Page 1 of 6 D A T A S H E E T S85001-0611
Not to be used for installation purposes. Issue 1
Edwards Signaling Catalog u Intelligent Input-Output
Overview
Edwards intelligent modules are engineered to deliver high-perfor­
mance features, superb reliability, and unbeatable quality. From
control of ancillary equipment, to enhanced signaling functionality,
these products add flexibility and powerful options to Edwards
Signaling intelligent systems.
Designed expressly for small buildings, Edwards Signaling mod-
ules are addressable devices that are uniquely identified on the
system by means of familiar rotary switches. Once registered, they
share data and update status information that determines how
the system behaves and how connected devices interact with one
another.
Unique to Edwards Signaling modules is ground fault detection
so precise that it actually pinpoints the specific module where the
wiring problem has occurred. This saves hours of troubleshoot-
ing and wire tracing. And only Edwards Signaling provides this
important feature!
The Edwards Signaling family of intelligent modules also offers
contractors and installers simple setup and installation, while
delivering options that take full advantage of intelligent fire alarm
processing. With a microprocessor in each device, intelligence is
distributed throughout the system so that command decisions are
made instantly at the individual module, rather than bottlenecking
at the control panel.
This not only speeds event processing, it also makes a more ro-
bust and reliable system – so robust, in fact, that when upgrading
from a conventional panel to a Edwards Signaling intelligent sys-
tem, you can usually use existing wiring – no twisted or shielded
cable required!
Standard Features
•	 Class A-B Two-Wire Module
Acts as an interface between conventional two-wire smoke
detectors and the Edwards Signaling control panel.
•	 Analog Class A Single Input Module
Used to connect a normally open, alarm, supervisory, or moni-
tor type dry contact initiating device circuit to the Edwards
Signaling control panel.
•	 Analog Dual Input Module
Connects two normally open, alarm, supervisory, or monitor
type dry contact initiating device circuits to the Edwards Signal-
ing control panel.
•	 Analog Dual Input Waterflow, Supervisory Module
Used to connect normally open waterflow alarm and supervi-
sory initiating device circuits to the Edwards Signaling control
panel. For Class B circuit operation.
•	 Analog SLC Fault Isolator Module
Protects a Class A SLC from total collapse due to wire-to-wire
short circuits.
•	 Analog NAC Module
Connects a supervised output circuit to a signal riser.
•	 Analog Contact Relay Module
Provides one Form C dry relay contact and can be configured
to provide polarity reversal of its output.
•	 Analog Single Input Mini Module
Connects a normally open, alarm, supervisory, or monitor type
dry contact initiating device circuit (IDC) to the Edwards Signal-
ing control panel. For Class B circuit operation.
Intelligent Input-Output
Modules
Models: E-2WIRE, E-IDC1A,
E-IDC2B, E-IDCWS, E-ISO,
E-NAC, E-RLY, E-IDC1B
Page 2 of 6 D A T A S H E E T S85001-0611
Not to be used for installation purposes. Issue 1
Warning
This module will not operate without electrical power. As fires
frequently cause power interruption, you should discuss further
safeguards with your local fire protection specialist.
This module does not support conventional smoke detectors.
Module Addressing
Use a screwdriver to adjust the two rotary switches on the front of
the module. Set the TENS rotary switch (0 through 12) for the 10s
digit and the ONES rotary switch for the 0 through 9 digit.
Insert
screwdriver
here
Example:	 device address 21, set TENS rotary switch to 2
and set the ONES rotary switch to 1.
Refer to the Specifications Table for available address numbers.
LED operation
Modules provide a bicolor LED for status indication.
Flashing Green LED	 Normal
Flashing Red LED	 Active
Installation
Screw
4-24
screws
Module
Wall plate
Compatible
electrical box
Mount in a North American 4 inch square x 2-1/2 in. (64 mm)
