The document provides installation instructions for the Automatic Genset Controller AGC-4. It includes information on mounting the controller, terminal strip descriptions, input/output lists, and wiring details. The controller has standard functions for genset control, protection, and display. Optional applications include Automatic Mains Failure control, island operation, and power management for multiple gensets.
Eberspacher Airtronic D2 Instruction Manual. A compact and economical heater. The Airtronic D2 offers optimised fuel effeciency and comes with a range of operation modes and unsurpassed safety standards.
Technical manual for the Eberspacher Airtronic D4 heater designed to support anyone installing the heater or users looking for important technical information about this product.
Eberspacher Airtronic D2 Instruction Manual. A compact and economical heater. The Airtronic D2 offers optimised fuel effeciency and comes with a range of operation modes and unsurpassed safety standards.
Technical manual for the Eberspacher Airtronic D4 heater designed to support anyone installing the heater or users looking for important technical information about this product.
Valeo Engine Cooling 2012-2013 catalogue 955486
Catalogue Valeo Thermique moteur pour les véhicules de tourisme 2012-2013 955486
ENGINE COOLING
THERMIQUE MOTEUR
TÉRMICO MOTOR
SISTEMAS TÉRMICOS
TERMICO MOTORE
MOTO R KO E L I N G
MOTORKÜHLUNG
SYSTEM CHŁODZENIA
S I L N I K A
C H L A Z E N Í
M O T O R Ů
MO T O R H U T É S
M O T O R
S O Ğ U T M A
С И C T E M A
O X Л А Ж Д Е Н И Я
Д В И Г А Т Е Л Я
Ψύξη Μηχανής
Trust Valeo, your Engine Cooling Multi-specialist!
As one of the world’s leaders in Engine Cooling, Valeo delivers:
- its expertise through its strong O.E. experience
- a complete Aftermarket product offer made of more than 1,800 part numbers for:
• Radiators (Premium and Valeo CLASSIC range adapted to customer needs)
• EGR Coolers
• Charge Air Coolers
• Fan Systems
• Oil Coolers
• Condensors
• Heater cores
- a full range of services: training, technical support, point of sales material, logistics “speed, service and quality”
• Discover the complete Valeo Thermal System aftermarket offer on http://www.valeoservice.com
• See also the Valeo Thermal System Control 2014-2015 catalogue 955607: http://www.slideshare.net/ValeoService/valeo-thermal-system-control-2014-2015-catalogue-955607
• See also the Valeo Engine Cooling 2013 supplement catalogue 955606: http://www.slideshare.net/ValeoService/valeo-engine-cooling-2013-supplement-catalogue-955606
Valeo, automotive technology, naturally.
• Follow Valeo on facebook : http://www.facebook.com/Valeo.Group
• Follow Valeo on twitter : http://twitter.com/#!/Valeo_Group
KUBOTA V2607-DI-T-E3B DIESEL ENGINE Service Repair Manualjksemndmm
This is the Highly Detailed factory service repair manual for theKUBOTA V2607-DI-T-E3B DIESEL ENGINE, this Service Manual has detailed illustrations as well as step by step instructions,It is 100 percents complete and intact. they are specifically written for the do-it-yourself-er as well as the experienced mechanic.KUBOTA V2607-DI-T-E3B DIESEL ENGINE Service Repair Workshop Manual provides step-by-step instructions based on the complete dis-assembly of the machine. It is this level of detail, along with hundreds of photos and illustrations, that guide the reader through each service and repair procedure. Complete download comes in pdf format which can work under all PC based windows operating system and Mac also, All pages are printable. Using this repair manual is an inexpensive way to keep your vehicle working properly.
Service Repair Manual Covers:
Engine Identification
General Precautions
Maintenance Check List
Check and Maintenance
Special Tools
Feature
Engine Body
Lubricating System
Cooling System
Fuel System
Intake and Exhaust System
Exhaust Gas Recirculation System
Troubleshooting
Servicing Specifications
Tightening Torques
Checking, Disassembly and Servicing
File Format: PDF
Compatible: All Versions of Windows & Mac
Language: English
Requirements: Adobe PDF Reader
NO waiting, Buy from responsible seller and get INSTANT DOWNLOAD, Without wasting your hard-owned money on uncertainty or surprise! All pages are is great to haveKUBOTA V2607-DI-T-E3B DIESEL ENGINE Service Repair Workshop Manual.
Looking for some other Service Repair Manual,please check:
https://www.aservicemanualpdf.com/
Thanks for visiting!
8
Komatsu D375A-5E0 Dozer Bulldozer Service Repair Manual S/N 50001 and uphdksemmme
This is the Highly Detailed factory service repair manual for theKOMATSU D375A-5E0 DOZER BULLDOZER, this Service Manual has detailed illustrations as well as step by step instructions,It is 100 percents complete and intact. they are specifically written for the do-it-yourself-er as well as the experienced mechanic.KOMATSU D375A-5E0 DOZER BULLDOZER Service Repair Workshop Manual provides step-by-step instructions based on the complete dis-assembly of the machine. It is this level of detail, along with hundreds of photos and illustrations, that guide the reader through each service and repair procedure. Complete download comes in pdf format which can work under all PC based windows operating system and Mac also, All pages are printable. Using this repair manual is an inexpensive way to keep your vehicle working properly.
Service Repair Manual Covers:
Index and Foreword
Specification
Structure, Function and Maintenance Standard
Standard Value Table
Testing and Adjusting
Troubleshooting
Disassembly and Assembly
Diagrams and Drawings
+++++Field Assembly Instruction
Manual Covers:
Specifications
Precautions for Field Assembly
Disposal of Removed Parts
Assembly Procedure, Necessary Equipment, and Schedule
Layout of Kit
Style for Transportation
Table of Tools for Field Assembly
Tightening Torque
Coating Materials List
File Format: PDF
Compatible: All Versions of Windows & Mac
Language: English
Requirements: Adobe PDF Reader
NO waiting, Buy from responsible seller and get INSTANT DOWNLOAD, Without wasting your hard-owned money on uncertainty or surprise! All pages are is great to haveKOMATSU D375A-5E0 DOZER BULLDOZER Service Repair Workshop Manual.
Looking for some other Service Repair Manual,please check:
https://www.aservicemanualpdf.com/
Thanks for visiting!
8
UHF partial discharge detection system for GIS Application guide for sensitiv...Power System Operation
UHF partial discharge
detection system for GIS:
Application guide for
sensitivity verification
UHF partial discharge detection system for GIS Application
JCB 456 WHEELED LOADER Service Repair Manualfujsjefjkkekem
This is the Highly Detailed factory service repair manual for theJCB 456 WHEELED LOADER, this Service Manual has detailed illustrations as well as step by step instructions,It is 100 percents complete and intact. they are specifically written for the do-it-yourself-er as well as the experienced mechanic.JCB 456 WHEELED LOADER Service Repair Workshop Manual provides step-by-step instructions based on the complete dis-assembly of the machine. It is this level of detail, along with hundreds of photos and illustrations, that guide the reader through each service and repair procedure. Complete download comes in pdf format which can work under all PC based windows operating system and Mac also, All pages are printable. Using this repair manual is an inexpensive way to keep your vehicle working properly.
Service Repair Manual Covers:
General Information
Care and Safety
Routine Maintenance
Attachments
Body and Framework
Electrics
Hydraulics
Transmission
Brakes
Steering
Engine
File Format: PDF
Compatible: All Versions of Windows & Mac
Language: English
Requirements: Adobe PDF Reader
NO waiting, Buy from responsible seller and get INSTANT DOWNLOAD, Without wasting your hard-owned money on uncertainty or surprise! All pages are is great to haveJCB 456 WHEELED LOADER Service Repair Workshop Manual.
Looking for some other Service Repair Manual,please check:
https://www.aservicemanualpdf.com/
Thanks for visiting!
Valeo Engine Cooling 2012-2013 catalogue 955486
Catalogue Valeo Thermique moteur pour les véhicules de tourisme 2012-2013 955486
ENGINE COOLING
THERMIQUE MOTEUR
TÉRMICO MOTOR
SISTEMAS TÉRMICOS
TERMICO MOTORE
MOTO R KO E L I N G
MOTORKÜHLUNG
SYSTEM CHŁODZENIA
S I L N I K A
C H L A Z E N Í
M O T O R Ů
MO T O R H U T É S
M O T O R
S O Ğ U T M A
С И C T E M A
O X Л А Ж Д Е Н И Я
Д В И Г А Т Е Л Я
Ψύξη Μηχανής
Trust Valeo, your Engine Cooling Multi-specialist!
As one of the world’s leaders in Engine Cooling, Valeo delivers:
- its expertise through its strong O.E. experience
- a complete Aftermarket product offer made of more than 1,800 part numbers for:
• Radiators (Premium and Valeo CLASSIC range adapted to customer needs)
• EGR Coolers
• Charge Air Coolers
• Fan Systems
• Oil Coolers
• Condensors
• Heater cores
- a full range of services: training, technical support, point of sales material, logistics “speed, service and quality”
• Discover the complete Valeo Thermal System aftermarket offer on http://www.valeoservice.com
• See also the Valeo Thermal System Control 2014-2015 catalogue 955607: http://www.slideshare.net/ValeoService/valeo-thermal-system-control-2014-2015-catalogue-955607
• See also the Valeo Engine Cooling 2013 supplement catalogue 955606: http://www.slideshare.net/ValeoService/valeo-engine-cooling-2013-supplement-catalogue-955606
Valeo, automotive technology, naturally.
