CONTRACTOR :
LEGEND:
GENERAL NOTES:-
1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE
FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101,
UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103
UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105
UEC-SD-ER-E10-B1-S6901
2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S6901 FOR GENERAL PLAN
SECTIONAL AND DETAILS LOCATIONS.
3- THIS DRAWING AND ARRANGEMENT DESIGN OF CABLE TRAYS AND
RISERS IS BASED ON - AND TAKING INTO CONSIDERATION- THE
ALREADY APPROVED SHOP DRAWINGS#SHS-SD-ER-E03-BM-600608 &
SHS-SD-ER-E03-BM-600651 (SCOPE OF PBAD OF INSTALLING AND
LAYING THE CABLES AND CABLES OF THE NORMAL SUPPLY SERVICE
BUILDING AND THEIR CABLE TRAYS AND SUPPORTING SYSTEM.
4- ALL DIMENTIONS ARE IN MM.
7TH FEEDER (NORMAL SUPPLY)
(2 CABLES
SPACE FOR 2 CABLES
RESERVED FOR FUTURE
CABLES ALONG THE ROUTE
OF ET-1 TUNNEL/CULVERT
FROM SHAMIYA-2 UP TO
MAIN ELECTRICAL CULVERT
7TH FEEDER (EMERGENCY SUPPLY)
(2 CABLES
ADDITIONAL TWO CABLE
TRAYS
CONTRACTOR :
LEGEND:
GENERAL NOTES:-
1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE
FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101,
UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103
UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105,
UEC-SD-ER-E10-B1-S6901
2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S6901 FOR GENERAL PLAN
SECTIONAL LOCATIONS.
EXISTING
LAYERS
PROPOSED
LAYERS
DETAIL 'A'
CULVERT TO
TUNNEL LINK AREA
(ISOMETRIC VIEW)
ADDITIONAL CABLE TRAY
CULVERT TO
TUNNEL LINK AREA
(PLAN VIEW)
REFER TO DWG#
UEC-SD-ER-E10-B1-S1102
FOR CABLE TRAYS
CONTRACTOR :
LEGEND:
GENERAL NOTES:-
1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE
FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101,
UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103
UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105
UEC-SD-ER-E10-B1-S6901
2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S6901 FOR GENERAL PLAN
SECTIONAL AND DETAILS LOCATIONS.
3- THIS DRAWING AND ARRANGEMENT DESIGN OF CABLE TRAYS AND
RISERS IS BASED ON - AND TAKING INTO CONSIDERATION- THE
ALREADY APPROVED SHOP DRAWINGS#SHS-SD-ER-E03-BM-600608 &
SHS-SD-ER-E03-BM-600651 (SCOPE OF PBAD OF INSTALLING AND
LAYING THE CABLES AND CABLES OF THE NORMAL SUPPLY SERVICE
BUILDING AND THEIR CABLE TRAYS AND SUPPORTING SYSTEM.
4- ALL DIMENTIONS ARE IN MM.
CONTRACTOR :
LEGEND:
GENERAL NOTES:-
1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE
FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101,
UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103
UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105,
UEC-SD-ER-E10-B1-S6901
2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S6901 FOR GENERAL PLAN
SECTIONAL LOCATIONS.
CONTRACTOR :
LEGEND:
GENERAL NOTES:-
1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE
FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101,
UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103
UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105,
UEC-SD-ER-E10-B1-S6901
2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S6901 FOR GENERAL PLAN
SECTIONAL LOCATIONS.
CONTRACTOR :
CONSULTANT :
LEGEND:
Kingdom of Saudi Arabia
EXISTINGINSTALLATIONOF
THE16CABLETRAYS
PROPOSALROUTINGOFTHE
NEWADDITIONAL2LAYERS
(ONEONEACHSIDE)
ONTHEEXISTING
INSTALLATIONOFTHE16
CABLETRAYS
NEWLY INSTALLED
CABLE TRAYS LAYER IS
TO BE DOWN SHIFTED
WITH EXISTING TRAYS
GENERAL NOTES:-
ET-1 TUNNEL TO CULVERT MEETING ZONE
COMPLEX SOLUTION
1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWINGSHOP DRAWINGS:
SHT-SD-ER-E10-ET-S0080
SHT-SD-ER-E10-ET-S0081
SHT-SD-ER-E10-ET-S0082
SHT-SD-ER-E10-ET-S0083
SHT-SD-ER-E10-ET-S0084
SHT-SD-ER-E10-ET-S0085
SHT-SD-ER-E10-ET-S0086
SHT-SD-ER-E10-ET-S0087
2- FOR FURTHER DETAILS ON ET-1 TUNNEL TO CULVERT MEETING ZONE COMPLEX SOLUTION
ILLUSTRATED IN THIS DRAWING, REFER TO SHOP DRAWING SHEETSETS#
SHT-SD-ER-E10-ET-S0085
SHT-SD-ER-E10-ET-S0086
SHT-SD-ER-E10-ET-S0087
3- REFER TO DRAWING # SHT-SD-ER-E10-ET-S0085 FOR GENERAL VIEW AND ILLUSTRATION OF THE
ET-1 TUNNEL TO CULVERT MEETING ZONE.
4- REFER TO DRAWING # SHT-SD-ER-E10-ET-S0088 FOR FURTHER DETAILS ON ILLUSTRATED PART
SHOWN IN THIS DRAWINGS (I.E. PART 'V')
5- NEWLY PROPOSED LAYERS STRUCTURE MATERIALS FOR ET-1 TUNNEL TO CULVERT MEETING ZONE
SHALL BE PROVIDED WITH MATERIALS SAMPLE SUBMITTALS UPON APPROVAL .
6- ALL DIMENSIONS ARE IN MM.
SIDEVIEW
EXISTING LAYERS
PROPOSED
LAYERS
PART 'V'
CONTRACTOR :
CONSULTANT :
LEGEND:
Kingdom of Saudi Arabia
VERTICAL PLATE IS USED TO FIX THE
GROUND STEEL SUPPORT PART 'V' ON
THE WALL FOR EASE OF
INSTALLATION USING DRILLER
HORIZONTALLY IN SUCH NARROW
AREA.
HORIZONTAL PLATE ON THE
GROUND WITH NO FIXATION TO
ENSURE SUPPORTING PURPOSES.
GROUND
WALL
HORIZONTAL PLATE IS USED TO FIX
THE GROUND STEEL SUPPORT PART
'V' ON THE GROUND DUE TO IT'S EASE
OF INSTALLATION AND TO AVOID
MOMENT TO IT.
THRUSS HEAD BOLTS
PART 'V'
THIKNESS OF THE GROUND
SUPPORT AND IT'S WIDTH,
ALONG WITH SIZE OF BOLTS
ARE TO BE DETERMINED
UPON STEEL STRUCTURE
CALCULATIONS.
GENERAL NOTES:-
ET-1 TUNNEL TO CULVERT MEETING ZONE
COMPLEX SOLUTION
1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWINGSHOP DRAWINGS:
SHT-SD-ER-E10-ET-S0080
SHT-SD-ER-E10-ET-S0081
SHT-SD-ER-E10-ET-S0082
SHT-SD-ER-E10-ET-S0083
SHT-SD-ER-E10-ET-S0084
SHT-SD-ER-E10-ET-S0085
SHT-SD-ER-E10-ET-S0086
SHT-SD-ER-E10-ET-S0087
2- FOR FURTHER DETAILS ON ET-1 TUNNEL TO CULVERT MEETING ZONE COMPLEX SOLUTION
ILLUSTRATED IN THIS DRAWING, REFER TO SHOP DRAWING SHEETSETS#
SHT-SD-ER-E10-ET-S0085
SHT-SD-ER-E10-ET-S0086
SHT-SD-ER-E10-ET-S0087
3- REFER TO DRAWING # SHT-SD-ER-E10-ET-S0085 FOR GENERAL VIEW AND ILLUSTRATION OF THE
ET-1 TUNNEL TO CULVERT MEETING ZONE.
4- REFER TO DRAWING # SHT-SD-ER-E10-ET-S0086 FOR PLAN AND SIDE VIEW OF THE ET-1 TUNNEL TO
CULVERT MEETING ZONE.
5- NEWLY PROPOSED LAYERS STRUCTURE MATERIALS FOR ET-1 TUNNEL TO CULVERT MEETING ZONE
SHALL BE PROVIDED WITH MATERIALS SAMPLE SUBMITTALS UPON APPROVAL .
6- ALL DIMENSIONS ARE IN MM.
LIMIT OF BASEMENT
0+000
P.S
ET1ET2
CONTRACTOR :
CONSULTANT :
GENERAL NOTES:-
Kingdom of Saudi Arabia
0+000
ET1
ET1ET2
CONTRACTOR :
CONSULTANT :
KEY-MAP
GENERAL NOTES:-
Kingdom of Saudi Arabia
1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE
FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101,
UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103
UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105,
UEC-SD-ER-E10-B1-S6901
2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S1100,
UEC-SD-ER-E10-B1-S1101, UEC-SD-ER-E10-B1-S1102 &
UEC-SD-ER-E10-B1-S1103
UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105, FOR
SECTIONS AND DETAILS.
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
G
E
E
E
E
E
M
M
G
M
G
G
M
ST
S
UP
S
2
UP
S
2
BA
T
2
UP
S
2
BA
T
1
4x9
00m
m
CABLE
TR
AYS
3.0000
LIMIT OF PROPOSED CULVERT
LIMIT OF EXISTING CULVERT
21
21
6a
6d6d
66
6a
6b6b
6c 6c
6d'
6d'
21A
21A
21B
21B
55
55
44
44
CLOUDED AREA SHOWS
THE PART OF WORK FOR
ELECTRICAL CABLE
TRAYS.
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
2- COORDINATION BETWEEN ALL ELECTROMECHANICAL UTILITIES FOUND AT THE
ELECTROMECHANICAL CULVERT IS COMPLETELY THE CONTRACTOR RESPONSIBILITY TO
ASSURE IT.
E/M UTILITIES CULVERT
ELECTRICAL CULVERT
CABLE TRAYS ROUTE
LOCATION@ E/M CULVERT
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05
3- FOR CEILING MOUNTED TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS SUPPORTING SYSTEM, KINDLY REFER TO SUBMITTAL FOR MATERIALS
APPROVAL REF# SHE-MA-EWD-EL-MV-0006-REV. 00
FOR FURTHER METALLIC CABLE MANAGEMENT SYSTEM FOR CABLE TRAYS , KINDLY REFER TO
MATERIAL
SUBMITTAL APPROVAL REF# SHE-MA-EX-EL-PO-1048-R00.
4- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE
TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS MAINTAINED.
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05
1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000.
2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
5- ALL DIMENTIONS ARE IN MM.
3- FOR CEILING MOUNTED TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS SUPPORTING SYSTEM, KINDLY REFER TO SUBMITTAL FOR MATERIALS
APPROVAL REF# SHE-MA-EWD-EL-MV-0006-REV. 00
FOR FURTHER METALLIC CABLE MANAGEMENT SYSTEM FOR CABLE TRAYS , KINDLY REFER TO
MATERIAL
SUBMITTAL APPROVAL REF# SHE-MA-EX-EL-PO-1048-R00.
4- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE
TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS MAINTAINED.
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05
1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000.