deep 2 gang box or a standard 4 in. square box 1-1/2 in. (38 mm)
deep.
Caution
Wire in accordance with NFPA 72 and CAN/
ULC-S524. Be sure to observe the polarity of the
wires as shown in the diagram.
Class A Single Input Module	 E-IDC1A
The Class A Single Input Module is used to connect a normally
open, alarm, supervisory, or monitor type dry contact initiating
device circuit (IDC) to the Edwards Signaling control panel. The
module is designed for Class A circuit operation.
The module's device address is set using the two rotary switches
located on the front of the module. One device address is re-
quired.
The device can be preset for alarm or supervisory operation using
the slide switch located on the front of the module. The module
can also be configured for other device types through front panel
programming or the configuration utility.
TB2 TB1
(+)
(+)
(+)
(+)
RETURN
IDC
Typical NO
Initiating device
Style D Class A
To next
device
From
previous
device
SLC out
SLC out
SLC in
SLC in
SLC
(+) ( )
( )
( )
( )
( )
Communication line voltage Maximum 20 V peak-to-peak
Current
Standby
Activated
400 μA
500 μA
Ground fault impedance 10 k ohm
Operating environment
Temperature
Humidity
32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F
(32°C)
Storage temperature range –4 to 140°F (–20 to 60°C)
Compatible electrical boxes North American 4 inch square x 2-1/2
in. (64 mm) deep 2 gang box
Standard 4 in. square box 1-1/2 in. (38
mm) deep box
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 sq. mm)  (Sizes 16 and 18
AWG are preferred)
Device address 01 to 64 (64 point control panel)
01 to 127 (127 point control panel)
Initiating device circuit (IDC)
Max. circuit resistance
Max. circuit capacitance
50 Ω (25 Ω per wire)
0.1 μF
Page 3 of 6 D A T A S H E E T S85001-0611
Not to be used for installation purposes. Issue 1
Class A-B Two-Wire Module	 E-2WIRE
The E-2WIRE module interfaces between conventional two-wire
smoke detectors and the Edwards Signaling control panel. It
monitors the circuit and smoke detectors, and signals the control
panel of any trouble or alarm conditions. The module also regu-
lates and supervises the 24 VDC input power.
The E-2WIRE is configured to operate as a two-wire alarm device
that does not require alarm verification. It can be set for two-wire
alarm verified operation through front panel programming or the
configuration utility. When using the alarm verification feature of the
control panel, do not mix normally open contact initiating devices
with two-wire conventional smoke detectors.
This module recognizes the CleanMe signal from detectors that
support this feature.
The device address is set using the two rotary switches located on
the front of the module. One device address is required.
The E-2WIRE can be set for Class B or Class A operation using
the slide switch located on the front of the module.
Note: This module cannot be used on a device loop with isolator
modules or isolator bases.
Dual Input Module	 E-IDC2B
The E-IDC2B connects two normally open, alarm, supervisory, or
monitor type dry contact initiating device circuits (IDCs) to the Ed-
wards Signaling control panel. This module is designed for Class B
circuit operation.
The device address is set using the two rotary switches located on
the front of the module. Two consecutive addresses are required.
The second address is automatically assigned one number higher
than the value set on the rotary switches.
The E-IDC2B can be preset for alarm or supervisory operation us-
ing the slide switch located on the front of the module. It can also
be configured for other device types through front panel program-
ming or the configuration utility.
Communication line voltage Maximum 20.6 V peak-to-peak
Current Standby: 350 μA. Activated: 350 μA
Control panel input power 12.4 to 28.3 VDC (not resettable)
Smoke power current Standby: 17 mA. Alarm: 58 mA
Smoke detector current 3 mA
UL compatibility ID 0.0
Ground fault impedance 5 k ohm
Operating environment
	 Temperature
	 Humidity
32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F
(32°C)
Storage temperature –4 to 140°F (–20 to 60°C)
