• The most common causes of system effect include uneven or spinning airflow at a fan’s inlet, obstructions to airflow at
the inlet or outlet, improperly configured ductwork at the inlet or outlet, and/or failure to correct for losses caused by
fan accessories.
• System effect can be avoided by accounting for all factors, including the shape of the transition points between the fan
and existing ducts, ductwork configuration close to the fan, and accessories.
• For optimum air performance, airflow at the fan’s inlet needs to be uniform, symmetrical, and free of swirl. Similarly,
airflow must be able to diffuse and fully develop across the fan’s outlet. Even minor improvements to airflow stability
can reduce system effect and, in turn, increase fan performance and operating efficiency.
• An inlet vane damper is a modulating device that affects fan performance. As a damper is closed, air begins to pre-spin
into the fan; the fan wheel no longer can move as much air, and flow, pressure, and brake horsepower all decrease.
Even when a damper is fully open, the vanes interfere with normal flow and reduce fan performance. If the losses are
not accounted for, the fan will have to run at a speed higher than the one specified during fan selection. Fans should be
tested with accessories that determine the losses and the fan speed required to overcome them.
Common Causes of System Effect
Reducing System Effect at a Fan’s Inlet
• A lack of uniform airflow entering a fan’s inlet is one of the greatest and most common causes of system effect.
Often, these losses are the result of elbows and isolation dampers being installed too close to a fan’s inlet.
• Depending on the application, a variety of strategies can be employed to improve airflow at a fan’s inlet.
• Take, for example, the 90-degree round elbow located at the inlet of a fan shown in below figure.
• Air entering the fan wheel is not uniform, loading on various parts of the fan wheel instead of at the center as
designed for optimal performance. Some air is circulating back into the elbow, creating additional losses. In this
case, the addition of turning vanes in the elbow will help direct air toward the center of the fan wheel.
• Below shows the effect of a rectangular inlet box mounted
directly to the inlet of a fan. Again, the fan wheel is not being
uniformly loaded, resulting in performance loss.
• With an inlet box, the cavity, or dead area, below the outlet
is where air will get hung up, creating additional losses.
• Improving the shape of the inlet box or adding straightening
vanes can help to redirect the flow of air into the wheel.
• Figure shows air entering a fan from the side
as opposed to straight through the inlet. The air
is spinning in the opposite direction of the fan
wheel. Consequently, the fan is having to work
harder, resulting in greater energy consumption
and stress on fan components.
Reducing System Effect at a Fan’s Outlet
• Similar to inlet flow, outlet flow is impacted significantly by the placement and distancing of ductwork and dampers. The effective length
of ductwork at a fan’s outlet is one of the most important factors in fan and system efficiency. In most cases, the profile of the air coming
out of a fan is asymmetrical, causing turbulence and a lack of static-pressure regain.
• For symmetrical and uniform flow to be achieved, outlet ducting must be long enough to allow airflow to diffuse and fully develop. This is
called 100-percent effective duct length.
• As a rule of thumb, the effective length of outlet ducting should be no less than 2.5 duct diameters when duct velocity is 2,500 fpm (13
m/s) or less. For every additional 1,000 fpm (5 m/s), one duct diameter should be added.
Figure shows the velocity profile of air as it exits a fan. Air is forced against the outside of the scroll, resulting in uneven flow at the outlet.
An effective run of ductwork allows for a uniform velocity profile. Note that at approximately 50 percent of effective duct length the fan
achieves approximately 80 percent of its pressure regain.
In addition to effective duct length, the placement and direction of
elbows is significant at a fan’s outlet. An elbow installed too close to the
outlet will result in a significant loss of airflow. If the elbow turns in the
opposite direction of the fan’s rotation, the loss will be even greater.
When a design requires the installation of an elbow, a minimum of two
to three duct lengths is recommended to allow the velocity profile of
air exiting the fan to develop across the ductwork.
SIDEBAR: System Effect in Effect
1. Material Build-Up On the Wheel
If you have a material handling application or misfit another application with a fan that tends to build up material, fan vibration problems are
quite common. When that happens, it’s probably time to clean the wheel. That means shutting down, waiting for all the parts to stop moving,
locking out, opening the housing to clean it thoroughly, re-securing it, and starting back up. We recommend putting this on a regular
maintenance schedule to avoid vibration issues in the future. The other alternative is to replace the fan wheel with a self-cleaning blade or
material of construction.
2. Deteriorated Fan Wheel
There are many reasons for the deterioration of a fan wheel. Industrial fans can last for decades, so it could just be normal wear over time.
Many industrial processes involve corrosive gasses that can wear out the wheel much more quickly, causing the properties of the wheel to
change. The vibration comes from the changing properties inside the fan housing on the wheel. In this case, you will likely need to replace the
wheel with a new one, potentially designing with corrosive-resistant construction materials.
3. Loose Fasteners
Loose fasteners are actually quite common and fairly easy to fix. This is especially noticeable if your vibration is on the vertical side of your
bearing due to the fasteners at the base of the fan not being secure enough to the floor. If you find that this is the cause of the fan vibration
issues, just get out a drill and fasten them down.
4. Drive Component Misalignment
Regular maintenance requires occasional opening or disassembly and reassembly for things like cleaning, greasing, and part change outs. That
can create the potential for misalignment, which in turn can create fan vibration issues. To fix that, take your straight edge to it. You’ll want to
be sure to align the bearings, shaft, coupling, and motor to fully realign the drive.
Common Vibration Causes to Consider
5. Defective Bearings
If you’ve got bad or broken down grease or have let the bearings go too long without proper grease maintenance, you will
eventually start to get metal on metal and experience vibration. At this point, you’re well on your way to bearing failure.
Whether one or both bearings are defective and failing, you must replace them both. You’re far better off ensuring a regular
grease maintenance schedule, but bearing failure is one of the most common issues revealed by fan vibration.
7. Operating In – or Near – a Resonant Frequency
A resonant frequency is a specific frequency that “excites” your fan. It’s not exactly a performance problem; it’s just not a
good frequency for the particular wheel design of the fan, so it causes vibrations. If you’re having vibrations due to a
resonant frequency, you should be sure to avoid it, and that should resolve the fan vibration problems.

