Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd
AMENDMENTS
Dated: March, 2016
The Guidelines for Air Conditioning of OT as mentioned in Glossary at page no. 114-
115 is replaced by following text.
Air Conditioning The Revised Guidelines for Air-Conditioning System for
OT Operation Theatres
A. The air conditioning requirements for Operation Theater
in an HCO have been deliberated at length with
manufacturers, engineers, technical committee
members and other stake holders and the following
guidelines have been finalised.
B. For this purpose operation theaters have been divided
into two distinct groups:
a. Superspeciality OT: Superspeciality OT means
operations of Neurosciences, Orthopedics (Joint
Replacement), Cardiothoracic and Transplant
Surgery (Renal, Liver etc).
b. General OT: This includes Ophthalmology and all
other basic surgical disciplines. District hospital
OTs and FRU OT would fall under this category.
C. The following basic assumptions have been kept in
view:
 OT Size: Standard OT size of 20’ x 20’ x 10’ (Ht.
below the false ceiling level is considered).
 Occupancy: Standard occupancy of 5-8 persons
at any given point of time inside the OT is
considered.
 Equipment Load: Standard equipment load of 5-7
kW considered per OT.
 Ambient temperature & humidity at each
location to be considered while designing the
system.
Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd
1. REQUIREMENTS – Super-specialty
OT I. Air Changes Per Hour:
ƒ Minimum total air changes should be 30
based on international guidelines although
the same will vary with biological load and
the location.
ƒ The fresh air component of the air change is
required to be minimum 5 air changes out of
total minimum 30 air changes.
ƒ If HCO chooses to have 100% fresh air
system than appropriate energy saving
devices like Heat Recovery Wheel, Run
around Pipes etc should be installed.
II. Air Velocity: The vertical down flow of air coming
out of the diffusers should be able to carry bacteria
carrying particle load away from the operating
table. The airflow needs to be unidirectional and
downwards on the OT table. The air velocity
recommended as per the international and
national guidelines is 90-120 FPM at the Grille/
Diffuser level.
III. Positive Pressure: There is a requirement to
maintain positive pressure differential between OT
and adjoining areas to prevent outside air entry
into OT. The minimum positive pressure
recommended is 15 Pascal (0.05 inches of water)
as per ISO 14644 Clean Room Standard.
IV. Air handling in the OT including air Quality:
Air is supplied through Terminal HEPA filters in the
ceiling. The minimum size of the filtration area
should be 8’ x 6’ to cover the entire OT table and
surgical team. The minimum supply air volume to
the OT (in CFM) should be compliant with the
desired minimum air change. The return air should
be picked up/ taken out from the exhaust grille
located near the floor level (appx 6 inches above
the floor level). The air quality at the supply i.e. at
grille level should be Class 100/ ISO Class 5 (at
rest condition). Class 100 means a cubic foot of air
Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd
must have no more than 100 particles measuring
0.5 microns or larger.
V. Temperature and Humidity: The temperature
should be maintained at 21 +/- 3 Deg C inside the
OT all the time with corresponding relative
humidity between 40 to 60% though the ideal Rh
is considered to be 55%. Appropriate devices to
monitor and display these conditions inside the OT
may be installed.
VI. Air Filtration: The AHU must be an air purification
unit and air filtration unit. There must be two sets
of washable flange type pre filters of capacity 10
microns and 5 microns with aluminum/ SS 304
frame within the AHU. The necessary service
panels to be provided for servicing the filters,
motors & blowers. HEPA filters of efficiency
99.97% down to o.3 microns or higher efficiency
are to be provided in the OT and not in the AHU.
2. REQUIREMENTS – General OT
I. Air Change Per Hour:
ƒ Minimum total air changes should be 25
based on international guidelines although
the same will vary with biological load and
the location.
ƒ The fresh air component of the air change is
required to be minimum 4 air changes out of
total minimum 25 air changes.
II. Air Velocity: The vertical down flow of air coming out
of the diffusers should be able to carry bacteria
carrying particle load away from the operating
table. The airflow needs to be unidirectional and
downwards on the OT table.
III. Positive Pressure: There is a requirement to
maintain positive pressure differential between OT
and adjoining areas to prevent outside air entry
into OT. The minimum positive pressure
recommended is 15 Pascal (0.05 inches of water)
Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd
as per ISO 14644 Clean Room Standard.
IV. Air handling in the OT including Air Quantity:
Air is supplied through HEPA filters in the AHU.
The minimum size of the air supply area should be
6’ x 4’ to cover the entire OT table and surgical
team The minimum supply air volume to the OT (in
CFM) should be compliant with the desired
minimum air change. The return air should be
picked up/ taken out from the exhaust grille
located near the floor level (approx 6 inches above
the floor level). The air quality at the supply i.e. at
grille level should be Class 1000/ ISO Class 6 (at
rest condition). Class 1000 means a cubic foot of
air must have no more than 1000 particles
measuring 0.5 microns or larger.
V. Temperature and Humidity: The temperature
should be maintained at 21 +/- 3 Deg C inside the
OT all the time with corresponding relative
humidity between 40 to 60% though the ideal Rh
is considered to be 55%. Appropriate devices to
monitor and display these conditions inside the OT
may be installed.
VI. Air Filtration: The AHU must be an air purification
unit and air filtration unit. There must be two sets
of washable flange type pre filters of capacity 10
microns and 5 microns with aluminum/ SS 304
frame within the AHU. The necessary service
panels to be provided for servicing the filters,
motors & blowers. HEPA filters of efficiency
99.97% down to o.3 microns or higher efficiency
may be provided in the AHU.
3. General Guiding Notes:
a. The AHU of each OT should be dedicated one and
should not be linked to air conditioning of any
other area.
b. During the non functional hours AHU blower will
be operational round the clock (may be without
temperature control). VFD devices may be used
to conserve energy.
Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd
c. Window & split A/c should not be used in any type
of OT because they are pure re circulating units
and have convenient pockets for microbial growth
which cannot be sealed.
d. The flooring, walls and ceiling should be non
porous, smooth, seamless without corners and
should be easily cleanable repeatedly. The
material should be chosen accordingly.
e. Validation of system to be done as per ISO 14664
standards and to be necessarily include:
 Temperature and Humidity check 