• Follow Valeo on facebook : http://www.facebook.com/Valeo.Group
• Follow Valeo on twitter : http://twitter.com/#!/Valeo_Group
KUBOTA V2607-DI-T-E3B DIESEL ENGINE Service Repair Manualjksemndmm
This is the Highly Detailed factory service repair manual for theKUBOTA V2607-DI-T-E3B DIESEL ENGINE, this Service Manual has detailed illustrations as well as step by step instructions,It is 100 percents complete and intact. they are specifically written for the do-it-yourself-er as well as the experienced mechanic.KUBOTA V2607-DI-T-E3B DIESEL ENGINE Service Repair Workshop Manual provides step-by-step instructions based on the complete dis-assembly of the machine. It is this level of detail, along with hundreds of photos and illustrations, that guide the reader through each service and repair procedure. Complete download comes in pdf format which can work under all PC based windows operating system and Mac also, All pages are printable. Using this repair manual is an inexpensive way to keep your vehicle working properly.
Service Repair Manual Covers:
Engine Identification
General Precautions
Maintenance Check List
Check and Maintenance
Special Tools
Feature
Engine Body
Lubricating System
Cooling System
Fuel System
Intake and Exhaust System
Exhaust Gas Recirculation System
Troubleshooting
Servicing Specifications
Tightening Torques
Checking, Disassembly and Servicing
File Format: PDF
Compatible: All Versions of Windows & Mac
Language: English
Requirements: Adobe PDF Reader
NO waiting, Buy from responsible seller and get INSTANT DOWNLOAD, Without wasting your hard-owned money on uncertainty or surprise! All pages are is great to haveKUBOTA V2607-DI-T-E3B DIESEL ENGINE Service Repair Workshop Manual.
Looking for some other Service Repair Manual,please check:
https://www.aservicemanualpdf.com/
Thanks for visiting!
8
Komatsu D375A-5E0 Dozer Bulldozer Service Repair Manual S/N 50001 and uphdksemmme
This is the Highly Detailed factory service repair manual for theKOMATSU D375A-5E0 DOZER BULLDOZER, this Service Manual has detailed illustrations as well as step by step instructions,It is 100 percents complete and intact. they are specifically written for the do-it-yourself-er as well as the experienced mechanic.KOMATSU D375A-5E0 DOZER BULLDOZER Service Repair Workshop Manual provides step-by-step instructions based on the complete dis-assembly of the machine. It is this level of detail, along with hundreds of photos and illustrations, that guide the reader through each service and repair procedure. Complete download comes in pdf format which can work under all PC based windows operating system and Mac also, All pages are printable. Using this repair manual is an inexpensive way to keep your vehicle working properly.
Service Repair Manual Covers:
Index and Foreword
Specification
Structure, Function and Maintenance Standard
Standard Value Table
Testing and Adjusting
Troubleshooting
Disassembly and Assembly
Diagrams and Drawings
+++++Field Assembly Instruction
Manual Covers:
Specifications
Precautions for Field Assembly
Disposal of Removed Parts
Assembly Procedure, Necessary Equipment, and Schedule
Layout of Kit
Style for Transportation
Table of Tools for Field Assembly
Tightening Torque
Coating Materials List
File Format: PDF
Compatible: All Versions of Windows & Mac
Language: English
Requirements: Adobe PDF Reader
NO waiting, Buy from responsible seller and get INSTANT DOWNLOAD, Without wasting your hard-owned money on uncertainty or surprise! All pages are is great to haveKOMATSU D375A-5E0 DOZER BULLDOZER Service Repair Workshop Manual.
Looking for some other Service Repair Manual,please check:
https://www.aservicemanualpdf.com/
Thanks for visiting!
8
UHF partial discharge detection system for GIS Application guide for sensitiv...Power System Operation
UHF partial discharge
detection system for GIS:
Application guide for
sensitivity verification
UHF partial discharge detection system for GIS Application
JCB 456 WHEELED LOADER Service Repair Manualfujsjefjkkekem
This is the Highly Detailed factory service repair manual for theJCB 456 WHEELED LOADER, this Service Manual has detailed illustrations as well as step by step instructions,It is 100 percents complete and intact. they are specifically written for the do-it-yourself-er as well as the experienced mechanic.JCB 456 WHEELED LOADER Service Repair Workshop Manual provides step-by-step instructions based on the complete dis-assembly of the machine. It is this level of detail, along with hundreds of photos and illustrations, that guide the reader through each service and repair procedure. Complete download comes in pdf format which can work under all PC based windows operating system and Mac also, All pages are printable. Using this repair manual is an inexpensive way to keep your vehicle working properly.
Service Repair Manual Covers:
General Information
Care and Safety
Routine Maintenance
Attachments
Body and Framework
Electrics
Hydraulics
Transmission
Brakes
Steering
Engine
File Format: PDF
Compatible: All Versions of Windows & Mac
Language: English
Requirements: Adobe PDF Reader
NO waiting, Buy from responsible seller and get INSTANT DOWNLOAD, Without wasting your hard-owned money on uncertainty or surprise! All pages are is great to haveJCB 456 WHEELED LOADER Service Repair Workshop Manual.
Looking for some other Service Repair Manual,please check:
https://www.aservicemanualpdf.com/
Thanks for visiting!
CLV62x 시크 스캐너 제품 라인은 다양한 어플리케이션에 맞춰 개발된 콤팩트한 고성능 바코드 스캐너로 구성됩니다.
높은 성능, 간편한 조작과 유연성은 CLV62x 제품 라인의 특징입니다.
CLV62x는 높은 판독 성능을, 판독 알고리즘인 SMART620 코드 복원 기술과 결합해 손상되거나 반쯤 가려진 바코드도 정확하게 파악할 수 있습니다.
CLV62x는 직렬형 버전뿐 아니라 EtherNet/IP 및 PROFINET 프로토콜을 포함한 Ethernet 인터페이스 내장 버전으로도 제공됩니다.
웹서버와 판독 통계 평가 장치가 내장되어 원격 진단이 가능합니다.
이러한 추가 기능은 고성능 바코드스캐너 CLV62x를 보완해 줍니다.
FEATURE
Version : Mid Range
Connection type : Cable
Reading field : Front
Scanner design : Line scanner
Focus : Fixed focus
Light source : Visible red light (655 nm)
MTBF : 40,000 h
Laser class : 2 (EN 60825-1 (A2:2001-03))
Field of view : ≤ 50 °
Code resolution : 0.2 mm ... 1 mm
Reading distance : 60 mm ... 365 mm
Scanning frequency : 400 Hz ... 1,200 Hz
PERFORMANCE
Bar code types :
Interleaved 2 of 5, All current code types, Codabar, Code 128, Code 39, Code 93, GS1 DataBar, GS1-128 ∕ EAN 128, MSI/Plessey, Pharmacode, Telepen, UPC ∕ GTIN ∕ EAN
Print ratio : 2:1 ... 3:1
No. of codes per scan : 1 ... 20 (Standard decoder), 1 ... 6 (SMART620)
No. of codes per reading interval : 1 ... 50 (auto-discriminating)
No. of characters per reading interval : 1,500, 500 (for multiplexer function in CAN operation)
No. of multiple readings : 1 ... 99
INTERFACE
Serial (RS-232, RS-422/485) : V
Remark (Serial (RS-232, RS-422/485)) : AUX (only RS-232)
Function (Serial (RS-232, RS-422/485)) : Host, AUX
Data transmission rate (Serial (RS-232, RS-422/485)) : 2,400 Baud ... 115 kBaud, AUX: 57.6 kBaud
Ethernet : N/A
Protocol (Ethernet) :
PROFINET Dual Port (optional via external connection module CDF600-2) EtherCAT (optional via external connection module CDF600)
CAN bus : V
Function (CAN bus) : SICK CAN sensor network (Master/Slave, Multiplexer/Server)
Protocol (CAN bus) : CANopen, CSN (SICK CAN Sensor Network)
Data transmission rate (CAN bus) : 20 kbit/s ... 1 Mbit/s
PROFIBUS DP : V
Remark (PROFIBUS DP) : Optional via external connection module (CDF600-2)
DeviceNet : V
Remark (DeviceNet) : Optional via external connection module (CDM + CMF)
Reading pulse : Auto pulse, CAN, Non-powered, Switching inputs, Serial interface
Optical indicators : 6 LEDs (Ready, Result, laser, Data, CAN, LNK TX)
Acoustic indicators : Beeper/buzzer (can be switched off, can be allocated as a result indication function)
Configuration software : SOPAS ET
MECHANICS/ ELECTRONICS
Electrical connection : 1 x 15-pin D-Sub HD male connector (0.9 m)
Operating voltage : 10 V DC ... 30 V DC
Power consumption : 4.5 W
Housing : Die-cast aluminum
Housing color : Light blue (RAL 5012)
Front screen : Glass
Enclosure rating : IP 65 (DIN 40 050)
Protection class : III (VDE 0106/IEC 1010-1)
Weight : 225 g, with connecting cable
Dimensions : 61 mm x 66 mm x 38 mm
>하이온아이티
주소 : 서울 금천구 가산디지털2로 165, 1304호 (백상스타타워2차)
대표번호 : 02-2038-0018 / 이메일 : hion@hionit.com
홈페이지 : http://hionsmart.com
Siemens s7 300-400-sm 338 ultrasonic position encoding moduleDien Ha The
Siemens ,
Catalog Thiết Bị Điện Siemens , Catalog Thiết Tự Động
Catalog Phụ Kiện Siemens , Catalog Phụ Kiện,
Catalog Siemens , Catalog,
https://www.dienhathe.com,
Chi tiết các sản phẩm khác của Siemens tại https://dienhathe.com
Xem thêm các Catalog khác của Siemens tại https://dienhathe.info
Để nhận báo giá sản phẩm Siemens vui lòng gọi: 0907.764.966
5. 1. General information
1.1 Warnings, legal information and safety
1.1.1 Warnings and notes
Throughout this document, a number of warnings and notes with helpful user information will be presented.