2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
5- ALL DIMENTIONS ARE IN MM.
3- FOR CEILING MOUNTED TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS SUPPORTING SYSTEM, KINDLY REFER TO SUBMITTAL FOR MATERIALS
APPROVAL REF# SHE-MA-EWD-EL-MV-0006-REV. 00
FOR FURTHER METALLIC CABLE MANAGEMENT SYSTEM FOR CABLE TRAYS , KINDLY REFER TO
MATERIAL
SUBMITTAL APPROVAL REF# SHE-MA-EX-EL-PO-1048-R00.
4- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE
TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS MAINTAINED.
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05
1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000.
2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
5- ALL DIMENTIONS ARE IN MM.
3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL
SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00
FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES,
THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF.
#S10064-100/ SHE 3285.
4- FOR BLOCK WALL CABLE TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIALS
APPROVAL REF. #SHE-MA-EX-EL-0201-R01
FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES,
THICKNESS AND FIXATION METHODS, KINDLY REFER TO MATERIALS APPROVAL REF.
#S10064-100/ SHE 3423.
5- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE
TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS MAINTAINED.
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05
1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000.
2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
6- ALL DIMENTIONS ARE IN MM.
3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL
SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00
FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES,
THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF.
#S10064-100/ SHE 3285.
4- FOR BLOCK WALL CABLE TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIALS
APPROVAL REF. #SHE-MA-EX-EL-0201-R01
FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES,
THICKNESS AND FIXATION METHODS, KINDLY REFER TO MATERIALS APPROVAL REF.
#S10064-100/ SHE 3423.
5- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE
TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS MAINTAINED.
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05
1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000.
2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
6- ALL DIMENTIONS ARE IN MM.
3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL
SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00
FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES,
THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF.
#S10064-100/ SHE 3285.
4- FOR BLOCK WALL CABLE TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIALS
APPROVAL REF. #SHE-MA-EX-EL-0201-R01
FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES,
THICKNESS AND FIXATION METHODS, KINDLY REFER TO MATERIALS APPROVAL REF.
#S10064-100/ SHE 3423.
5- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE
CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS
MAINTAINED.
ALLOWED VERTICAL SPACE DISTANCE BETWEEN THE FINISH FLOOR LEVEL OF THE CULVERT TO THE
CEILING TAKING INTO CONSIDERATION THE MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15
CM) BETWEEN THE TOP FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER
FOLLOWING CABLE TRAYS LAYER.
THE DESIGN DRAWINGS; HOWEVER, THE SHOWN LAYERS NUMBERS/WIDTH ARE THE OPTIMUM FOR
CONTAINING AS MUCH CABLES AS POSSIBLE WHETHER IN THE PRESENT IN CONJUNCTION WITH OTHER
LAYER NUMBERS IN OTHER SECTIONS OR IN THE FUTURE.
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000.
2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
8- ALL DIMENTIONS ARE IN MM.
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
3- FOR BLOCK WALL CABLE TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIALS
APPROVAL REF. #SHE-MA-EX-EL-0201-R01
FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES,
THICKNESS AND FIXATION METHODS, KINDLY REFER TO MATERIALS APPROVAL REF.
#S10064-100/ SHE 3423.
1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000.
2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
6- ALL DIMENTIONS ARE IN MM.
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05
3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL
SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00
FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES,
THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF.
#S10064-100/ SHE 3285.
4- ALL DISTANCES BETWEEN CABLE TRAYS LAYERS ARE MAINTAINED AS PER THE ALLOWED VERTICAL
SPACE DISTANCE BETWEEN THE FINISH FLOOR LEVEL OF THE CULVERT TO THE CEILING TAKING INTO
CONSIDERATION THE MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP
FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS
LAYER.
5- NUMBER OF LAYERS TO BE INSTALLED IN THIS SECTION WASN'T PROVIDED IN THE DESIGN DRAWINGS;
HOWEVER, THE SHOWN LAYERS NUMBERS/WIDTH ARE THE OPTIMUM FOR CONTAINING AS MUCH
CABLES AS POSSIBLE WHETHER IN THE PRESENT IN CONJUNCTION WITH OTHER LAYER NUMBERS IN
OTHER SECTIONS OR IN THE FUTURE.
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05
1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000.
2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
6- ALL DIMENTIONS ARE IN MM.
3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL
SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00
FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES,
THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF.
#S10064-100/ SHE 3285.
4- ALL DISTANCES BETWEEN CABLE TRAYS LAYERS ARE MAINTAINED AS PER WHAT'S MENTIONED IN OTHER
SECTIONS OF THE DESIGN DRAWINGS (40 CM).
5- ALL DISTANCES BETWEEN CABLE TRAYS LAYERS ARE MAINTAINED AS PER THE ALLOWED VERTICAL
SPACE DISTANCE BETWEEN THE FINISH FLOOR LEVEL OF THE CULVERT TO THE CEILING TAKING INTO
CONSIDERATION THE MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP
FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS
LAYER.
6- NUMBER OF LAYERS TO BE INSTALLED IN THIS SECTION WASN'T PROVIDED IN THE DESIGN DRAWINGS;
HOWEVER, THE SHOWN LAYERS NUMBERS/WIDTH ARE THE OPTIMUM FOR CONTAINING AS MUCH
CABLES AS POSSIBLE WHETHER IN THE PRESENT IN CONJUNCTION WITH OTHER LAYER NUMBERS IN
OTHER SECTIONS OR IN THE FUTURE.
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000.
2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
7- ALL DIMENTIONS ARE IN MM.
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING#
UEC-SD-ER-E10-B1-S8000.
2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING
DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
3- FOR CEILING MOUNTED CABLE TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS SUPPORTING SYSTEM, KINDLY REFER TO
SUBMITTAL FOR MATERIALS APPROVAL REF#
SHE-MA-EWD-EL-MV-0006-REV. 00
FOR FURTHER METALLIC CABLE MANAGEMENT SYSTEM FOR CABLE TRAYS ,
KINDLY REFER TO MATERIAL SUBMITTAL APPROVAL REF#
SHE-MA-EX-EL-PO-1048-R00.
4- STRUCTURE DETAILS FOR THE CABLE TRAYS AND THEIR SUPPORTING SYSTEM
WAS APPROVED UPON BASED ON THE ABOVE MENTIONED MATERIAL APPROVALS
FOR 6 LAYERS CABLE TRAYS. HOWEVER, THE SAME STRUCTURE DETAILS AND
THICKNESS OF THE BASE PLATE 500X500, HEA AND UPN 80X900 AND THEIR
FIXATION BOLTS ARE USED FOR THE 4 LAYERS CABLE TRAYS WHERE IT'S
SUPPOSED TO BE USED AT (SEE SECTIONS 21-21, 21A-21A & 21B-21B). THIS IS
TO CONFIRM THE SOLIDITY OF THE SYSTEM EVEN WITH FEWER LAYERS (4
LAYERS).
5- ALL DIMENTIONS ARE IN MM.
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05
GENERAL NOTES:-
Kingdom of Saudi Arabia
LEGEND
CONTRACTOR :
CONSULTANT :
3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM:
FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL
SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00
FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES,
THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF.
#S10064-100/ SHE 3285.
1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000.
2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS:
UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200,
UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500,
UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800,
UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100
4- ALL DIMENTIONS ARE IN MM.
S07102_1-2-RE-FC-05-01-BS-0001-19
S07102_1-2-RE-FC-05-04-00-0016-08
S07102_1-2-RE-FC-05-04-00-0008-06
S07102_1-2-RE-FC-05-04-00-0029-06
S07102_1-2-RE-FC-05-04-00-0017-05
S07102_1-2-RE-FC-05-04-00-0030-05