Compatible
electrical boxes
North American 4 inch square x
2-1/2 in. (64 mm) deep 2 gang box.
Standard 4 in. square box 1-1/2 in. (38
mm) deep
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 sq. mm)  (Sizes 16 and 18
AWG are preferred)
Device address 01 to 64 (64 point control panel)
01 to 127 (127 point control panel)
Initiating device circuit
EOL resistor value
Max. circuit resistance
Max. circuit capacitance
4.7 kΩ, (P/N: EOL-4.7)
50 Ω (25 Ω per wire)
0.1 μF
Style D (Class A)
Style B (Class B)
Typical
initiating
device
TB2 TB1From
previous
device
To next
device
From control
panel (not
resettable)
24 V +
4.7 k Ohm EOLR
Used for
Class B only
SLC out (+)
SLC out
SLC in
SLC in (+)
SLC
DET. PWR.
(+)
(+) (+)
(+)
+ +
RETURN
DET.
( )
( )
( )
( )
( )
24 V
( )
47
EOLR
k Ohm
47
EOLR
k Ohm
IDC2
Style B (Class B)
IDC1
Typical NO
initiating device
TB2 TB1
(+)
(+)
SLC
(+)
( )
( )
( )
From
previous
device
To next
device
SLC out (+)
SLC out
SLC in
SLC in (+)
( )
( )
Communication line voltage Maximum 20 V peak-to-peak
Current
Standby
Activated
550 μA
725 μA
Ground fault impedance 10 k ohm
Operating environment
Temperature
Humidity
32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F
(32°C)
Storage temperature range –4 to 140°F (–20 to 60°C)
Compatible electrical boxes North American 4 inch square x 2-1/2
in. (64 mm) deep 2 gang box
Standard 4 in. square box 1-1/2 in.
(38 mm) deep
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 sq. mm)  (Sizes 16 and 18
AWG are preferred)
Device address 01 to 63 (64 point control panel)
01 to 126 (127point control panel)
Initiating device circuit (IDC)
EOL resistor value
Max. circuit resistance
Max. circuit capacitance
47 kΩ, (P/N: EOL-47)
50 Ω (25 Ω per wire)
0.1 μF
Page 4 of 6 D A T A S H E E T S85001-0611
Not to be used for installation purposes. Issue 1
Dual Input Waterflow, Supervisory Module	 E-IDCWS
•	 Nonlatching: Configures the module for normally open dry
contact initiating devices. When the NO input contact of an
initiating device is closed, a supervisory signal is sent to the
control panel and the supervisory condition is not latched at
the module.
•	 Latching: Configures the module for normally open dry con-
tact initiating devices. When the NO input contact of an initiat-
ing device is closed, a supervisory signal is sent to the control
panel and the supervisory condition is latched at the module.
The E-IDCWS connects normally open waterflow alarm and
supervisory initiating device circuits (IDCs) to the Edwards Signal-
ing control panel. The E-IDCWS is designed for Class B circuit
operation.
The device address is set using the two rotary switches located on
the front of the module. Two consecutive addresses are required.
The second address is automatically assigned one number higher
that the value set on the rotary switches.
The E-IDCWS can operate in the following modes:
Waterflow
•	 Alarm latching delayed: Configures the module for use with
only nonretarded waterflow alarm switches. When the NO
input contact of an initiating device is closed, an alarm is
sent to the control panel, which after a 16 second time delay,
generates an alarm signal.
Supervisory
•	 Supervisory active nonlatching US marketplace
•	 Supervisory active latching Canadian marketplace
SLC Fault Isolator Module	 E-ISO
The E-ISO protects a Class A SLC from total collapse due to
wire-to-wire short circuits. The module monitors line voltages and
opens the SLC when a short is detected. A short is isolated be-
tween the two modules located electrically closest to the short.
The device address is set using the two rotary switches located on
the front of the module. One device address is required.
From
previous
device
To next
device
TB2
SLC OUT
SLC IN
(+)
(+)
( )
( )
( )
( )
Communication line voltage Maximum 20 V peak-to-peak
Current
Standby
Activated
175 μA
200 μA
Ground fault impedance 10 k ohm
Maximum circuit resistance
between isolators
6 ohm
Operating environment
Temperature
Humidity
32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F
(32°C)
Storage temperature range –4 to 140°F (–20 to 60°C)