To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-
al text.
Warnings
Warnings indicate a potentially dangerous situation, which could result in death, personal in-
jury or damaged equipment, if certain guidelines are not followed.
Notes
Notes provide general information, which will be helpful for the reader to bear in mind.
1.1.2 Legal information and disclaimer
DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how
to install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for the
installation or the operation of the set must be contacted.
The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the war-
ranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
1.1.3 Safety issues
Installing and operating the Multi-line 2 unit may imply work with dangerous currents and voltages. Therefore,
the installation should only be carried out by authorised personnel who understand the risks involved in work-
ing with live electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-
puts as this could lead to injury or death.
1.1.4 Electrostatic discharge awareness
Sufficient care must be taken to protect the terminal against static discharges during the installation. Once the
unit is installed and connected, these precautions are no longer necessary.
1.1.5 Factory settings
The Multi-line 2 unit is delivered from factory with certain factory settings. These are based on average values
and are not necessarily the correct settings for matching the engine/generator set in question. Precautions
must be taken to check the settings before running the engine/generator set.
AGC-4 installation instructions 4189340687
UK
General information
DEIF A/S Page 5 of 69
6. 1.2 About the installation instructions
1.2.1 General purpose
These Installation Instructions mainly include general product and hardware information, mounting instruc-
tions, terminal strip descriptions, I/O lists and wiring descriptions.
The general purpose of this document is to give the user important information to be used in the installation of
the unit.
Please make sure to read this document before starting to work with the Multi-line 2 unit and
the gen-set to be controlled. Failure to do this could result in human injury or damage to the
equipment.
1.2.2 Intended users
These Installation Instructions are mainly intended for the person responsible for the design and installation.
In most cases, this would be a panel builder designer. Naturally, other users might also find useful information
in the document.
1.2.3 Contents and overall structure
This document is divided into chapters, and in order to make the structure simple and easy to use, each
chapter will begin from the top of a new page.
AGC-4 installation instructions 4189340687
UK
General information
DEIF A/S Page 6 of 69
7. 2. General product information
2.1 AGC-4 product information
2.1.1 Introduction
The AGC is part of the DEIF Multi-line 2 product family. Multi-line 2 is a complete range of multi-function gen-
erator protection and control products integrating all the functions you need into one compact and attractive
solution.
The concept of the AGC is to offer a cost-effective solution to genset builders, who need a flexible generator
protection and control unit for medium to large genset applications. Being part of the Multi-line product family,
the standard functions can be supplemented with a variety of optional functions.
2.1.2 Type of product
The Automatic Genset Controller is a micro-processor based control unit containing all necessary functions
for protection and control of a genset.
It contains all necessary 3-phase measuring circuits, and all values and alarms are presented on the LCD
display.
2.1.3 Options
The Multi-line 2 product range consists of different basic versions, which can be supplemented with the flexi-
ble options needed to provide the optimum solution. The options cover e.g. various protections for generator,
busbar and mains, voltage/VAr/PF control, various outputs, power management, serial communication, addi-
tional operator display etc.
2.2 Standard functions
2.2.1 Operation modes
● Automatic Mains Failure
● Island operation
● Fixed power/base load
● Peak shaving
● Load takeover
● Mains power export
2.2.2 Engine control
● Start/stop sequences
● Run and stop coil
● Relay outputs for governor control
2.2.3 Generator protection (ANSI)
● 2 x reverse power (32)
● 5 x overload (32)
● 6 x overcurrent (50/51)
● 2 x overvoltage (59)
● 3 x undervoltage (27)
● 3 x over-/underfrequency (81)
● Voltage-dependent overcurrent (51V)
● Current/voltage unbalance (60)
AGC-4 installation instructions 4189340687
UK
General product information
DEIF A/S Page 7 of 69
8. ● Loss of excitation/overexcitation (40/32RV)
● Non-essential load/load shedding, 3 levels (I, Hz, P>, P>>)
● Multi-inputs (digital, 4-20 mA, 0-40V DC, Pt100, Pt1000 or VDO)
● Digital inputs
2.2.4 Busbar protection (ANSI)
● 3 x overvoltage (59)
● 4 x undervoltage (27)
● 3 x overfrequency (81)
● 4 x underfrequency (81)
● Voltage unbalance (60)
2.2.5 Display
● Prepared for remote mounting
● Push-buttons for start and stop
● Push-buttons for breaker operations
● Status texts
2.2.6 M-Logic
● Simple logic configuration tool
● Selectable input events
● Selectable output commands
2.3 Standard and optional applications
In the following sections, the standard and optional applications of the AGC will be presented. In addition, the
correct application configuration for the different applications is listed. It is only possible to use the unit for one
of the purposes, e.g. AMF (Automatic Mains Failure). The selection must be made on site.
All units are supplied with AMF as factory setting.
2.3.1 Automatic Mains Failure, AMF
G
Controller
Load
AGC-4 installation instructions 4189340687
UK
General product information
DEIF A/S Page 8 of 69
9. No. Setting Setting
6071 Genset mode AMF AMF
2.3.2 Island operation
G
Controller
Load
No. Setting Setting
6071 Genset mode Island operation Island operation
2.3.3 Fixed power/base load
G
Controller
Load
No. Setting Setting
6071 Genset mode Fixed power Fixed power
AGC-4 installation instructions 4189340687
UK
General product information
DEIF A/S Page 9 of 69
10. 2.3.4 Peak shaving
G
Controller
Load
P/4-20 mA
TRANSDUCER
No. Setting Setting
6071 Genset mode Peak shaving Peak shaving
2.3.5 Load takeover
G
Controller
Load
P/4-20 mA
TRANSDUCER
No. Setting Setting
6071 Genset mode Load takeover Load takeover
AGC-4 installation instructions 4189340687
UK
General product information
DEIF A/S Page 10 of 69
11. 2.3.6 Mains power export (fixed power to mains)
G
Controller
Load
P/4-20 mA
TRANSDUCER
No. Setting Setting
6071 Genset mode Mains power export Mains power export
2.3.7 Multiple gensets, analogue load sharing
G
Controller
Load
G
Controller
No. Setting Setting
6071 Genset mode Island operation Island operation
2.3.8 Multiple gensets, power management
For information about the power management application, please refer to "Description of Op-
tion G4, G5 and G8".
AGC-4 installation instructions 4189340687
UK
General product information
DEIF A/S Page 11 of 69
12. 3. Mounting
3.1 AGC-4 mounting
3.1.1 Mounting of the unit
The unit is designed for mounting inside the switchboard. The display can be installed on the switchboard
door and connected to the main unit with a display cable. The technical specifications include detailed infor-
mation about:
● Unit dimensions
● Panel cut-out
● Screw hole positions and dimensions
3.1.2 Panel cut-out
In order to ensure optimum mounting, the switchboard door must be cut out according to the panel cut-out
illustration in the chapter Technical information.
3.1.3 Mounting instructions
The unit can be mounted in two different ways:
1. Directly mounted on a DIN rail.
2. Fastened with screws to the rear side of the cabinet. Six screw holes are available for this mounting
method.
DEIF recommends using the screw hole fastening.
AGC-4 installation instructions 4189340687
UK
Mounting
DEIF A/S Page 12 of 69
13. 4. Hardware
4.1 Board slot positions
The unit housing is divided into board slot positions. This means that the unit consists of a number of printed
circuit boards (PCB) mounted in numbered slots. The green terminal blocks are then mounted in the PCBs.
Some of these board slots are standard and some are intended for options. The board slot positions are ar-
ranged as illustrated below.
