DF-52013:D • E-100

BG-12LX
Addressable Manual Pull Station

                                                                                                       Addressable Devices

General
The Fire·Lite BG-12LX is a state-of-the-art, dual-action (i.e.,
requires two motions to activate the station) pull station that
includes an addressable interface (mounted inside) for
Fire·Lite’s addressable fire alarm control panels (FACPs)
Because the BG-12LX is addressable, the control panel can
display the exact location of the activated manual station. This
leads fire personnel quickly to the location of the alarm.

Features
• Maintenance personnel can open station for inspection and
  address setting without causing an alarm condition.
• Built-in bicolor LED, which is visible through the handle of
  the station, flashes in normal operation and latches steady
  red when in alarm.
• Handle latches in down position and the word “ACTIVATED”
  appears to clearly indicate the station has been operated.
• Captive screw terminals wire-ready for easy connection to
  SLC loop (accepts up to 12 AWG/3.25 mm² wire).
• Can be surface mounted (with SB-10 or SB-I/O) or semi-
  flush mounted. Semi-flush mount to a standard single-




                                                                                                                                  FLPullStation.jpg
  gang, double-gang, or 4" (10.16 cm) square electrical box.
• Smooth dual-action design.
• Meets ADAAG controls and operating mechanisms guide-
  lines (Section 4.1.3[13]); meets ADA requirement for 5 lb.
  maximum activation force.
• Highly visible.                                                  usually needed for semi-flush mounting with 4" (10.16 cm) or
                                                                   double-gang boxes (not with single-gang boxes).
• Attractive shape and textured finish.
• Key reset.
                                                                   Operation
• Includes Braille text on station handle.
                                                                   Pushing in, then pulling down on the handle causes it to latch
• Optional trim ring (BG12TR).
                                                                   in the down/activated position. Once latched, the word “ACTI-
• Meets UL 38, Standard for Manually Actuated Signaling            VATED” (in bright yellow) appears at the top of the handle,
  Boxes.                                                           while a portion of the handle protrudes from the bottom of the
                                                                   station. To reset the station, simply unlock the station with the
Construction                                                       key and pull the door open. This action resets the handle; clos-
                                                                   ing the door automatically resets the switch.
Shell, door, and handle are molded of durable polycarbonate
material with a textured finish.                                   Each manual station, on command from the control panel,
                                                                   sends data to the panel representing the state of the manual
Specifications                                                     switch. Two rotary decimal switches allow address settings
                                                                   (1 – 159 with Breakaway Tab removed for MS-9600 Series, 1 –
•   Shipping Weight: 9.6 oz. (272.15 g)                            99 and MS-9200UDLS, 1 – 50 for MS-9050UD).
•   Normal operating voltage: 24 VDC.
•   Maximum SLC loop voltage: 28.0 VDC.                            Architectural/Engineering
•   Maximum SLC standby current: 375 μA.                           Specifications
•   Maximum SLC alarm current: 5 mA.                               Manual Fire Alarm Stations shall be non-coded, with a key-
•   Temperature Range: 32°F to 120°F (0°C to 49°C)                 operated reset lock in order that they may be tested, and so
•   Relative Humidity: 10% to 93% (noncondensing)                  designed that after actual Emergency Operation, they cannot
                                                                   be restored to normal except by use of a key. An operated sta-
•   For use indoors in a dry location                              tion shall automatically condition itself so as to be visually
                                                                   detected as activated. Manual stations shall be constructed of
Installation                                                       red-colored polycarbonate material with clearly visible operat-
                                                                   ing instructions provided on the cover. The word FIRE shall
The BG-12LX will mount semi-flush into a single-gang, double-
                                                                   appear on the front of the stations in white letters, 1.00 inches
gang, or standard 4" (10.16 cm) square electrical outlet box, or
                                                                   (2.54 cm) or larger. Stations shall be suitable for surface
will surface mount to the model SB-10 or SB-I/O surface back-
                                                                   mounting on matching backbox SB-10 or SB-I/O; or semi-flush
box. If the BG-12LX is being semi-flush mounted, then the
                                                                   mounting on a standard single-gang, double-gang, or
optional trim ring (BG12TR) may be used. The BG12TR is
                                                                   4" (10.16 cm) square electrical box, and shall be installed