Compatible electrical boxes North American 4 inch square x 2-1/2
in. (64 mm) deep 2 gang box
Standard 4 in. square box 1-1/2 in.
(38 mm) deep
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 sq. mm)  (Sizes 16 and 18
AWG are preferred)
Module address 01 to 64 (64 point control panel)
01 to 127 (127 point control panel)
Typical NO
Waterflow Switch
47
EOLR
k Ohm
47
EOLR
k Ohm
SUP.
Style B (Class B)
W/FLOW
Typical NO
Supervisory/
Tamper Switch
TB2 TB1
(+)
(+)
SLC
(+)
( )
( )
( )
From
previous
device
To next
device
SLC out (+)
SLC out
SLC in
SLC in (+)
( )
( )
Communication line voltage Maximum 20 V peak-to-peak
Current
Standby
Activated
550 μA
725μA
Ground fault impedance 10 k ohm
Operating environment
Temperature
Humidity
32 to 120°F (0 to 49°C)
0 to 93% RH
Storage temperature range –4 to 140°F (–20 to 60°C)
Compatible electrical boxes North American 4 inch square x 2-1/2
in. (64 mm) deep 2 gang box
Standard 4 in. square box 1-1/2 in.
(38 mm) deep
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 sq. mm)  (Sizes 16 and
18 AWG are preferred)
Device address 01 to 63 (64 point control panel)
01 to 126 (127 point control panel)
Initiating device circuit (IDC)
EOL resistor value
Max. circuit resistance
Max. circuit capacitance
47 kΩ, (P/N: EOL-47)
50 Ω (25 Ω per wire)
0.1 μF
Page 5 of 6 D A T A S H E E T S85001-0611
Not to be used for installation purposes. Issue 1
NAC Module	 E-NAC
The E-NAC connects a supervised output circuit to a signal riser.
The output wiring is monitored for open and short circuits. A short
circuit causes the module to inhibit the activation of the audible/
visual signal circuit so the riser is not connected to the wiring fault.
Upon command from the control panel, the module connects the
output circuit to the riser input. The output circuit energizes a riser
to operate polarized audible and visual signals. The module can
be used for connection of a Class A or Class B (with EOL) output
notification appliance circuit (NAC).
The E-NAC module is configured to operate as a Continuous
Silenceable device type from the factory. It can also be configured
for other device types, such as Genesis (for synchronization of
Edwards Genesis series strobes) through front panel programming
or the configuration utility.
Genesis Audible/Visual/Silence: Used with Genesis and En-
hanced Integrity horns and strobes. Signals maintain synchroniza-
tion per UL 1971. For Genesis devices, this configuration allows
connected horns to be silenced while strobes on the same two-
wire circuit continue to flash until the panel is reset.From
listed
power
supply
[4]
24 VDC (+)
24 VDC
Circuit wired
same as
diagram above
Style Z (Class A)
Style Z (Class A)
Style Y (Class B)
Style Y (Class B)
Typical bell circuit
Typical horn or
strobe circuit
TB2 TB1
+ +
- -
+ +
- -
+ +
- -
RETURNNAC PWR. IN
NACSLC
(+)
(+)
From
previous
device
To next
device
SLC out (+)
SLC out
SLC in
SLC in (+)
( )
( )
( ) ( )
( )
( )
( )
47 k Ohm ELOR
used for
Class B only
47 k Ohm ELOR
used for
Class B only
Communication line voltage Maximum 20 V peak-to-peak
Current
Standby
Activated
350 μA
200 μA
Ground fault impedance 10 k ohm
Operating environment
Temperature
Humidity
32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F
(32°C)
Output ratings
Circuit current
EOL resistor value
24 VDC at 2 A max.
47 kΩ UL listed
Storage temperature range –4 to 140°F (–20 to 60°C)
Compatible electrical boxes North American 4 inch square x 2-1/2
in. (64 mm) deep 2 gang box
Standard 4 in. square box 1-1/2 in.
(38 mm) deep
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 sq. mm)  (Sizes 16 and 18
AWG are preferred)
Device address
(one address required)
01 to 64 (64 point control panel)
01 to 127 (127 point control panel)
Communication line voltage Maximum 20 V peak-to-peak
Current
Standby
Activated
125 µA
125 µA
Contact ratings (pilot duty)
30 VDC
125 VAC
2 A
0.5A resistive load 60 W or 62.5 VA
max.
Relay type Form C, programmable
Operating environment
Temperature
Humidity
32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F
(32°C)
Storage temperature range –4 to 140°F (–20 to 60°C)
