighten the two fastening work: 75A Junction temperature: ≤ 125°C screws until reaching a torque of 1.2 Nm Non-repetitive overcurrent t=20 ms: Rth junction/case: ≤ 0.3 K/W Rth junction/ambient: ≤ 12 K/W for the M4 screws and 1.5 Nm for the M5 1300A I2t for blowout: ≤ 8000A2s screws. GT 90 We advise you to randomly check for dV/dt critical with output deactivated: Junction temperature: ≤ 125°C proper installation by dismantling the 1000V/µs Rth junction/case: ≤ 0.3 K/W Rth junction/ambient: ≤ 12 K/W module to make sure there are no air GT 90 (SCR version) bubbles under the copper plate. Nominal currents of the device with GT 120 opportune heatsink in continuous Junction temperature: ≤ 125°C Limits of use work: 90A Rth junction/case: ≤ 0.25 K/W • dissipation of thermal power of device Non-repetitive overcurrent t=20 ms: Rth junction/ambient: ≤ 12 K/W with restrictions on temperature of 1500A Solid State Relay Dissipated Power installation site. I2t for blowout: ≤ 11200A2s Calculation • requires exchange with outside air dV/dt critical with output deactivated: Singol-phase static relay or an air conditioner to transfer 1000V/µs Pds = 1.4 * IRMS [W] dissipated power outside the panel. IRMS = singol phase load current • installation restrictions (distances GT 120 (SCR version) between devices to guarantee dissipation Nominal currents of the device with Heatsink thermal resistance Calculation by natural convection). opportune heatsink in continuous Rth = (90°C - T.amb. max) / Pd • max. voltage limits and derivative work: 120A (complete with fan and standard thermostat). where Pd = dissipated power of transients in line, for which the Non-repetitive overcurrent t=20 ms: T.amb.max = max air temperature inside solid state unit has internal protection 1500A the electrical cabinet. devices (depending on model). I2t for blowout: ≤ 11200A2s Use a heatsink with thermal resistance • presence of dispersion current dV/dt critical with output deactivated: inferior to the calculated one (Rth). < 3mA for SCR version GS 1000V/µs < 4mA for TRIAC version GS Ambient conditions (max. value with rated voltage Isolation • Working temperature: 0 to 80°C. and junction temperature of 125°C). Rated isolation voltage input/output: • Max. relative humidity: 50% at 40°C 4000Vac • Max. installation altitude: 2000m asl Power supply: • Pollution level: 3 24Vac ±10%, 50/60 Hz • Storage temperature: -20..85°C Absorption: 1.5VA Max. isolation voltage: 300Vdc
  • 3. WORKING TYPOOLOGY “Zero crossing” with variable cycle time Examples of the operation of the GT for different values of the input drive signal and the consequent different cycle times (100msec and 40msec respectively). Example of input at 20% = 2V (IN 0-10V) or 4mA (IN 0-20mA) V V=Voltage across load 100msec Logic output control for GT V Example of input at 50% = 5V (IN 0-10V) or 10mA (IN 0-20mA) V=Voltage across load 40msec GT thermal protection Control input ON OFF t Red LED Red LED ON Thermal alarm t V = Load voltage t Thermal protection activation
  • 4. FACEPLATE DESCRIPTION Synchronism signal for - control signal Master/Slave connection + control signal Alarm output Reference voltage for potentiometer power supply (+ 10V) (solid state relay, HB option) 24 Vac 50/60 Hz power terminal Green LED (power on), Red LED (GT running) a Red LED (thermal alarm), yellow LED (load interrupt alarm, HB option) b Monorev trimmer for minimum c Dip switch for selection of input signal calibration of input signal (S1, S2, S3) d e f Monorev trimmer for calibration of load interrupt (HB) alarm limit g Monorev trimmer for maximum calibration of load signal LINE connection LOAD connection Reference connection of 230V line voltage Reference connection of 480V line voltage (HB option (HB option with 150V to 300V load) with 300V to 530V load) CALIBRATION PROCEDURE OF THE INPUT SIGNAL The solid-state power unit, Gt, is supplied factory calibrated for 0..5V, 0..10V, 0..20mA, 4..20mA, 10Kohm potentiometer. Minimum and maximum values are adjusted with two monorev trimmers (d,e). Input signal type is selected with the adjustment f dip switches (S1,S2,S3). Control signal Dip Switch Position e V/mA V/mA f Rin In In S1-S3 S1 S2 S3 96% On 0-5V 100KΩ 82% Off 0...5Vdc OFF OFF ON 0-10V 100KΩ 0...10Vdc ON OFF ON d 0-20mA 125Ω 0...20mA OFF ON ON 18% 4% 4-20mA 4...20mA OFF ON OFF 125Ω T Minimum adjustment trimmer (d) turned fully counterclockwise sets the start conducting limit at 4% of the signal; turned fully clockwise, the minimum conducting limit is set at 18% of the input signal. Maximum adjustment trimmer (e) turned fully clockwise sets the full conducting limit at 96% of the signal; turned fully counterclockwise, the full conducting limit is set at 82% of the input signal.