 Air particulate count 

 Air Change Rate Calculation 

 Air velocity at outlet of terminal filtration unit /
filters 

 Pressure Differential levels of the OT wrt
ambient / adjoining areas 

 Validation of HEPA Filters by appropriate
tests like DOP etc. 

f. Maintenance of the system: It is recommended
that periodic preventive maintenance be carried
out in terms of cleaning of pre filters at the interval
of 15 days. Preventive maintenance of all the parts
is carried out as per manufacturer
recommendations.
Guide Book to NABH Standards for Hospitals by Dr.Mahboob
Khan Phd

More Related Content

What's hot

Guidelines & main requirements in the planning and design of hospitals
Guidelines & main requirements in the planning and design of hospitalsGuidelines & main requirements in the planning and design of hospitals
Guidelines & main requirements in the planning and design of hospitals
Mahmoud Shaqria
 

What's hot (20)

1. concepts of ot & setting of ot
1. concepts of ot & setting of ot1. concepts of ot & setting of ot
1. concepts of ot & setting of ot
 
Guidelines & main requirements in the planning and design of hospitals
Guidelines & main requirements in the planning and design of hospitalsGuidelines & main requirements in the planning and design of hospitals
Guidelines & main requirements in the planning and design of hospitals
 
Hospital hvac design salah ramadan
Hospital hvac design  salah ramadanHospital hvac design  salah ramadan
Hospital hvac design salah ramadan
 
Engineering Services in Hospital
Engineering Services in HospitalEngineering Services in Hospital
Engineering Services in Hospital
 