Compatible electrical boxes North American 4 inch square x 2-1/2
in. (64 mm) deep 1 gang box
North American 4 inch square x 2-1/2
in. (64 mm) deep 2 gang box
Standard 4 in. square box 1-1/2 in. (38
mm) deep box
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 sq. mm)  (Sizes 16 and 18
AWG are preferred)
Module address
(one address required)
01 to 64 (64 point control panel)
01 to 127 (127 point control panel)
Contact Relay Module	 E-RLY
The E-RLY provides one Form C dry relay contact. It can also be
configured to provide polarity reversal of its output. The E-RLY can
be used to control external appliances or shut down equipment.
The E-RLY is wired according to its operation. It is configured to op-
erate as a relay nonsilence device type, and can function as either a
control relay or polarity reversal relay, depending on how it is wired.
Control relay function: Provides one Form C dry relay contact.
Polarity reversal relay function: Provides polarity reversal of its
output.
Note: Additional device types are available through front panel
programming or the configuration utility. Refer to applicable control
panel technical reference manual.
TB2 TB1From
previous
device
SLC in (+)
SLC out (+)
SLC in
SLC out
To next
device
Normally open
Common
Not used
Normally closed
SLC
(+)
(NC)
(NO)
(C)
( )
( )
( )
Page 6 of 6 D A T A S H E E T S85001-0611
Not to be used for installation purposes. Issue 1
09-06-13
Contact us...
Phone:	 1-800-336-4206
Web:	 www.edwardssignaling.com
Edwards Signaling is
an EDWARDS brand.
3 Farm Glen Boulevard
Farmington, CT 06032
In Canada, contact Chubb Edwards...
	Email:	 inquiries@chubbedwards.com
	 Web:	 www.chubbedwards.com
© 2013 UTC Fire & Security Americas
Corporation, Inc. All rights reserved.
Specifications subject to change
without notice. Edwards is part of UTC
Climate, Controls & Security, a unit of
United Technologies Corporation.
Ordering Information
Model Description Ship Weight
E-IDC1A Analog Class A Single Input Module 0.50 lbs. (0.23 kg.)
E-IDC1B Analog Single Input Mini Module 0.34 lbs. (0.15 kg.)
E-2WIRE Analog Class A-B Two-Wire Module 0.50 lbs. (0.23 kg.)
E-IDC2B Analog Dual Input Module 0.50 lbs. (0.23 kg.)
E-2IDCWS Analog Dual Input Waterflow-Supervisory Module 0.50 lbs. (0.23 kg.)
E-NAC Analog NAC Module 0.50 lbs. (0.23 kg.)
E-RLY Analog Contact Relay Module 0.50 lbs. (0.23 kg.)
E-ISO Analog SLC Fault Isolator Module 0.50 lbs. (0.23 kg.)
Communication line voltage Maximum 20 V peak-to-peak
Current
Standby
Activated
350 μA
500 μA
Ground fault impedance 10 k ohm
Operating environment
Temperature
Humidity
32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F (32°C)
Storage temperature range –4 to 140°F (–20 to 60°C)
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm)  (Sizes 16
and 18 AWG are preferred)
Device address
(two addresses required)
01 to 64 (64 point control panel)
01 to 127 (127 point control panel)
Initiating device circuit (IDC)
EOL resistor value
Max. circuit resistance
Max. circuit capacitance
47 kΩ, (P/N: EOL-47)
50 Ω (25 Ω per wire)
0.1 μF
Single Input Mini Module	 E-IDC1B
The E-IDC1B connects a normally open, alarm, supervisory, or monitor type dry contact
initiating device circuit (IDC) to the Edwards Signaling control panel. This module is for Class B
circuit operation.
The device address is set using the two rotary switches located on the front of the module.
One device address is required.
The module is configured to operate as an alarm latching device type from the factory. When
the NO contact of an initiating device is closed, an alarm signal is sent to the control panel and
the alarm condition is latched at the module.
Additional device types are available through front panel programming or the configuration util-
ity. Refer to applicable control panel technical reference manual.
Red (+) IDC (+)
Orange
IDC
Yellow
01
2
3
4
5 6
12
11
10
9
87
0 9
1
2
3
4 5
6
7
8
47
EOLR
k Ohm
Typical NO
initiating device
From
previous
device
SLC in
SLC out
Wire nut
SLC in (+)
SLC out (+)
To next
device
Style B (Class B)
Black( ) ( )
( )
( )
Insert screwdriver here
LEDs on reverse side