More Related Content

What's hot

Inertia dynamics pb500f_specsheet
Inertia dynamics pb500f_specsheetInertia dynamics pb500f_specsheet
Inertia dynamics pb500f_specsheetElectromate
 
Nexans Euromold 180AR High Voltage Oil Insulated Bushing
Nexans Euromold 180AR High Voltage Oil Insulated BushingNexans Euromold 180AR High Voltage Oil Insulated Bushing
Nexans Euromold 180AR High Voltage Oil Insulated BushingThorne & Derrick International
 
Thomson roundrail 2_ca_web_universal_carriage_specsheet
Thomson roundrail 2_ca_web_universal_carriage_specsheetThomson roundrail 2_ca_web_universal_carriage_specsheet
Thomson roundrail 2_ca_web_universal_carriage_specsheetElectromate
 
Samsung bn44 00232a-inverter_sch
Samsung bn44 00232a-inverter_schSamsung bn44 00232a-inverter_sch
Samsung bn44 00232a-inverter_schg5857p
 
Great plains parts manual center pivot hitch cph-12, cph-15, chp-20
Great plains parts manual center pivot hitch cph-12, cph-15, chp-20Great plains parts manual center pivot hitch cph-12, cph-15, chp-20
Great plains parts manual center pivot hitch cph-12, cph-15, chp-20PartCatalogs Net
 
Inertia dynamics cb_couplings304_specsheet
Inertia dynamics cb_couplings304_specsheetInertia dynamics cb_couplings304_specsheet
Inertia dynamics cb_couplings304_specsheetElectromate
 
Catalogue tunisie cable
Catalogue  tunisie cableCatalogue  tunisie cable
Catalogue tunisie cableBen Hichem
 
Thomson roundrail 2_ca_web_flanged_carriage_specsheet
Thomson roundrail 2_ca_web_flanged_carriage_specsheetThomson roundrail 2_ca_web_flanged_carriage_specsheet
Thomson roundrail 2_ca_web_flanged_carriage_specsheetElectromate
 
Advanced motion controls 20a20
Advanced motion controls 20a20Advanced motion controls 20a20
Advanced motion controls 20a20Electromate
 
1991 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual
1991 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual1991 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual
1991 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manualjksemkdmm
 
Inertia dynamics sfc1525f_specsheet
Inertia dynamics sfc1525f_specsheetInertia dynamics sfc1525f_specsheet
Inertia dynamics sfc1525f_specsheetElectromate
 
1997 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual
1997 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual1997 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual
1997 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manualjkksemd yeuyhd
 
Great plains parts manual air drill cart 2220
Great plains parts manual air drill cart 2220Great plains parts manual air drill cart 2220
Great plains parts manual air drill cart 2220PartCatalogs Net
 
Bertam Field Development Project Major HUC Campaign
Bertam Field Development Project Major HUC Campaign Bertam Field Development Project Major HUC Campaign
Bertam Field Development Project Major HUC Campaign Mohd Syafiq Shawaludin
 