Slot type Option Slot #1 Slot #3 Slot #5 Slot #7
Terminals 1-28 37-64 73-89 98-125
Power supply Standard X
AC measurements Standard X
Engine interface Standard/M4 X
Load sharing G3 X
Power management G4/G5/G7/G8 X
Engine communication H7 X
I/O extension M12 X
Slot type Option Slot #2 Slot #4 Slot #6 Slot #8
Terminals 29-34 65-72 90-97 126-133
Analogue controller outputs E1/E2 X
Analogue transducer outputs F1 X
Combination outputs EF2/EF4/EF5/EF6 X
Serial communication H2/H3/H8.2/H9 X
Engine communication H5/H6 X
I/O extension cards M13.2/M14.2 X
I/O extension cards M13.6/M14.6/M15 X
I/O extension cards M13.8/M14.8/H8.8 X
Plant management G7 X
Only hardware options, which will affect the hardware of the unit, are represented in the table.
The software options will be seen through the PC utility software. The software options that are
not represented in the above table can be found in the data sheet.
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 13 of 69
14. 4.1.1 Unit top side overview
An overview of the terminals is presented below. The slot positions are as follows:
Ethernet
787776757473 96 979594929190 9389888785 8683 8482818079
727169 70686765 6662 6359 60 615856 575553 54 645251504947464443 45 4841403837 39 42
Service port Display
Ethernet
CAN B
CAN A
Power
Self check ok
Alarm inhibit
1
4
9
5 6
3
7 8
2
1
:
The numbers in the drawing above refer to the slot numbers indicated in the table below.
No. Slot
1 #1, terminal 1-28, power supply (standard)
2 #2, terminal 29-36, communication and I/O extensions
3 #3, terminal 37-64, in-/outputs/load sharing
4 #4, terminal 65-72, governor, AVR, in-/outputs (standard)
5 #5, terminal 73-89, AC measuring (standard)
6 #6, terminal 90-97, in-/outputs
7 #7, terminal 98-125, engine I/F (standard)
8 #8, terminal 126-133, engine communication, in-/outputs, plant management comm.
9 LED I/F
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 14 of 69
15. 4.1.2 Terminal strip overviews
Standard unit
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 15 of 69
16. The hardware shown in slot #3 is option M12 and G3. For a detailed description of these op-
tions, please refer to the option manuals.
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 16 of 69
18. The hardware shown in slot #3 is option M12 and G3. For a detailed description of these op-
tions, please refer to the option manuals.
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 18 of 69
20. The hardware shown in slot #3 is option M12 and G3. For a detailed description of these op-
tions, please refer to the option manuals.
4.1.3 Input/output lists
In the I/O lists, the following terms will be used in connection with the relay outputs:
NO means Normally Open
NC means Normally Closed
NE means Normally Energised
ND means Normally Deenergised
Com. means common terminal
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 20 of 69
21. 4.1.4 Slot #1, power supply PCB
Term. Function Technical data Description
1 +12/24V DC 12/24V DC
+/-30%
Power supply
2 0V DC
3 NC Status relay
24V DC/1 A
Normally closed relay, processor/power supply
status supervision4 Com.
5 NO Relay 05
250V AC/8 A
Central alarm HORN/configurable
6 Com.
7 NC
8 NO Relay 08
250V AC/8 A
Open mains breaker/configurable
9 Com.
10 NC
11 NO Relay 11
250V AC/8 A
Close mains breaker (synchronising)/configurable
12 Com.
13 NC
14 NO Relay
250V AC/8 A
Open generator breaker
15 Com.
16 NC
17 NO Relay
250V AC/8 A
Close generator breaker (synchronising)
18 Com.
19 NC
20 Open collector 1 Transistor output/Relay 20 Pulse output 1, kWh counter/configurable
21 Open collector 2 Transistor output/Relay 21 Pulse output 2, kVArh counter/configurable
22 Com. Common Common terminal for terminals 20 and 21
23 Digital input 23 Optocoupler Configurable
24 Digital input 24 Optocoupler Mains breaker open/configurable
25 Digital input 25 Optocoupler Mains breaker closed/configurable
26 Digital input 26 Optocoupler Generator breaker open
27 Digital input 27 Optocoupler Generator breaker closed
28 Com. Common Common for terminals 23 to 27
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 21 of 69
22. 4.1.5 Slot #1, power supply PCB - AGC mains unit
The I/O list below is for the AGC mains unit.
Term. Function Technical data Description
1 +12/24V DC 12/24V DC
+/-30%
Power supply
2 0V DC
3 NC Status relay
24V DC/1 A
Normally closed relay, processor/power supply
status supervision4 Com.
5 NO Relay 05
250V AC/8 A
Central alarm HORN/configurable
6 Com.
7 NC
8 NO Relay 08
250V AC/8 A
Open mains breaker/configurable
9 Com.
10 NC
11 NO Relay 11
250V AC/8 A
Close mains breaker (synchronising)/configurable
12 Com.
13 NC
14 NO Relay 14
250V AC/8 A
Open tie breaker/configurable
15 Com.
16 NC
17 NO Relay 17
250V AC/8 A
Close tie breaker (synchronising)/configurable
18 Com.
19 NC
20 Open collector 1 Transistor output/Relay 20 Pulse output 1, kWh counter/configurable
21 Open collector 2 Transistor output/Relay 21 Pulse output 2, kVArh counter/configurable
22 Com. Common Common terminal for terminals 20 and 21
23 Digital input 23 Optocoupler Configurable
24 Digital input 24 Optocoupler Mains breaker open/configurable
25 Digital input 25 Optocoupler Mains breaker closed/configurable
26 Digital input 26 Optocoupler Tie breaker open/configurable
27 Digital input 27 Optocoupler Tie breaker closed/configurable
28 Com. Common Common for terminals 23 to 27
4.1.6 Slot #2, serial communication (option H)
Modbus (option H2)
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 22 of 69
23. Term. Function Description
29 DATA + (A) Modbus RTU, RS485
30 GND
31 DATA - (B)
32 Not used
33 DATA + (A)
34 Not used
35 DATA - (B)
36 Not used
The serial communication line should be terminated between DATA + and DATA - with a resistor equal to the
cable impedance. The terminals 29/33 and 31/35 are internally connected.
Never connect the GND terminal 30 to earth. Only connect it to a third wire in the communica-
tion cable!
Modbus (option H9)
Term. Function Description
29 DATA + (A) Modbus RTU, RS232
30 GND
31 DATA - (B)
32 Not used
33 DATA + (A)
34 Not used
35 DATA - (B)
36 Not used
The serial communication line should be terminated between DATA + and DATA - with a resistor equal to the
cable impedance. The terminals 29/33 and 31/35 are internally connected.
Never connect the GND terminal 30 to earth. Only connect it to a third wire in the communica-
tion cable!
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 23 of 69
24. Profibus (option H3)
Term. Function Description
29 DATA + (B) Pin 3 on 9 pole sub-D connector
Pin 5 on 9 pole sub-D connector
Pin 8 on 9 pole sub-D connector
30 GND
31 DATA - (A)
32 DATA + (B)
33 GND
34 DATA - (A)
35 Not used
36 Not used
Never connect the GND terminal 30 to earth. Only connect it to a third wire in the communica-
tion cable!
4.1.7 Slot #2, external I/O module (option H8.2)
Term. Function Description
29 CAN-H CANbus card option H8.2
30 CAN-GND
31 CAN-L
32 CAN-H
33 CAN-GND
34 CAN-L
35 Not used
36 Not used
Terminals 29 and 32 are internally connected. Terminals 31 and 34 are internally connected.
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 24 of 69
25. 4.1.8 Slot #2, 7 digital inputs (option M13.2)