                                                                                                  DF-52013:D • 4/13/2012 — Page 1 of 2
within the limits defined by the Americans with Disabilities Act
(ADA) or per national/local requirements. Manual Stations
shall be Underwriters Laboratories listed.
Manual stations shall connect with two wires to one of the con-
trol panel SLC loops. The manual station shall, on command
from the control panel, send data to the panel representing the
state of the manual switch. Manual stations shall provide
address setting by use of rotary decimal switches.

Product Line Information
BG-12LX: Dual-action addressable pull station. Includes key
locking feature. (Listed for Canadian and non-Canadian appli-
cations.)
SB-10: Surface backbox; metal.
SB-I/O: Surface backbox; plastic.
BG12TR: Optional trim ring.
17003: Keys, set of two.

Agency Listings and Approvals
In some cases, certain modules or applications may not be
listed by certain approval agencies, or listing may be in pro-
cess. Consult factory for latest listing status.
• UL/ULC Listed: S711 (listed for Canadian and non-Cana-
   dian applications).
• MEA: 67-02-E.
• CSFM: 7150-0075:0184.
• FM Approved.
Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772;
6,632,108.




                                                                          FireLite® Alarms® is a registered trademark of Honeywell International Inc.
                                                                          ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
                                                                          of this document is strictly prohibited.



                                        This document is not intended to be used for installation purposes.
                                          We try to keep our product information up-to-date and accurate.
                                       We cannot cover all specific applications or anticipate all requirements.
                                              All specifications are subject to change without notice.
                                                                                                                                Made in the U.S. A.
                             For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
                                                                    www.firelite.com
Page 2 of 2 — DF-52013:D • 4/13/2012

More Related Content

What's hot (13)

Eti products 02 2012 copy
Eti products 02 2012 copyEti products 02 2012 copy
Eti products 02 2012 copy
 
Edgereadererw400 ds en
Edgereadererw400 ds enEdgereadererw400 ds en
Edgereadererw400 ds en
 
Product Brief Mini Dsp
Product Brief Mini DspProduct Brief Mini Dsp
Product Brief Mini Dsp
 
Edgereaderesrp40 ds en
Edgereaderesrp40 ds enEdgereaderesrp40 ds en
Edgereaderesrp40 ds en
 
Sd355
Sd355Sd355
Sd355
 
Edgereaderer40 ds en
Edgereaderer40 ds enEdgereaderer40 ds en
Edgereaderer40 ds en
 
HFES Quick Intro
HFES Quick IntroHFES Quick Intro
HFES Quick Intro
 
A05 0180
A05 0180A05 0180
A05 0180
 
Vertx v1000 ds_en
Vertx v1000 ds_enVertx v1000 ds_en
Vertx v1000 ds_en
 
I300
I300I300
I300
 
Pdiusbd11
Pdiusbd11Pdiusbd11
Pdiusbd11
 
NavigateWorx_Product_Catalog_Ver1.01.01
NavigateWorx_Product_Catalog_Ver1.01.01NavigateWorx_Product_Catalog_Ver1.01.01
NavigateWorx_Product_Catalog_Ver1.01.01
 
io-esd
io-esdio-esd
io-esd
 

Similar to Bg12 lx

Similar to Bg12 lx (20)

Ad355
Ad355Ad355
Ad355
 
Mmf302
Mmf302Mmf302
Mmf302
 
Cmf300
Cmf300Cmf300
Cmf300
 
Manual osciloscopio GDS-800
Manual osciloscopio GDS-800Manual osciloscopio GDS-800
Manual osciloscopio GDS-800
 
Manual steinel rs led d2 (indoor light with led)
Manual steinel rs led d2 (indoor light with led)Manual steinel rs led d2 (indoor light with led)
Manual steinel rs led d2 (indoor light with led)
 