What's hot (17)

Inertia dynamics pb500f_specsheet
Inertia dynamics pb500f_specsheetInertia dynamics pb500f_specsheet
Inertia dynamics pb500f_specsheet
 
Nexans Euromold 180AR High Voltage Oil Insulated Bushing
Nexans Euromold 180AR High Voltage Oil Insulated BushingNexans Euromold 180AR High Voltage Oil Insulated Bushing
Nexans Euromold 180AR High Voltage Oil Insulated Bushing
 
Contactor lc1f schneider
Contactor lc1f schneiderContactor lc1f schneider
Contactor lc1f schneider
 
Thomson roundrail 2_ca_web_universal_carriage_specsheet
Thomson roundrail 2_ca_web_universal_carriage_specsheetThomson roundrail 2_ca_web_universal_carriage_specsheet
Thomson roundrail 2_ca_web_universal_carriage_specsheet
 
Samsung bn44 00232a-inverter_sch
Samsung bn44 00232a-inverter_schSamsung bn44 00232a-inverter_sch
Samsung bn44 00232a-inverter_sch
 
Great plains parts manual center pivot hitch cph-12, cph-15, chp-20
Great plains parts manual center pivot hitch cph-12, cph-15, chp-20Great plains parts manual center pivot hitch cph-12, cph-15, chp-20
Great plains parts manual center pivot hitch cph-12, cph-15, chp-20
 
Inertia dynamics cb_couplings304_specsheet
Inertia dynamics cb_couplings304_specsheetInertia dynamics cb_couplings304_specsheet
Inertia dynamics cb_couplings304_specsheet
 
Catalogue tunisie cable
Catalogue  tunisie cableCatalogue  tunisie cable
Catalogue tunisie cable
 
Thomson roundrail 2_ca_web_flanged_carriage_specsheet
Thomson roundrail 2_ca_web_flanged_carriage_specsheetThomson roundrail 2_ca_web_flanged_carriage_specsheet
Thomson roundrail 2_ca_web_flanged_carriage_specsheet
 
Sistema electrico 785 b
Sistema electrico 785 bSistema electrico 785 b
Sistema electrico 785 b
 
Cptg011 en (web)
Cptg011 en (web)Cptg011 en (web)
Cptg011 en (web)
 
Advanced motion controls 20a20
Advanced motion controls 20a20Advanced motion controls 20a20
Advanced motion controls 20a20
 
1991 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual
1991 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual1991 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual
1991 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual
 
Inertia dynamics sfc1525f_specsheet
Inertia dynamics sfc1525f_specsheetInertia dynamics sfc1525f_specsheet
Inertia dynamics sfc1525f_specsheet
 
1997 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual
1997 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual1997 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual
1997 YAMAHA VENTURE VT480 SNOWMOBILE Service Repair Manual
 
Great plains parts manual air drill cart 2220
Great plains parts manual air drill cart 2220Great plains parts manual air drill cart 2220
Great plains parts manual air drill cart 2220
 
Bertam Field Development Project Major HUC Campaign
Bertam Field Development Project Major HUC Campaign Bertam Field Development Project Major HUC Campaign
Bertam Field Development Project Major HUC Campaign
 

Viewers also liked

Haram Expansion M.V substations diversified feeding sources Scenrio
Haram Expansion M.V substations diversified feeding sources ScenrioHaram Expansion M.V substations diversified feeding sources Scenrio
Haram Expansion M.V substations diversified feeding sources ScenrioMohamed Azzam
 
Diversifying source feeding loads for chiller Ajyad Haram
Diversifying source feeding loads for chiller Ajyad HaramDiversifying source feeding loads for chiller Ajyad Haram
Diversifying source feeding loads for chiller Ajyad HaramMohamed Azzam
 
Temp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa Project
Temp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa ProjectTemp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa Project
Temp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa ProjectMohamed Azzam
 
TGI LEICESTER SQUARE ELECTRICAL DRAWING XREF C6 17 9 15-A0 Electrical ONE LIN...
TGI LEICESTER SQUARE ELECTRICAL DRAWING XREF C6 17 9 15-A0 Electrical ONE LIN...TGI LEICESTER SQUARE ELECTRICAL DRAWING XREF C6 17 9 15-A0 Electrical ONE LIN...
TGI LEICESTER SQUARE ELECTRICAL DRAWING XREF C6 17 9 15-A0 Electrical ONE LIN...Nick Hyde CEng MIMechE
 
110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIO
110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIO110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIO
110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIOMohamed Azzam
 
Pinnacle Infotech partaking at 2017 PCI Convention
 Pinnacle Infotech partaking at 2017 PCI Convention  Pinnacle Infotech partaking at 2017 PCI Convention
Pinnacle Infotech partaking at 2017 PCI Convention Pinnacle Infotech
 
Honeymoon suite bedroom tutorial ferry
Honeymoon suite bedroom tutorial ferryHoneymoon suite bedroom tutorial ferry
Honeymoon suite bedroom tutorial ferryNomer Adona
 
How to write a good business letter
How to write a good business letter   How to write a good business letter
How to write a good business letter Sukh Sandhu
 

Viewers also liked (11)

Haram Expansion M.V substations diversified feeding sources Scenrio
Haram Expansion M.V substations diversified feeding sources ScenrioHaram Expansion M.V substations diversified feeding sources Scenrio
Haram Expansion M.V substations diversified feeding sources Scenrio
 
3D Renderings
3D Renderings3D Renderings
3D Renderings
 
STAINES AP-PLANS PHDD C2-A0 HVAC MECH
STAINES AP-PLANS PHDD C2-A0 HVAC  MECHSTAINES AP-PLANS PHDD C2-A0 HVAC  MECH
STAINES AP-PLANS PHDD C2-A0 HVAC MECH
 
Diversifying source feeding loads for chiller Ajyad Haram
Diversifying source feeding loads for chiller Ajyad HaramDiversifying source feeding loads for chiller Ajyad Haram
Diversifying source feeding loads for chiller Ajyad Haram
 
Temp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa Project
Temp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa ProjectTemp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa Project
Temp. Relocation of Electrical utilities @ Lowering Of Jabal Al-Kabaa Project
 
TGI LEICESTER SQUARE ELECTRICAL DRAWING XREF C6 17 9 15-A0 Electrical ONE LIN...
TGI LEICESTER SQUARE ELECTRICAL DRAWING XREF C6 17 9 15-A0 Electrical ONE LIN...TGI LEICESTER SQUARE ELECTRICAL DRAWING XREF C6 17 9 15-A0 Electrical ONE LIN...
TGI LEICESTER SQUARE ELECTRICAL DRAWING XREF C6 17 9 15-A0 Electrical ONE LIN...
 