Term. Function Technical data Description
29 Binary input 29 Optocoupler Configurable
30 Binary input 30 Optocoupler Configurable
31 Binary input 31 Optocoupler Configurable
32 Binary input 32 Optocoupler Configurable
33 Binary input 33 Optocoupler Configurable
34 Binary input 34 Optocoupler Configurable
35 Binary input 35 Optocoupler Configurable
36 Com. Optocoupler Common for terminals 29-35
4.1.9 Slot #2, relay outputs (option M14.2)
Term. Function Technical data Description
29 NE/ND Relay 29
250V AC/5 A
Configurable
30 Com.
31 NE/ND Relay 31
250V AC/5 A
Configurable
32 Com.
33 NE/ND Relay 33
250V AC/5 A
Configurable
34 Com.
35 NE/ND Relay 35
250V AC/5 A
Configurable
36 Com.
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 25 of 69
26. 4.1.10 Slot #3, load sharing control (option G3)
Term. Function Technical data Description
37 -5…0…5V DC Analogue I/O Active load sharing line
38 Com. Common Common for load sharing lines
39 -5…0…5V DC Analogue I/O Reactive load sharing
40 -10…0…10V DC Analogue I/O f/P setpoint (passive)
41 Com. Common Common for 40/42
42 -10…0…10V DC Analogue I/O U/Q setpoint (passive)
43
Not used
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 26 of 69
27. 4.1.11 Slot #3, 13 binary inputs and 4 relay outputs (option M12)
Term. Function Technical data Description
37
Not used38
39
40 -10/+10V DC Analogue I/O f/P setpoint
41 Com. Common Common
42 -10/+10V DC Analogue I/O U/Q setpoint
43 Binary input Optocoupler Configurable
44 Binary input Optocoupler Configurable
45 Binary input Optocoupler Configurable
46 Binary input Optocoupler Configurable
47 Binary input Optocoupler Configurable
48 Binary input Optocoupler Configurable
49 Binary input Optocoupler Configurable
50 Binary input Optocoupler Configurable
51 Binary input Optocoupler Configurable
52 Binary input Optocoupler Configurable
53 Binary input Optocoupler Configurable
54 Binary input Optocoupler Configurable
55 Binary input Optocoupler Configurable
56 Com. Common Common for terminals 43 to 55
57 NE/ND Relay 57
250V AC/5 A
Configurable
58 Com.
59 NE/ND Relay 59
250V AC/5 A
Configurable
60 Com.
61 NE/ND Relay 61
250V AC/5 A
Configurable
62 Com.
63 NE/ND Relay 63
250V AC/5 A
Configurable
64 Com.
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 27 of 69
28. 4.1.12 Slot #4, relay outputs (option M14.4, standard)
Term. Function Technical data Description
65 NE/ND Relay 65
250V AC/5 A
Generator GOV: Increase frequency/configurable
66 Com.
67 NE/ND Relay 67
250V AC/5 A
Generator GOV: Decrease frequency/configurable
68 Com.
69 Not used Relay 69
250V AC/5 A
Configurable
70 Com.
71 Not used Relay 71
250V AC/5 A
Configurable
72 Com.
4.1.13 Slot #4, analogue outputs for GOV/AVR or transducer (option E1)
Term. Function Description
65 Not used
66 +/-25 mA Configurable
67 0
68 Not used
69 Not used
70 +/-25 mA Configurable
71 0
72 Not used
AVR control requires option D1.
4.1.14 Slot #4, analogue outputs for GOV/AVR or transducer (option EF2)
Term. Function Description
65 Not used
66 +/-25 mA Configurable
67 0
68 Not used
69 Not used
70 0(4)-20 mA out Configurable
71 0
72 Not used
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 28 of 69
29. AVR control requires option D1.
4.1.15 Slot #4, combination outputs for GOV/AVR or transducer (option EF4)
Term. Function Description
65 +/-25 mA Configurable
66 0
67 Not used
68 Not used
69 Relay Relay 69
70 Relay
71 Relay Relay 71
72 Relay
AVR control requires option D1.
4.1.16 Slot #4, PWM, relay and analogue outputs for GOV/AVR (option EF5)
Term. Function Description
65 +/-25 mA AVR setpoint output
66 0
67 PWM + PWM speed governor signal
68 PWM -
69 NO Relay output for AVR. Raise voltage
70 Com.
71 NO Relay output for AVR. Lower voltage
72 Com.
AVR control requires option D1.
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 29 of 69
30. 4.1.17 Slot #4, PWM and analogue outputs for GOV/AVR (option EF6)
Term. Function Description
65 Not used
66 Not used
67 0 Speed governor, AVR or transducer output 68
68 +/-25 mA
69 PWM - PWM speed governor signal
70 PWM +
71 0 Speed governor, AVR or transducer output 72
72 +/-25 mA
Connect PWM - to the engine battery negative and PWM + to the engine control system S-SPD
(speed) input (called RATED SPEED on the ADEM controller and PRIMARY THROTTLE on the
PEEC controller).
AVR control requires option D1.
4.1.18 Slot #4, analogue outputs for GOV/AVR or transducer (option E2)
Term. Function Description
65 Not used
66 0(4)-20 mA out Configurable
67 0
68 Not used
69 Not used
70 0(4)-20 mA out Configurable
71 0
72 Not used
AVR control requires option D1.
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 30 of 69
31. 4.1.19 Slot #5, AC measuring
Term. Function Technical data Description
73 I L1, s1 Generator current L1 x/1 A or x/5 A input
74 I L1, s2
75 I L2, s1 Generator current L2 x/1 A or x/5 A input
76 I L2, s2
77 I L3, s1 Generator current L3 x/1 A or x/5 A input
78 I L3, s2
79 U L1 Generator voltage L1 Max. 690V AC phase-phase value
80 Not used
81 U L2 Generator voltage L2 Max. 690V AC phase-phase value
82 Not used
83 U L3 Generator voltage L3 Max. 690V AC phase-phase value
84 UNEUTRAL Generator voltage neutral
85 U L1 Mains/bus voltage L1 Max. 690V AC phase-phase value
86 Not used
87 U L2 Mains/bus voltage L2 Max. 690V AC phase-phase value
88 UNEUTRAL Mains/bus voltage neutral
89 U L3 Mains/bus voltage L3 Max. 690V AC phase-phase value
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 31 of 69
32. 4.1.20 Slot #5, AC measuring - AGC mains unit
The I/O list below is for the AGC mains unit (G5) and for the AGC group tie (G7) and plant con-
trol unit (G7).
Term. Function Technical data Description
73 I L1, s1 Mains current L1 x/1 A or x/5 A input
74 I L1, s2
75 I L2, s1 Mains current L2 x/1 A or x/5 A input
76 I L2, s2
77 I L3, s1 Mains current L3 x/1 A or x/5 A input
78 I L3, s2
79 U L1 Mains voltage L1 Max. 690V AC phase-phase value
80 Not used
81 U L2 Mains voltage L2 Max. 690V AC phase-phase value
82 Not used
83 U L3 Mains voltage L3 Max. 690V AC phase-phase value
84 UNEUTRAL Mains voltage neutral
85 U L1 Bus voltage L1 Max. 690V AC phase-phase value
86 Not used
87 U L2 Bus voltage L2 Max. 690V AC phase-phase value
88 UNEUTRAL Bus voltage neutral
89 U L3 Bus voltage L3 Max. 690V AC phase-phase value
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 32 of 69
33. 4.1.21 Slot #5, AC measuring - AGC BTB unit
The I/O list below is for the AGC BTB unit.
Term. Function Technical data Description
73 I L1, s1 Bus A current L1 x/1 A or x/5 A input
74 I L1, s2
75 I L2, s1 Bus A current L2 x/1 A or x/5 A input
76 I L2, s2
77 I L3, s1 Bus A current L3 x/1 A or x/5 A input
78 I L3, s2
79 U L1 Bus A voltage L1 Max. 690V AC phase-phase value
80 Not used
81 U L2 Bus A voltage L2 Max. 690V AC phase-phase value
82 Not used
83 U L3 Bus A voltage L3 Max. 690V AC phase-phase value
84 UNEUTRAL Bus A voltage neutral
85 U L1 Bus B voltage L1 Max. 690V AC phase-phase value
86 Not used
87 U L2 Bus B voltage L2 Max. 690V AC phase-phase value
88 UNEUTRAL Bus B voltage neutral
89 U L3 Bus B voltage L3 Max. 690V AC phase-phase value
4.1.22 Slot #6, 7 digital inputs (option M13.6)
Term. Function Technical data Description
90 Com. Common Common for terminals 90-97
91 Binary input 91 Optocoupler Configurable
92 Binary input 92 Optocoupler Configurable
93 Binary input 93 Optocoupler Configurable
94 Binary input 94 Optocoupler Configurable
95 Binary input 95 Optocoupler Configurable
96 Binary input 96 Optocoupler Configurable
97 Binary input 97 Optocoupler Configurable
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 33 of 69
34. 4.1.23 Slot #6, 4 relay outputs (option M14.6)
Term. Function Technical data Description
90 NE/ND Relay 90
250V AC 5 A
Configurable
91 Com.
92 NE/ND Relay 92
250V AC 5 A
Configurable
93 Com.
94 NE/ND Relay 94
250V AC 5 A
Configurable
95 Com.
96 NE/ND Relay 96
250V AC 5 A
Configurable
97 Com.
4.1.24 Slot #6, 4 analogue inputs (option M15.6)
Term. Function Technical data Description
90 Analogue input 91 - Common Configurable
91 Analogue input 91 + 4-20 mA in
92 Analogue input 93 - Common Configurable
93 Analogue input 93 + 4-20 mA in
94 Analogue input 95 - Common Configurable
95 Analogue input 95 + 4-20 mA in
96 Analogue input 97 - Common Configurable
97 Analogue input 97 + 4-20 mA in
4.1.25 Slot #6, analogue outputs for transducer (option F1)
Term. Function Description
90 Not used
91 0 Transducer output
92 0(4)-20 mA out
93 Not used
94 Not used
95 0 Transducer output
96 0(4)-20 mA out
97 Not used
The option F1 cannot be used for GOV/AVR outputs.
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 34 of 69
35. 4.1.26 Slot #7, engine interface card (std.)
