1. BREAK LINE
0
A-000
WALL SECTIONS
XXX ROOM
XXX
ROOM NUMBER
XXX
DOOR NUMBER
X
WINDOW TYPE
A-5.0
A
C
BD
INTERIOR ELEVATIONS
PARTITION TYPE
DOOR TYPE
WINDOW TYPE
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET,
BROOKLINE,MA
TITLE SHEET
T-1.0
06/05/17
IO
GWH
289 TAPPAN STREET BUILDING
289 TAPPAN STREET, BROOKLINE, MA
NOTES:
1. THE GENERAL CONTRACTOR SHALL NOTIFY THE ARCHITECTS OF ALL DISCREPANCIES BETWEEN CONSTRUCTION DOCUMENTS
AND EXISTING CONDITIONS
2. THE GENERAL CONTRACTOR SHALL COMPLY WITH ALL FEDERAL, AND LOCAL REGULATIONS THAT MAY APPLY TO THE
CONSTRUCTION OF THE PROJECT.
3.THE GENERAL CONTRACTOR SHALL LEAVE THE PROJECT SITE AND ALL SURROUNDING AREAS IN FINAL CLEAR CONDITION INCL.
THE REMOVAL OF ALL DEBRIS RESULTING
FROM CONSTRUCTION.
4. THE CONTRACTORS SHALL AT ALL TIMES DURING THE PROGRESS OF THE WORK REMOVE ALL CONSTRUCTION DEBRIS AND
MAINTAIN A DUST FREE ENVIRONMENT FOR ALL
ADJACENT AREAS.
5. THE CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES AND VERIFY THAT ALL CUTTING AND PATCHING REQ. FOR
THE INSTALLATION OF ALL MATERIALS BY
ALL TRADES ARE PROPERLY EXECUTED.
6. ALL WRITTEN DIMENSIONS SHALL HAVE PRECEDENCE OVER ALL OTHERS.
7. VERIFY FIELD CONDITIONS PRIOR TO COMMENCEMENT OF EACH PORTION OF THE WORK. THE CONTRACT DRAWINGS ARE
COMPLIMENTARY AND WHAT IS REQUIRED
BY ONE IS BINDING AS IF REQUIRED BY ALL.
THE CONTRACTORS SHALL COORDINATE ALL PORTIONS OF WORK.
8. EXTERIOR DIMENSIONS ARE TO CENTER LINES OF OPENINGS, Exist BUILDING GRID LINES OR FACE OF PANEL UNLESS
OTHERWISE NOTED. INTERIOR DIMENSIONS ARE
TO FACE OF STUD UNLESS OTHERWISE NOTED.
9. ALL GYPSUM WALL BOARD CONSTRUCTION SHALL CONFORM TO RECOMMENDATIONS, PRACTICES, STANDARDS AND
INSTRUCTIONS PUBLISHED BY US GYPSUM
COMPANY HANDBOOK.
10. ALL FINISHED WORK SHALL BE FREE OF DEFECTS. THE ARCHITECT RESERVES THE RIGHT TO REJECT ANY MATERIALS AND
WORKMANSHIP WHICH ARE NOT CONSIDERED TO
BE AT THE HIGHEST STANDARDS OF THE
VARIOUS TRADES INVOLVED.
11. NO CHANGES OR SUBSTITUTIONS ARE ALLOWED UNLESS APPROVED BY HE ARCHITECT.
3. GFA AREA
USABLE OPEN
SPACE
LANDSCAPE
AREA
5' - 0"
48" ACOUSTIC
SCREEN
CONDEN
SERS
ELEVATOR
EQ.
CONDENSERS
CONDENSERS
5'-0"
7' - 8 1/2"
ELEVATOR
EQ.
ELEVATOR
EQ.
198.6 SF
198.6
SF
198.6 SF
5'-0"
5' - 0 1/2"
3' - 4"
STORAGE
2'-11"
3' - 0"3' - 0"
STORAGE
3'-0"
3' - 0" 0' - 3"
0'-91/2"
STORAGE
2' - 5"
2' - 6"
7' - 0"
4'-101/2"
GATE
15' - 0"
15'-0"
10'-10"
15' - 5 1/2"
24'-6"
22' - 7"
15'-0"
15' - 0"
19'-101/2"
26' - 0"
USABLE DECK
AREA/ USABLE
OPEN SPACE
380 SF
USABLE DECK
AREA/ USABLE
OPEN SPACE
240 SF
16'-11/2"
15'-0"
15' - 0"
USABLE DECK
AREA/ USABLE
OPEN SPACE
470 SF
UNIT-C Roof
174
13' - 10"
154' GROUND
ELEVATION
REAR LOT LINE.
GRADE LEVEL
154'
RECORD
GRADE
LINE
FRONT
LOT LINE
MEAN GRADE
OF GROUND
33'-0"
128'
GROUND
LEVEL
BUILDING
HEIGHT 33' 5"
'
UNIT-C GARAGE
133
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET,
BROOKLINE,MA
ZONING-2
LA-1.1
06/05/17
IO
GWH
1/8" = 1'-0"
1
ROOF- ZONING
1/8" = 1'-0"
2
3RD FLOOR- ZONING
1/16" = 1'-0"
3
right Elevation 1 - a-ZONONG
BUILDING HEIGHT DIAGRAM
4. UP
UP
UP
UP
UP
UP
UP
DN
UP
8'-6"
3'-3"
8'-6"
3' - 11"
4' - 4"
128.5
128.0
129
.5
127.
6
5%
131.6
132.0
138
131.7
132.9
142
156 156
156
.0
142
140
135
133
.2
7'-91/2"
5' - 8"
5' - 8"
20'-0"
NEW
RETAINING
WALL
EXISTING
ADJACENT
RETAINING
WALL
8' - 6" 8' - 6"
0' - 11"
18' - 0"
1
A-3.2
16'-51/2"
5' - 1"
ELEVATOR C-102
C-102
ELEVATOR B-102
B-102
ELEVATOR A-102
A-102
ENTRANCE C-101
C-101
ENTRANCE B-101
B-101
STAIRS B-103
B-103
STAIRS C-103
C-103
A-101-b
B-101-bB-101-a
C-101-bC-101-a
G-101
HEATED
DRIVEWAY
PAVERS
15' SETBACK
135
136
138
4" X 24" SET
IN
PRECAST
CONC.
CURB
SIDEWALK
PAVERS
4"
STEP
PLANTER
PLANTER
SIDEWAL
K
PAVERS
ENTRY
ARCH
WATER/ GAS
G -102
G-102
7 T @11"
G-103
ELECT METEWRS
G-103
G -103
4" STEP
8'-6"8'-6"
- 4000 PSI - AIV
ANTRAINED CONC.
SLAB W/ 6X6 WWM ON
WALL COMPOUNTED
GRAVEL
4" STEP
SP CT CT
SP
4" STEP
133
.4
5'-0"
VENT SHAFT
EXAHST FAN
EASEMENT
137
136.10
POLISHED 8"
CMU
FINISH TO
EXT. PAINT IN
4'-2"
ENTRANCE A-101
A-101
STAIRS A-103
A-103
A-101-a
0' - 6 1/2"
SETBACKTO
GARAGE
DOOR
REBUILD
EXISTING
STEPS
EXISTING
CONC.
SIDEWALK
REPLACE
CONC.
SIDEWALK
MATCH
TOWN
SPECIFICATI
ONS
15' - 11"
5' - 0 1/2"
PLANTER
PLANTER
PLANTER
STL. CONC. W/
RUBBER
BUMBER GUARD
PAVERS
SEALD CONC.
0' - 8 1/2"
PAINTED WHITE STRIPE
PAINTED WHITE STRIPE
4'-5"
4" X 24" SET
IN
PRECAST
CONC.
CURB
EXISTING
CONC.
SIDEWALK
REPLACE
CONC.
SIDEWALK
MATCH
TOWN
SPECIFICATI
ONS
EXISTING
REMAINING
WALL TO
REMAIN
4" X 24" SET IN
PRECAST CONC.
CURB
42" GUARD RAILING
AT TOP OF WALL
(TYPICAL)
12" CONC. RETAINING
WALL W/STONE
VENEER AND CAP.
17'-8"4'-51/2"
15'-10"
35'-91/2"
0'-6"
13'-3"
20'-3"
1' - 10 1/2"
3' - 2"
13'-91/2"3'-10"26'-4"25'-9"
6' - 2"
-
---
4' - 3"
-
---
7'-10"7'-10"
7'-9"
-
---
15'-0"
11' - 0"
7'-10"
8" CMU 2 HR FIRE RATED
14" CONCRETE
WALL
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/8" MR GYP ON MTL
FLASHING AT WET SIDE
SHAFT SIDE
5/8"GYP
5/8" MR GYP AT WET SIDE
5/8"GYP
5/8"GYP
2"x 6" WOOD STUDS @ 16 OC
AIR INFILTARATION BARRIER
2"x 4" WOOD STUDS @ 16 OC5/8" GYP
1 x 6 CLAPBOARD SIDING
ON 3/4" PLYWOOD
SHEATHING PANEL
8" CMU 2 HR FIRE RATED
8" CMU 2 HR FIRE RATED
8" CMU 2 HR FIRE RATED
STONE VENEER W/ GALV.
MTL. TIES
5/8" GYP
STUCCO ON MTL LATH, WOOD
SHEATHING
5/8" GYP
5/8" GYP ON MTL FLASHING
2"x 6" WOOD STUDS @ 16 OC
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
A
B
C
D
F
G
I
K
L
P
N
2"x 4" WOOD STUDS @ 16 OC
5/8" GYP
O
14" CONCRETE WALL
2" MTL STUDS @16 OC
RIGID INSULATION5/8"GYP
M
REFER TO FINISH
Q
2"x 4" WOOD STUDS @ 16 OC
ACUISTIC BATT INSULATION
R
H
2"x 4" WOOD STUDS @ 16 OC
STACK BOND POLISHED
CMU 8" x 16"
EXPOSED INSIDE E. SHAFT
EXPOSED INSIDE ELV.
SHAFT
REFER TO FINISH
5/8" MR GYP AT WET SIDE
5/8" MR GYP AT WET SIDE
STACK BOND POLISHED
CMU 8" x 16"
5/8" MR GYP AT WET SIDE
FIBER GLASS BATT INSULATION MIN. R.20
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/8" MR GYP AT WET SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U3365/8" MR GYP AT WET SIDE
E
5/8" MR GYP AT WET SIDE
J
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
1 x 6 CLAPBOARD SIDING
ON 3/4" PLYWOOD
SHEATHING PANEL
5/8" GYP
5/8" MR GYP AT WET SIDE
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
5/8" MR GYP ON WET SIDE
STUCCO ON MTL LATH, WOOD
SHEATHING
5/8" GYP
WALL TYPES
5/8" MR GYP AT WET SIDE
6 MIL POLYETHYLENE VAPOR BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
FIBER GLASS BATT INSULATION MIN. R.20
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
5/8" GYP ON MTL FLASHING 8" CMU 2 HR FIRE RATED
S 5/8" GYP ON MTL FLASHING
T 2"x 6" WOOD STUDS @ 16 OC
1 x 6 CLAPBOARD SIDING ON
3/4" PLYWOOD SHEATHING
PANEL AIR INFILTARATION BARRIER
STUCCO ON MTL LATH,
PLYWOOD SHEATHING
2"x 6" WOOD STUDS @ 16 OC
U
V
5/16" FIBER CEMENT PANELS
ON GALVENIZED FURRING
STRIPS ON ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
2"x 6" WOOD STUDS @ 16 OC
AIR INFILTARATION BARRIER
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
W
5/8" GYP AT INTERIOR SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
X
5/8" GYP AT INTERIOR SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
EXTERIOR SIDE
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
1 x 6 CLAPBOARD SIDING ON
3/4" PLYWOOD SHEATHING
PANEL
ISSUE/DESCRIPTION DATE NO.