More Related Content

Similar to System effect on fan performance.pptx

Propelling nozzle
Propelling nozzlePropelling nozzle
Propelling nozzlesundaraero
 
Chapter 51
Chapter 51Chapter 51
Chapter 51mcfalltj
 
K10913 dhirendra gocher me 6th sem cpu kota
K10913 dhirendra gocher me 6th sem cpu kotaK10913 dhirendra gocher me 6th sem cpu kota
K10913 dhirendra gocher me 6th sem cpu kotaChetan Kumar
 
Chapter 2 - Force Induction System.pptx
Chapter 2 - Force Induction System.pptxChapter 2 - Force Induction System.pptx
Chapter 2 - Force Induction System.pptxNemoKoh
 
What Is The Function Of An Air Vent Valve-veritenews.com
What Is The Function Of An Air Vent Valve-veritenews.comWhat Is The Function Of An Air Vent Valve-veritenews.com
What Is The Function Of An Air Vent Valve-veritenews.comangelinarobert1
 
How toselecta fanorblower
How toselecta fanorblowerHow toselecta fanorblower
How toselecta fanorblowerhabib ghanbari
 
Pneumatics – Choose the Best Valve for Optimum Performance
Pneumatics – Choose the Best Valve for Optimum PerformancePneumatics – Choose the Best Valve for Optimum Performance
Pneumatics – Choose the Best Valve for Optimum PerformanceDesign World
 
Aircraft Engine
Aircraft Engine Aircraft Engine
Aircraft Engine tamer999
 
Compressor and types of compressors (Thermodynamics)
Compressor and types of compressors (Thermodynamics)Compressor and types of compressors (Thermodynamics)
Compressor and types of compressors (Thermodynamics)Hasnain Yaseen
 
kitchen.services-Your ultimate guide on Range Hood backdraft damper.pdf
kitchen.services-Your ultimate guide on Range Hood backdraft damper.pdfkitchen.services-Your ultimate guide on Range Hood backdraft damper.pdf
kitchen.services-Your ultimate guide on Range Hood backdraft damper.pdfAhmad Affan
 
Air suspension ppt (3)
Air suspension ppt (3)Air suspension ppt (3)
Air suspension ppt (3)MohamedAasif6
 
centrifugal pump.pptx
centrifugal pump.pptxcentrifugal pump.pptx
centrifugal pump.pptxAsmaCh17
 
Tips for maintenance of the air compressor
Tips for maintenance of the air compressorTips for maintenance of the air compressor
Tips for maintenance of the air compressorDevanshVarma1
 

Similar to System effect on fan performance.pptx (20)