110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIO
110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIO110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIO
110 K.V SIEMENS TRANSFORMER JACKING AND SLIDING SCENARIO
 
1 Generral Layout
1 Generral Layout1 Generral Layout
1 Generral Layout
 
Pinnacle Infotech partaking at 2017 PCI Convention
 Pinnacle Infotech partaking at 2017 PCI Convention  Pinnacle Infotech partaking at 2017 PCI Convention
Pinnacle Infotech partaking at 2017 PCI Convention
 
Honeymoon suite bedroom tutorial ferry
Honeymoon suite bedroom tutorial ferryHoneymoon suite bedroom tutorial ferry
Honeymoon suite bedroom tutorial ferry
 
How to write a good business letter
How to write a good business letter   How to write a good business letter
How to write a good business letter
 

Similar to Haram Expansion cables arrangement, MEP coordination and cable trays maneuver

Ananth.K.Samy_PRo_Sample
Ananth.K.Samy_PRo_SampleAnanth.K.Samy_PRo_Sample
Ananth.K.Samy_PRo_SampleAnanth K.Samy
 
Analisis de filtraciones_en_presas_us_army
Analisis de filtraciones_en_presas_us_armyAnalisis de filtraciones_en_presas_us_army
Analisis de filtraciones_en_presas_us_armytorres8006
 
IRJET- Finite Element Analysis of Stempipe Used in Deepwater Pipeline Install...
IRJET- Finite Element Analysis of Stempipe Used in Deepwater Pipeline Install...IRJET- Finite Element Analysis of Stempipe Used in Deepwater Pipeline Install...
IRJET- Finite Element Analysis of Stempipe Used in Deepwater Pipeline Install...IRJET Journal
 
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers11 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1NASSAR KALLIKETTIYAPURAKAL
 
ABB CEF-OT Indoor Current Limiting Fuses - IEC Standard 12kV-24kV
ABB CEF-OT Indoor Current Limiting Fuses -  IEC Standard 12kV-24kVABB CEF-OT Indoor Current Limiting Fuses -  IEC Standard 12kV-24kV
ABB CEF-OT Indoor Current Limiting Fuses - IEC Standard 12kV-24kVThorne & Derrick International
 
Uep bulletin 1728_f-810
Uep bulletin 1728_f-810Uep bulletin 1728_f-810
Uep bulletin 1728_f-810Diego Terrazas
 
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdfJCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdffujskekdmmd3e
 
JCB 507-42 Telescopic Handler Service Repair Manual.pdf
JCB 507-42 Telescopic Handler Service Repair Manual.pdfJCB 507-42 Telescopic Handler Service Repair Manual.pdf
JCB 507-42 Telescopic Handler Service Repair Manual.pdff8sejdkddmmd
 
JCB 506-36 Telescopic Handler Service Repair Manual.pdf
JCB 506-36 Telescopic Handler Service Repair Manual.pdfJCB 506-36 Telescopic Handler Service Repair Manual.pdf
JCB 506-36 Telescopic Handler Service Repair Manual.pdff8sejdkddmmd
 
JCB 509-42 Telescopic Handler Service Repair Manual.pdf
JCB 509-42 Telescopic Handler Service Repair Manual.pdfJCB 509-42 Telescopic Handler Service Repair Manual.pdf
JCB 509-42 Telescopic Handler Service Repair Manual.pdff8sejdkddmmd
 
JCB 510-56 Telescopic Handler Service Repair Manual.pdf
JCB 510-56 Telescopic Handler Service Repair Manual.pdfJCB 510-56 Telescopic Handler Service Repair Manual.pdf
JCB 510-56 Telescopic Handler Service Repair Manual.pdff8sejdkddmmd
 
JCB 512-56 Telescopic Handler Service Repair Manual.pdf
JCB 512-56 Telescopic Handler Service Repair Manual.pdfJCB 512-56 Telescopic Handler Service Repair Manual.pdf
JCB 512-56 Telescopic Handler Service Repair Manual.pdff8sejdkddmmd
 
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdfJCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdff8sejdkddmmd
 
JCB 512-56 Telescopic Handler Service Repair Manual.pdf
JCB 512-56 Telescopic Handler Service Repair Manual.pdfJCB 512-56 Telescopic Handler Service Repair Manual.pdf
JCB 512-56 Telescopic Handler Service Repair Manual.pdfuvu724939
 
JCB 510-56 Telescopic Handler Service Repair Manual.pdf
JCB 510-56 Telescopic Handler Service Repair Manual.pdfJCB 510-56 Telescopic Handler Service Repair Manual.pdf
JCB 510-56 Telescopic Handler Service Repair Manual.pdfuvu724939
 
JCB 509-42 Telescopic Handler Service Repair Manual.pdf
JCB 509-42 Telescopic Handler Service Repair Manual.pdfJCB 509-42 Telescopic Handler Service Repair Manual.pdf
JCB 509-42 Telescopic Handler Service Repair Manual.pdfuvu724939
 
JCB 507-42 Telescopic Handler Service Repair Manual.pdf
JCB 507-42 Telescopic Handler Service Repair Manual.pdfJCB 507-42 Telescopic Handler Service Repair Manual.pdf
JCB 507-42 Telescopic Handler Service Repair Manual.pdfuvu724939
 
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdfJCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdfuvu724939
 
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdfJCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdftff4339441
 

Similar to Haram Expansion cables arrangement, MEP coordination and cable trays maneuver (20)

Ananth.K.Samy_PRo_Sample
Ananth.K.Samy_PRo_SampleAnanth.K.Samy_PRo_Sample
Ananth.K.Samy_PRo_Sample
 
Analisis de filtraciones_en_presas_us_army
Analisis de filtraciones_en_presas_us_armyAnalisis de filtraciones_en_presas_us_army
Analisis de filtraciones_en_presas_us_army
 
IRJET- Finite Element Analysis of Stempipe Used in Deepwater Pipeline Install...
IRJET- Finite Element Analysis of Stempipe Used in Deepwater Pipeline Install...IRJET- Finite Element Analysis of Stempipe Used in Deepwater Pipeline Install...
IRJET- Finite Element Analysis of Stempipe Used in Deepwater Pipeline Install...
 
Pm102 electric schematics
Pm102 electric schematicsPm102 electric schematics
Pm102 electric schematics
 
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers11 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1
 
ABB CEF-OT Indoor Current Limiting Fuses - IEC Standard 12kV-24kV
ABB CEF-OT Indoor Current Limiting Fuses -  IEC Standard 12kV-24kVABB CEF-OT Indoor Current Limiting Fuses -  IEC Standard 12kV-24kV
ABB CEF-OT Indoor Current Limiting Fuses - IEC Standard 12kV-24kV
 
Uep bulletin 1728_f-810
Uep bulletin 1728_f-810Uep bulletin 1728_f-810
Uep bulletin 1728_f-810
 
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdfJCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
 
JCB 507-42 Telescopic Handler Service Repair Manual.pdf
JCB 507-42 Telescopic Handler Service Repair Manual.pdfJCB 507-42 Telescopic Handler Service Repair Manual.pdf
JCB 507-42 Telescopic Handler Service Repair Manual.pdf
 
JCB 506-36 Telescopic Handler Service Repair Manual.pdf
JCB 506-36 Telescopic Handler Service Repair Manual.pdfJCB 506-36 Telescopic Handler Service Repair Manual.pdf
JCB 506-36 Telescopic Handler Service Repair Manual.pdf
 
JCB 509-42 Telescopic Handler Service Repair Manual.pdf
JCB 509-42 Telescopic Handler Service Repair Manual.pdfJCB 509-42 Telescopic Handler Service Repair Manual.pdf
JCB 509-42 Telescopic Handler Service Repair Manual.pdf
 
JCB 510-56 Telescopic Handler Service Repair Manual.pdf
JCB 510-56 Telescopic Handler Service Repair Manual.pdfJCB 510-56 Telescopic Handler Service Repair Manual.pdf
JCB 510-56 Telescopic Handler Service Repair Manual.pdf
 