SHEETTITLE:
DRAWNBY:
DATE:
JOBNO.:
CHKD.BY:
DWG.NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T6177826003
F6177826063
SUITE315
ARCHITECT
GARYW.HENDREN,AIA
BOSTON,MA02134
119BRAINTREESTREET
ARCHITECTS+PLANNERS PERMITSUBMISSION 11/21/16 1
289TAPPANSTREET,
BROOKLINE,MA
GARAGE
PLAN
A-1.0
06/05/17
IO
GWH
1/4" = 1'-0"
1
GARAGE
5. R
R
DN
UP
R
DN
DN
DN
DN
UP
DN
UP
18' - 5"
6' - 1"
4'-0"6'-0"
4' - 0"
4' - 0"
6' - 0"
1'-111/2"
6' - 0"
3'-5"
3' - 6"
20' - 10"
3'-6"
3' - 6"
3'-6"
7' - 1" 7' - 4 1/2"
6' - 2"
8' - 7 1/2"
3' - 11 1/2"
6'-111/2"
11' - 0"
4' - 0"
3'-4"
3'-6"
3'-9"
3' - 6"
3'-6"
3'-6"
4' - 1"
20' - 10"
1
A-3.2
KITCHEN B-205
B-205
LIVING ROOM B-204
B-204
BATHROOM B-206
B-206
ELEVATOR A-203
B-203
LOBBY B-201
B-201
STAIRS B-202
B-202
KITCHEN C-205
C-205
UTILITY C-208
C-208
C-207 C-206
C-205
B-204
A-204
A-206
LIVING ROOM A-204
A-204
KITCHEN A-205
A-205
BATHROOM A-206
A-206
LOBBY A-201
A-201
STAIRS A-202
A-202
PATIO C-208
C-209
BALCONY B-208
B-208
PATIO A-208
A-208
PATIO C-209
C-209
B-206
8" CMU
140'-4"
WOOD
FENCE
5R @8.8"
PATIO PAVERS @
140'
136
7' - 4"
137
141' 6"
4' - 0"
138
PLANTER
VENT
WD
FENC
E
140
2" MTL STUD
RIGID INSUL
5/8" GYB
143
143' 4"
PLANTER
PLANTER
PRECAST
WATER TABLE
BELOW
LIVING ROOM C-204
C-204
5'-0"
C-204
BATHROOM C-206
C-206
4' - 5"
6' - 11"
28'-2"
12'-9"
10' - 11"
LOBBY C-201
C-201
STAIRS C-202
C-202 ELEVATOR C-203
C-203
27'-111/2"27'-71/2"
18' - 1"
2'-4"12'-2"13'-2"
PRECAST
WATER TABLE
BELOW
2' - 2"
1' - 1 1/2"
12'-21/2"
5'-5"12'-11/2"10'-5"
39' - 0 1/2"
3' - 6"
3' - 1 1/2"
5'-0"
WOOD
FENCE
3' - 8"
2' - 1 1/2"
0' - 8"
9'-11/2"
4'-10"12'-1"3'-91/2"1'-41/2"12'-1"6'-21/2"
3' - 5"
6'-0"
-
---
-
---
4'-9"12'-21/2"6'-3"
1'-111/2"6'-0"1'-8"6'-1"
6'-5"12'-1"1'-41/2"
3'-9"12'-1"
6' - 5 1/2"
3'-21/2"
15' - 11"
3'-10"
0'-81/2"9'-01/2"3'-10"12'-2"2'-7"
-
---
1'-111/2"
1' - 10"
7'-6"7'-91/2"
5' - 10"
5' - 10"
7'-11"
7'-71/2"
UNIT C
UNIT B
UNIT A
UNIT C
UNIT B
UNIT A
-
---
CUT OF 4'
SEE RETAINNIG EALL
DETAIL SHEET A-5.2
8" CMU 2 HR FIRE RATED
14" CONCRETE
WALL
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/8" MR GYP ON MTL
FLASHING AT WET SIDE
SHAFT SIDE
5/8"GYP
5/8" MR GYP AT WET SIDE
5/8"GYP
5/8"GYP
2"x 6" WOOD STUDS @ 16 OC
AIR INFILTARATION BARRIER
2"x 4" WOOD STUDS @ 16 OC5/8" GYP
1 x 6 CLAPBOARD SIDING
ON 3/4" PLYWOOD
SHEATHING PANEL
8" CMU 2 HR FIRE RATED
8" CMU 2 HR FIRE RATED
8" CMU 2 HR FIRE RATED
STONE VENEER W/ GALV.
MTL. TIES
5/8" GYP
STUCCO ON MTL LATH, WOOD
SHEATHING
5/8" GYP
5/8" GYP ON MTL FLASHING
2"x 6" WOOD STUDS @ 16 OC
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
A
B
C
D
F
G
I
K
L
P
N
2"x 4" WOOD STUDS @ 16 OC
5/8" GYP
O
14" CONCRETE WALL
2" MTL STUDS @16 OC
RIGID INSULATION5/8"GYP
M
REFER TO FINISH
Q
2"x 4" WOOD STUDS @ 16 OC
ACUISTIC BATT INSULATION
R
H
2"x 4" WOOD STUDS @ 16 OC
STACK BOND POLISHED
CMU 8" x 16"
EXPOSED INSIDE E. SHAFT
EXPOSED INSIDE ELV.
SHAFT
REFER TO FINISH
5/8" MR GYP AT WET SIDE
5/8" MR GYP AT WET SIDE
STACK BOND POLISHED
CMU 8" x 16"
5/8" MR GYP AT WET SIDE
FIBER GLASS BATT INSULATION MIN. R.20
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/8" MR GYP AT WET SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U3365/8" MR GYP AT WET SIDE
E
5/8" MR GYP AT WET SIDE
J
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
1 x 6 CLAPBOARD SIDING
ON 3/4" PLYWOOD
SHEATHING PANEL
5/8" GYP
5/8" MR GYP AT WET SIDE
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
5/8" MR GYP ON WET SIDE
STUCCO ON MTL LATH, WOOD
SHEATHING
5/8" GYP
WALL TYPES
5/8" MR GYP AT WET SIDE
6 MIL POLYETHYLENE VAPOR BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
FIBER GLASS BATT INSULATION MIN. R.20
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
5/8" GYP ON MTL FLASHING 8" CMU 2 HR FIRE RATED
S 5/8" GYP ON MTL FLASHING
T 2"x 6" WOOD STUDS @ 16 OC
1 x 6 CLAPBOARD SIDING ON
3/4" PLYWOOD SHEATHING
PANEL AIR INFILTARATION BARRIER
STUCCO ON MTL LATH,
PLYWOOD SHEATHING
2"x 6" WOOD STUDS @ 16 OC
U
V
5/16" FIBER CEMENT PANELS
ON GALVENIZED FURRING
STRIPS ON ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
2"x 6" WOOD STUDS @ 16 OC
AIR INFILTARATION BARRIER
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
W
5/8" GYP AT INTERIOR SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
X
5/8" GYP AT INTERIOR SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
EXTERIOR SIDE
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
1 x 6 CLAPBOARD SIDING ON
3/4" PLYWOOD SHEATHING
PANEL
ISSUE/DESCRIPTION DATE NO.
SHEETTITLE:
DRAWNBY:
DATE:
JOBNO.:
CHKD.BY:
DWG.NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T6177826003
F6177826063
SUITE315
ARCHITECT
GARYW.HENDREN,AIA
BOSTON,MA02134
119BRAINTREESTREET
ARCHITECTS+PLANNERS PERMITSUBMISSION 11/21/16 1
289TAPPANSTREET,
BROOKLINE,MA
FIRST
FLOOR
PLAN
A-1.1
06/05/17
IO
GWH
1/4" = 1'-0"
1
1ST FLOOR
GAS FIRE PLACE
GAS FIRE PLACE
GAS FIRE PLACE
6. UP
DN
UP
UP
5' - 0"
5' - 0"
16'-9"
7'-71/2"
7'-0"
UTILITY
BEDROOM
3'-01/2"
7'-3"
3'-7"
5' - 0"
8'-21/2"
16'-7"
4' - 9 1/2"
4'-11/2"
5' - 0"
10'-71/2"
4'-61/2"
2'-2"
14' - 5 1/2"
6' - 0 1/2"
3' - 5"
16' - 3"
8' - 0"
15' - 8"
12' - 6 1/2"
8' - 0"
7' - 0"
6'-0"
5' - 0"
8' - 11"
3'-5"
5' - 0"
L.C.
L.C.
1'-101/2"
8'-6"
2'-0"
4' - 5"
5' - 0" 7' - 0"
5' - 9 1/2"
BEDROOM A-305
A-305
LOBBY A-301
A-301
ELEVATOR A-303
A-303
STAIRS A-302
A-302
L. CLOSET A-312
A-312
CLOSET A-313
A-313
BEDROOM A-304
A-304UTILITY A-314
A-314
CLOSET A-311
A-311
BATHROOM A-309
A-309
CLOSET A-310
A-310
SHOWER A-308
A-308
TOILET A-307
A-307
BATH A-306
A-306
3' - 0"
5' - 0"
5' - 0"
BEDROOM B-305
B-305
UTILITY B-313
B-313
CLOSET B-311
B-311
BATHROOM B-309
B-309
CLOSET B-310
B-310
SHOWER B-308
B-308
TOILET B-307
B-307
BATHROOM B-306
B-306
BEDROOM B-304
B-304
ELEVATOR C-303
C-303
STAIRS B-302
B-302
4' - 6"
6'-0"
4' - 5"
13'-11"
BEDROOM C-305
C-305
CLOSET C-313
C-313
L.C. C-314
C-312
UTILITY C-314
C-314
CLOSET C-310
C-310
BATHROOM C-309
C-309
TOILET C-308
C-308
BEDROOM C-304
C-304
BALCONY A-315
A-315
A-304-a
A-314
A-312
A-313
A-310
A-306
A-308
A-307
A-309
A-304-b
E
E
E
E
I
I
B
A
A-305
B-309
B-310
B-311
B-306
B-313
B-305
B-312
C-307
C-306
C-308
C-311
C-312
C-314
C-305 C-310
C-304-b
C-309
L.CLOSET
B-312
5' - 0"
B-308
B-307
B-304-bB-304-a
BALCONY B-314
B-314
C-313
155' 6"
GRASS
PATIO
PAVERS
CONC. RETAINING WALL
141
LANDSCAPE BLOCK
CONC.