Dual action manual pull station
Dual action manual pull stationDual action manual pull station
Dual action manual pull station
 
5808spec
5808spec5808spec
5808spec
 
Datavideo TLM-702
Datavideo TLM-702Datavideo TLM-702
Datavideo TLM-702
 
Datavideo TLM-702
Datavideo TLM-702Datavideo TLM-702
Datavideo TLM-702
 
Crf300
Crf300Crf300
Crf300
 
Mmf300
Mmf300Mmf300
Mmf300
 
Pi logo csm230-86 (1)
Pi logo csm230-86 (1)Pi logo csm230-86 (1)
Pi logo csm230-86 (1)
 
Pi logo csm230-86
Pi logo csm230-86Pi logo csm230-86
Pi logo csm230-86
 
Datavideo TLm-700 Instruction manual
Datavideo TLm-700 Instruction manualDatavideo TLm-700 Instruction manual
Datavideo TLm-700 Instruction manual
 
Manual Steinel l 810 led i hf (outdoor light with led)
Manual Steinel l 810 led i hf (outdoor light with led)Manual Steinel l 810 led i hf (outdoor light with led)
Manual Steinel l 810 led i hf (outdoor light with led)
 
Dnr
DnrDnr
Dnr
 
7SR45 Self Powered Overcurrent Protection Relay
7SR45 Self Powered Overcurrent Protection Relay7SR45 Self Powered Overcurrent Protection Relay
7SR45 Self Powered Overcurrent Protection Relay
 
Datavideo DAC-7L
Datavideo DAC-7LDatavideo DAC-7L
Datavideo DAC-7L
 
Electro-Hydraulic Damper Drives for Combustion Control
Electro-Hydraulic Damper Drives for Combustion ControlElectro-Hydraulic Damper Drives for Combustion Control
Electro-Hydraulic Damper Drives for Combustion Control
 
Manual Smart Switch Walli Fibaro
Manual Smart Switch Walli FibaroManual Smart Switch Walli Fibaro
Manual Smart Switch Walli Fibaro
 

More from sanzen enterprises (20)

Odyssey 3
Odyssey 3Odyssey 3
Odyssey 3
 
Vm3240va ce cb1e
Vm3240va ce cb1eVm3240va ce cb1e
Vm3240va ce cb1e
 
Vm 3240 e
Vm 3240 eVm 3240 e
Vm 3240 e
 
Sv200ma mi1e
Sv200ma mi1eSv200ma mi1e
Sv200ma mi1e
 
Sc610 cs1e
Sc610 cs1eSc610 cs1e
Sc610 cs1e
 
Sc610 cs1e
Sc610 cs1eSc610 cs1e
Sc610 cs1e
 
Cs154 cs1e
Cs154 cs1eCs154 cs1e
Cs154 cs1e
 
Bs678 cs1e tei rev1
Bs678 cs1e tei rev1Bs678 cs1e tei rev1
Bs678 cs1e tei rev1
 
Bs633a data sheet
Bs633a data sheetBs633a data sheet
Bs633a data sheet
 
Data sheet en_us_1902186891
Data sheet en_us_1902186891Data sheet en_us_1902186891
Data sheet en_us_1902186891
 
Data sheet en_us_1902186891
Data sheet en_us_1902186891Data sheet en_us_1902186891
Data sheet en_us_1902186891
 
Data sheet en_us_1911721995
Data sheet en_us_1911721995Data sheet en_us_1911721995
Data sheet en_us_1911721995
 
La1 uw24 x column loudspeakers
La1 uw24 x column loudspeakersLa1 uw24 x column loudspeakers
La1 uw24 x column loudspeakers
 