Hospital planning
Hospital planningHospital planning
Hospital planning
 
Central sterile supply department
Central sterile supply departmentCentral sterile supply department
Central sterile supply department
 
Central Sterile & Supply Department (CSSD)
Central Sterile & Supply Department (CSSD)Central Sterile & Supply Department (CSSD)
Central Sterile & Supply Department (CSSD)
 
Designing of OPD and day care services
Designing of OPD and day care servicesDesigning of OPD and day care services
Designing of OPD and day care services
 
literature study for EMERGENCY DEPARTMENT in hospital
literature study for EMERGENCY DEPARTMENT in hospitalliterature study for EMERGENCY DEPARTMENT in hospital
literature study for EMERGENCY DEPARTMENT in hospital
 
mortuary and its setup
mortuary and its setupmortuary and its setup
mortuary and its setup
 
Emergency department planning and design
Emergency department planning and designEmergency department planning and design
Emergency department planning and design
 
Central Sterile Supply Department (CSSD)
Central Sterile Supply Department (CSSD)Central Sterile Supply Department (CSSD)
Central Sterile Supply Department (CSSD)
 
Central sterile supply department(cssd)
Central sterile supply department(cssd)Central sterile supply department(cssd)
Central sterile supply department(cssd)
 
CSSD by Dr Zulfiquer Ahmed Amin
CSSD by Dr Zulfiquer Ahmed AminCSSD by Dr Zulfiquer Ahmed Amin
CSSD by Dr Zulfiquer Ahmed Amin
 
Hospital emergency services
Hospital emergency servicesHospital emergency services
Hospital emergency services
 
200 bed-hospital-project-report
200 bed-hospital-project-report200 bed-hospital-project-report
200 bed-hospital-project-report
 
Inpatient Services- Introduction, Planning and Designing
Inpatient Services- Introduction, Planning and DesigningInpatient Services- Introduction, Planning and Designing
Inpatient Services- Introduction, Planning and Designing
 
Inpatient dpt of Hospital (IPD)
Inpatient dpt of Hospital (IPD)Inpatient dpt of Hospital (IPD)
Inpatient dpt of Hospital (IPD)
 
gynecology , neurology , nephrology
gynecology , neurology , nephrologygynecology , neurology , nephrology
gynecology , neurology , nephrology
 
Spatial organisation in Hospital Design
Spatial organisation in Hospital DesignSpatial organisation in Hospital Design
Spatial organisation in Hospital Design
 

Similar to Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd

USP 797/800 Cleanroom Compliance by Terra Universal
USP 797/800 Cleanroom Compliance by Terra UniversalUSP 797/800 Cleanroom Compliance by Terra Universal
USP 797/800 Cleanroom Compliance by Terra Universal
Terra Universal
 
Ot infection control rkch
Ot infection control rkchOt infection control rkch
Ot infection control rkch
sabahjak
 

Similar to Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd (20)

HVAC validation.pdf
HVAC validation.pdfHVAC validation.pdf
HVAC validation.pdf
 
Chapter 9 room ventilation systems (1)
Chapter 9 room ventilation systems (1)Chapter 9 room ventilation systems (1)
Chapter 9 room ventilation systems (1)
 
GMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturingGMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturing
 
GMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturingGMP Requirements for Sterile Products manufacturing
GMP Requirements for Sterile Products manufacturing
 
One slider for qualification and validation of depyrogenation and sterilizati...
One slider for qualification and validation of depyrogenation and sterilizati...One slider for qualification and validation of depyrogenation and sterilizati...
One slider for qualification and validation of depyrogenation and sterilizati...
 