RETAINING WALL
LANDSCAPE BLOCK
143' 4"
50' - 3 1/2"
21'-6"
14'-0"
18' - 0"
8'-21/2"
4'-5"
4'-61/2"
5'-21/2"
C-304-a
RAILING ON TOP
1' - 11"
3' - 2"3' - 5"6' - 0"
2'-21/2"12'-01/2"6'-4"
1'-101/2"6'-1"
2' - 0"
6'-11/2"
12'-1"
1'-51/2"
1' - 0 1/2"
3'-91/2"12'-0"4'-111/2"
2' - 9 1/2"
9'-11/2"
6' - 5 1/2"
2'-111/2"
15' - 8"
3'-61/2"
5' - 11"
1'-5"3'-2"6'-0"
12' - 10"
17'-10"
10'-21/2"
12' - 8"
5'-6"
16'-0"
4' - 0"
2'-6"6'-0"3'-2"0'-6"
6' - 0 1/2" 2'-11"12'-1"4'-0"6'-01/2"
87'-01/2"
44' - 1 1/2"
87'-9"
90'-81/2"
5'-0"
15'-71/2"
3'-10"
6' - 9"
12' - 9 1/2"
7' - 0"
5' - 1"
1' - 0"
2' - 0"2' - 2"
5' - 8"
1'-7"9'-11/2"9'-101/2"6'-1"3'-5"
12'-2"
I
C
A
A
E
E
J
X
---
-
7'-10"7'-8"
UNIT C
UNIT B
UNIT A
8" CMU 2 HR FIRE RATED
14" CONCRETE
WALL
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/8" MR GYP ON MTL
FLASHING AT WET SIDE
SHAFT SIDE
5/8"GYP
5/8" MR GYP AT WET SIDE
5/8"GYP
5/8"GYP
2"x 6" WOOD STUDS @ 16 OC
AIR INFILTARATION BARRIER
2"x 4" WOOD STUDS @ 16 OC5/8" GYP
1 x 6 CLAPBOARD SIDING
ON 3/4" PLYWOOD
SHEATHING PANEL
8" CMU 2 HR FIRE RATED
8" CMU 2 HR FIRE RATED
8" CMU 2 HR FIRE RATED
STONE VENEER W/ GALV.
MTL. TIES
5/8" GYP
STUCCO ON MTL LATH, WOOD
SHEATHING
5/8" GYP
5/8" GYP ON MTL FLASHING
2"x 6" WOOD STUDS @ 16 OC
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
A
B
C
D
F
G
I
K
L
P
N
2"x 4" WOOD STUDS @ 16 OC
5/8" GYP
O
14" CONCRETE WALL
2" MTL STUDS @16 OC
RIGID INSULATION5/8"GYP
M
REFER TO FINISH
Q
2"x 4" WOOD STUDS @ 16 OC
ACUISTIC BATT INSULATION
R
H
2"x 4" WOOD STUDS @ 16 OC
STACK BOND POLISHED
CMU 8" x 16"
EXPOSED INSIDE E. SHAFT
EXPOSED INSIDE ELV.
SHAFT
REFER TO FINISH
5/8" MR GYP AT WET SIDE
5/8" MR GYP AT WET SIDE
STACK BOND POLISHED
CMU 8" x 16"
5/8" MR GYP AT WET SIDE
FIBER GLASS BATT INSULATION MIN. R.20
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/8" MR GYP AT WET SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U3365/8" MR GYP AT WET SIDE
E
5/8" MR GYP AT WET SIDE
J
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
1 x 6 CLAPBOARD SIDING
ON 3/4" PLYWOOD
SHEATHING PANEL
5/8" GYP
5/8" MR GYP AT WET SIDE
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
5/8" MR GYP ON WET SIDE
STUCCO ON MTL LATH, WOOD
SHEATHING
5/8" GYP
WALL TYPES
5/8" MR GYP AT WET SIDE
6 MIL POLYETHYLENE VAPOR BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
FIBER GLASS BATT INSULATION MIN. R.20
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
5/8" GYP ON MTL FLASHING 8" CMU 2 HR FIRE RATED
S 5/8" GYP ON MTL FLASHING
T 2"x 6" WOOD STUDS @ 16 OC
1 x 6 CLAPBOARD SIDING ON
3/4" PLYWOOD SHEATHING
PANEL AIR INFILTARATION BARRIER
STUCCO ON MTL LATH,
PLYWOOD SHEATHING
2"x 6" WOOD STUDS @ 16 OC
U
V
5/16" FIBER CEMENT PANELS
ON GALVENIZED FURRING
STRIPS ON ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
2"x 6" WOOD STUDS @ 16 OC
AIR INFILTARATION BARRIER
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
W
5/8" GYP AT INTERIOR SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
X
5/8" GYP AT INTERIOR SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
EXTERIOR SIDE
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
1 x 6 CLAPBOARD SIDING ON
3/4" PLYWOOD SHEATHING
PANEL
ISSUE/DESCRIPTION DATE NO.
SHEETTITLE:
DRAWNBY:
DATE:
JOBNO.:
CHKD.BY:
DWG.NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T6177826003
F6177826063
SUITE315
ARCHITECT
GARYW.HENDREN,AIA
BOSTON,MA02134
119BRAINTREESTREET
ARCHITECTS+PLANNERS PERMITSUBMISSION 11/21/16 1
289TAPPANSTREET,
BROOKLINE,MA
SECOND
FLOOR
PLAN
A-1.2
06/05/17
IO
GWH
7. DN
UP
DN
DN
UP
5'-6"
5' - 0"
5' - 0"
5' - 0"
0'-111/2"
5' - 0"
1'-31/2"
7'-01/2"
17' - 1"
13' - 0"
8'-21/2"
8' - 0"
2'-0"
2'-0"
L.C.
8' - 0"
6' - 6"
6'-81/2"
4'-10"
39' - 6"
8' - 0"
4' - 1"
6' - 3"
6' - 4"
2' - 0"
4'-81/2" 13' - 0"
14' - 5 1/2"
14'-11/2"
13'-1"
3' - 6"
6'-6"
5' - 0"
13' - 7"
5' - 0"
2' - 8"
2'-6"
12'-5"
14' - 2 1/2"
12'-9"
16'-51/2"
BEDROOM A-405
A-405
BEDROOM B-406
B-406
BEDROOM B-405
B-405
LOFT B-404
B-404
LAUNDRY B-409
B-409
BATHROOM B-407
B-407
BATHROOM B-408
B-408
CLOSET B-410
B-410
CLOSET B-411
B-411
BEDROOM C-404
C-404
BEDROOM C-405
C-405
LAUNDRY C-410
C-410
BATHROOM C-408
C-408
ELEVATOR A-403
A-403
CLOSET A-411
A-411
UTILITY A-412
A-412
CLOSET A-410
A-410
ELEVATOR B-403
B-403
C-408
LOBBY A-401
A-401
STAIRS A-402
A-402
STAIRS B-402
B-402
UTILITY B-412
B-412
CLOSET C-412
C-412
CLOSET C-411
C-411
L.C. C-414
C-414
C-412
C-411C-404
C-407
B-405
B-412
B-409
B-406
B-408 B-407
B-410B-411
A-407A-408
A-409 A-405
A-406
A-412
A-411
C-414
C-410
BEDROOM A-406
A-406
BATHROOM A-408
A-408 BATHROOM A-407
A-407
LAUNDRY A-409
A-409
LOFT A-404
A-404
A-410
C-405
BEDROOM C-406
C-406STAIR C-402
C-402
ELEVATOR C-403
C-403
LOBBY C-401
C-401
LOBBY C-401
C-401
30'-0"
BATHROOM C-407
C-407
1' - 6 1/2"6' - 0"3' - 0" 11' - 7"6' - 2"9' - 0"
2'-3"12'-01/2"6'-3"
1' - 1"
17'-9"
2' - 0"
9'-2"9'-11/2"1'-5"
1' - 0 1/2"
3'-9"
12'-0"4'-111/2"
2' - 9 1/2"
9'-11/2"
6' - 5 1/2"
2'-111/2"
15' - 8"
3'-61/2"
2' - 8" 12' - 0 1/2" 1' - 7"
1'-41/2"9'-11/2"3'-01/2"
5' - 9"
6'-61/2"6'-01/2"3'-11"12'-1"2'-11"
6' - 0 1/2"
0'-8"
9'-0"2'-6"
4' - 0"
3'-6"6'-01/2"9'-10"9'-11/2"1'-61/2"
30'-0"
87'-2"
87'-9"
14' - 4"
4' - 0"
4'-0"
8'-21/2"
12'-21/2"
15'-11/2"
5'-2"
2'-0"
8' - 0"
3' - 10"
2'-0"
BATHROOM C-409
C-409
CLOSET C-413
C-413
4' - 5"
C-413
C-409
C-404
12'-91/2"
5'-0"
12' - 0"
12'-11/2"
P
RR
X
K
K
1' - 11"
8'-2"
7'-61/2"
7'-10"
UNIT C
UNIT B
UNIT A
8" CMU 2 HR FIRE RATED
14" CONCRETE
WALL
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/8" MR GYP ON MTL
FLASHING AT WET SIDE
SHAFT SIDE
5/8"GYP
5/8" MR GYP AT WET SIDE
5/8"GYP
5/8"GYP
2"x 6" WOOD STUDS @ 16 OC
AIR INFILTARATION BARRIER
2"x 4" WOOD STUDS @ 16 OC5/8" GYP
1 x 6 CLAPBOARD SIDING
ON 3/4" PLYWOOD
SHEATHING PANEL
8" CMU 2 HR FIRE RATED
8" CMU 2 HR FIRE RATED
8" CMU 2 HR FIRE RATED
STONE VENEER W/ GALV.
MTL. TIES
5/8" GYP
STUCCO ON MTL LATH, WOOD
SHEATHING
5/8" GYP
5/8" GYP ON MTL FLASHING
2"x 6" WOOD STUDS @ 16 OC
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
A
B
C
D
F
G
I
K
L
P
N
2"x 4" WOOD STUDS @ 16 OC
5/8" GYP
O
14" CONCRETE WALL
2" MTL STUDS @16 OC
RIGID INSULATION5/8"GYP
M
REFER TO FINISH
Q
2"x 4" WOOD STUDS @ 16 OC
ACUISTIC BATT INSULATION
R
H
2"x 4" WOOD STUDS @ 16 OC
STACK BOND POLISHED
CMU 8" x 16"
EXPOSED INSIDE E. SHAFT
EXPOSED INSIDE ELV.
SHAFT
REFER TO FINISH
5/8" MR GYP AT WET SIDE
5/8" MR GYP AT WET SIDE
STACK BOND POLISHED
CMU 8" x 16"
5/8" MR GYP AT WET SIDE
FIBER GLASS BATT INSULATION MIN. R.20
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/8" MR GYP AT WET SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U3365/8" MR GYP AT WET SIDE
E
5/8" MR GYP AT WET SIDE
J
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
1 x 6 CLAPBOARD SIDING
ON 3/4" PLYWOOD
SHEATHING PANEL
5/8" GYP
5/8" MR GYP AT WET SIDE
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
5/8" MR GYP ON WET SIDE
STUCCO ON MTL LATH, WOOD
SHEATHING
5/8" GYP
WALL TYPES
5/8" MR GYP AT WET SIDE
6 MIL POLYETHYLENE VAPOR BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
FIBER GLASS BATT INSULATION MIN. R.20
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
5/8" GYP ON MTL FLASHING 8" CMU 2 HR FIRE RATED
S 5/8" GYP ON MTL FLASHING
T 2"x 6" WOOD STUDS @ 16 OC
1 x 6 CLAPBOARD SIDING ON
3/4" PLYWOOD SHEATHING
PANEL AIR INFILTARATION BARRIER
STUCCO ON MTL LATH,
PLYWOOD SHEATHING
2"x 6" WOOD STUDS @ 16 OC
U
V
5/16" FIBER CEMENT PANELS
ON GALVENIZED FURRING
STRIPS ON ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
2"x 6" WOOD STUDS @ 16 OC
AIR INFILTARATION BARRIER
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
W
5/8" GYP AT INTERIOR SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
X
5/8" GYP AT INTERIOR SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
EXTERIOR SIDE
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
1 x 6 CLAPBOARD SIDING ON
3/4" PLYWOOD SHEATHING
PANEL
ISSUE/DESCRIPTION DATE NO.