JCB 512-56 Telescopic Handler Service Repair Manual.pdf
JCB 512-56 Telescopic Handler Service Repair Manual.pdfJCB 512-56 Telescopic Handler Service Repair Manual.pdf
JCB 512-56 Telescopic Handler Service Repair Manual.pdf
 
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdfJCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
 
JCB 512-56 Telescopic Handler Service Repair Manual.pdf
JCB 512-56 Telescopic Handler Service Repair Manual.pdfJCB 512-56 Telescopic Handler Service Repair Manual.pdf
JCB 512-56 Telescopic Handler Service Repair Manual.pdf
 
JCB 510-56 Telescopic Handler Service Repair Manual.pdf
JCB 510-56 Telescopic Handler Service Repair Manual.pdfJCB 510-56 Telescopic Handler Service Repair Manual.pdf
JCB 510-56 Telescopic Handler Service Repair Manual.pdf
 
JCB 509-42 Telescopic Handler Service Repair Manual.pdf
JCB 509-42 Telescopic Handler Service Repair Manual.pdfJCB 509-42 Telescopic Handler Service Repair Manual.pdf
JCB 509-42 Telescopic Handler Service Repair Manual.pdf
 
JCB 507-42 Telescopic Handler Service Repair Manual.pdf
JCB 507-42 Telescopic Handler Service Repair Manual.pdfJCB 507-42 Telescopic Handler Service Repair Manual.pdf
JCB 507-42 Telescopic Handler Service Repair Manual.pdf
 
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdfJCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
 
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdfJCB 514-56 Telescopic Handler Service Repair Manual.pdf
JCB 514-56 Telescopic Handler Service Repair Manual.pdf
 

Recently uploaded

Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxk795866
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 

Recently uploaded (20)

Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptx
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 