More Related Content

What's hot

Honeywell 5806w3-data-sheet
Honeywell 5806w3-data-sheetHoneywell 5806w3-data-sheet
Honeywell 5806w3-data-sheetAlarm Grid
 
Catalog MCB Shillin Electric - beeteco.com
Catalog MCB Shillin Electric - beeteco.comCatalog MCB Shillin Electric - beeteco.com
Catalog MCB Shillin Electric - beeteco.comBeeteco
 
Rsf ms 2x_series_catalog
Rsf ms 2x_series_catalogRsf ms 2x_series_catalog
Rsf ms 2x_series_catalogElectromate
 
Sk6812 rgbxp8 xx rev.01 en(nut)
Sk6812 rgbxp8 xx rev.01  en(nut)Sk6812 rgbxp8 xx rev.01  en(nut)
Sk6812 rgbxp8 xx rev.01 en(nut)ivan zhang
 
Netzer ds 130-specsheet
Netzer ds 130-specsheetNetzer ds 130-specsheet
Netzer ds 130-specsheetElectromate
 
Applying Digital Isolators in Motor Control
Applying Digital Isolators in Motor ControlApplying Digital Isolators in Motor Control
Applying Digital Isolators in Motor ControlAnalog Devices, Inc.
 
Sk6812 rgbp8 rev.01 en(nut)
Sk6812 rgbp8 rev.01  en(nut)Sk6812 rgbp8 rev.01  en(nut)
Sk6812 rgbp8 rev.01 en(nut)ivan zhang
 
Lc8805 b 1515 led
Lc8805 b 1515 ledLc8805 b 1515 led
Lc8805 b 1515 ledAlanWang129
 
Netzer ds 37-16-specsheet
Netzer ds 37-16-specsheetNetzer ds 37-16-specsheet
Netzer ds 37-16-specsheetElectromate
 
Joral Non Contact Encoders Ppt
Joral Non Contact Encoders PptJoral Non Contact Encoders Ppt
Joral Non Contact Encoders Pptjoralllc
 
Xt1511 rgbp8 rev.01 en(nut)
Xt1511 rgbp8 rev.01  en(nut)Xt1511 rgbp8 rev.01  en(nut)
Xt1511 rgbp8 rev.01 en(nut)ivan zhang
 

What's hot (17)

Honeywell 5806w3-data-sheet
Honeywell 5806w3-data-sheetHoneywell 5806w3-data-sheet
Honeywell 5806w3-data-sheet
 
Vertx v300 ds_en
Vertx v300 ds_enVertx v300 ds_en
Vertx v300 ds_en
 
Catalog MCB Shillin Electric - beeteco.com
Catalog MCB Shillin Electric - beeteco.comCatalog MCB Shillin Electric - beeteco.com
Catalog MCB Shillin Electric - beeteco.com
 
Sr
SrSr
Sr
 
Vertx v2000 ds_en
Vertx v2000 ds_enVertx v2000 ds_en
Vertx v2000 ds_en
 
Rsf ms 2x_series_catalog
Rsf ms 2x_series_catalogRsf ms 2x_series_catalog
Rsf ms 2x_series_catalog
 
Sk6812 rgbxp8 xx rev.01 en(nut)
Sk6812 rgbxp8 xx rev.01  en(nut)Sk6812 rgbxp8 xx rev.01  en(nut)
Sk6812 rgbxp8 xx rev.01 en(nut)
 
Netzer DS 130
Netzer DS 130Netzer DS 130
Netzer DS 130
 
Edgereadererp40 ds en
Edgereadererp40 ds enEdgereadererp40 ds en
Edgereadererp40 ds en
 
H355
H355H355
H355
 
Netzer ds 130-specsheet
Netzer ds 130-specsheetNetzer ds 130-specsheet
Netzer ds 130-specsheet
 
Applying Digital Isolators in Motor Control
Applying Digital Isolators in Motor ControlApplying Digital Isolators in Motor Control
Applying Digital Isolators in Motor Control
 
Sk6812 rgbp8 rev.01 en(nut)
Sk6812 rgbp8 rev.01  en(nut)Sk6812 rgbp8 rev.01  en(nut)
Sk6812 rgbp8 rev.01 en(nut)
 
Lc8805 b 1515 led
Lc8805 b 1515 ledLc8805 b 1515 led
Lc8805 b 1515 led
 
Netzer ds 37-16-specsheet
Netzer ds 37-16-specsheetNetzer ds 37-16-specsheet
Netzer ds 37-16-specsheet
 
Joral Non Contact Encoders Ppt
Joral Non Contact Encoders PptJoral Non Contact Encoders Ppt
Joral Non Contact Encoders Ppt
 
Xt1511 rgbp8 rev.01 en(nut)
Xt1511 rgbp8 rev.01  en(nut)Xt1511 rgbp8 rev.01  en(nut)
Xt1511 rgbp8 rev.01 en(nut)
 

Similar to Edwards Signaling E-NAC Data Sheet

System Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data SheetSystem Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data SheetJMAC Supply
 
K49 Controller
K49 ControllerK49 Controller
K49 ControllerJoseph
 
K48 Controller
K48 ControllerK48 Controller
K48 ControllerJoseph
 
DSE335-Data-Sheet (1).pdf
DSE335-Data-Sheet (1).pdfDSE335-Data-Sheet (1).pdf
DSE335-Data-Sheet (1).pdfIrvingGuatemala
 
K32 Controller
K32 ControllerK32 Controller
K32 ControllerJoseph
 
SDC 602RF Data Sheet
SDC 602RF Data SheetSDC 602RF Data Sheet
SDC 602RF Data SheetJMAC Supply
 
iLumTech Connected lighting
iLumTech Connected lightingiLumTech Connected lighting
iLumTech Connected lightingiLumTech
 
Series One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchSeries One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchIves Equipment
 
Safety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and PressureSafety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and PressureMiller Energy, Inc.
 
United Electric One Series Safety Transmitter
United Electric One Series Safety TransmitterUnited Electric One Series Safety Transmitter
United Electric One Series Safety TransmitterMiller Energy, Inc.
 