SHEETTITLE:
DRAWNBY:
DATE:
JOBNO.:
CHKD.BY:
DWG.NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T6177826003
F6177826063
SUITE315
ARCHITECT
GARYW.HENDREN,AIA
BOSTON,MA02134
119BRAINTREESTREET
ARCHITECTS+PLANNERS PERMITSUBMISSION 11/21/16 1
289TAPPANSTREET,
BROOKLINE,MA
THIRD
FLOOR
PLAN
A-1.3
06/05/17
IO
GWH
1/4" = 1'-0"
1
3RD FLOOR
8. DN
DN
DN
5' - 0"
48"
ACOUSTIC
SCREEN
CONDENSE
RS
CONDENSE
RS
CONDENSERS
5'-0"
7' - 8 1/2"
198.
6 SF
198.6
SF
198.6
SF
5'-0"
5' - 0 1/2"
3' - 4"
2'-11"
3' - 0"3' - 0"
3'-0"
3' - 0" 0' - 3"
0'-91/2"
1
A-3.2
2' - 5"
2' - 6"
7' - 0"
4'-101/2"
ROOF DECK C-506
C-506
ROOF C-507
C-507
LOBBY C-501
C-501
STORAGE C-505
C-505
ELEV. EQ. B-504
B-504
ROOF B-507
B-507
ROOF DECK A-506
A-506
STORAGE A-505
A-505
ELEVATOR A-502
A-502
ELEVATOR
EQUIPMENT A-504
A-504
B-505
B-501
B-504
C-505C-504
C-501
GATE
10'-10"
15' - 5 1/2"
24'-6"
22' - 7"
19'-101/2"
26' - 0"
16'-11/2"
ROOF DECK B-506
B-506
LOBBY A-501
A-501
STAIR A-503
A-503
STAIRS B-503
B-503
ELEVATOR B-502
B-502
STORAGE B-505
B-505
LOBBY B-501
B-501
ROOF A-507
A-507
14' - 4 1/2"
A-505
A-501
A-504
ELEV. EQ. C-504
C-504
ELEVATOR C-502
C-503
LOBBY C-503
C-503
OVERFLOW SCUPPER
10'-0"
OVERFLOW SCUPPER
10'-0"
OVERFLOW SCUPPER
9'-81/2"
17'-11"19'-51/2"9'-11/2"20'-81/2"
6' - 5 1/2" 15' - 8"
3'-61/2"
16' - 0"
13'-6"
5' - 9"
31'-6"12'-2"30'-0"
90'-81/2"
38' - 4 1/2"
87'-2"
-
---
-
---
5'-61/2"
48"
ACOUSTIC
SCREEN
U
U
U
T
T
T
T
T
T
T
U
U
T
V
W
-
---
7'-10"7'-10"
-
---
8" CMU 2 HR FIRE RATED
14" CONCRETE
WALL
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/8" MR GYP ON MTL
FLASHING AT WET SIDE
SHAFT SIDE
5/8"GYP
5/8" MR GYP AT WET SIDE
5/8"GYP
5/8"GYP
2"x 6" WOOD STUDS @ 16 OC
AIR INFILTARATION BARRIER
2"x 4" WOOD STUDS @ 16 OC5/8" GYP
1 x 6 CLAPBOARD SIDING
ON 3/4" PLYWOOD
SHEATHING PANEL
8" CMU 2 HR FIRE RATED
8" CMU 2 HR FIRE RATED
8" CMU 2 HR FIRE RATED
STONE VENEER W/ GALV.
MTL. TIES
5/8" GYP
STUCCO ON MTL LATH, WOOD
SHEATHING
5/8" GYP
5/8" GYP ON MTL FLASHING
2"x 6" WOOD STUDS @ 16 OC
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
A
B
C
D
F
G
I
K
L
P
N
2"x 4" WOOD STUDS @ 16 OC
5/8" GYP
O
14" CONCRETE WALL
2" MTL STUDS @16 OC
RIGID INSULATION5/8"GYP
M
REFER TO FINISH
Q
2"x 4" WOOD STUDS @ 16 OC
ACUISTIC BATT INSULATION
R
H
2"x 4" WOOD STUDS @ 16 OC
STACK BOND POLISHED
CMU 8" x 16"
EXPOSED INSIDE E. SHAFT
EXPOSED INSIDE ELV.
SHAFT
REFER TO FINISH
5/8" MR GYP AT WET SIDE
5/8" MR GYP AT WET SIDE
STACK BOND POLISHED
CMU 8" x 16"
5/8" MR GYP AT WET SIDE
FIBER GLASS BATT INSULATION MIN. R.20
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/8" MR GYP AT WET SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U3365/8" MR GYP AT WET SIDE
E
5/8" MR GYP AT WET SIDE
J
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
1 x 6 CLAPBOARD SIDING
ON 3/4" PLYWOOD
SHEATHING PANEL
5/8" GYP
5/8" MR GYP AT WET SIDE
2"x 6" WOOD STUDS @ 16 OC
FIBER GLASS BATT INSULATION MIN. R.20
5/8" MR GYP ON WET SIDE
STUCCO ON MTL LATH, WOOD
SHEATHING
5/8" GYP
WALL TYPES
5/8" MR GYP AT WET SIDE
6 MIL POLYETHYLENE VAPOR BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
FIBER GLASS BATT INSULATION MIN. R.20
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
5/8" GYP ON MTL FLASHING 8" CMU 2 HR FIRE RATED
S 5/8" GYP ON MTL FLASHING
T 2"x 6" WOOD STUDS @ 16 OC
1 x 6 CLAPBOARD SIDING ON
3/4" PLYWOOD SHEATHING
PANEL AIR INFILTARATION BARRIER
STUCCO ON MTL LATH,
PLYWOOD SHEATHING
2"x 6" WOOD STUDS @ 16 OC
U
V
5/16" FIBER CEMENT PANELS
ON GALVENIZED FURRING
STRIPS ON ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
AIR INFILTARATION BARRIER
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
2"x 6" WOOD STUDS @ 16 OC
AIR INFILTARATION BARRIER
UNCURED RUBBER
UNCURED RUBBER
AIR INFILTARATION BARRIER
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
ROOF SIDE
W
5/8" GYP AT INTERIOR SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
X
5/8" GYP AT INTERIOR SIDE
2 LAYERS 1" GYP PANEL -2 HR FIRE
RATED WITH 3/4" AIR GAP, FIBER GLASS
BATT INSULATION MIN. 20. ACOUSTIC
SEALANT AT CORNERS AND PERIMETERS.
UL DESIGN NO.U336
5/16" FIBER CEMENT PANELS
ON 3/4" CDX PLYWOOD AT
EXTERIOR SIDE
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
AIR INFILTARATION BARRIER
6 MIL POLYETHYLENE VAPOR BARRIER
1 x 6 CLAPBOARD SIDING ON
3/4" PLYWOOD SHEATHING
PANEL
ISSUE/DESCRIPTION DATE NO.
SHEETTITLE:
DRAWNBY:
DATE:
JOBNO.:
CHKD.BY:
DWG.NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T6177826003
F6177826063
SUITE315
ARCHITECT
GARYW.HENDREN,AIA
BOSTON,MA02134
119BRAINTREESTREET
ARCHITECTS+PLANNERS PERMITSUBMISSION 11/21/16 1
289TAPPANSTREET,
BROOKLINE,MA
ROOF
PLAN
A-1.4
06/05/17
IO
GWH
1/4" = 1'-0"
1
ROOF
9. PLANTERS
3'-6"
POLISHED CMU
STUCCO
COLOR A
STONE VENEER
PLANTER
11
11
22
22
2 2
2 2
2 2
2 2
5 5 5 5
CLAPBOARD
SIDING
CLAPBOARD
SIDING
5555
12 12 12
4 4 4
5 5 5 5
5 5 5 5
4 4 4 4
4 4 4 4
4444C-205
C-101
B-101
GALVANIZED STEEL RAIL
AT 42" AFG
ANNODIZED ALLUMINUM
FASCIA
CURTAIN WALL
ANNODIZED ALLUMINUM
FASCIA
STUCCO
COLOR B
ANNODIZED ALLUMINUM
FASCIA
2 X 8 COMPOSITE
CAP
GALVANIZED STEEL RAIL
AT 42" AFG
POLISHED CMU
PRE CAST
WATER TABLE
UNIT C
ROOF
129'-6"
UNIT A
1ST FLOOR
140'-4"
UNIT A
2ND FLOOR
151'-4"
UNIT A
3RD FLOOR
161'-7"
UNIT A
ROOF
171'-11"
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET
LEFT
ELEVATIONS
A-2.0
04/14/17
IO
GWH
1/4" = 1'-0"
1
West Elevation
BROOKLINE,MA
10. 4 4 4 4
4 4 4 4
13 13 13 13 13 13
G-101
14
A-501
STONE
VANEER
POLISHED
CONCRETE BLOCK
SHADE DEVICE
ANODIZED
ALLUMINUM
FASCIA
GARAGE
DOOR
C.I.P. CONCRETE
LANDSCAPE WALL
CLAPBOARD
SIDING WITH
MITERED CORNERS
GLASS CURTAIN
WALL WITH
VISION SCREEN
ENTRY
ARCH
GRADE
129'-6"
143'-5"
MEDIAN GRADE
UNIT A 1ST
FLOOR
141'-10"
151'-4"
161'-7"
171'-11"
UNIT A 2ND
FLOOR
UNIT A 3RD
FLOOR
UNIT A ROOF
STAIR A ROOF
ELEV PENTHOUSE
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET
FRONT
ELEVATION
A-2.1
04/28/17
IO
GWH
1/4" = 1'-0"
2
South Elevation
BROOKLINE,MA
11. 4 3
34
44 4
4
4
C-304a
GRADE
CLAPBOARD
SIDING
DOOR BROW
UNIT C
3RD FLOOR
164'-7"
UNIT C
ROOF
174'-11"
154'-4"
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET
BACK
ELEVATION
A-2.2
04/28/17
IO
GWH
1/4" = 1'-0"
1
North Elevation
BROOKLINE,MA
12. 2'-0"
4 4 4 4 4
4 4
A-304-b
11 11
10
10 10 10
4 4 4 4
4 4 4 4 4 4 4
B-304a
11 11
4 4
4 4
4 4 4
4 4 4
C204
9
999
A-204
B-204
575
99 9 99
SCUPPER
CLAPBOARD
SIDING
PARGE ON
CONCRETE FOUNDATION WALL
FENCE
1010
CLAPBOARD
SIDING
STUCCO
COLOR A
STUCCO
COLOR B
2 X 8 COMPOSITE CAPSTUCCO SURROUND
GLASS CURTAIN WALL
SUN SHADE
DEVICE
UNIT C
1ST FLOOR
143'-4"
UNIT C
2ND FLOOR
154'-4"
UNIT C
3RD FLOOR
164'-7"
UNIT C
ROOF
174'-11"
1'-0"
1'-0"
1'-0"
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET
RIGHT
ELEVATION
A-2.3
04/28/17
IO
GWH
1/4" = 1'-0"
1
East Elevation
BROOKLINE,MA
13. UNIT-B 1st FL
141'
UNIT-B 2nd FL
152'
UNIT-B 3rd FL
162'
UNIT-B ROOF
172'
8'-33/4"
2' PRECAST CONC.