  • 5. CALIBRATION PROCEDURE OF THE INTERRUPTED LOAD ALARM The interrupted load alarm function enables the GT to diagnose a variation of the load current (compared to a set limit), distinguishing it from one caused by a change in grid voltage. You therefore have to bring the grid voltage to the appropriate terminals ("h" for 150V to 300V, "i" for 300-530 V). The alarm activates (relay closed and yellow alarm LED on) when the current, during the conduction of the device, falls below a preset level that may be adjusted using the trimmer on the faceplate. Calibration procedure (refer to the faceplate description drawing) 1) Use the adjustment system (or a calibrator) in order to supply the maximum signal (100% conduction or thered “ON” LED always illuminated). As an alternative, you can configure the GT to 0-10 V DC input configuration and connect terminals 5 and 6. 2) Use a current sensing pliers to check that the load current is at rated level. 3) Turn alarm limit adjustment trimmer (g) fully clockwise. Check that yellow alarm LED (b) turns on. 4) Slowly turn trimmer (g) counterclockwise until the alarm LED turns off. 5) Turn the trimmer counterclockwise another 1/10 of a turn (1 notch on the scale). In this way, the alarm limit is set below 10% of the rated load current. N.B: the partial load break alarm function operates with power partialization exceeding 15%. For partializations below 20%, tripping times increase due to the reduced load activation time. For correct operation of the option, the load current has to exceed 30% of rated current for the GT. Notes on use of the GT with the digital On/Off control - The logic control signal has to be connected with the correct polarities to terminals 4 and 5 of the analog input. - Turn minimum adjustment trimmer (d) fully counterclockwise and maximum adjustment trimmer (e) fully clockwise. - Set the 3 dip switches (f) to off. For applications with a very short work cycle, you can drive the solid state group by means of the Master/Slave signal by driving it with a digital signal (OFF = 0 V dc; ON = from 4 V dc to 10 V dc) Inhibiting the GT You can inhibit operation of the GT by means of the Master/Slave signal. To inhibit, connect control signal - (4) with the synchronism signal for Master/Slave connection (3). Notes on use of the GT in Master/Slave configuration The GT can be used as a master to drive other solid state groups (slaves). With Master/Slave signal (3), you can drive up to 9 GTs (see connection examples for GT solid state power relays with three-phase load). You can also use a GT to drive GS solid state power relays (maximum of 2), as shown in the connection diagrams for GT/GS solid state power relays with three-phase load (attention: the HB option cannot be used for a three-phase application with neutral).