IAQ-Rep1.pdf
IAQ-Rep1.pdfIAQ-Rep1.pdf
IAQ-Rep1.pdf
 
USP 797/800 Cleanroom Compliance by Terra Universal
USP 797/800 Cleanroom Compliance by Terra UniversalUSP 797/800 Cleanroom Compliance by Terra Universal
USP 797/800 Cleanroom Compliance by Terra Universal
 
GMP sterile products
GMP sterile products GMP sterile products
GMP sterile products
 
ANES 1501 - Module 7 PPT: Safety
ANES 1501 - Module 7 PPT: SafetyANES 1501 - Module 7 PPT: Safety
ANES 1501 - Module 7 PPT: Safety
 
Alternate ventilation in hospitals
Alternate ventilation in hospitalsAlternate ventilation in hospitals
Alternate ventilation in hospitals
 
Validation of hvac
Validation of hvacValidation of hvac
Validation of hvac
 
Hvac
HvacHvac
Hvac
 
Criteria of avp
Criteria of avpCriteria of avp
Criteria of avp
 
Presentation on HVAC
Presentation on HVAC Presentation on HVAC
Presentation on HVAC
 
Ot infection control rkch
Ot infection control rkchOt infection control rkch
Ot infection control rkch
 
hvac_basics
hvac_basicshvac_basics
hvac_basics
 
HVAC system
 HVAC system HVAC system
HVAC system
 
Air circulation maintenance industry for sterile and non sterile area
Air circulation maintenance  industry for sterile and non sterile areaAir circulation maintenance  industry for sterile and non sterile area
Air circulation maintenance industry for sterile and non sterile area
 
Contamination Control in Cleanrooms_Dr.A. Amsavel
Contamination Control in Cleanrooms_Dr.A. AmsavelContamination Control in Cleanrooms_Dr.A. Amsavel
Contamination Control in Cleanrooms_Dr.A. Amsavel
 
Who 2019-n cov-psa-specification
Who 2019-n cov-psa-specificationWho 2019-n cov-psa-specification
Who 2019-n cov-psa-specification
 

More from Healthcare consultant

More from Healthcare consultant (20)

In India, Young Graduates Struggle by Dr. Mahboob Khan to Get Jobs.pdf
In India, Young Graduates Struggle by Dr. Mahboob Khan  to Get Jobs.pdfIn India, Young Graduates Struggle by Dr. Mahboob Khan  to Get Jobs.pdf
In India, Young Graduates Struggle by Dr. Mahboob Khan to Get Jobs.pdf
 
The Missing Middle class from Indian Healthcare System..pdf
The Missing Middle class from Indian Healthcare System..pdfThe Missing Middle class from Indian Healthcare System..pdf
The Missing Middle class from Indian Healthcare System..pdf
 
Chat GPT for Doctors -Revolutionizing Healthcare Communication by Dr.Mahboob.pdf
Chat GPT for Doctors -Revolutionizing Healthcare Communication by Dr.Mahboob.pdfChat GPT for Doctors -Revolutionizing Healthcare Communication by Dr.Mahboob.pdf
Chat GPT for Doctors -Revolutionizing Healthcare Communication by Dr.Mahboob.pdf
 
Hospital Management By Dr. Mahboob Khan
Hospital Management By Dr. Mahboob KhanHospital Management By Dr. Mahboob Khan
Hospital Management By Dr. Mahboob Khan
 
Leadership lessons
Leadership lessonsLeadership lessons
Leadership lessons
 
The Psychopathic CEO
The Psychopathic CEO The Psychopathic CEO
The Psychopathic CEO
 
QUANTUM PHYSICS AND ITS POWER BY DR.MAHBOOB KHAN .pdf
QUANTUM PHYSICS AND ITS POWER BY DR.MAHBOOB KHAN .pdfQUANTUM PHYSICS AND ITS POWER BY DR.MAHBOOB KHAN .pdf
QUANTUM PHYSICS AND ITS POWER BY DR.MAHBOOB KHAN .pdf
 
Ways to increase hospital profitability By.Dr.Mahboob Khan
Ways to increase hospital profitability By.Dr.Mahboob KhanWays to increase hospital profitability By.Dr.Mahboob Khan
Ways to increase hospital profitability By.Dr.Mahboob Khan
 