9" CONC SLAB
ON 7" METAL DECK
16" BOND BEAM
8" TH MASONRY WALL
METAL FLASHING
DRIP EDGE
EIFS SEE ELEVATION
CAULKING WITH BACKER
ROD
EIFS SEE ELEVATION
5/8" DENSE GLASS
6" WOOD WALL
3 (2X12 ) LVL
SEE STRUCTURAL DRAWINGS
6" FIBER GLASS INSULATION
FOR BEAM SIZE SEE
STRUCTURAL DRAWINGS
R-38 FOAM
INSULATION
6" CONC
PLANTER WALL
STONE CAP
MIN4'-0"
CONC. FOUNDATION WALL
SEE STRUCTURAL DRAWINGS
COMPACTED GRAVEL
2" THICK RIGID
INSULATION
FOR FOUNDATION SEE
STRUCTURAL DRAWINGS
2" THICK RIGID
INSULATION
5" CONC. SLAB
5/8" DENSE GLASS
3 (2X12 ) LVL
SEE STRUCTURAL DRAWINGS
R-20 FIBER GLASS INSULATION
1X2 FURRING
5/8" GYP
FOR BEAM SIZE SEE
STRUCTURAL DRAWINGS
FOR STEEL BEAM SIZE SEE
STRUCTURAL DRAWINGS
1X2 FURRING
5/8" GYP
R-38 FIBER GLASS INSULATION
3/4" T& G
3/4" ISOLATION BOARD
EPDM ROOFING
FOR BEAM SIZE SEE
STRUCTURAL DRAWINGS
5" CONC. ON DECK
10" CONC. WALL
2" THICK RIGID
INSULATION
0'-4"
0'-5"
2'-0"
8'-0"
2'-0"
8'-0"
8'-0"
10'-8"10'-3"10'-4"4'-0"
VAPOR BARRIER (TYP)
2'-0" CANOPY
3'-6"
2'X2'X2' CONC. PAVERS ON 4" STONE DUST
12" CONC. FOUNDATION WALL
SEE STRUCTURAL DRAWINGS
2" THICK RIGID
INSULATION (TYP)
FOR FOUNDATION SEE
STRUCTURAL DRAWINGS (TYP)
VAPOR BARRIER (TYP)
4" CONC. SLAB
COMPACTED GRAVEL
4" DIA PERFORATED
PERIMETER DRAIN (TYP)
2 LAYERS OF TYPE X GYP BOARD
UNIT-B 2nd FL
152'
METAL RAILING
WITH MRE MESH FABRIC
SYNTHETIC WOOD
DECKING
TAPERED P.T WD SLEEPERS ON
UNCURED RUBBER SLIP SHEET
.060 EPDM
3 1/2" 2" TAPERED INSULATION
CAULK JOINT
3'-6"
2X8 FLOOR JOIST 16" OC. WITH 7
1/2" FIBER GLASS INSULATIONS
3/4" T&G PLYWOOD SHEATHING
WD CLAPBOARD
SIDING ON
FURRING
5/8" PLYWD SHEATHING
WITH VAPOR
INFILTRATION BARRIER
2X4 P.T BLOCKING
ANODRES
ALUM DRIP
3'-6"
0'-11/2"0'-4"0'-1"
0'-3"
0'-1"
GALV STEEL PIPE
HEAVY DUTY WELDED WIRE FABRIC
2'X2' PAINTED BLACK
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
BIDDINGSET
289TAPPANSTREET
BROOKLINE,MA
BUILDING
SECTION
A-A
A-3.0
06/05/17
IO
GWH
1 SECTION A-A
141'-10"
2 BALCONY SECTION C-CSCALE 3/8"=1'-0" SCALE 3/4"=1'-0"
152'-10"
163'-1"
173'-5"
152'-10"
3 RAILING DETAIL
14. UNIT-A 1st FL
139'
UNIT-A 2nd FL
150'
UNIT-A 3rd FL
160'
UNIT-A ROOF
171'
UNIT-B 1st FL
141'
UNIT-C 1st FL
143'
UNIT-B 2nd FL
152'
UNIT-C 2nd FL
153'
UNIT-B 3rd FL
162'
UNIT-C 3rd FL
163'
UNIT-B ROOF
172'
UNIT-C Roof
174'
GARAGE
129'
8'-2"
8'-2"
4'-0"
1/4"/FT SLOPE
14'
1/4"/ FT SLOPE
13'
8'-0"
9'-9".
1'-6"
9'-0"9'
7'-0"7'-0"7'-0"7'-0"
14'-3"
4'-0"
4'-0"
EPDM ROOFING
STONE VENEER
2X6 PRESSURE TREATED
9'-0"
3'-0"
1'-6"1'-6"
R-38 INSULATION
R-20 INSULATION
EPDM ROOFING
METAL ANGLE
SEE STRUCTURAL DRAWINGS
2X6 PRESSURE
TREATED
R-38 INSULATION
0'-4"
3'-0"3'-0"
1X2 FURRING
5/8" GYP
R-38 FIBER GLASS INSULATION
3/4" T&G PLYWOOD
3/4" ISOLATION BOARD
EPDM ROOFING
STAIR PENTHOUSE
SUB FLOOR
SEE STRUCTURAL
DRAWINGS
ALUMINUM
LOUVERS CANOPY
SEE SOUTH
ELEVATION
CONC. FOUNDATION WALL
SEE STRUCTURAL DRAWINGS
COMPACTED GRAVEL
2" THICK RIGID INSULATION (TYP)
FOR FOUNDATION SEE
STRUCTURAL DRAWINGS (TYP)
VAPOR BARRIER (TYP)
4" CONC. SLAB
COMPACTED GRAVEL
4" DIA PERFORATED PERIMETER DRAIN (TYP)
2' PRECAST CONC.
METAL FLASHING
DRIP EDGE
CAULKING WITH BACKER ROD
LANDSCAPE BLOCK
R-20 INSULATION
ALUMINUM
LOUVERS CANOPY
SEE SOUTH
ELEVATION
ALUMINUM
LOUVERS CANOPY
SEE SOUTH
ELEVATION
FOR BEAM SEE
STRUCTURAL DRAWINGS
9" CONC SLAB WITH 7 1/2" DECK
FOR BEAM SIZE SEE
STRUCTURAL DRAWINGS
3/4" GAP
3'-0"
3'-0"
0'-4"
1'-6"1'-6"
1'-6"
1'-6".
1'-6"1'-6"
6 MIL VAPOR BARRIER (TYP)
4" CONC. SLAB
COMPACTED GRAVEL
2" METAL STUD @ 16" OC
WITH 1 1/2" RIGID INSULATION (R-10)
5/8" GYPSUM BLUE BOARD
WITH PLASTER
TROWEL ON WATER PROOFING
2" TH RIGID INSULATION
ENGINEERED WOOD FLOORING
ON ISOLATION PAD
4" BASE BOARD
5/8" GYPSUM BLUE BOARD ON 1X2
WOOD FURRING
TJI FLOOR JOIST @ 16" OC
REFER STRUCTURAL DRAWINGS
ENGINEERED WOOD FLOORING
3/4" T&G PLYWOOD SUB FLOOR
WITH ISOLATION PAD
2" METAL STUD @ 16" OC
WITH 1 1/2" RIGID INSULATION (R-10)
4" BASE BOARD
2X6 WOOD STUD @ 16" O.C
2X10 RIM BOARD
3/4" SHEATHING WITH AIR
FILTRATION BARRIER
ROOF FRAMING REFER TO
STRUCTURAL DRAWING
R-38 INSULATIONS WITH AIR BAFFLES
2 2X8 HEADER
1X6 CLAPBOARD SIDING
SEE ELEVATION
2X8 COMPOSITE WITH CAP
2X4 WITH @ 16" WITH
5/8" FIBER CEMENT
PANEL
2X2 P.T SLEEPERS ON
UNCURED RUBBER SLIP SHEET
AIR FILTRATION BARRIER
FIBER CEMENT PANEL
3/4" CDX PLY
EPDM ROOFING
8" CMU WALL
5/8" GYP BLUEBOARD ON RIGID
SUSPENSION SYSTEM
ENGINEERED WOOD FLOORING
ON ISOLATION PAD
4" BASE BOARD
2 LAYERS 1" GYP PANEL
CONTINUOUS TO ROOF- 2HR FIRE RATING
ENGINEERED WOOD FLOORING
ON ISOLATION PAD
4" BASE BOARD
0'-4"
SYNTHETIC WOOD DECKING
ON 2X2 PT SLEEPERS
FIBER CEMENT PANELS
5% SLOPE
1" GAP MAX
7'-0"
1'-0"
4'-0"MIN
1" GAP MAX
5/4X6 AZAK TRIM
3'-0"
3'-0"
2 HR FIRE SEPARATION
WALL
2 HR FIRE SEPARATION
WALL
SPRINKLED GARAGE
A-3.1
2
2X4 WITH @ 16" WITH
5/8" FIBER CEMENT
PANEL
2X2 P.T SLEEPERS
ON UNCURED
RUBBER SLIP
SHEET
AIR FILTRATION BARRIER
FIBER CEMENT PANEL
3/4" CDX PLY
EPDM ROOFING
2" x 8" COMPOSITE WOOD CAP
UNCURED RUBBER
UNCURED RUBBER
ADHERED BELLOW
CAP
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
BIDDINGSET
289TAPPANSTREET
BROOKLINE,MA
BUILDUNG
SECTION
B-B
A-3.1
06/05/17
IO
GWH
1 SECTION B-B
129'-6"
140'-4"
141'-10"
143'-4"
151'-4"
152'-10"
154'-4"
164'-7"
163'-1"
161'-7"
171'-11"
173'-5"
174'-11"
SCALE 1/4"=1'-0"
2 SECTION B-B - Callout 1
15. LANDSCAP
E BLOCKS
4"X24"
GUARD
RAILING AT
TOP OF
WALL
PLANTER
FIRST
FLOOR
PATIO
PLANTER
16"
CONCRETE
WALL WITH
STONE
VENEER
GATE
16' - 2"
4'-0"
16' - 9"
5'-4"
11' - 6"
7'-0"
7' - 0"
8'-10"
PLANTE
R
PLANTE
R
11' - 5"
8'-3"
16' - 6"
9'-4"
1'-6"
3'-0"
3'-0"
2'-0"
13' - 7"
20' - 6 1/2"
12' - 4 1/2"
10' - 10 1/2"
4' - 3"
3' - 3"
8'-91/2"
9'-11"
1'-6"
15'-6"
21' - 4 1/2"
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET,
BROOKLINE,MA
RETAINING
WALL
A-3.2
06/05/17
IO
GWH
1/4" = 1'-0"
1
LEFT SIDE WALL
16. ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET,
BROOKLINE,MA
ROOM
FINISH
SCHEDULE
A-4.0
06/05/17
IO
GWH
ROOM FINISH SCHEDULE
ROOM NO. ROOM NAME FLOOR BASE
WALLS CEILING
REMARKSNORTH EAST WEST SOUTH MATERIAL
RATIN
G HEIGHT
B-409 LAUNDRY B-409 VCT WD PTD PTD PTD
B-410 CLOSET B-410 ENG WD
B-411 CLOSET B-411 ENG WD
B-412 UTILITY B-412 VCT
B-501 LOBBY B-501
B-502 ELEVATOR B-502
B-503 STAIRS B-503
B-504 ELEV. EQ. B-504
B-505 STORAGE B-505
B-506 ROOF DECK B-506 WD
DECKING
B-507 ROOF B-507
C-101 ENTRANCE C-101 CT-1 CT-1 PTD PTD PTD PLASTER NA 10'- 0"
C-102 ELEVATOR C-102 SEE ELEVATOR CAB
C-103 STAIRS C-103 WD PL NA PTD PTD PTD PTD PLASTER NA 10' -0"
C-201 LOBBY C-201 CT-1 CT-1 PTD PTD PTD PTD PLASTER NA 10'- 0"
C-201 LOBBY C-201
C-202 STAIRS C-202 WD PL NA PTD PTD PTD PTD PLASTER NA 10' -0"
C-202 STAIRS C-202
C-203 ELEVATOR C-203 NA NA NA NA NA NA NA NA NA SEE ELEVATOR CAB
C-203 ELEVATOR C-203
C-204 LIVING ROOM C-204 ENG WD WD PTD PTD PTD PTD PLASTER NA 10' -0"
C-204 LIVING ROOM C-204
C-205 KITCHEN C-205 ENG WD WD PTD PTD PTD PTD PLASTER NA 10'- 0"