  • 6. DIMENSIONS AND CUT-OUT GT 25 - 40 - 50 - 60 - 75 - 90 - 120A 60 mm L2 i h L1 Load Line Line Line 480 V 230 V 0..10V g Alarm Adj f Input selection 0..5V e Max Adj 4..20mA d Min Adj 0..20mA c Reset Alarm Accessory LAB-1 GT 25A/480 Vac 100mm AC1 50/60 Hz AL PWR ON Analog Alarm Input Master Out 24 Vac +10 Vdc Supply Out Slave 30 Vdc/ac 8 7 6 5 4 3 2 1 Depth 34 mm. Weight 200gr. TEMPLATE DIMENSIONS 60 mm 26 mm 47.5 mm 100 mm
  • 7. CONNECTION EXAMPLES Single-phase connection with optional monitoring of interrupted load (command input from analog signal or potentiometer) Ground Neutral Phase Load Fuse L2 i h L1 Load Line Line Line 480 V 230 V 0..10V g Alarm Adj f Input selection 0..5V e Max Adj 4..20mA d Min Adj 0..20mA c Reset Alarm GT 25A/480 Vac AC1 50/60 Hz 24Vac 1,5VA Controller AL Digital output 0-20mA PWR ON 4-20mA 0-10Vdc 24 Vac +10 Vdc Analog Input Master Slave Alarm Out Supply Out 30 Vdc/ac 0-5Vdc 8 7 6 5 4 3 2 1 Relay output - Alarm Potentiometer (solid state relay) Star or delta three-phase connection without neutral, with control of two phases. Phase R Phase S Phase T Ground Fuse Fuse Star connection Three-phase connection L2 i h L1 L2 i h L1 Load Line Line Line Load Line Line Line 480 V 230 V 480 V 230 V 0..10V g Alarm Adj 0..10V g Alarm Adj f Input selection f Input selection 0..5V 0..5V e Max Adj e Max Adj 4..20mA d Min Adj 4..20mA d Min Adj 0..20mA c Reset Alarm 0..20mA c Reset Alarm GT 25A/480 Vac GT 25A/480 Vac AC1 50/60 Hz AC1 50/60 Hz 24Vac 1,5VA AL AL PWR ON PWR ON Controller Analog Alarm Analog Alarm Input Master Out Input Master Out 24 Vac +10 Vdc 24 Vac +10 Vdc Supply Out Slave 30 Vdc/ac Supply Out Slave 30 Vdc/ac 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 Digital output 0-20mA Potentiometer 4-20mA 0-10Vdc 0-5Vdc Relay output - Alarm (Solid state relay)
  • 8. CONNECTION EXAMPLES Three-phase star connection with neutral. Phase R Phase S Phase T Neutral Ground Fuse Fuse Fuse L2 i h L1 L2 i h L1 L2 i h L1 Load Line Line Line Load Line Line Line Load Line Line Line 480 V 230 V 480 V 230 V 480 V 230 V 0..10V g Alarm Adj 0..10V g Alarm Adj 0..10V g Alarm Adj f Input selection f Input selection f Input selection 0..5V 0..5V 0..5V e Max Adj e Max Adj e Max Adj 4..20mA d Min Adj 4..20mA d Min Adj 4..20mA d Min Adj 0..20mA c Reset Alarm 0..20mA c Reset Alarm 0..20mA c Reset Alarm GT 25A/480 Vac GT 25A/480 Vac GT 25A/480 Vac AC1 50/60 Hz AC1 50/60 Hz Carico AC1 50/60 Hz 24Vac 1,5VA AL AL AL PWR ON PWR ON PWR ON Controller Analog Alarm Analog Alarm Analog Alarm Master Out 24 Vac Master Out 24 Vac Master Out 24 Vac +10 Vdc Input +10 Vdc Input +10 Vdc Input Supply Supply Supply Out Slave 30 Vdc/ac Out Slave 30 Vdc/ac Out Slave 30 Vdc/ac 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 Digital output 0-20mA Potentiometer 4-20mA 0-10Vdc 0-5Vdc Relay output - Alarm (solid state relay) Three-phase connection (triangle or star) without neutral, with control of two phases using one GT in Master configuration and one GS in Slave configuration. Phase R Phase S Phase T Ground Fuse Fuse Star connection Three-phase connection L2 i h L1 Load Line Line Load Line Line 480 V 230 V 0..10V g Alarm Adj f Input selection 0..5V e Max Adj 4..20mA d Min Adj 0..20mA c Reset Alarm GT 50A/480 Vac GS 50A/480 Vac AC1 50/60 Hz AC1 50/60 Hz 24Vac 1,5VA AL AL ON Controller PWR ON Digital output 24 Vac Supply +10 Vdc Out Analog Input Master Slave Alarm Out 30 Vdc/ac 6÷32Vcc ON/OFF Control 0-20mA 8 7 6 5 4 3 2 1 4-20mA 0-10Vdc 0-5Vdc Potentiometer Relay output - Alarm (solid state relay)
  • 9. CONNECTION EXAMPLES Three-phase star connection with neutral using one GT in Master configuration and two GSs in Slave configuration. Phase R Phase S Phase T Neutral Ground Load Fuse Fuse Fuse L2 i h L1 Load Line Line Load Line Load Line Line 480 V 230 V 0..10V g Alarm Adj f Input selection 0..5V e Max Adj 4..20mA d Min Adj 0..20mA c Reset Alarm GS 50A/480 Vac GS 50A/480 Vac GT 50A/480 Vac AC1 50/60 Hz AC1 50/60 Hz AC1 50/60 Hz 24Vac 1,5VA AL AL AL PWR ON ON ON Controller Analog Alarm Input Master Out 6÷32Vcc 6÷32Vcc 24 Vac +10 Vdc Slave ON/OFF Control ON/OFF Control Digital output 8 Supply 7 6 Out 5 4 3 30 Vdc/ac 2 1 0-20mA 4-20mA 0-10Vdc 0-5Vdc Potentiometer