Term. Function Technical data Description
98 +12/24V DC 12/24V DC
+/-30%
DC power supply
99 0V DC
100 MPU input 0.5-70V AC/
10-10,000 Hz
Magnetic pick-up with wire break
101 MPU GND
102 A 0(4)-20 mA
Digital
Pt100
Pt1000
VDO
0-40V DC
Multi-input 1
103 B
104 C
105 A Multi-input 2
106 B
107 C
108 A Multi-input 3
109 B
110 C
111 Com. Common Common for terminals 112-117
112 Digital input 112 Optocoupler Configurable
113 Digital input 113 Optocoupler Configurable
114 Digital input 114 Optocoupler Configurable
115 Digital input 115 Optocoupler Configurable
116 Digital input 116 Optocoupler Configurable
117 Digital input 117 Optocoupler Configurable
118 Digital input 118 Optocoupler Emergency stop and common for 119 and 120
119 NO Relay
24V DC/5 A
Run coil
120 NO Relay
24V DC/5 A
Start prepare
121 Com. Relay
250V AC/5 A
Crank (starter)
122 NO
123 Com. Relay
24V DC/5 A
Stop coil w/wire failure detection
124 NO
A1 CAN-H CANbus interface A
(option G4, G5, G7, G8 or H7)A2 GND
A3 CAN-L
B1 CAN-H CANbus interface B
(option G4 or G5, G8)B2 GND
B3 CAN-L
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 35 of 69
36. 4.1.27 Slot #7, engine interface card (std.) AGC mains/BTB/group/plant
Term. Function Technical data Description
98 +12/24V DC 12/24V DC
+/-30%
DC power supply
99 0V DC
100 MPU input 0.5-70V AC/
10-10,000 Hz
Magnetic pick-up
101 MPU GND
102 A 0(4)-20 mA
Digital
Pt100
Pt1000
VDO
0-40V DC
Multi-input 1
103 B
104 C
105 A Multi-input 2
106 B
107 C
108 A Multi-input 3
109 B
110 C
111 Com. Common Common for terminals 112-117
112 Digital input 112 Optocoupler Configurable
113 Digital input 113 Optocoupler Configurable
114 Digital input 114 Optocoupler Configurable
115 Digital input 115 Optocoupler Configurable
116 Digital input 116 Optocoupler Configurable
117 Digital input 117 Optocoupler Configurable
118 Digital input 118 Optocoupler Emergency stop and common for 119 and 120
119 NO Relay
24V DC/5 A
Not used
120 NO Relay
24V DC/5 A
Not used
121 Com. Relay
250V AC/5 A
Not used
122 NO
123 Com. Relay
24V DC/5 A
Not used
124 NO
A1 CAN-H CANbus interface A
(option G4, G5 or G7)A2 GND
A3 CAN-L
B1 CAN-H CANbus interface B
(option G4 or G5)B2 GND
B3 CAN-L
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 36 of 69
37. 4.1.28 Slot #8, engine interface communication (option H5)
Term. Function Description
126 Not used CANbus-based engine interface communication
127 Not used
128 CAN-L
129 GND
130 CAN-H
131 CAN-L
132 GND
133 CAN-H
4.1.29 Slot #8, Cummins engine interface communication (option H6)
Term. Function Description
126 Not used Modbus RTU (RS485)
127 DATA - (B)
128 Not used
129 DATA + (A)
130 Not used
131 DATA - (B)
132 GND
133 DATA + (A)
4.1.30 Slot #8, 7 digital inputs (option M13.8)
Term. Function Technical data Description
126 Com. Common Common for terminals 127-133
127 Digital input 127 Optocoupler Configurable
128 Digital input 128 Optocoupler Configurable
129 Digital input 129 Optocoupler Configurable
130 Digital input 130 Optocoupler Configurable
131 Digital input 131 Optocoupler Configurable
132 Digital input 132 Optocoupler Configurable
133 Digital input 133 Optocoupler Configurable
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 37 of 69
38. 4.1.31 Slot #8, 4 relay outputs (option M14.8)
Term. Function Technical data Description
126 NE/ND Relay 126
250V AC/5 A
Configurable
127 Com.
128 NE/ND Relay 128
250V AC/5 A
Configurable
129 Com.
130 NE/ND Relay 130
250V AC/5 A
Configurable
131 Com.
132 NE/ND Relay 132
250V AC/5 A
Configurable
133 Com.
4.1.32 Slot #8, external I/O module (option H8.8)
Term. Function Description
126 Not used CANbus card option H8.8
127 Not used
128 CAN-L
129 GND
130 CAN-H
131 CAN-L
132 GND
133 CAN-H
Terminals 133 and 130 are internally connected. Terminals 131 and 128 are internally connec-
ted.
4.1.33 Slot #8, plant management (option G7, AGC group tie)
Term. Function Description
126 Not used CANbus card option G7
127 Not used
128 CAN-L
129 GND
130 CAN-H
131 CAN-L
132 GND
133 CAN-H
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 38 of 69
39. Terminals 133 and 130 are internally connected. Terminals 131 and 128 are internally connec-
ted.
AGC-4 installation instructions 4189340687
UK
Hardware
DEIF A/S Page 39 of 69
40. 5. Wirings
5.1 AC connections
The Multi-line 2 unit can be wired up in 1-phase, 2-phase or 3-phase configuration.
Contact the switchboard manufacturer for accurate information about required wiring for the
specific application.
5.1.1 Neutral line (N)
When three-phase distribution systems are used, the neutral line (N) is only necessary if it is a three-phase +
neutral system. If the distribution system is a three-phase system without neutral, then leave the terminals 84
and 88 empty.
5.1.2 Current transformer grounding
The current transformer ground connection can be made on s1 or s2 connection, whichever is preferred.
5.1.3 Fuses
If the cables are protected with fuses, then use 2 A, slow blow.
5.1.4 Breaker wiring
The breaker off wiring is an example only.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 40 of 69
41. 5.1.5 3-phase
AMF, fixed power, peak shaving, load takeover, mains power export.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 41 of 69
43. 5.1.7 2-phase L1L2 (split phase)
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 43 of 69
44. 5.1.8 2-phase L1L3 (split phase)
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 44 of 69
45. 5.1.9 Island mode and power management (option G4/G5/G8)
1-phase and 2-phase (split phase) systems also supported.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 45 of 69
46. 5.1.10 Power management (option G5), AGC mains
1-phase and 2-phase (split phase) systems also supported.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 46 of 69
47. 5.1.11 Power management (option G5), AGC BTB
1-phase and 2-phase (split phase) systems also supported.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 47 of 69
48. 5.2 DC connections
5.2.1 Load sharing lines (option G3)
37 38 39
PS COMMON QS
LOAD SHARING LINES
±0...5 ±0...5
V DC V DC
Multi-line 2
37 38 39
PS COMMON QS
LOAD SHARING LINES
±0...5 ±0...5
V DC V DC
Multi-line 2
37 38 39
PS COMMON QS
LOAD SHARING LINES
±0...5 ±0...5
V DC V DC
Multi-line 2
Always use screened cable
5.2.2 Digital inputs
Battery positive to input: Battery negative to input:
Multi-line 2
23
28 (COM.)
Switch
12/24V DC
Multi-line 2
23
28 (COM.)
Switch
12/24V DC
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 48 of 69
49. Emergency stop:
Multi-line 2
118
99 (COM.)
12/24V DC
0V DC
5.2.3 Analogue inputs
4-20 mA (option M15)
Active transducer
91
0V DC
Multi-line 2
Analogue input 91
90 (Common)
+12/24V DC + +
- -
4-20 mA
transducer
Measurement
Passive transducer
91
0V DC
Multi-line 2
Analogue input 91
90 (Common)
+12/24V DC + -
4-20 mA
transducer
Measurement
V DC sensor
91
Multi-line 2
Analogue input 91
90 (Common)
0-10V DC
sensor
R = 450 Ω
External setpoints (option G3/M12)
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 49 of 69
50. The setpoint inputs are passive, i.e. an external power source is needed. This can be an active output from
e.g. a PLC, or a potentiometer can be used.
0-10V DC input using potentiometer
Multi-line 2
40 or 42
41 (Common)
10V DC
0V DC
Ø
Ø
2000 Ohm
¼ W
potentiometer
+/-10V DC input using potentiometer
Multi-line 2
40 or 42
41 (Common)
10V DC
-10V DC
Ø
Ø
2000 Ohm
¼ W
potentiometer
0V DC Ø
5.2.4 Multi-inputs
The multi-inputs are placed in slot #7, the terminal numbers for the individual multi-inputs can be seen in the
"Input/output list".
0(4)-20 mA
Active transducer
0V DC
Multi-line 2
Multi-input
+12/24V DC + +
- -
4-20 mA
transducer
Measurement
A
B
C
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 50 of 69
51. Passive transducer
0 V DC
Multi-line 2
Multi-input
+12/24V DC + -
4-20 mA
transducer
Measurement
A
B
C
If the passive sensor has its own battery supply, the voltage must not exceed 30V DC.
5.2.5 Digital inputs
Multi-line 2
Multi-input
A
B
C
R
The resistor is only mounted if wire fail supervision is required. The value of the resistor
should be 270 Ω +/-10%.