Bgt 4139 ts
Bgt 4139 tsBgt 4139 ts
Bgt 4139 ts
 
Bgt 5504 a
Bgt 5504 aBgt 5504 a
Bgt 5504 a
 
Bgt 5140 a
Bgt 5140 aBgt 5140 a
Bgt 5140 a
 
Bgt 9120 ts
Bgt 9120 tsBgt 9120 ts
Bgt 9120 ts
 
Bgt 9119 as
Bgt 9119 asBgt 9119 as
Bgt 9119 as
 
Bgt 720 tos
Bgt 720 tosBgt 720 tos
Bgt 720 tos
 
Bgt 5221 as
Bgt 5221 asBgt 5221 as
Bgt 5221 as
 

Bg12 lx

  • 1. DF-52013:D • E-100 BG-12LX Addressable Manual Pull Station Addressable Devices General The Fire·Lite BG-12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that includes an addressable interface (mounted inside) for Fire·Lite’s addressable fire alarm control panels (FACPs) Because the BG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features • Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. • Handle latches in down position and the word “ACTIVATED” appears to clearly indicate the station has been operated. • Captive screw terminals wire-ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm² wire). • Can be surface mounted (with SB-10 or SB-I/O) or semi- flush mounted. Semi-flush mount to a standard single- FLPullStation.jpg gang, double-gang, or 4" (10.16 cm) square electrical box. • Smooth dual-action design. • Meets ADAAG controls and operating mechanisms guide- lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. • Highly visible. usually needed for semi-flush mounting with 4" (10.16 cm) or double-gang boxes (not with single-gang boxes). • Attractive shape and textured finish. • Key reset. Operation • Includes Braille text on station handle. Pushing in, then pulling down on the handle causes it to latch • Optional trim ring (BG12TR). in the down/activated position. Once latched, the word “ACTI- • Meets UL 38, Standard for Manually Actuated Signaling VATED” (in bright yellow) appears at the top of the handle, Boxes. while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the Construction key and pull the door open. This action resets the handle; clos- ing the door automatically resets the switch. Shell, door, and handle are molded of durable polycarbonate material with a textured finish. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual Specifications switch. Two rotary decimal switches allow address settings (1 – 159 with Breakaway Tab removed for MS-9600 Series, 1 – • Shipping Weight: 9.6 oz. (272.15 g) 99 and MS-9200UDLS, 1 – 50 for MS-9050UD). • Normal operating voltage: 24 VDC. • Maximum SLC loop voltage: 28.0 VDC. Architectural/Engineering • Maximum SLC standby current: 375 μA. Specifications • Maximum SLC alarm current: 5 mA. Manual Fire Alarm Stations shall be non-coded, with a key- • Temperature Range: 32°F to 120°F (0°C to 49°C) operated reset lock in order that they may be tested, and so • Relative Humidity: 10% to 93% (noncondensing) designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated sta- • For use indoors in a dry location tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of Installation red-colored polycarbonate material with clearly visible operat- ing instructions provided on the cover. The word FIRE shall The BG-12LX will mount semi-flush into a single-gang, double- appear on the front of the stations in white letters, 1.00 inches gang, or standard 4" (10.16 cm) square electrical outlet box, or (2.54 cm) or larger. Stations shall be suitable for surface will surface mount to the model SB-10 or SB-I/O surface back- mounting on matching backbox SB-10 or SB-I/O; or semi-flush box. If the BG-12LX is being semi-flush mounted, then the mounting on a standard single-gang, double-gang, or optional trim ring (BG12TR) may be used. The BG12TR is 4" (10.16 cm) square electrical box, and shall be installed DF-52013:D • 4/13/2012 — Page 1 of 2
  • 2. within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. Product Line Information BG-12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian appli- cations.) SB-10: Surface backbox; metal. SB-I/O: Surface backbox; plastic. BG12TR: Optional trim ring. 17003: Keys, set of two. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. • UL/ULC Listed: S711 (listed for Canadian and non-Cana- dian applications). • MEA: 67-02-E. • CSFM: 7150-0075:0184. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. FireLite® Alarms® is a registered trademark of Honeywell International Inc. ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 2 of 2 — DF-52013:D • 4/13/2012