XVII CONVEGNO EUROPEO J. Gerstel - LOW GWP REPLACEMENTS FOR R-404A IN A COMMERCIAL FREEZER
1. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
Very Low GWP Replacements for R-404A
–
Performance Tests in a Commercial Freezer
Joachim Gerstel
Technology and Regulatory Affairs
Manager EMEA
Chemours Deutschland GmbH
joachim.gerstel@chemours.com
2. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
Introduction
R404A-Alternatives with very low GWP
Main Properties of R-454A & R-454C
TD-Cycle Analysis
Drop-In Test Results in a Freezer
Compatibility with Materials & POE
Charge Size Calculation
Summary
Agenda
3. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
Mid- and Long-Term Requirements to fulfill the EU
F-Gas Regulation
are new tailor made solutions by application.
They need:
• GWP << 400 → Therefore likely safety class A2L or A3
• Risk Analysis
• Favorable Total Costs of Ownership (TCO)
Introduction
4. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
Very Low GWP Replacements for R-404A
XL20 (R-454C) XL40 (R-454A)
< 150 GWP < 250 GWP
Refrigeration – replace R-404A, 507, 407s
Lowest GWP Closest match
5. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
Thermophysical Properties
R-404A
Opteon™ XL20
(R-454C)
Opteon™ XL40
(R-454A)
Boiling Point [°C] -47 -46 -48
Critical Point [°C] 72 82 79
Vapor Pressure
at 25°C in kPa 1254 1169 1342
Liquid Density at
25°C in kg/m3 1044 984 977
Vapor Density at
25°C in kg/m3 65,3 44,3 47,7
6. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
Thermodynamic Cycle Analysis
• New & simple Chemours Software
• Contains all the new refrigerants
• Based on REFPROP V9.1
7. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
Thermodynamic Cycle Performance
Psuct
bar g
Pdisch
bar g
Tdisch
°C
Tglide,
Evap °C
CAP
kW
CAP Rel to
R-404A
COP COP Rel to
R-404A
R-404A 0,64 17,2 84 0,4 82,3 100 % 1,25 100 %
Opteon™ XL20
(R-454C)
0,25 14,5 95 4,4 73,3 89 % 1,36 109 %
Opteon™ XL40
(R-454A)
0,54 17,2 108 4,3 91,0 111 % 1,37 110 %
Evaporator temp = -35 °C, Condenser temp = 40 °C, Subcool = 2 K, Superheat = 15 K and
compressor isentropic efficiency = 70 %
8. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
Drop-in commercial freezer testing
R-454A and R-454C test-conditions:
• 1,5 m3 double-door unit with two piston comp designed for
R-404A
• Refrigerant charge size is 1,15 kg for R-404A
• Superheat 3-4 K; TXV closed by 1 ½ turn vs R-404A
• Tested at three ambient temps: 32 °C, 24 °C and 21 °C
• Average freezer compartment temp controlled at -17 °C
9. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
Results with R-454C
EC
(kWhr/day)
EC Rel to
R404A
M
(kg/hr)
Psuct
(kPa)
Pdisch
(kPa)
CR
Tdisch
(°C)
Ambient T = 32°C
R404A 34.34 100% 43 220 2068 9.4 96
XL20 34.84 101% 35 172 1785 10.4 103
Ambient T = 21°C
R404A 23.69 100% 48 200 1585 7.9 77
XL20 24.41 103% 33 165 1351 8.2 82
• 1-3% higher energy consumption despite higher
COP from Cycle Calc
• 20-30% lower massflow →lower pressure drop
• Lower evap. and cond. pressure
• Compressor discharge temp 5-7 K higher
10. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
Results with R-454A
• 3-8% lower energy consumption; positive trend
at higher ambient temp
• 20-30% lower massflow → lower pressure drop
• Similar evap. and cond. Pressure
• Compressor discharge temp 15 K higher
EC (kWhr/day)
EC Rel to
R404A
M
(kg/hr)
Psuct
(bar a)
Pdisch
(bar a)
CR Tdisch (C)
Ambient t = 32°C
R404A 33,46 100% 44 2.1 20.3 10 90
XL40 30,81 92% 34 1.9 21.3 11 105
Ambient t = 24°C
R404A 25,11 100% 46 2.0 16.5 8 75
XL40 23,91 95% 35 1.8 17.3 9 91
Ambient t = 21°C
R404A 23,39 100% 48 2.0 15.6 8 70
XL40 22,62 97% 36 1.8 16.0 9 85
11. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
R-454A/ C - Compatibility with Materials & POE
• Seal Tube tests
• POE Miscibility measurements
• Elastomer Compatibility
• Plastic Compatibility
Similar behavior vs R-404A
12. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
0
2
4
6
8
10
12
0 50 100 150 200 250
ChargeSize(kg)
Room Size (m³)
R-454A/ C
A2L
HFC-152a
A2
HC-290
A3
Calculation is based on EN378 (2016)
R-454A/ C – Charge Size
13. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
R-454A/ C - Very Low GWP Replacements
With GWP-reductions around 95% vs. R-404A
Show promising properties and performances vs
R-404A
Show similar compatibility with materials & POE
Allow higher charge size vs. safety class 3-fluids
Are commercial available
Summary
14. Latest Technology in Refrigeration and Air Conditioning - XVII European Conference Milano, 9 - 10 June 2017
Molte Grazie!
Email: joachim.gerstel@chemours.com
Disclaimer: The information set forth herein is furnished free of charge and based on technical data that DuPont
believes to be reliable. It is intended for use by persons having technical skill, at their own risk. Since conditions of use
are outside our control, we make no warranties, expressed or implied and assume no liability in connection with any
use of this information. Nothing herein is to be taken as a license to operate under, or a recommendation to infringe
any patents or patent applications.