5.2.6 Pt100/Pt1000
2-wire
Multi-line 2
Multi-input
A
B
C
Pt100/1000
3-wire
Multi-line 2
Multi-input
A
B
C
Pt100/1000
0
I
P
5.2.7 VDO
1-wire 2-wire
Multi-line 2
Multi-input
A
B
C
VDO Multi-line 2
Multi-input
A
B
C
VDO
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 51 of 69
52. 5.2.8 0-40V DC
Multi-line 2
Multi-input
A
B
C
Battery
0-40V DC
0V DC
5.2.9 RPM input
Magnetic pick-up (MPU)
Multi-line 2
100
MPU
Output
101
NPN sensor
Multi-line 2
100
NPN
Output
101
+V DC
0V DC
R+12/24V DC
0V DC
C
C
C = 22 nF, 100V foil type
R = 1200Ω@24V DC, 600Ω@12V DC
PNP sensor
Multi-line 2
100
PNP
Output
101
+V DC
0V DC
+12/24V DC
0V DC
C
CR
C = 22 nF, 100V foil type
R = 1200Ω@24V DC, 600Ω@12V DC
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 52 of 69
53. Charger, W output
Multi-line 2
100
Charger
W
101
C
C = 22 nF, 100V foil type
5.2.10 Stop coil
Multi-line 2
+12/24V DC
123
124
0V DC
Stop coil
A1
A2
Remember to mount the free wheel diode.
5.2.11 Transistor outputs (open collector outputs)
The open collector outputs can be used as kWh and kVArh counter outputs or as relay outputs. The outputs
are low power outputs. For that reason, one of the following circuits must be applied.
External counter: Relay outputs:
20 kWh
Multi-line 2
22 (Com. For 20/21)
External
counter
+12/24 VDC
0 VDC
0,5 µF
100 V
20 (Relay 20)
Multi-line 2
22 (Common)
+12/24 VDC
0 VDC
Relay
A1
A2
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 53 of 69
54. Connection to PLC:
20 kWh
Multi-line 2
22 (Com. For 20/21)
+12/24 VDC
0 VDC
4,7 kΩ
PLC
Input (positive)
Remember to mount the free wheel diode.
Maximum load on the open collector outputs is 10 mA at 24V DC.
5.3 Communication
5.3.1 CANbus (option G4/G5/G8)
Examples with three AGC units connected, e.g. one AGC mains and two generator AGC units.
It is not possible to mix CANbus interface A and B.
Multi-line 2
CANbus interface A
A1 A2 A3
H GND L
Multi-line 2
CANbus interface A
A1 A2 A3
H GND L
Multi-line 2
CANbus interface A
A1 A2 A3
H GND L
120 Ω 120 Ω
Multi-line 2
CANbus interface B
B1 B2 B3
H GND L
Multi-line 2
CANbus interface B
B1 B2 B3
H GND L
Multi-line 2
CANbus interface B
B1 B2 B3
H GND L
120 Ω 120 Ω
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 54 of 69
55. Connect shield to earth at one end only. Shield ends must be insulated with tape or insulation
tubing.
Use shielded twisted cable.
End resistor R = 120 Ohm.
5.3.2 CANbus (option G7)
Example with three AGC group units connected in an island mode plant (no mains (AGC plant unit) is
present). Each of the three group units has a number of gensets connected (max. 16 gensets for each
group). The number of generators in this plant would therefore be between 3 and 48 gensets.
Please refer to paragraph 5.3.1 for information about the connection between the generators and the group
units (only CAN A can be used).
Multi-line 2
CANbus interface 1
130 129 128
H GND L
Multi-line 2
CANbus interface 1
130 129 128
H GND L
Multi-line 2
CANbus interface 1
130 129 128
H GND L
120 Ω 120 Ω
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 55 of 69
56. 5.3.3 Modbus (option H2)
Connection with 2-wire screened cable (recommended):
Multi-line 2
DATA+(A)
29 30 31
DATA(GND)
DATA-(B)
Multi-line 2
DATA+(A)29 30 31
DATA(GND)
DATA-(B)
Multi-line 2
DATA+(A)
29 30 31
DATA(GND)
DATA-(B)
DATA-(B)
PLC or other device
DATA(GND)
DATA+(A)
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
Use shielded twisted cable.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 56 of 69
57. Connection with 3-wire shielded cable:
Multi-line 2
DATA+(A)
29 30 31
DATA(GND)
DATA-(B) Multi-line 2
DATA+(A)
29 30 31
DATA(GND)
DATA-(B)
Multi-line 2
DATA+(A)
29 30 31
DATA(GND)
DATA-(B)
DATA-(B)
PLC or other device
DATA(GND)
DATA+(A)
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
Use shielded twisted cable.
This solution is only feasible if the COM line is insulated. Check PLC/other device before con-
necting.
A non-insulated COM line may result in damage to the equipment.
Normally, the Modbus does not need bias resistors (end terminators). These are only needed
in case of very long lines and/or many nodes (>32) on the Modbus network. If bias resistors
are needed, the calculation should be based on the following data:
- A line internal pull-up bias resistor: 22 kΩ
- B line internal pull-down bias resistor: 22 kΩ
- Receiver input sensitivity: +/-200 mV
- Receiver input impedance: 12 kΩ
Cable: Belden 3105A or equivalent. 22 AWG (0.6 mm2) twisted pair, shielded, <40 mΏ/m, min.
95% shield coverage.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 57 of 69
58. 5.3.4 Profibus DP (option H3)
Connection with 2-wire screened cable (recommended):
Multi-line 2
DATA+(B)
29 30 31
COM
DATA-(A)
Multi-line 2
DATA+(B)29 30 31
COM
DATA-(A)
Multi-line 2
DATA+(B)
29 30 31
COM
DATA-(A)
DATA-(A)
PLC or other device
COM
DATA+(B)
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
Use shielded twisted cable.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 58 of 69
59. 5.3.5 CANbus engine communication (option H5)
Connection with 2-wire screened cable (recommended):
Multi-line 2
CAN-H
133 132 131
CAN-GND
CAN-L
CAN-L
ECM
engine control module
CAN-GND
CAN-H
120 Ω
120 Ω
Connection with 3-wire shielded cable:
Multi-line 2
CAN-H
133 132 131
CAN-GND
CAN-L
CAN-L
ECM
engine control module
CAN-GND
CAN-H
120 Ω
120 Ω
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
Use shielded twisted cable.
End resistor R = 120 Ohm.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 59 of 69
60. The terminating resistor at the engine side might not be needed, please refer to the engine
manufacturer’s literature.
5.3.6 Cummins GCS (option H6)
Multi-line 2, option H6
DATA-B
131 132 133
DATA(GND)
DATA+A
Engine controller,
connector 06
DATA-B
18 20 31
DATA(GND)
DATA+A
RR
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
Use shielded twisted cable.
Normally, the communication does not need bias resistors (end terminators). These are only
needed in case of very long lines between the two modules. If bias resistors are needed, the
calculation should be based on the following data:
- A line internal pull-up bias resistor: 22 kΩ
- B line internal pull-down bias resistor: 22 kΩ
- Receiver input sensitivity: +/-200 mV
- Receiver input impedance: 12 kΩ
Cable: Belden 3105A or equivalent. 22 AWG (0.6 mm2) twisted pair, shielded, <40 mΏ/m, min.
95% shield coverage.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 60 of 69
61. 5.3.7 CANbus engine communication (option H7)
Multi-line 2
CAN-H
A1 A2 A3
CAN-GND
CAN-L
CAN-L
ECM
engine control module
CAN-GND
CAN-H
120 Ω
120 Ω
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
Use shielded twisted cable.
End resistor R = 120 Ohm.
The terminating resistor at the engine side might not be needed, please refer to the engine
manufacturer’s literature.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 61 of 69
62. 5.3.8 External I/O module (option H8)
120Ω
CAN-H
CAN-L
CANopen
CANopen
BECKHOFF
12345678
ONDIP
OptionH8.8
OptionH8.229
133131
31
120Ω
Multi-line 2
5.3.9 Display cable (option J)
A standard computer extension cable can be used (9-pole SUB-D male/female plugs) or a cable can be tail-
ored.
4
5
6
7
8
9
2
1
3
1
2
3
4
5
6
7
8
9
9-p SUB D
male
9-p SUB D
female
Connect shield to plug metallic casing
Wires min. 0.22 m2, max. cable length 6 m.
Cable types: Belden 9540, BICC H8146, Brand Rex BE57540 or equivalent.
No use of tools or brute force when tightening finger-screws on display cable.
AGC-4 installation instructions 4189340687
UK
Wirings
DEIF A/S Page 62 of 69
63. 6. Technical information
6.1 Technical information, AGC-4
6.1.1 Technical specifications
Accuracy Class 1.0
-25...15...30...70°C
Temperature coefficient: +/-0.2% of full scale per 10°C
Class 0.5 with option Q1
Positive, negative and zero sequence alarms: class 1 within 5% voltage unbalance
Class 1.0 for negative sequence current
Fast overcurrent: 3% of 350%*In
Analogue outputs: class 1.0 according to total range
Option EF4/EF5: class 4.0 according to total range
To IEC/EN60688
Operating
temperature
-25…70°C (-13...158°F)
-25...60°C (-13...140°F) if Modbus TCP/IP (option N) is available in the controller.