Haram Expansion cables arrangement, MEP coordination and cable trays maneuver

  • 1. CONTRACTOR : LEGEND: GENERAL NOTES:- 1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101, UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103 UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105 UEC-SD-ER-E10-B1-S6901 2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S6901 FOR GENERAL PLAN SECTIONAL AND DETAILS LOCATIONS. 3- THIS DRAWING AND ARRANGEMENT DESIGN OF CABLE TRAYS AND RISERS IS BASED ON - AND TAKING INTO CONSIDERATION- THE ALREADY APPROVED SHOP DRAWINGS#SHS-SD-ER-E03-BM-600608 & SHS-SD-ER-E03-BM-600651 (SCOPE OF PBAD OF INSTALLING AND LAYING THE CABLES AND CABLES OF THE NORMAL SUPPLY SERVICE BUILDING AND THEIR CABLE TRAYS AND SUPPORTING SYSTEM. 4- ALL DIMENTIONS ARE IN MM. 7TH FEEDER (NORMAL SUPPLY) (2 CABLES SPACE FOR 2 CABLES RESERVED FOR FUTURE CABLES ALONG THE ROUTE OF ET-1 TUNNEL/CULVERT FROM SHAMIYA-2 UP TO MAIN ELECTRICAL CULVERT 7TH FEEDER (EMERGENCY SUPPLY) (2 CABLES
  • 2. ADDITIONAL TWO CABLE TRAYS CONTRACTOR : LEGEND: GENERAL NOTES:- 1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101, UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103 UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105, UEC-SD-ER-E10-B1-S6901 2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S6901 FOR GENERAL PLAN SECTIONAL LOCATIONS. EXISTING LAYERS PROPOSED LAYERS DETAIL 'A' CULVERT TO TUNNEL LINK AREA (ISOMETRIC VIEW) ADDITIONAL CABLE TRAY CULVERT TO TUNNEL LINK AREA (PLAN VIEW) REFER TO DWG# UEC-SD-ER-E10-B1-S1102 FOR CABLE TRAYS
  • 3. CONTRACTOR : LEGEND: GENERAL NOTES:- 1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101, UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103 UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105 UEC-SD-ER-E10-B1-S6901 2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S6901 FOR GENERAL PLAN SECTIONAL AND DETAILS LOCATIONS. 3- THIS DRAWING AND ARRANGEMENT DESIGN OF CABLE TRAYS AND RISERS IS BASED ON - AND TAKING INTO CONSIDERATION- THE ALREADY APPROVED SHOP DRAWINGS#SHS-SD-ER-E03-BM-600608 & SHS-SD-ER-E03-BM-600651 (SCOPE OF PBAD OF INSTALLING AND LAYING THE CABLES AND CABLES OF THE NORMAL SUPPLY SERVICE BUILDING AND THEIR CABLE TRAYS AND SUPPORTING SYSTEM. 4- ALL DIMENTIONS ARE IN MM.
  • 4. CONTRACTOR : LEGEND: GENERAL NOTES:- 1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101, UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103 UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105, UEC-SD-ER-E10-B1-S6901 2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S6901 FOR GENERAL PLAN SECTIONAL LOCATIONS.
  • 5. CONTRACTOR : LEGEND: GENERAL NOTES:- 1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101, UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103 UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105, UEC-SD-ER-E10-B1-S6901 2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S6901 FOR GENERAL PLAN SECTIONAL LOCATIONS.
  • 6. CONTRACTOR : CONSULTANT : LEGEND: Kingdom of Saudi Arabia EXISTINGINSTALLATIONOF THE16CABLETRAYS PROPOSALROUTINGOFTHE NEWADDITIONAL2LAYERS (ONEONEACHSIDE) ONTHEEXISTING INSTALLATIONOFTHE16 CABLETRAYS NEWLY INSTALLED CABLE TRAYS LAYER IS TO BE DOWN SHIFTED WITH EXISTING TRAYS GENERAL NOTES:- ET-1 TUNNEL TO CULVERT MEETING ZONE COMPLEX SOLUTION 1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWINGSHOP DRAWINGS: SHT-SD-ER-E10-ET-S0080 SHT-SD-ER-E10-ET-S0081 SHT-SD-ER-E10-ET-S0082 SHT-SD-ER-E10-ET-S0083 SHT-SD-ER-E10-ET-S0084 SHT-SD-ER-E10-ET-S0085 SHT-SD-ER-E10-ET-S0086 SHT-SD-ER-E10-ET-S0087 2- FOR FURTHER DETAILS ON ET-1 TUNNEL TO CULVERT MEETING ZONE COMPLEX SOLUTION ILLUSTRATED IN THIS DRAWING, REFER TO SHOP DRAWING SHEETSETS# SHT-SD-ER-E10-ET-S0085 SHT-SD-ER-E10-ET-S0086 SHT-SD-ER-E10-ET-S0087 3- REFER TO DRAWING # SHT-SD-ER-E10-ET-S0085 FOR GENERAL VIEW AND ILLUSTRATION OF THE ET-1 TUNNEL TO CULVERT MEETING ZONE. 4- REFER TO DRAWING # SHT-SD-ER-E10-ET-S0088 FOR FURTHER DETAILS ON ILLUSTRATED PART SHOWN IN THIS DRAWINGS (I.E. PART 'V') 5- NEWLY PROPOSED LAYERS STRUCTURE MATERIALS FOR ET-1 TUNNEL TO CULVERT MEETING ZONE SHALL BE PROVIDED WITH MATERIALS SAMPLE SUBMITTALS UPON APPROVAL . 6- ALL DIMENSIONS ARE IN MM. SIDEVIEW EXISTING LAYERS PROPOSED LAYERS PART 'V'
  • 7. CONTRACTOR : CONSULTANT : LEGEND: Kingdom of Saudi Arabia VERTICAL PLATE IS USED TO FIX THE GROUND STEEL SUPPORT PART 'V' ON THE WALL FOR EASE OF INSTALLATION USING DRILLER HORIZONTALLY IN SUCH NARROW AREA. HORIZONTAL PLATE ON THE GROUND WITH NO FIXATION TO ENSURE SUPPORTING PURPOSES. GROUND WALL HORIZONTAL PLATE IS USED TO FIX THE GROUND STEEL SUPPORT PART 'V' ON THE GROUND DUE TO IT'S EASE OF INSTALLATION AND TO AVOID MOMENT TO IT. THRUSS HEAD BOLTS PART 'V' THIKNESS OF THE GROUND SUPPORT AND IT'S WIDTH, ALONG WITH SIZE OF BOLTS ARE TO BE DETERMINED UPON STEEL STRUCTURE CALCULATIONS. GENERAL NOTES:- ET-1 TUNNEL TO CULVERT MEETING ZONE COMPLEX SOLUTION 1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWINGSHOP DRAWINGS: SHT-SD-ER-E10-ET-S0080 SHT-SD-ER-E10-ET-S0081 SHT-SD-ER-E10-ET-S0082 SHT-SD-ER-E10-ET-S0083 SHT-SD-ER-E10-ET-S0084 SHT-SD-ER-E10-ET-S0085 SHT-SD-ER-E10-ET-S0086 SHT-SD-ER-E10-ET-S0087 2- FOR FURTHER DETAILS ON ET-1 TUNNEL TO CULVERT MEETING ZONE COMPLEX SOLUTION ILLUSTRATED IN THIS DRAWING, REFER TO SHOP DRAWING SHEETSETS# SHT-SD-ER-E10-ET-S0085 SHT-SD-ER-E10-ET-S0086 SHT-SD-ER-E10-ET-S0087 3- REFER TO DRAWING # SHT-SD-ER-E10-ET-S0085 FOR GENERAL VIEW AND ILLUSTRATION OF THE ET-1 TUNNEL TO CULVERT MEETING ZONE. 4- REFER TO DRAWING # SHT-SD-ER-E10-ET-S0086 FOR PLAN AND SIDE VIEW OF THE ET-1 TUNNEL TO CULVERT MEETING ZONE. 5- NEWLY PROPOSED LAYERS STRUCTURE MATERIALS FOR ET-1 TUNNEL TO CULVERT MEETING ZONE SHALL BE PROVIDED WITH MATERIALS SAMPLE SUBMITTALS UPON APPROVAL . 6- ALL DIMENSIONS ARE IN MM.
  • 8. LIMIT OF BASEMENT 0+000 P.S ET1ET2 CONTRACTOR : CONSULTANT : GENERAL NOTES:- Kingdom of Saudi Arabia
  • 9. 0+000 ET1 ET1ET2 CONTRACTOR : CONSULTANT : KEY-MAP GENERAL NOTES:- Kingdom of Saudi Arabia 1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101, UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103 UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105, UEC-SD-ER-E10-B1-S6901 2- REFER TO DRAWING# UEC-SD-ER-E10-B1-S1100, UEC-SD-ER-E10-B1-S1101, UEC-SD-ER-E10-B1-S1102 & UEC-SD-ER-E10-B1-S1103 UEC-SD-ER-E10-B1-S1104, UEC-SD-ER-E10-B1-S1105, FOR SECTIONS AND DETAILS.
  • 10. M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M G E E E E E M M G M G G M ST S UP S 2 UP S 2 BA T 2 UP S 2 BA T 1 4x9 00m m CABLE TR AYS 3.0000 LIMIT OF PROPOSED CULVERT LIMIT OF EXISTING CULVERT 21 21 6a 6d6d 66 6a 6b6b 6c 6c 6d' 6d' 21A 21A 21B 21B 55 55 44 44 CLOUDED AREA SHOWS THE PART OF WORK FOR ELECTRICAL CABLE TRAYS. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : 1- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 2- COORDINATION BETWEEN ALL ELECTROMECHANICAL UTILITIES FOUND AT THE ELECTROMECHANICAL CULVERT IS COMPLETELY THE CONTRACTOR RESPONSIBILITY TO ASSURE IT. E/M UTILITIES CULVERT ELECTRICAL CULVERT CABLE TRAYS ROUTE LOCATION@ E/M CULVERT S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05
  • 11. 3- FOR CEILING MOUNTED TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS SUPPORTING SYSTEM, KINDLY REFER TO SUBMITTAL FOR MATERIALS APPROVAL REF# SHE-MA-EWD-EL-MV-0006-REV. 00 FOR FURTHER METALLIC CABLE MANAGEMENT SYSTEM FOR CABLE TRAYS , KINDLY REFER TO MATERIAL SUBMITTAL APPROVAL REF# SHE-MA-EX-EL-PO-1048-R00. 4- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS MAINTAINED. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05 1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000. 2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 5- ALL DIMENTIONS ARE IN MM.
  • 12. 3- FOR CEILING MOUNTED TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS SUPPORTING SYSTEM, KINDLY REFER TO SUBMITTAL FOR MATERIALS APPROVAL REF# SHE-MA-EWD-EL-MV-0006-REV. 00 FOR FURTHER METALLIC CABLE MANAGEMENT SYSTEM FOR CABLE TRAYS , KINDLY REFER TO MATERIAL SUBMITTAL APPROVAL REF# SHE-MA-EX-EL-PO-1048-R00. 4- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS MAINTAINED. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05 1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000. 2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 5- ALL DIMENTIONS ARE IN MM.