TABLE OF TERMINALS AND CONDUCTORS CONTROL TERMINAL POWER TERMINAL GROUND TERMINAL • Contact Type of pre- Max section. ** Contact Type of pre- Max section. ** Contact Max section. ** Size area isolated terminal conductor area isolated terminal conductor area conductor (WxD) tightening (WxD) tightening (WxD) tightening screw type torque screw type torque screw type torque 25/40A 6,3x9 Eye/fork 2.5mm2 16x18 Eye/fork 50mm2 14x16 50mm2 50/60A M3 tip 0.6Nm Max M6 3.5-6 Nm M5 1.8-2.5Nm 75-90A 6,3x9 Eye/fork 2.5mm2 16x18 Eye/fork 50mm2 14x16 50mm2 M3 tip 0.6Nm Max M6 3.5-6 Nm M5 1.8-2.5 Nm 120A 6,3x9 Eye/fork 2.5mm2 16x18 Eye/fork 50mm2 14x16 50mm2 M3 tip 0.6Nm Max M6 3.5-6 Nm M5 1.8-2.5 Nm (**) The max. sections specified refer to unipolar copper wires isolated in PVC. • Note: For the ground terminal, you have to use an eye wire terminal. (WxD) = Width x depth ACCESSORIES A wide range of accessories is available (including fuses and fuse holders, supports for fastening DIN bar, ID plates, thermostats, current transformers and isolation transformers). To choose accessories, see the section "Solid state relays - Accessories."
  • 10. ORDER CODE GT / 480 - Model GT Nominal current 25Aac 25 40Aac 40 50Aac 50 60Aac 60 75Aac 75 90Aac 90 120Aac 120 Nominal voltage 480Vac 480 Load interrupt (HB) option Without option 0 With load 1 interrupt option Please contact GEFRAN personnel for information on availability of codes. •WARNINGS ! WARNING: this symbol indicates danger. Before installation, please read the following advices: • follow the indications of the manual scrupulously when making the connections to the instrument. • use a cable that is suitable for the ratings of voltage and current indicated in the technical specifications. • if the instrument is used in applications where there is risk of injury to persons and damage to machines or materials, it is essential that it is used with an auxiliary alarm device. It is advisable to verify frequently that the alarm device is functional even during the normal operation of the equipment. • The instrument must NOT be used in environments where there could be the presence of dangerous atmospheres (inflammable or explosive). • During continuous operation, the heatsink may reach 100°C and remain at a high temperature due to thermal inertia even after the device is switched off. Therefore, DO NOT touch the heat sink or the electrical wires. • do not operate on the power circuit untless the main supply is disconnected. • DO NOT open the cover if device is “ON”! (use the holes in the cover for eventual re-calibration). Installation: • connect the device to the ground using the proper ground terminal. • the power supply wiring must be kept separate from that of inputs and outputs of the instrument; always check that the supply voltage corresponds to that indicated on the instrument cover. • evitare la polvere, l’ umidità, i gas corrosivi, le fonti di calore. • keep away from dust, humidity, corrosive gases and heat sources. • The connection cable must be shorter than 3 meters if the current transformer is used. Maintenance: Check the correct operation of the cooling fans at regular intervals; clean the ventilation air filters of the installation at regular intervals. • Repairs must be performed only by specialized or appropriately trained personnel. Cut off power to the device before accessing internal parts. • Do not clean the box with solvents derived from hydrocarbons (trichloroethylene, gasoline, etc.). Using such solvents will compromise the mechanical reliability of the device. To clean external plastic parts, use a clean cloth wet with ethyl alcohol or water. Technical service : GEFRAN has a technical service department. Defects caused by use not conforming to the instructions are excluded from the warranty. GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice In conformity to ECC 89/336/CEE and 73/23/CEE with reference to standards: CEI-EN 61000-6-2 (immunity in industrial enviroment)- EN 50081-1 (emission in residential enviroment) - CEI 17-38 and further modification GEFRAN spa via Sebina, 74 - 25050 Provaglio d’Iseo (BS) Tel. 03098881 - fax 0309839063 - Internet: http://www.gefran.it cod. GT - 09/03