K39 Controller
K39 ControllerK39 Controller
K39 ControllerJoseph
 
V350-35-RA22_INSTAL-GUIDE_10-08
V350-35-RA22_INSTAL-GUIDE_10-08V350-35-RA22_INSTAL-GUIDE_10-08
V350-35-RA22_INSTAL-GUIDE_10-08Cara Bereck Levy
 
K31 Controller
K31 ControllerK31 Controller
K31 ControllerJoseph
 
Edwards Signaling SA-ETH Data Sheet
Edwards Signaling SA-ETH Data SheetEdwards Signaling SA-ETH Data Sheet
Edwards Signaling SA-ETH Data SheetJMAC Supply
 
Edwards Signaling SA-CLA Data Sheet
Edwards Signaling SA-CLA Data SheetEdwards Signaling SA-CLA Data Sheet
Edwards Signaling SA-CLA Data SheetJMAC Supply
 
iLumTech Technical catalogue
iLumTech Technical catalogueiLumTech Technical catalogue
iLumTech Technical catalogueiLumTech
 
NE030DC48_DAT
NE030DC48_DATNE030DC48_DAT
NE030DC48_DATminho kim
 
IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...
IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...
IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...BluBoxx Communication Pvt. ltd
 

Similar to Edwards Signaling E-NAC Data Sheet (20)

System Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data SheetSystem Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data Sheet
 
K49 Controller
K49 ControllerK49 Controller
K49 Controller
 
K48 Controller
K48 ControllerK48 Controller
K48 Controller
 
DSE335-Data-Sheet (1).pdf
DSE335-Data-Sheet (1).pdfDSE335-Data-Sheet (1).pdf
DSE335-Data-Sheet (1).pdf
 
K32 Controller
K32 ControllerK32 Controller
K32 Controller
 
RN221N
RN221NRN221N
RN221N
 
SDC 602RF Data Sheet
SDC 602RF Data SheetSDC 602RF Data Sheet
SDC 602RF Data Sheet
 
Ex rc1 spec-en_1215
Ex rc1 spec-en_1215Ex rc1 spec-en_1215
Ex rc1 spec-en_1215
 
iLumTech Connected lighting
iLumTech Connected lightingiLumTech Connected lighting
iLumTech Connected lighting
 
Series One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchSeries One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature Switch
 
Safety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and PressureSafety Transmitters for Temperature and Pressure
Safety Transmitters for Temperature and Pressure
 
United Electric One Series Safety Transmitter
United Electric One Series Safety TransmitterUnited Electric One Series Safety Transmitter
United Electric One Series Safety Transmitter
 
K39 Controller
K39 ControllerK39 Controller
K39 Controller
 
V350-35-RA22_INSTAL-GUIDE_10-08
V350-35-RA22_INSTAL-GUIDE_10-08V350-35-RA22_INSTAL-GUIDE_10-08
V350-35-RA22_INSTAL-GUIDE_10-08
 
K31 Controller
K31 ControllerK31 Controller
K31 Controller
 
Edwards Signaling SA-ETH Data Sheet
Edwards Signaling SA-ETH Data SheetEdwards Signaling SA-ETH Data Sheet
Edwards Signaling SA-ETH Data Sheet
 
Edwards Signaling SA-CLA Data Sheet
Edwards Signaling SA-CLA Data SheetEdwards Signaling SA-CLA Data Sheet
Edwards Signaling SA-CLA Data Sheet
 
iLumTech Technical catalogue
iLumTech Technical catalogueiLumTech Technical catalogue
iLumTech Technical catalogue
 
NE030DC48_DAT
NE030DC48_DATNE030DC48_DAT
NE030DC48_DAT
 
IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...
IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...
IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...
 

More from JMAC Supply

Bosch ALTV244UL Data Sheet
Bosch ALTV244UL Data SheetBosch ALTV244UL Data Sheet
Bosch ALTV244UL Data SheetJMAC Supply
 
Bosch AL1002WAL Data Sheet
Bosch AL1002WAL Data SheetBosch AL1002WAL Data Sheet
Bosch AL1002WAL Data SheetJMAC Supply
 
Bosch AIM-AEC21-CVT Data Sheet
Bosch AIM-AEC21-CVT Data SheetBosch AIM-AEC21-CVT Data Sheet
Bosch AIM-AEC21-CVT Data SheetJMAC Supply
 
Bosch AI1 Data Sheet
Bosch AI1 Data SheetBosch AI1 Data Sheet
Bosch AI1 Data SheetJMAC Supply
 
Bosch AH-24WP-R Data Sheet
Bosch AH-24WP-R Data SheetBosch AH-24WP-R Data Sheet
Bosch AH-24WP-R Data SheetJMAC Supply
 
Bosch AEC-8I8O-EXT Data Sheet
Bosch AEC-8I8O-EXT Data SheetBosch AEC-8I8O-EXT Data Sheet
Bosch AEC-8I8O-EXT Data SheetJMAC Supply
 
