2. The AMAX System
AMAX uses multiple heat exchange stages to
maximize the energy savings potential of
evaporative cooling while maintaining comfort
across a broad range of ambient conditions.
AMAX offers Indirect Only Evaporative Cooling
(IEC), Indirect/Direct (IDEC) and Hybrid DX
configurations to meet all cooling requirements
while saving up to 80% of the electric cost of
comparable compressor based systems.
3. AMAX Applications
• AMAX offers the greatest energy saving benefits in
extreme climate conditions- the hotter the ambient
conditions the better the performance compared to DX.
• AMAX can provide 100% outdoor air and is ideal for
casinos, hospitals, schools, restaurants or other
installations that require large amounts of fresh
conditioned air.
• AMAX Return on Investment is greatest when large
amount of process cooling are required for extended
periods – for example, in data centers, manufacturing
facilities etc. Outdoor air is not required for these
applications.
4. AMAX Indirect/Direct Evaporative Coolers
Commercial and Industrial Cooling Solutions
• Custom Engineering Solutions with
variable sizing and configuration to meet
all requirements.
• Powered Economizers and Powered Pre-
Coolers sized for quick retrofit to existing
RTUs
• Integrated chilled or hot water coils for
cost effective full HVAC solution.
5. AMAX Features and Benefits
• Up to 125% adiabatic effectiveness
• EER 40+
• Competitive pricing and low installed cost
for quick payback
• Rugged, proven and designed for harsh
environmental conditions
• Easy assembly and maintenance
• Full engineering support
6. AMAX Retrofit Options
• Powered Economizers™ in IDEC or Indirect
Only configuration significantly reduce DX
cooling hours while providing cold conditioned
fresh air.
• Powered Economizers can also be used to pre-
cool condensing units for significant energy
savings.
• Adding low cost Powered Economizers to RTUs
results in Energy Savings, Rebates and
Extended Life of the RTU.
13. AMAX Supply Temperature and Cooling Output
ASHRAE 1% Design Condition for Denver, Colorado
ASHRAE Design Conditions Ambient Unit AMAX Supply
Dry Bulb Wet Bulb Delta Temp
°F °F Delta T Effectiveness T °F
AMAX 1.0% 93 59 34 115% 39.1 54
AMAX Premium 1.0% 93 59 34 125% 42.5 51
AMAX IEC Only 1.0% 93 59 34 75% 25.5 68
Single Stage Cooler 1.0% 93 59 34 85% 28.9 64
Single
AMAX Stage AMAX
AMAX Calculated Cooling Output AMAX Premium Cooler Indirect Only
Unit size (cfm) 5,500 5,500 5,500 5,500
Unit Power Consumption (watts) 1,950 2,680 1,500 2,193
Unit Sensible Cooling (tons) 15 17 11 10
Unit EER (using Equivalent Tons) 87 72 69 54
14. AMAX Cooling Output and Energy Consumption
Economizer Retrofit Proposal – Monte Vista, CO
AMAX Sizing - Colorado ASHRAE Design Conditions Ambient AMAX AMAX AMAX
Dry Bulb °F Wet Bulb Delta T effectiveness Delta T Supply
1.0% 97 61 36 115% 41.4 55.6
AMAX Calculated Cooling Output
in Monte Vista
Project Total Supply Air (CFM) 77,101
AMAX Total Power Consumption (watts) 7,500
Additional RTU Fan Power 7,710 (.1watt/cfm at .7" based on generic blower curve)
Total AMAX Power Consumption (watts) 15,210
AMAX Unit Sensible Cooling (tons) 226
AMAX Unit EER 178
17. AMAX Data Center Units
Rated at 15,000 cfm and 75% Effectiveness
18. AMAX Indirect Only Data Center Units
EasyStreet® Online Services, Inc. is Oregon’s largest independent Internet
and IT services provider. Founded in 1995, EasyStreet is Oregon’s leading
independent Managed Hosting and Co-location provider because it is
reliable, responsive and responsible — to its customers, its community and
the environment. http://easystreet.com/about/
For more information on the AMAX installation at EasyStreet Data Services please contact:
Jack Flug
Vice President of Finance
Direct: 503-671-1894
Email: jackflug@easystreet.com
19. AMAX Indirect Only Data Center Units
EasyStreet Sustainablility Data Sheet
• “Energy-saving technologies such as Indirect Evaporative Cooling…
reduce costs as well as carbon emissions while directing more
power to customer cabinets.”
• “With this state-of-the-art design we have achieved an estimated 1.3
PUE (Power Use Effectiveness) where a traditional data is typically
above a 2.0.”
• PUE is calculated by dividing total facility power consumption by
server power use.
• PUE with standard CRAC was estimated at 1.6. PUE with AMAX is
estimated at 1.3. Total AMAX cooling power use is .07.
• AMAX power consumption is estimated to cost $7,000 per month
and save $30,000 per month compared with traditional CRAC units
according to Rich Bader, President and CEO of EasyStreet.
20. AMAX