C-206 BATHROOM C-206 CT-2 CT-2 PTD/WT-1 PTD/WT-1 PTD/WT-1 PTD/WT-1 PLASTER NA 8'-0
C-206 BATHROOM C-206
C-207 Room
C-208 UTILITY C-208 VCT WD PTD PTD PTD PTD PLASTER NA 10' -0"
C-209 PATIO C-208 PAVER - A NA NA NA NA NA NA NA NA 2' x 2' x 2" PRECAST PAVER
C-209 PATIO C-209 PAVER - A NA NA NA NA NA NA NA NA 2' x 2' x 2" PRECAST PAVER
C-301 LOBBY C-301 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
C-302 STAIRS C-302 WD PL
C-303 ELEVATOR C-303 NA NA NA NA NA NA NA NA NA SEE ELEVATOR CAB
C-304 BEDROOM C-304 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
C-305 BEDROOM C-305 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
C-306 BATHROOM C-306 CT-2 CT-2 WT-2 PTD PTD PTD PLASTER NA 9'-0"
C-307 SHOWER C-307 CT-4 CT-4 CT-5 CT-5 CT-5 CT-5 CT-5 NA 8'-0
C-308 TOILET C-308 CT-3 CT-3 PTD FR. GL PTD FR GL CT-5 NA 8'-0
C-309 BATHROOM C-309 CT-6 CT-6 PTD/CT-7 PTD/CT7 PTD/CT7 PTD/CT7 PTD/CT7 NA 9'-0"
C-310 CLOSET C-310 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
C-311 CLOSET C-311 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
C-312 L.C. C-314 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
C-313 CLOSET C-313
C-314 UTILITY C-314 VCT WD PTD PTD PTD PTD PLASTER NA 9'-0"
C-315 PATIO C-315 PAVER - A 2' x 2' x 2" PRECAST PAVER
C-401 LOBBY C-401 ENG WD WD
C-401 LOBBY C-401
C-401 LOBBY C-401
C-402 STAIRS C-402 WD PL WD
C-402 STAIR C-402
C-403 ELEVATOR C-403 NA WD SEE ELEVATOR CAB
C-403 ELEVATOR C-403
C-404 BEDROOM C-404 ENG WD WD
C-405 BEDROOM C-405 ENG WD WD
C-406 BEDROOM C-406 ENG WD WD
C-407 BATHROOM C-407 ENG WD WD
C-407 BATHROOM C-407
C-408 BATHROOM C-408 ENG WD WD
C-409 BATHROOM C-409
C-410 LAUNDRY C-410 VCT WD
C-411 CLOSET C-411 ENG WD WD
C-412 CLOSET C-412 ENG WD WD
C-413 CLOSET C-413
C-414 L.C. C-414 ENG WD WD
C-501 LOBBY C-501
C-503 ELEVATOR C-502
C-503 LOBBY C-503
C-504 ELEV. EQ. C-504
C-505 STORAGE C-505
C-506 ROOF DECK C-506
C-507 ROOF C-507
G -101 GARAGE G-101 SEALED
CONC.
NA PTD PTD PTD PTD GWB 2HR 8'-0
G -102 WATER/ GAS CONC.
G -103 ELECT METEWRS G-103
G-104 VENT G-104 STONE NA CONC. CONC. CONC. CONC. NA GALV. STEEL GRATE
ROOM FINISH SCHEDULE
ROOM NO. ROOM NAME FLOOR BASE
WALLS CEILING
REMARKSNORTH EAST WEST SOUTH MATERIAL
RATIN
G HEIGHT
A-101 ENTRANCE A-101 CT-1 CT-1 GFB GL GFB GL PLASTER NA 10' -0"
A-102 ELEVATOR A-102 SEE ELEVATOR CAB
A-103 STAIRS A-103 CT-1 NA PTD GL GFB GL
A-201 LOBBY A-201 CT-1 CT-1
A-202 STAIRS A-202 WD PL NA PTD GL GFB GL PLASTER NA 10' -0" VISION SCREENING
A-203 ELEVATOR A-203
A-204 LIVING ROOM A-204 ENG:WD WD PTD PTD PTD PTD PLASTER NA 10' -0"
A-205 KITCHEN A-205 ENG:WD WD PTD PTD PTD PTD PLASTER NA 10' -0"
A-206 BATHROOM A-206 CT-2 CT-2 PTD/WT-1 PTD/WT-1 PTD/WT-1 PTD/WT-1 PLASTER NA 8'-0 CT. WAINSCOT TO 48"
A-208 PATIO A-208 PAVER - A 2' x 2' x 2" PRECAST PAVER
A-301 LOBBY A-301 ENG:WD
A-302 STAIRS A-302 WD PL
A-303 ELEVATOR A-303
A-304 BEDROOM A-304 ENG:WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-305 BEDROOM A-305 ENG:WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-306 BATH A-306 CT-2 CT-2 WT-2 NA 9'-0" SEE INTERIOR ELEVATIONS
A-307 TOILET A-307 CT-3 CT-3 PTD FR. GL PTD FR GL PLASTER NA 8'-0
A-308 SHOWER A-308 CT-4 CT-4 CT-5 CT-5 CT-5 CT-5 CT-5 NA 8'-0
A-309 BATHROOM A-309 CT-6 CT-6 PTD/CT-7 PTD/CT7 PTD/CT7 PTD/CT7 PTD/CT7 NA 9'-0"
A-310 CLOSET A-310 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-311 CLOSET A-311 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-312 L. CLOSET A-312 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-313 CLOSET A-313 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-314 UTILITY A-314 VCT WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-315 BALCONY A-315 SN WD NA NA NA SENTHETIC DECKING ON P:T. WD SLEEPERS
A-401 LOBBY A-401 ENG WD NA
A-402 STAIRS A-402 WD PL NA
A-403 ELEVATOR A-403 NA SEE ELEVATOR CAB
A-404 LOFT A-404 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-405 BEDROOM A-405 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-406 BEDROOM A-406 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-407 BATHROOM A-407 ENG WD WD PTD/CT 8 PTD/CT8 PTD/CT8 PTD PLASTER NA 9'-0"
A-408 BATHROOM A-408 ENG WD WD PTD PTD/CT8 PTD/CT8 PTD PLASTER NA 9'-0"
A-409 LAUNDRY A-409 VCT WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-410 CLOSET A-410 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-411 CLOSET A-411 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-412 UTILITY A-412 VCT WD PTD PTD PTD PTD PLASTER NA 9'-0"
A-501 LOBBY A-501
A-502 ELEVATOR A-502
A-503 STAIR A-503
A-504 ELEVATOR EQUIPMENT
A-504
A-505 STORAGE A-505
A-506 ROOF DECK A-506
A-507 ROOF A-507
B-101 ENTRANCE B-101 CT-1 CT-1 GFB PTD PTD PTD PLASTER
B-102 ELEVATOR B-102 CT-1 NA NA NA NA SEE ELEVATOR CAB
B-103 STAIRS B-103 CT-1 NA PTD PTD PTD PTD NA NA 10'- 0"
B-201 LOBBY B-201 CT-1 CT-1 PTD PTD PTD PTD PLASTER NA 10'- 0"
B-202 STAIRS B-202 WD PL NA PTD PTD PTD PTD PLASTER NA 10' -0"
B-203 ELEVATOR A-203 SEE ELEVATOR CAB
B-204 LIVING ROOM B-204 ENG WD WD PTD PTD PTD PTD PLASTER NA 10' -0"
B-205 KITCHEN B-205 ENG WD WD PTD PTD PTD PTD PLASTER NA 10' -0"
B-206 BATHROOM B-206 CT-2 CT-2 PTD/WT-1 PTD/WT-1 PTD/WT-1 PTD/WT-1 PLASTER NA 8'-0 CT. WAINSCOT TO 48"
B-208 BALCONY B-208 PAVER - A 2' x 2' x 2" PRECAST PAVER
B-301 LOOBY B-301 ENG WD
B-302 STAIRS B-302 WD PL
B-303 ELEVATOR B-303
B-304 BEDROOM B-304 ENG WD WD PTD PTD
B-305 BEDROOM B-305 ENG WD WD PTD PTD
B-306 BATHROOM B-306 CT-2 CT-2 WT-2
B-307 TOILET B-307 CT-3 CT-3 PTD FR. GL. PTD PTD PLASTER NA 8'-0
B-308 SHOWER B-308 CT-4 CT-4 CT-5 CT-5 CT-5 CT-5 CT-5 NA 8'-0
B-309 BATHROOM B-309 CT-6 CT-6 PTD/CT-7 PTD/CT7 PTD/CT7 PTD/CT7 PTD/CT7 NA 9'-0"
B-310 CLOSET B-310 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
B-311 CLOSET B-311 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
B-312 L.CLOSET ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
B-313 UTILITY B-313 ENG WD WD PTD PTD PTD PTD PLASTER NA 9'-0"
B-314 BALCONY B-314 ENG WD NA NA NA SYNTHETIC DECKING ON P:T. WD SLEEPERS
B-401 LOBBY B-401 ENG WD WD PTD PTD PTD
B-402 STAIRS B-402 WD PL WD PTD PTD PTD
B-403 ELEVATOR B-403 SEE ELEVATOR CAB
B-404 LOFT B-404 ENG WD WD PTD PTD PTD PTD
B-405 BEDROOM B-405 ENG WD WD PTD PTD PTD PTD
B-406 BEDROOM B-406 ENG WD WD PTD PTD PTD PTD
B-407 BATHROOM B-407 ENG WD WD PTD/CT 8 PTD/CT8 PTD/CT8 PTD PLASTER NA
B-408 BATHROOM B-408 ENG WD WD PTD/CT 8 PTD/CT8 PTD/WT-1
17. 8'-0"
3' - 0"
7'-0"
3' - 0"
7'-0"
3' - 0"
8'-0"
3' - 0"
TYPE A TYPE B TYPE C TYPE D
1
2
3
4
PASSAGE LOCKSET WITH PANIC BAR AND CLOSER. PUSH OVER ACTION ON DOOR WILL ACTIVATE FIRE ALARM. FIRE ALARM CAN
BE ACTIVATED BY P.I.N. ON KEYPAD ADJACENT TO DOOR. DE-ACTIVATE WILL BE EFFECTIVE FOR 60 SECONDS AFTER DOOR
CLOSED. OPENING OF DOOR WITH DEACTIVATION PERIOD WILL RESET TIMER FOR 60 SECONDS, AFTER 60 SECONDS, PIN ENTRY
WILL BE REQUIRED.