Why Indian students fly out to persue career in Medicine by Dr.Mahboob Khan
Why Indian students fly out to persue career in Medicine by Dr.Mahboob KhanWhy Indian students fly out to persue career in Medicine by Dr.Mahboob Khan
Why Indian students fly out to persue career in Medicine by Dr.Mahboob Khan
 
Healthcare in a Digital Economy By. Dr. Mahboob Khan
Healthcare in a Digital Economy By. Dr. Mahboob KhanHealthcare in a Digital Economy By. Dr. Mahboob Khan
Healthcare in a Digital Economy By. Dr. Mahboob Khan
 
Winning strategy-By.Dr. Mahboob Khan
Winning strategy-By.Dr. Mahboob Khan Winning strategy-By.Dr. Mahboob Khan
Winning strategy-By.Dr. Mahboob Khan
 
Couch Potato Syndrome by Dr. Mahboob Khan
Couch Potato Syndrome by Dr. Mahboob KhanCouch Potato Syndrome by Dr. Mahboob Khan
Couch Potato Syndrome by Dr. Mahboob Khan
 
The Rise of METAVERSE in Healthcare By.Dr.Mahboob Khan
The Rise of METAVERSE in Healthcare By.Dr.Mahboob Khan The Rise of METAVERSE in Healthcare By.Dr.Mahboob Khan
The Rise of METAVERSE in Healthcare By.Dr.Mahboob Khan
 
Robotic Process Automation in Healthcare-An Urgency! By.Dr.Mahboob Khan
Robotic Process Automation in Healthcare-An Urgency! By.Dr.Mahboob KhanRobotic Process Automation in Healthcare-An Urgency! By.Dr.Mahboob Khan
Robotic Process Automation in Healthcare-An Urgency! By.Dr.Mahboob Khan
 
The art of filing by Dr.Mahboob Khan
The art of filing by Dr.Mahboob Khan The art of filing by Dr.Mahboob Khan
The art of filing by Dr.Mahboob Khan
 
Chained Globalization Issues in Healthcare by Dr.Mahboob Khan
Chained Globalization Issues in Healthcare by Dr.Mahboob KhanChained Globalization Issues in Healthcare by Dr.Mahboob Khan
Chained Globalization Issues in Healthcare by Dr.Mahboob Khan
 
New Standards of Care By.Dr.Mahboob Khan
New Standards of Care By.Dr.Mahboob KhanNew Standards of Care By.Dr.Mahboob Khan
New Standards of Care By.Dr.Mahboob Khan
 
Ways That Quantum Technology Could transform Health Care. By.Dr.Mahboob Khan
Ways That Quantum Technology Could transform Health Care. By.Dr.Mahboob KhanWays That Quantum Technology Could transform Health Care. By.Dr.Mahboob Khan
Ways That Quantum Technology Could transform Health Care. By.Dr.Mahboob Khan
 
How is COVID-19 Reshaping the role of Institutional strategy? By.Dr.Mahboob Khan
How is COVID-19 Reshaping the role of Institutional strategy? By.Dr.Mahboob KhanHow is COVID-19 Reshaping the role of Institutional strategy? By.Dr.Mahboob Khan
How is COVID-19 Reshaping the role of Institutional strategy? By.Dr.Mahboob Khan
 
Retaining Healthcare Quality During COVID-19 and Future of Care Delivery. By....
Retaining Healthcare Quality During COVID-19 and Future of Care Delivery. By....Retaining Healthcare Quality During COVID-19 and Future of Care Delivery. By....
Retaining Healthcare Quality During COVID-19 and Future of Care Delivery. By....
 