Propelling nozzle
Propelling nozzlePropelling nozzle
Propelling nozzle
 
Chapter 51
Chapter 51Chapter 51
Chapter 51
 
UNIT 4.pdf
UNIT 4.pdfUNIT 4.pdf
UNIT 4.pdf
 
K10913 dhirendra gocher me 6th sem cpu kota
K10913 dhirendra gocher me 6th sem cpu kotaK10913 dhirendra gocher me 6th sem cpu kota
K10913 dhirendra gocher me 6th sem cpu kota
 
Airflow Research Paper
Airflow Research PaperAirflow Research Paper
Airflow Research Paper
 
Chapter 2 - Force Induction System.pptx
Chapter 2 - Force Induction System.pptxChapter 2 - Force Induction System.pptx
Chapter 2 - Force Induction System.pptx
 
Basics of fans
Basics of fansBasics of fans
Basics of fans
 
What Is The Function Of An Air Vent Valve-veritenews.com
What Is The Function Of An Air Vent Valve-veritenews.comWhat Is The Function Of An Air Vent Valve-veritenews.com
What Is The Function Of An Air Vent Valve-veritenews.com
 
How toselecta fanorblower
How toselecta fanorblowerHow toselecta fanorblower
How toselecta fanorblower
 
Pneumatics – Choose the Best Valve for Optimum Performance
Pneumatics – Choose the Best Valve for Optimum PerformancePneumatics – Choose the Best Valve for Optimum Performance
Pneumatics – Choose the Best Valve for Optimum Performance
 
Aircraft Engine
Aircraft Engine Aircraft Engine
Aircraft Engine
 
Compressor and types of compressors (Thermodynamics)
Compressor and types of compressors (Thermodynamics)Compressor and types of compressors (Thermodynamics)
Compressor and types of compressors (Thermodynamics)
 
Fan and Blowers
 Fan and Blowers Fan and Blowers
Fan and Blowers
 
Air distribution Product
Air distribution ProductAir distribution Product
Air distribution Product
 
Ch06
Ch06Ch06
Ch06
 
kitchen.services-Your ultimate guide on Range Hood backdraft damper.pdf
kitchen.services-Your ultimate guide on Range Hood backdraft damper.pdfkitchen.services-Your ultimate guide on Range Hood backdraft damper.pdf
kitchen.services-Your ultimate guide on Range Hood backdraft damper.pdf
 
Fefi belt-direct-drives
Fefi belt-direct-drivesFefi belt-direct-drives
Fefi belt-direct-drives
 
Air suspension ppt (3)
Air suspension ppt (3)Air suspension ppt (3)
Air suspension ppt (3)
 
centrifugal pump.pptx
centrifugal pump.pptxcentrifugal pump.pptx
centrifugal pump.pptx
 
Tips for maintenance of the air compressor
Tips for maintenance of the air compressorTips for maintenance of the air compressor
Tips for maintenance of the air compressor
 

Recently uploaded

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 

Recently uploaded (20)