5
6
HINGES HANDLE DEADBOLT
FINISH MANUFAC.
4" x 4"
ITEM NO.
NO.
PRIVACY LEVER SET
WITH SQUARE ROSE
BRUSHED
STAINLESS
STEELPLAIN BEARING
MANUFACT.
OMNIA 985/4
ITEM NO.DESCRIPTION DESCRIPTION
OMNIA 25SPR
4" x 4" LEVER SET WITH
SQUARE ROSE
BRUSHED
STAINLESS
STEELPLAIN BEARING
OMNIA 985/4 OMNIA 25S
DESCRIPTION FINISH MANUFAC. ITEM NO.
4" x 4"
BALL BEARING
OMNIA
CONTEMPRARY
SMARTCODE
ELECTRONIC
DEADBOLT
SATIN
CHROME
KWIKSET 909CNT
26D SMT
TAVARIS SINGLE
CYLINDER
HANDLESET,
EXTERIOR ONLY
KATARA INTERIOR
LEVER
SATIN
CHROM KWIKSET
720KTL
26D
SATIN
CHROM
KWIKSET 800TVH
LIP 26D
SMT4" x 4"
OMNIA
NONE
NONE
PLAIN BEARING
985/4 MODERN
MULTIPOINT TRIM
(KEYED)
BRUSHED
STAINLESS
STEEL
OMNIA 73025 NONE
SAN CLEMENTE
HANDLESET ONLY
WITH HALIFAX LEVER
SATIN
CHROM
KWIKSET 815SCEX
HFL 26D
BALL BEARING
4" x 4" OMNIA 985BB/4
985BB/4
909CNT
26D SMT
SLIDING POCKET
DOORMORTISE
LOCK
SOLID
STAINLESS
STEEL
OMNIA
MODERN DOOR PULL
ON BOTH SIDES
FIND
COMPATABLE
HARDWARE SET
SOLID
STAINLESS
STEEL
OMNIA 721
7
HARDWARESETS SCHEDULE
PASSAGE
PROPOSED LOCATION
BEDROOM
LOCKED
/STORAGE
PATIO/
BALCONY
MAIN
ENTRANCE
POCKET
DOOR/
BATHROOM
UNIT
ENTERANCE
FROM
GARAGE
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET,
BROOKLINE,MA
DOORS
SCHEDULE
A-4.1
06/05/17
IO
GWH
DOOR SCHEDULE
DOOR NO. LOCATION LEAF
DOOR FRAME
FIRE
RATING THRESH. UNDER-CUT
WEATHE
R STRIP
HDW
SET
NO. REMARKS
SIZE
MATERIALWIDTH HEIGHT THICKNESS MAT TYPE GAUGE.
C-314 UTILITY C-314 1 2 7 1 3/4" WD C 1" NA 3
C-404 BEDROOM C-404 1 3 7 1 3/4" WD C 1" NA 2
C-404 BEDROOM C-405 1 3 7 1 3/8" WD C 1" NA 2
C-405 BEDROOM C-405 1 3 7 1 3/8" WD C 1" NA 2
C-406 BEDROOM C-406 1 3 7 1 3/4" 1" NA
C-407 BEDROOM C-407 1 3 7 1 3/8" WD C 1" NA 2
C-408 BATHROOM C-408 1 3 7 1 3/8" WD C 1" NA 2
C-409 BATHROOM C-408 1 3 7 1 3/8" WD C 1" NA 2
C-410 LAUNDRY C-409 1 3 7 2" WD C 1" NA 1
C-411 CLOSET C-410 2 4 7 1 3/4" WD C 1" NA 1
C-412 CLOSET C-411 2 4 7 1 3/4" WD C 1" NA 1
C-413 CLOSET C-410 2 4 7 1 3/4" WD C 1" NA 1
C-414 L.C. C-412 1 3 7 0" WD C 1" NA 1
C-501 LOBBY C-501 1 3 7 1 3/4" WD A AL N Y 4
C-504 ELE. EQ. C-504 1 4 7 1 3/4" WD B N Y 3
C-505 STORAGE C-505 1 3 8 1 3/4" WD B N Y 3
G-101 GARAGE G-101 1 16 7 2" Y N Y NA GARAGE
DOOR
G-102 WATER-GAS G-102 2 5 7 3/8" B N Y 3
G-103 ELE. METER G-103 1 3 7 1 3/8" B N Y 3
DOOR SCHEDULE
DOOR NO. LOCATION LEAF
DOOR FRAME
FIRE
RATING THRESH. UNDER-CUT
WEATHE
R STRIP
HDW
SET
NO. REMARKS
SIZE
MATERIALWIDTH HEIGHT THICKNESS MAT TYPE GAUGE.
A-101-a ENTRANCE A-101 1 3 8 1 1/4" STL A NA STL 1 HR Y N Y 5
A-101-b ENTRANCE A-101 1 3 7 1 3/4" HM B Y AL N Y 7
A-204 LIVING ROOM
A-204
1 3 8 1 1/4" FG D NA AL AL N Y 4
A-206 BATHROOM A-206 1 3 7 1 3/4" WD C NA WD MARBLE 1" NA 6 POCKET
A-304-a BEDROOM A-304 1 3 8 1 3/4" WD C NA WD 1" NA 2
A-304-b BEDROOM A-304 1 3 7 1 3/4" WD C NA WD 1" NA 4
A-305 BEDROOM A-305 1 3 8 1 3/4" WD C NA WD 1" NA 2
A-306 BATHROOM A-306 1 3 7 1 3/4" WD C NA WD 1" NA 2
A-307 TOILET A-307 1 3 7 1 3/4" NA NA NA
A-308 SHOWER A-308 1 3 7 1 3/4" NA NA NA
A-309 BATHROOM A-309 1 3 7 1 3/4" WD C NA WD 1" NA 2
A-310 CLOSET A-310 1 3 7 1 3/4" WD C NA WD 1" NA 1
A-312 CLOSET A-312 1 2 7 1 3/4" WD C NA WD 1" NA 1
A-313 L.CLOSET A-313 2 4 7 1 3/4" WD C NA WD 1" NA 1
A-314 UTILITY A-314 1 3 8 1 3/4" WD C NA WD 1" NA 1
A-405 BEDROOM A-405 1 3 8 1 3/4" WD C NA WD 1" NA 2
A-406 BEDROOM A-406 1 3 7 0" WD C NA WD 1" NA 2
A-407 BATHROOM A-407 1 3 7 1 3/4" WD C NA WD 1" NA 2
A-408 BATHROOM A-408 1 3 8 1 3/4" WD C NA WD 1" NA 2
A-409 LAUNDRY A-409 1 3 8 1 3/4" WD C NA WD 1" NA 2
A-410 CLOSET A-410 2 4 7 1 3/4" WD C NA WD 1" NA 1
A-411 CLOSET A-411 2 4 7 1 3/4" WD C NA WD 1" NA 1
A-412 UTILITY A-412 1 3 7 1 3/8" WD C NA WD 1" NA 1
A-501 LOBBY A-501 1 3 7 1 3/4" A NA N Y 4
A-504 ELEVATOR EQ.
A-504
1 4 7 1 3/4" B NA N Y 3
A-505 STORAGE A-505 1 3 7 1 3/4" WD B NA N Y 3
B-101-a ENTRANCE B-101 1 3 8 1 1/4" STL A NA STL 1 HR Y N Y 5
B-101-b ENTRANCE B-101 1 4 7 1 3/4" HM B Y AL N Y 7
B-204 LIVING ROOM
B-204
1 3 8 1 1/4" WD D NA FG AL N Y 4
B-206 BATHROOM B-206 1 3 7 1 3/4" WD C NA WD MARBLE 1" NA 6 POCKET
B-304-a BEDROOM B-304 1 3 7 1 3/4" WD C NA WD 1" NA 2
B-304-b BEDROOM B-304 1 3 7 1 3/4" WD C NA WD 1" NA 4
B-305 BEDROOM B-305 1 3 8 1 3/4" WD C NA WD 1" NA 2
B-306 BATHROOM B-306 1 3 7 0" WD C NA WD 1" NA 2
B-307 TOILET B-307 1 3 7 1 3/8" - NA
B-308 SHOWER B-308 1 2 7 1 3/4" NA
B-309 BATHROOM B-309 1 3 7 0" WD C WD 1" NA 2
B-310 CLOSET B-310 1 3 7 0" WD C WD 1" NA 1
B-311 CLOSET B-311 1 3 7 0" WD C WD 1" NA 1
B-312 L.CLOSET B-312 1 3 7 1 3/8" WD C WD 1" NA 3
B-313 UTILITY B-313 1 3 7 1 3/8" WD C WD 1" NA 3
B-405 BEDROOM B-405 1 3 7 0" WD C WD 1" NA 2
B-406 BEDROOM B-406 1 3 7 0" WD C WD 1" NA 2
B-407 BATHROOM B-407 3 7 2" WD C WD 1" NA 2
B-408 BATHROOM B-408 3 7 2" WD C WD 1" NA 2
B-409 LAUNDRY B-409 1 3 7 0" WD C WD 1" NA 1
B-410 CLOSET B-410 1 3 7 1 3/8" WD C WD 1" NA 1
B-411 CLOSET B-411 1 3 7 1 3/8" WD C WD 1" NA 1
B-412 UTILITY B-412 1 2 7 1 3/4" WD C WD 1" NA 3
B-501 LOBBY B-501 1 3 7 1 3/4" WD A WD N Y 4
B-504 ELE. EQ. B-504 1 4 7 1 3/4" WD B N Y 3
B-505 STORAGE B-505 5 7 2" WD B N Y 3
C-101-a ENTRANCE C-101 1 3 8 1 1/4" STL A STL 1 HR Y N Y 5
C-101-b ENTRANCE C-101 1 4 7 1 3/4" HM B Y AL N Y 6
C-204 PATIO 1 3 8 1 3/8" FG D AL AL N Y 4
C-205 KITCHEN C-205 1 3 8 1 3/8" WD D AL N Y 4
C-206 BATHROOM C-206 1 3 7 1 3/8" WD C MARBLE 1" NA 3
C-207 UTILITY C-207 1 3 7 0" WD C 1" NA 3
C-304-a BEDROOM C-304 1 3 7 1 3/4" WD C 1" NA 2
C-304-b BEDROOM C-304 1 3 8 1 1/4" WD C 1" NA 2
C-305 BEDROOM C-305 1 3 7 0" WD C 1" NA 2
C-306 BATHROOM C-306 1 3 8 1 3/4" WD C 1" NA 2
C-307 SHOWER C-307 1 3 7 1 3/8" NA
C-308 TOILET C-308 1 3 7 1 3/8" NA
C-309 BATHROOM C-309 3 7 2" WD C 1" NA 2
C-310 CLOSET C-310 1 3 7 0" WD C 1" NA 1
C-311 CLOSET C-311 2 4 7 1 3/4" WD C 1" NA 1
C-312 L.C. C-314 1 3 7 1 3/8" WD C 1" NA 1