Recently uploaded

Call Girls Service Faridabad 📲 9999965857 ヅ10k NiGhT Call Girls In Faridabad
Call Girls Service Faridabad 📲 9999965857 ヅ10k NiGhT Call Girls In FaridabadCall Girls Service Faridabad 📲 9999965857 ヅ10k NiGhT Call Girls In Faridabad
Call Girls Service Faridabad 📲 9999965857 ヅ10k NiGhT Call Girls In Faridabad
gragmanisha42
 
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetJalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Call Girls Service
 
VIP Call Girl Sector 10 Noida Call Me: 9711199171
VIP Call Girl Sector 10 Noida Call Me: 9711199171VIP Call Girl Sector 10 Noida Call Me: 9711199171
VIP Call Girl Sector 10 Noida Call Me: 9711199171
Call Girls Service Gurgaon
 
Hubli Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Hubli Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetHubli Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Hubli Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Call Girls Service
 
9316020077📞Goa Call Girls Numbers, Call Girls Whatsapp Numbers Goa
9316020077📞Goa  Call Girls  Numbers, Call Girls  Whatsapp Numbers Goa9316020077📞Goa  Call Girls  Numbers, Call Girls  Whatsapp Numbers Goa
9316020077📞Goa Call Girls Numbers, Call Girls Whatsapp Numbers Goa
russian goa call girl and escorts service
 
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meet
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real MeetChandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meet
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meet
priyashah722354
 
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...
Sheetaleventcompany
 
Ozhukarai Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Ozhukarai Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetOzhukarai Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Ozhukarai Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Call Girls Service
 
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Me
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near MeVIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Me
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Me
mriyagarg453
 
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meetooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Call Girls Service
 
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meetdhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Call Girls Service
 
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetTirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Call Girls Service
 
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Me
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near MeRussian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Me
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Me
mriyagarg453
 
Punjab❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Moh...
Punjab❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Moh...Punjab❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Moh...
Punjab❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Moh...
Sheetaleventcompany
 

Recently uploaded (20)

Call Girls Service Faridabad 📲 9999965857 ヅ10k NiGhT Call Girls In Faridabad
Call Girls Service Faridabad 📲 9999965857 ヅ10k NiGhT Call Girls In FaridabadCall Girls Service Faridabad 📲 9999965857 ヅ10k NiGhT Call Girls In Faridabad
Call Girls Service Faridabad 📲 9999965857 ヅ10k NiGhT Call Girls In Faridabad
 
(Ajay) Call Girls in Dehradun- 8854095900 Escorts Service 50% Off with Cash O...
(Ajay) Call Girls in Dehradun- 8854095900 Escorts Service 50% Off with Cash O...(Ajay) Call Girls in Dehradun- 8854095900 Escorts Service 50% Off with Cash O...
(Ajay) Call Girls in Dehradun- 8854095900 Escorts Service 50% Off with Cash O...
 
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetJalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
VIP Call Girl Sector 10 Noida Call Me: 9711199171
VIP Call Girl Sector 10 Noida Call Me: 9711199171VIP Call Girl Sector 10 Noida Call Me: 9711199171
VIP Call Girl Sector 10 Noida Call Me: 9711199171
 
Hubli Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Hubli Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetHubli Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Hubli Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
9316020077📞Goa Call Girls Numbers, Call Girls Whatsapp Numbers Goa
9316020077📞Goa  Call Girls  Numbers, Call Girls  Whatsapp Numbers Goa9316020077📞Goa  Call Girls  Numbers, Call Girls  Whatsapp Numbers Goa
9316020077📞Goa Call Girls Numbers, Call Girls Whatsapp Numbers Goa
 
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meet
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real MeetChandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meet
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meet
 
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...
 
Call Girls Hyderabad Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Hyderabad Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Hyderabad Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Hyderabad Just Call 9907093804 Top Class Call Girl Service Available
 
Ozhukarai Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Ozhukarai Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetOzhukarai Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Ozhukarai Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
Enjoyment ★ 8854095900 Indian Call Girls In Dehradun 🍆🍌 By Dehradun Call Girl ★
Enjoyment ★ 8854095900 Indian Call Girls In Dehradun 🍆🍌 By Dehradun Call Girl ★Enjoyment ★ 8854095900 Indian Call Girls In Dehradun 🍆🍌 By Dehradun Call Girl ★
Enjoyment ★ 8854095900 Indian Call Girls In Dehradun 🍆🍌 By Dehradun Call Girl ★
 