(UL/cUL Listed: max. surrounding air temperature: 55°C/131°F)
Storage tem-
perature
-40…70°C (-40...158°F)
Climate 97% RH to IEC 60068-2-30
Operating al-
titude
0-4000 m above sea level
Derating 2001-4000 m above sea level:
Max. 480V AC phase-phase 3W4 measuring voltage
Max. 690V AC phase-phase 3W3 measuring voltage
Measuring
voltage
100-690V AC +/-20%
(UL/cUL Listed: 600V AC phase-phase)
Consumption: max. 0.25 VA/phase
Measuring
current
-/1 or -/5 A AC
(UL/cUL Listed: from CTs 1-5 A)
Consumption: max. 0.3 VA/phase
Current over-
load
4 x In continuously
20 x In, 10 sec. (max. 75 A)
80 x In, 1 sec. (max. 300 A)
Measuring
frequency
30...70 Hz
Aux. supply Terminals 1 and 2: 12/24V DC (8...36 V continuously, 6 V 1 sec.). Max. 11 W consump-
tion
Terminals 98 and 99: 12/24V DC (8...36 V continuously, 6 V 1 sec.). Max. 5 W consump-
tion
The aux. supply inputs are to be protected by a 2 A slow blow fuse. (UL/cUL Listed: AWG
24)
AGC-4 installation instructions 4189340687
UK
Technical information
DEIF A/S Page 63 of 69
64. Binary inputs Optocoupler, bi-directional
ON: 8...36V DC
Impedance: 4.7 kΩ
OFF: <2V DC
Analogue in-
puts
-10...+10V DC: not galvanically separated. Impedance: 100 kΩ
0(4)...20 mA: impedance 50 Ω. Not galvanically separated
RPM (MPU): 2...70V AC, 10...10000 Hz, max. 50 kΩ
Multi-inputs 0(4)...20 mA: 0-20 mA, +/-1%. Not galvanically separated
Binary: max. resistance for ON detection: 100 Ω. Not galvanically separated
Pt100/1000: -40...250°C, +/-1%. Not galvanically separated. To IEC/EN60751
VDO: 0-1700 Ω, +/-2%. Not galvanically separated
V DC: 0...40V DC, +/-1%. Not galvanically separated
Relay outputs Electrical rating: 250V AC/30V DC, 5 A. (UL/cUL Listed: 250V AC/24V DC, 2 A resistive
load)
Thermal rating @ 50°C: 2 A: continuously. 4 A: ton= 5 sec., toff = 15 sec.
(Unit status output: 1 A)
Open collec-
tor outputs
Supply: 8...36V DC, max. 10 mA (terminal 20, 21, 22 (com))
Analogue out-
puts
0(4)...20 mA and +/-25 mA. Galvanically separated. Active output (internal supply). Load
max. 500 Ω. (UL/cUL Listed: max. 20 mA output)
Update rate: transducer output: 250 ms. Regulator output: 100 ms
Load sharing
lines
-5...0...+5V DC. Impedance: 23.5 kΩ
Galvanic sep-
aration
Between AC voltage and other I/Os: 3250 V, 50 Hz, 1 min.
Between AC current and other I/Os: 2200 V, 50 Hz, 1 min.
Between analogue outputs and other I/Os: 550 V, 50 Hz, 1 min.
Between binary input groups and other I/Os: 550 V, 50 Hz, 1 min.
AGC-4 installation instructions 4189340687
UK
Technical information
DEIF A/S Page 64 of 69
65. Response
times
(delay set to
min.)
Busbar:
Over-/undervoltage: <50 ms
Over-/underfrequency: <50 ms
Voltage unbalance: <250 ms
Generator:
Reverse power: <250 ms
Overcurrent: <250 ms
Fast overcurrent: <40 ms
Directional overcurrent: <150 ms
Over-/undervoltage: <250 ms
Over-/underfrequency: <350 ms
Overload: <250 ms
Current unbalance: <250 ms
Voltage unbalance: <250 ms
Reactive power import: <250 ms
Reactive power export: <250 ms
Voltage-dependent I>: <250 ms
Negative sequence I: <500 ms
Negative sequence U: <500 ms
Zero sequence I: <500 ms
Zero sequence U: <500 ms
Overspeed: <500 ms
Digital inputs: <250 ms
Emergency stop: <200 ms
Multi-inputs: 800 ms
Wire failure: <600 ms
Mains:
df/dt (ROCOF): <130 ms (4 periods)
Vector jump: <40 ms
Positive sequence: <60 ms
Time-dependent undervoltage, Ut<: <50 ms
Undervoltage and reactive power low, UQ<: <250 ms
Mounting DIN-rail mount or base mount with six screws
Safety To EN 61010-1, installation category (overvoltage category) III, 600 V, pollution degree 2
To UL 508 and CSA 22.2 no. 14-05, overvoltage category III, 600 V, pollution degree 2
EMC/CE To EN 61000-6-2, EN 61000-6-4, IEC 60255-26.
Vibration 3…13.2 Hz: 2 mmpp. 13.2…100 Hz: 0.7 g. To IEC 60068-2-6 & IACS UR E10
10…60 Hz: 0.15mmpp. 60…150 Hz: 1 g. To IEC 60255-21-1 Response (class 2)
10…150 Hz: 2 g. To IEC 60255-21-1 Endurance (class 2)
Shock (base
mount)
10 g, 11 ms, half sine. To IEC 60255-21-2 Response (class 2)
30 g, 11 ms, half sine. To IEC 60255-21-2 Endurance (class 2)
50 g, 11 ms, half sine. To IEC 60068-2-27
Bump 20 g, 16 ms, half sine. To IEC 60255-21-2 (class 2)
Material All plastic materials are self-extinguishing according to UL94 (V1)
AGC-4 installation instructions 4189340687
UK
Technical information
DEIF A/S Page 65 of 69
66. Plug connec-
tions
AC current: 0.2-4.0 mm2 stranded wire. (UL/cUL Listed: AWG 18)
AC voltage: 0.2-2.5 mm2 stranded wire. (UL/cUL Listed: AWG 20)
Relays: (UL/cUL Listed: AWG 22)
Terminals 98-116: 0.2-1.5 mm2 stranded wire. (UL/cUL Listed: AWG 24)
Other: 0.2-2.5mm2 stranded wire. (UL/cUL Listed: AWG 24)
Display: 9-pole Sub-D female
Service port: USB A-B
Protection Unit: IP20. Display: IP52 (IP54 with gasket: option L). (UL/cUL Listed: Type Complete De-
vice, Open Type). To IEC/EN 60529
Governors
and AVRs
Multi-line 2 interfaces to all governors and AVRs using analogue, relay control or CAN-
based J1939 communication
See interfacing guide at www.deif.com
Approvals UL/cUL Listed to UL508
Applies to VDE-AR-N 4105
UL markings Wiring: use 60/75°C copper conductors only
Mounting: for use on a flat surface of type 1 enclosure
Installation: to be installed in accordance with the NEC (US) or the CEC (Canada)
AOP-2:
Maximum ambient temperature: 60°C
Wiring: use 60/75°C copper conductors only
Mounting: for use on a flat surface of type 3 (IP54) enclosure. Main disconnect must be
provided by installer
Installation: to be installed in accordance with the NEC (US) or the CEC (Canada)
DC/DC converter for AOP-2:
Tightening torque: 0.5 Nm (4.4 lb-in)
Wire size: AWG 22-14
Weight Base unit: 1.6 kg (3.5 lbs.)
Option J1/J4/J6/J7: 0.2 kg (0.4 lbs.)
Option J2: 0.4 kg (0.9 lbs.)
Option J8: 0.3 kg (0.58 lbs.)
Display: 0.4 kg (0.9 lbs.)
AGC-4 installation instructions 4189340687
UK
Technical information
DEIF A/S Page 66 of 69
67. 6.2 Unit dimensions
6.2.1 Unit dimensions
Display or AOP
220 (8.661)
165(6.496)
144(5.669)
115(4.528)
220 (8.661)
115 (4.528)
20.0 (0.787)
Dimensions are given in mm (inches).
AGC-4 installation instructions 4189340687
UK
Technical information
DEIF A/S Page 67 of 69
68. 6.3 Panel cut-out
6.3.1 Panel cutout
Required space 222X115mm
Gasket outer 186X77mm
Screws for fastning:
3.5mm selfcutting threads
max. depth in display 9 mm
26.0
= =
==
50.5
66.0
26.0
61.0
174.0
15.0
41.0
Dimensions are given in mm.
AGC-4 installation instructions 4189340687
UK
Technical information
DEIF A/S Page 68 of 69
69. 6.3.2 Drilling template in mm (inches)
230.0 (9.055)
119.1(4.689)
6.6(0.260)
112.6(4.433)
215.5 (8.484)
114.9 (4.524)
14.3 (0.563)
AGC-4 installation instructions 4189340687
UK
Technical information
DEIF A/S Page 69 of 69