C-313 CLOSET C-313 2 4 7 1 3/4" WD C 1" NA 1
19. SLOPE
0'-2"
HOIST BEAM 2" BELLOW CIELING
SHAFT VENT
7'-0"
PIT
10"
FOUNDATIO
N WALL
TROWEL WATER
PROOFING
7'-0"
BOND BEAM AT
EACH FLOOR
7' - 8"
0' - 8"
0' - 8"
5'-10"
0'-8"
4' - 3" 0' - 2 3/4"
HOISTWAY
3' - 2 1/4"
ROUGH OPENING
PI
HOIST WAY
7' - 8"
0' - 8"
0' - 8"
5'-10"
0'-8"
HOISTWAY
HOIST WAY
4' - 3"0' - 2 3/4" 3' - 2 1/4"
ROUGH OPENING
RIGHT HANDED RIGHT HANDED
UNIT A & UNIT CUNIT B
HOISTWAY HOISTWAY
7' - 8"
0' - 10"
0' - 10"
5'-10"
0'-10"
4' - 3"
0' - 2 3/4"HOISTWAY 3' - 2 1/4"
ROUGH OPENING
PI
HOIST WAY 0' - 10"
5'-10"
0'-10"
HOISTWAY
HOIST WAY
4' - 3"
3' - 2 1/2"
ROUGH OPENING
RIGHT HANDED RIGHT HANDED
UNIT A & UNIT CUNIT B
PIT
0' - 2 1/2"
1'-111/2"
0' - 4 1/2"
PIT LADDER POCKET
2 1/2" X 1 11 1/2"
PIT LIGHT
0' - 2 1/2"
1'-111/2"
PIT LADDER POCKET
2 1/2" X 1 11 1/2"
THYSSENKRUPP ELEVATOR
SYNERGY -SELF
SUPPORTED
SEISMIC 2100 LB. RH
DOOR & SILL
ONE-SPEED DOOR, RIGHT HAND OPENING
PITCH BLACK POWER COAT DOOR
KICKPLATE WITH BRUSHED STAINLESS
STEEL FINISH BRONZE SILL
FRONT RETURN & FIXTURES
WRAP AROUND RETURN BRUSHED
STAINLESS STEEL FRONT SIGNA4
FIXTURES
WALLS
FORMICA NATURAL CANE WALL
PANELS PITCH BLACK POWDER COAT
BASE/REVEAL/ FRIEZE
HANDRAIL
2"FLAT BAR WITH RETURNED ENDS
ON ALL SIDES BRUSHED STAINLESS
STEEL FINISH
FLOOR
PRAIRIE SKY CARPET
OTHER OPTIONS
REGULAR CAB HEIGHT
PIT LIGHT
7' - 8"
0' - 10"
0'-10"
0'-10"
LADDER PROVIDED BY MANIFACTURER, LADDER
CAVITY NOT NECESSERY
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET
BROOKLINE,MA
ELEVATOR
SECTION
A-5.1
06/05/17
IO
GWH
1/4" = 1'-0"
1
elevator section detail
1/2" = 1'-0"
elevator plans
8" I-BEAM @ 13' 4" HIGH
THEN 2" FOR CLEARANCE
20. UNIT-C 1st FL
143' - 4"
UNIT-C 2nd FL
154' - 4"
UNIT-C 3rd FL
164' - 7"
UNIT-C Roof
174' - 11"
GARAGE
129' - 6"
unit 3 ELEVATOE
TOP
185' - 5"
unit 3 level 7
133' - 2"
11'-0"10'-3"
6 MIL VAPOR BARRIER (TYP)
4" CONC. SLAB
COMPACTED GRAVEL
2" TH RIGID INSULATION
3'-4"
10'-11/2"10'-111/4"
12'-103/4"
ENGINEERED WOOD
FLOORING
3/4" T&G PLYWOOD SUB
FLOOR
WITH ISOLATION PAD
BRUSHED STAINLESS STEEL
RAILING
METAL PAN STAIR W/ C.T.
STEP
A-5.2
2
A-5.2
3
6'-7"6'-111/2"6'-113/4"
UP
GARAGE/ ENTRANCE
3'-11"3'-11"
3' - 10"
3'-7"
7'-10"
0'-8"
3'-7"
HEIGHT 10'-1"
15 RISERS
R = 8.0"
T = 11"
UP
FIRST FLOOR
3'-11"3'-11"
3' - 10"
3'-7"
7'-10"
0'-8"
3'-7"
HEIGHT 11'-0"
16 RISERS
R = 8.25"
T = 11"
UP
THIRD FLOOR
3'-11"3'-11"
3' - 10"
3'-7"
7'-10"
0'-8"
3'-7"
HEIGHT 10'-11"
16 RISERS
R = 8.2"
T = 11"
UP
SECOND FLOOR
3'-11"3'-11"
3' - 10"
3'-7"
7'-10"
0'-8"
3'-7"
HEIGHT 10'-3"
15 RISERS
R = 8.2"
T = 11"
4' - 0"
1234567
141312111098 15
0' - 1"
1234567
14131211109
8
15 16
1234567
141312111098 15
4' - 0"
1234567
14131211109
8
15 16
FOR UNIT A
REPLACE LARGE
THREAD WITH
REGULAR
THREAD REFER
TO PLANS
FOR UNIT A
REPLACE LARGE
THREAD WITH
REGULAR
THREAD REFER
TO PLANS
0'-81/2"
0' - 1"
0' - 11"
3/4"
WOOD STAIR
TREAD
BLOCKING
ENGINEERED WOOD
FLOORING
3/4" T&G PLYWOOD SUB
FLOOR
WITH ISOLATION PAD
NATURAL WOOD TRIM
PAINT
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
BIDDINGSET
289TAPPANSTREET
BROOKLINE,MA
STAIRS
DETAILS
A-5.2
05/16/17
IO
GWH
1 STAIRS
STAIRS PLANS
2 STAIRS - Callout 1 3 STAIRS - Callout 2
21. EXHAUST FAN
AIR INTAKE
AFL
AFL
LWP
LWP
LWP
LWP
LWP
LWP
LWP
LWP
LWP
LWP
LWP
LWP
RWP
RWP
RWP RWP
GDO
M
M
M
MM
P
RWP
M
M
3
R
R
3 R
R
R
3
R
R
R
R
R
R
R
CC
C
R R
R
R R
D
D
R R
R
R R
D
D
R R
R
R R
D
D
C
3 3
3
EXT.
EXT.
EXT.
EXT.
R
R
R
R
RR
R R
RR
R
RR
RR
R
R R
RR
B
B
B
A
A
A
WP
WP
B
WP
3
3
3
R
R
B
WP
A SURFACE MOUNTED LIGHT FIXTURE
SURFACE MOUNTED LIGHT FIXTURE
RECESSED ROUND FIXTURE
RECESSED WATERPROOF FIXTURE
RECESSED SQUARE FIXTURE
LINEAR LED FIXTURE
WALL MOUNTED FIXTURE
EXHAUST FAN / LIGHT COMBINATION
LEGEND
LWP LANDSCAPE WALL PACK
AFL
LANDSCAPE DIRECTIONAL SPOTLIGHT
RWP
RECESSED WATERPROOF FIXTURE
SWITCH
3 3-WAY SWITCH
GARAGE DOOR OPENER
GDO
M MOTION SENSOR
P PHOTO CELL
BUTTON SWITCH
D
C CHANDELIER MOUNTING BOX
SURFACE LIGHT FIXTURE TYPE 'D'
R
R
R
R
A A
A A
A
A
R
3
R
R
R
R
R R
R R
R R
R R
3
3
BB
R
LWP
LWP
LWP
LWP
3
R
LWP
LWP
3
3
R
R
LWP
LWP
LWP
LWP
LWP
LWP
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET
BROOKLINE
MASSACHUSETTS
LIGHTING
PLAN
A-1.6
04/13/17
KS
GWH
1/8" = 1'-0"
1
GARAGE LIGHTING PLAN
1/8" = 1'-0"
2
FIRST FLOOR LIGHTING PLAN
1/8" = 1'-0"
3
SECOND FLOOR LIGHTING PLAN
1/8" = 1'-0"
LIGHTING LEGEND
1/8" = 1'-0"
4
THIRD FLOOR LIGHTING PLAN
1/8" = 1'-0"
5
ROOF LIGHTING PLAN
22. J
GFI
J
GARAGE DOOR
OPENER
GFI
GFI
CO
CO
COUNTER
BALANCED
LOUVER
GFI
3636
36 36
30
GD WINE
COOLER
J
GFI--WPGFI--WP
GFI--WP
GFI--WP
3636
36
GD
36
36
30
GFI
3636
GD
30
30
36
WINE
COOLER
60
60
J
GFI
GFI
GFI
GFIGFI
GFI GFI
GFI
GFI
J
GFI GFI
GFI
GFI
GFI
J
J
GFI
36
J
GFI
GFIGFI
GFI
GFIGFI
GFI
GFI
GFI
JGFI
GFI
GFI
GFI
J
J
DUPLEX RECEPTACLE
LEGEND
GFI
36
GFI--WP
J
DUPLEX RECEPTACLE AT 36" A.F.F.
GROUND FAULT RECEPTACLE
GFI DUPLEX RECEPTACLE IN
WATERPROOF COVER
JUNCTION BOX
CONDENSER POWER SWITCH
CABLE OUTLET
SWITCHED DUPLEX RECEPTACLE
TELEPHONE OUTLETT
S
APPLIANCE OUTLET
CARBON MONOXIDE DETECTION -
LINKED TO EXHAUST FAN
CO
INTERCONNECTED
PHOTOELECTRIC SMOKE ALARM
PERMANENTLY POWERED WITH
BATTERY BACK-UP CARBON MONOXIDE DETECTOR
J
GFI--WP
GFI--WP
GFI--WP
GFI--WP
GFI
J
J
GFI
S S S
S
S
S
S
S
S
GFI--WP GFI--WP
J
GFI
ISSUE/DESCRIPTIONDATENO.
SHEET TITLE:
DRAWN BY:
DATE:
JOB NO.:
CHKD. BY:
DWG. NO.:
REVISIONS
ARCHITECT@HENDRENASSOCIATES.COM
T 617 782 6003
F 617 782 6063
SUITE 315
ARCHITECT
GARY W. HENDREN, AIA
BOSTON, MA 02134
119 BRAINTREE STREET
ARCHITECTS + PLANNERS
PERMITSUBMISSION11/21/161
289TAPPANSTREET
BROOKLINE
MASSACHUSETTS
POWER
PLANS
A-1.7
04/13/17
KS
GWH
1/8" = 1'-0"
1
GARAGE POWER PLAN
1/8" = 1'-0"
2
FIRST FLOOR POWER PLAN
1/8" = 1'-0"
3
SECOND FLOOR POWER
1/8" = 1'-0"
4
THIRD FLOOR POWER PLAN
1/8" = 1'-0"
POWER LEGEND
1/8" = 1'-0"
5
ROOF POWER PLAN