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Me
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near MeVIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Me
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Me
 
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meetooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meetdhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetTirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
Call Girls Patiala Just Call 8250077686 Top Class Call Girl Service Available
Call Girls Patiala Just Call 8250077686 Top Class Call Girl Service AvailableCall Girls Patiala Just Call 8250077686 Top Class Call Girl Service Available
Call Girls Patiala Just Call 8250077686 Top Class Call Girl Service Available
 
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Me
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near MeRussian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Me
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Me
 
Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.
Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.
Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.
 
❤️♀️@ Jaipur Call Girl Agency ❤️♀️@ Manjeet Russian Call Girls Service in Jai...
❤️♀️@ Jaipur Call Girl Agency ❤️♀️@ Manjeet Russian Call Girls Service in Jai...❤️♀️@ Jaipur Call Girl Agency ❤️♀️@ Manjeet Russian Call Girls Service in Jai...
❤️♀️@ Jaipur Call Girl Agency ❤️♀️@ Manjeet Russian Call Girls Service in Jai...
 
Punjab❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Moh...
Punjab❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Moh...Punjab❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Moh...
Punjab❤️Call girls in Mohali ☎️7435815124☎️ Call Girl service in Mohali☎️ Moh...
 

Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd

  • 1. Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd AMENDMENTS Dated: March, 2016 The Guidelines for Air Conditioning of OT as mentioned in Glossary at page no. 114- 115 is replaced by following text. Air Conditioning The Revised Guidelines for Air-Conditioning System for OT Operation Theatres A. The air conditioning requirements for Operation Theater in an HCO have been deliberated at length with manufacturers, engineers, technical committee members and other stake holders and the following guidelines have been finalised. B. For this purpose operation theaters have been divided into two distinct groups: a. Superspeciality OT: Superspeciality OT means operations of Neurosciences, Orthopedics (Joint Replacement), Cardiothoracic and Transplant Surgery (Renal, Liver etc). b. General OT: This includes Ophthalmology and all other basic surgical disciplines. District hospital OTs and FRU OT would fall under this category. C. The following basic assumptions have been kept in view:  OT Size: Standard OT size of 20’ x 20’ x 10’ (Ht. below the false ceiling level is considered).  Occupancy: Standard occupancy of 5-8 persons at any given point of time inside the OT is considered.  Equipment Load: Standard equipment load of 5-7 kW considered per OT.  Ambient temperature & humidity at each location to be considered while designing the system.
  • 2. Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd 1. REQUIREMENTS – Super-specialty OT I. Air Changes Per Hour: ƒ Minimum total air changes should be 30 based on international guidelines although the same will vary with biological load and the location. ƒ The fresh air component of the air change is required to be minimum 5 air changes out of total minimum 30 air changes. ƒ If HCO chooses to have 100% fresh air system than appropriate energy saving devices like Heat Recovery Wheel, Run around Pipes etc should be installed. II. Air Velocity: The vertical down flow of air coming out of the diffusers should be able to carry bacteria carrying particle load away from the operating table. The airflow needs to be unidirectional and downwards on the OT table. The air velocity recommended as per the international and national guidelines is 90-120 FPM at the Grille/ Diffuser level. III. Positive Pressure: There is a requirement to maintain positive pressure differential between OT and adjoining areas to prevent outside air entry into OT. The minimum positive pressure recommended is 15 Pascal (0.05 inches of water) as per ISO 14644 Clean Room Standard. IV. Air handling in the OT including air Quality: Air is supplied through Terminal HEPA filters in the ceiling. The minimum size of the filtration area should be 8’ x 6’ to cover the entire OT table and surgical team. The minimum supply air volume to the OT (in CFM) should be compliant with the desired minimum air change. The return air should be picked up/ taken out from the exhaust grille located near the floor level (appx 6 inches above the floor level). The air quality at the supply i.e. at grille level should be Class 100/ ISO Class 5 (at rest condition). Class 100 means a cubic foot of air