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 

System effect on fan performance.pptx

  • 1. • The most common causes of system effect include uneven or spinning airflow at a fan’s inlet, obstructions to airflow at the inlet or outlet, improperly configured ductwork at the inlet or outlet, and/or failure to correct for losses caused by fan accessories. • System effect can be avoided by accounting for all factors, including the shape of the transition points between the fan and existing ducts, ductwork configuration close to the fan, and accessories. • For optimum air performance, airflow at the fan’s inlet needs to be uniform, symmetrical, and free of swirl. Similarly, airflow must be able to diffuse and fully develop across the fan’s outlet. Even minor improvements to airflow stability can reduce system effect and, in turn, increase fan performance and operating efficiency. • An inlet vane damper is a modulating device that affects fan performance. As a damper is closed, air begins to pre-spin into the fan; the fan wheel no longer can move as much air, and flow, pressure, and brake horsepower all decrease. Even when a damper is fully open, the vanes interfere with normal flow and reduce fan performance. If the losses are not accounted for, the fan will have to run at a speed higher than the one specified during fan selection. Fans should be tested with accessories that determine the losses and the fan speed required to overcome them. Common Causes of System Effect
  • 2. Reducing System Effect at a Fan’s Inlet • A lack of uniform airflow entering a fan’s inlet is one of the greatest and most common causes of system effect. Often, these losses are the result of elbows and isolation dampers being installed too close to a fan’s inlet. • Depending on the application, a variety of strategies can be employed to improve airflow at a fan’s inlet. • Take, for example, the 90-degree round elbow located at the inlet of a fan shown in below figure. • Air entering the fan wheel is not uniform, loading on various parts of the fan wheel instead of at the center as designed for optimal performance. Some air is circulating back into the elbow, creating additional losses. In this case, the addition of turning vanes in the elbow will help direct air toward the center of the fan wheel.
  • 3. • Below shows the effect of a rectangular inlet box mounted directly to the inlet of a fan. Again, the fan wheel is not being uniformly loaded, resulting in performance loss. • With an inlet box, the cavity, or dead area, below the outlet is where air will get hung up, creating additional losses. • Improving the shape of the inlet box or adding straightening vanes can help to redirect the flow of air into the wheel. • Figure shows air entering a fan from the side as opposed to straight through the inlet. The air is spinning in the opposite direction of the fan wheel. Consequently, the fan is having to work harder, resulting in greater energy consumption and stress on fan components.
  • 4. Reducing System Effect at a Fan’s Outlet • Similar to inlet flow, outlet flow is impacted significantly by the placement and distancing of ductwork and dampers. The effective length of ductwork at a fan’s outlet is one of the most important factors in fan and system efficiency. In most cases, the profile of the air coming out of a fan is asymmetrical, causing turbulence and a lack of static-pressure regain. • For symmetrical and uniform flow to be achieved, outlet ducting must be long enough to allow airflow to diffuse and fully develop. This is called 100-percent effective duct length. • As a rule of thumb, the effective length of outlet ducting should be no less than 2.5 duct diameters when duct velocity is 2,500 fpm (13 m/s) or less. For every additional 1,000 fpm (5 m/s), one duct diameter should be added. Figure shows the velocity profile of air as it exits a fan. Air is forced against the outside of the scroll, resulting in uneven flow at the outlet. An effective run of ductwork allows for a uniform velocity profile. Note that at approximately 50 percent of effective duct length the fan achieves approximately 80 percent of its pressure regain. In addition to effective duct length, the placement and direction of elbows is significant at a fan’s outlet. An elbow installed too close to the outlet will result in a significant loss of airflow. If the elbow turns in the opposite direction of the fan’s rotation, the loss will be even greater. When a design requires the installation of an elbow, a minimum of two to three duct lengths is recommended to allow the velocity profile of air exiting the fan to develop across the ductwork.
  • 6. 1. Material Build-Up On the Wheel If you have a material handling application or misfit another application with a fan that tends to build up material, fan vibration problems are quite common. When that happens, it’s probably time to clean the wheel. That means shutting down, waiting for all the parts to stop moving, locking out, opening the housing to clean it thoroughly, re-securing it, and starting back up. We recommend putting this on a regular maintenance schedule to avoid vibration issues in the future. The other alternative is to replace the fan wheel with a self-cleaning blade or material of construction. 2. Deteriorated Fan Wheel There are many reasons for the deterioration of a fan wheel. Industrial fans can last for decades, so it could just be normal wear over time. Many industrial processes involve corrosive gasses that can wear out the wheel much more quickly, causing the properties of the wheel to change. The vibration comes from the changing properties inside the fan housing on the wheel. In this case, you will likely need to replace the wheel with a new one, potentially designing with corrosive-resistant construction materials. 3. Loose Fasteners Loose fasteners are actually quite common and fairly easy to fix. This is especially noticeable if your vibration is on the vertical side of your bearing due to the fasteners at the base of the fan not being secure enough to the floor. If you find that this is the cause of the fan vibration issues, just get out a drill and fasten them down. 4. Drive Component Misalignment Regular maintenance requires occasional opening or disassembly and reassembly for things like cleaning, greasing, and part change outs. That can create the potential for misalignment, which in turn can create fan vibration issues. To fix that, take your straight edge to it. You’ll want to be sure to align the bearings, shaft, coupling, and motor to fully realign the drive. Common Vibration Causes to Consider
  • 7. 5. Defective Bearings If you’ve got bad or broken down grease or have let the bearings go too long without proper grease maintenance, you will eventually start to get metal on metal and experience vibration. At this point, you’re well on your way to bearing failure. Whether one or both bearings are defective and failing, you must replace them both. You’re far better off ensuring a regular grease maintenance schedule, but bearing failure is one of the most common issues revealed by fan vibration. 7. Operating In – or Near – a Resonant Frequency A resonant frequency is a specific frequency that “excites” your fan. It’s not exactly a performance problem; it’s just not a good frequency for the particular wheel design of the fan, so it causes vibrations. If you’re having vibrations due to a resonant frequency, you should be sure to avoid it, and that should resolve the fan vibration problems.