  • 13. 3- FOR CEILING MOUNTED TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS SUPPORTING SYSTEM, KINDLY REFER TO SUBMITTAL FOR MATERIALS APPROVAL REF# SHE-MA-EWD-EL-MV-0006-REV. 00 FOR FURTHER METALLIC CABLE MANAGEMENT SYSTEM FOR CABLE TRAYS , KINDLY REFER TO MATERIAL SUBMITTAL APPROVAL REF# SHE-MA-EX-EL-PO-1048-R00. 4- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS MAINTAINED. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05 1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000. 2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 5- ALL DIMENTIONS ARE IN MM.
  • 14. 3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00 FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES, THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF. #S10064-100/ SHE 3285. 4- FOR BLOCK WALL CABLE TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIALS APPROVAL REF. #SHE-MA-EX-EL-0201-R01 FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES, THICKNESS AND FIXATION METHODS, KINDLY REFER TO MATERIALS APPROVAL REF. #S10064-100/ SHE 3423. 5- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS MAINTAINED. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05 1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000. 2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 6- ALL DIMENTIONS ARE IN MM.
  • 15. 3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00 FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES, THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF. #S10064-100/ SHE 3285. 4- FOR BLOCK WALL CABLE TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIALS APPROVAL REF. #SHE-MA-EX-EL-0201-R01 FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES, THICKNESS AND FIXATION METHODS, KINDLY REFER TO MATERIALS APPROVAL REF. #S10064-100/ SHE 3423. 5- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS MAINTAINED. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05 1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000. 2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 6- ALL DIMENTIONS ARE IN MM.
  • 16. 3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00 FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES, THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF. #S10064-100/ SHE 3285. 4- FOR BLOCK WALL CABLE TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIALS APPROVAL REF. #SHE-MA-EX-EL-0201-R01 FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES, THICKNESS AND FIXATION METHODS, KINDLY REFER TO MATERIALS APPROVAL REF. #S10064-100/ SHE 3423. 5- MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER IS MAINTAINED. ALLOWED VERTICAL SPACE DISTANCE BETWEEN THE FINISH FLOOR LEVEL OF THE CULVERT TO THE CEILING TAKING INTO CONSIDERATION THE MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER. THE DESIGN DRAWINGS; HOWEVER, THE SHOWN LAYERS NUMBERS/WIDTH ARE THE OPTIMUM FOR CONTAINING AS MUCH CABLES AS POSSIBLE WHETHER IN THE PRESENT IN CONJUNCTION WITH OTHER LAYER NUMBERS IN OTHER SECTIONS OR IN THE FUTURE. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : 1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000. 2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 8- ALL DIMENTIONS ARE IN MM. S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05
  • 17. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : 3- FOR BLOCK WALL CABLE TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIALS APPROVAL REF. #SHE-MA-EX-EL-0201-R01 FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES, THICKNESS AND FIXATION METHODS, KINDLY REFER TO MATERIALS APPROVAL REF. #S10064-100/ SHE 3423. 1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000. 2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 6- ALL DIMENTIONS ARE IN MM. S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05
  • 18. 3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00 FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES, THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF. #S10064-100/ SHE 3285. 4- ALL DISTANCES BETWEEN CABLE TRAYS LAYERS ARE MAINTAINED AS PER THE ALLOWED VERTICAL SPACE DISTANCE BETWEEN THE FINISH FLOOR LEVEL OF THE CULVERT TO THE CEILING TAKING INTO CONSIDERATION THE MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER. 5- NUMBER OF LAYERS TO BE INSTALLED IN THIS SECTION WASN'T PROVIDED IN THE DESIGN DRAWINGS; HOWEVER, THE SHOWN LAYERS NUMBERS/WIDTH ARE THE OPTIMUM FOR CONTAINING AS MUCH CABLES AS POSSIBLE WHETHER IN THE PRESENT IN CONJUNCTION WITH OTHER LAYER NUMBERS IN OTHER SECTIONS OR IN THE FUTURE. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05 1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000. 2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 6- ALL DIMENTIONS ARE IN MM.
  • 19. 3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00 FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES, THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF. #S10064-100/ SHE 3285. 4- ALL DISTANCES BETWEEN CABLE TRAYS LAYERS ARE MAINTAINED AS PER WHAT'S MENTIONED IN OTHER SECTIONS OF THE DESIGN DRAWINGS (40 CM). 5- ALL DISTANCES BETWEEN CABLE TRAYS LAYERS ARE MAINTAINED AS PER THE ALLOWED VERTICAL SPACE DISTANCE BETWEEN THE FINISH FLOOR LEVEL OF THE CULVERT TO THE CEILING TAKING INTO CONSIDERATION THE MINIMUM CABLES ALLOWABLE CLEARANCE DISTANCE (15 CM) BETWEEN THE TOP FLANGE OF ONE CABLE TRAYS LAYER TO THE BOTTOM SUPPORT OF THE UPPER FOLLOWING CABLE TRAYS LAYER. 6- NUMBER OF LAYERS TO BE INSTALLED IN THIS SECTION WASN'T PROVIDED IN THE DESIGN DRAWINGS; HOWEVER, THE SHOWN LAYERS NUMBERS/WIDTH ARE THE OPTIMUM FOR CONTAINING AS MUCH CABLES AS POSSIBLE WHETHER IN THE PRESENT IN CONJUNCTION WITH OTHER LAYER NUMBERS IN OTHER SECTIONS OR IN THE FUTURE. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : 1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000. 2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 7- ALL DIMENTIONS ARE IN MM. S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05
  • 20. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : 1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000. 2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 3- FOR CEILING MOUNTED CABLE TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS SUPPORTING SYSTEM, KINDLY REFER TO SUBMITTAL FOR MATERIALS APPROVAL REF# SHE-MA-EWD-EL-MV-0006-REV. 00 FOR FURTHER METALLIC CABLE MANAGEMENT SYSTEM FOR CABLE TRAYS , KINDLY REFER TO MATERIAL SUBMITTAL APPROVAL REF# SHE-MA-EX-EL-PO-1048-R00. 4- STRUCTURE DETAILS FOR THE CABLE TRAYS AND THEIR SUPPORTING SYSTEM WAS APPROVED UPON BASED ON THE ABOVE MENTIONED MATERIAL APPROVALS FOR 6 LAYERS CABLE TRAYS. HOWEVER, THE SAME STRUCTURE DETAILS AND THICKNESS OF THE BASE PLATE 500X500, HEA AND UPN 80X900 AND THEIR FIXATION BOLTS ARE USED FOR THE 4 LAYERS CABLE TRAYS WHERE IT'S SUPPOSED TO BE USED AT (SEE SECTIONS 21-21, 21A-21A & 21B-21B). THIS IS TO CONFIRM THE SOLIDITY OF THE SYSTEM EVEN WITH FEWER LAYERS (4 LAYERS). 5- ALL DIMENTIONS ARE IN MM. S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05
  • 21. GENERAL NOTES:- Kingdom of Saudi Arabia LEGEND CONTRACTOR : CONSULTANT : 3- FOR DOUBLE C CHANNEL BACK TO BACK CABLE TRAYS AND SUPPORTING SYSTEM: FOR FURTHER CABLE TRAYS DETAILS AND INTERCONNECTION INFO, KINDLY REFER TO MATERIAL SUBMITTAL APPROVAL REF. #SHE-MA-EX-EL-PO-1048-R00 FOR FURTHER CANTILEVER AND SUPPORT SYSTEMS DETAILS AND INFO SUCH AS USED BOLTS SIZES, THICKNESS AND FIXATION METHODS, KINDLY REFER TO DAR REPLY REF. #S10064-100/ SHE 3285. 1- FOR FURTHER PLAN DETAILS, REFER TO SHOP DRAWING# UEC-SD-ER-E10-B1-S8000. 2- THIS DRAWING IS PART OF SHEETSET CONSISTING OF THE FOLLOWING DRAWINGS: UEC-SD-ER-E10-B1-S8000, UEC-SD-ER-E10-B1-S8100, UEC-SD-ER-E10-B1-S8200, UEC-SD-ER-E10-B1-S8300, UEC-SD-ER-E10-B1-S8400, UEC-SD-ER-E10-B1-S8500, UEC-SD-ER-E10-B1-S8600, UEC-SD-ER-E10-B1-S8700, UEC-SD-ER-E10-B1-S8800, UEC-SD-ER-E10-B1-S8900, UEC-SD-ER-E10-B1-S9000, UEC-SD-ER-E10-B1-S9100 4- ALL DIMENTIONS ARE IN MM. S07102_1-2-RE-FC-05-01-BS-0001-19 S07102_1-2-RE-FC-05-04-00-0016-08 S07102_1-2-RE-FC-05-04-00-0008-06 S07102_1-2-RE-FC-05-04-00-0029-06 S07102_1-2-RE-FC-05-04-00-0017-05 S07102_1-2-RE-FC-05-04-00-0030-05