  • 3. Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd must have no more than 100 particles measuring 0.5 microns or larger. V. Temperature and Humidity: The temperature should be maintained at 21 +/- 3 Deg C inside the OT all the time with corresponding relative humidity between 40 to 60% though the ideal Rh is considered to be 55%. Appropriate devices to monitor and display these conditions inside the OT may be installed. VI. Air Filtration: The AHU must be an air purification unit and air filtration unit. There must be two sets of washable flange type pre filters of capacity 10 microns and 5 microns with aluminum/ SS 304 frame within the AHU. The necessary service panels to be provided for servicing the filters, motors & blowers. HEPA filters of efficiency 99.97% down to o.3 microns or higher efficiency are to be provided in the OT and not in the AHU. 2. REQUIREMENTS – General OT I. Air Change Per Hour: ƒ Minimum total air changes should be 25 based on international guidelines although the same will vary with biological load and the location. ƒ The fresh air component of the air change is required to be minimum 4 air changes out of total minimum 25 air changes. II. Air Velocity: The vertical down flow of air coming out of the diffusers should be able to carry bacteria carrying particle load away from the operating table. The airflow needs to be unidirectional and downwards on the OT table. III. Positive Pressure: There is a requirement to maintain positive pressure differential between OT and adjoining areas to prevent outside air entry into OT. The minimum positive pressure recommended is 15 Pascal (0.05 inches of water)
  • 4. Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd as per ISO 14644 Clean Room Standard. IV. Air handling in the OT including Air Quantity: Air is supplied through HEPA filters in the AHU. The minimum size of the air supply area should be 6’ x 4’ to cover the entire OT table and surgical team The minimum supply air volume to the OT (in CFM) should be compliant with the desired minimum air change. The return air should be picked up/ taken out from the exhaust grille located near the floor level (approx 6 inches above the floor level). The air quality at the supply i.e. at grille level should be Class 1000/ ISO Class 6 (at rest condition). Class 1000 means a cubic foot of air must have no more than 1000 particles measuring 0.5 microns or larger. V. Temperature and Humidity: The temperature should be maintained at 21 +/- 3 Deg C inside the OT all the time with corresponding relative humidity between 40 to 60% though the ideal Rh is considered to be 55%. Appropriate devices to monitor and display these conditions inside the OT may be installed. VI. Air Filtration: The AHU must be an air purification unit and air filtration unit. There must be two sets of washable flange type pre filters of capacity 10 microns and 5 microns with aluminum/ SS 304 frame within the AHU. The necessary service panels to be provided for servicing the filters, motors & blowers. HEPA filters of efficiency 99.97% down to o.3 microns or higher efficiency may be provided in the AHU. 3. General Guiding Notes: a. The AHU of each OT should be dedicated one and should not be linked to air conditioning of any other area. b. During the non functional hours AHU blower will be operational round the clock (may be without temperature control). VFD devices may be used to conserve energy.
  • 5. Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd c. Window & split A/c should not be used in any type of OT because they are pure re circulating units and have convenient pockets for microbial growth which cannot be sealed. d. The flooring, walls and ceiling should be non porous, smooth, seamless without corners and should be easily cleanable repeatedly. The material should be chosen accordingly. e. Validation of system to be done as per ISO 14664 standards and to be necessarily include:  Temperature and Humidity check    Air particulate count    Air Change Rate Calculation    Air velocity at outlet of terminal filtration unit / filters    Pressure Differential levels of the OT wrt ambient / adjoining areas    Validation of HEPA Filters by appropriate tests like DOP etc.   f. Maintenance of the system: It is recommended that periodic preventive maintenance be carried out in terms of cleaning of pre filters at the interval of 15 days. Preventive maintenance of all the parts is carried out as per manufacturer recommendations. Guide Book to NABH Standards for Hospitals by Dr.Mahboob Khan Phd