Bosch AE774 Data Sheet
Bosch AE774 Data SheetBosch AE774 Data Sheet
Bosch AE774 Data SheetJMAC Supply
 
Bosch AE203R Data Sheet
Bosch AE203R Data SheetBosch AE203R Data Sheet
Bosch AE203R Data SheetJMAC Supply
 
Bosch AE101 Data Sheet
Bosch AE101 Data SheetBosch AE101 Data Sheet
Bosch AE101 Data SheetJMAC Supply
 
Bosch AE4 Data Sheet
Bosch AE4 Data SheetBosch AE4 Data Sheet
Bosch AE4 Data SheetJMAC Supply
 
Bosch AE1 Data Sheet
Bosch AE1 Data SheetBosch AE1 Data Sheet
Bosch AE1 Data SheetJMAC Supply
 
Bosch ACD-IC16K37-50 Data Sheet
Bosch ACD-IC16K37-50 Data SheetBosch ACD-IC16K37-50 Data Sheet
Bosch ACD-IC16K37-50 Data SheetJMAC Supply
 
Bosch ACD-IC2K37-50 Data Sheet
Bosch ACD-IC2K37-50 Data SheetBosch ACD-IC2K37-50 Data Sheet
Bosch ACD-IC2K37-50 Data SheetJMAC Supply
 
Bosch ACA-IC2K26-10 Data Sheet
Bosch ACA-IC2K26-10 Data SheetBosch ACA-IC2K26-10 Data Sheet
Bosch ACA-IC2K26-10 Data SheetJMAC Supply
 
Bosch 9208B Data Sheet
Bosch 9208B Data SheetBosch 9208B Data Sheet
Bosch 9208B Data SheetJMAC Supply
 
Bosch 7110XC Data Sheet
Bosch 7110XC Data SheetBosch 7110XC Data Sheet
Bosch 7110XC Data SheetJMAC Supply
 
Samsung Techwin SNB-1000 Data Sheet
Samsung Techwin SNB-1000 Data SheetSamsung Techwin SNB-1000 Data Sheet
Samsung Techwin SNB-1000 Data SheetJMAC Supply
 
Samsung Techwin SMT-4031 Data Sheet
Samsung Techwin SMT-4031 Data SheetSamsung Techwin SMT-4031 Data Sheet
Samsung Techwin SMT-4031 Data SheetJMAC Supply
 
Samsung Techwin SMT-4023 Data Sheet
Samsung Techwin SMT-4023 Data SheetSamsung Techwin SMT-4023 Data Sheet
Samsung Techwin SMT-4023 Data SheetJMAC Supply
 
Samsung Techwin SMT-3232 Data Sheet
Samsung Techwin SMT-3232 Data SheetSamsung Techwin SMT-3232 Data Sheet
Samsung Techwin SMT-3232 Data SheetJMAC Supply
 

More from JMAC Supply (20)

Bosch ALTV244UL Data Sheet
Bosch ALTV244UL Data SheetBosch ALTV244UL Data Sheet
Bosch ALTV244UL Data Sheet
 
Bosch AL1002WAL Data Sheet
Bosch AL1002WAL Data SheetBosch AL1002WAL Data Sheet
Bosch AL1002WAL Data Sheet
 
Bosch AIM-AEC21-CVT Data Sheet
Bosch AIM-AEC21-CVT Data SheetBosch AIM-AEC21-CVT Data Sheet
Bosch AIM-AEC21-CVT Data Sheet
 
Bosch AI1 Data Sheet
Bosch AI1 Data SheetBosch AI1 Data Sheet
Bosch AI1 Data Sheet
 
Bosch AH-24WP-R Data Sheet
Bosch AH-24WP-R Data SheetBosch AH-24WP-R Data Sheet
Bosch AH-24WP-R Data Sheet
 
Bosch AEC-8I8O-EXT Data Sheet
Bosch AEC-8I8O-EXT Data SheetBosch AEC-8I8O-EXT Data Sheet
Bosch AEC-8I8O-EXT Data Sheet
 
Bosch AE774 Data Sheet
Bosch AE774 Data SheetBosch AE774 Data Sheet
Bosch AE774 Data Sheet
 
Bosch AE203R Data Sheet
Bosch AE203R Data SheetBosch AE203R Data Sheet
Bosch AE203R Data Sheet
 
Bosch AE101 Data Sheet
Bosch AE101 Data SheetBosch AE101 Data Sheet
Bosch AE101 Data Sheet
 
Bosch AE4 Data Sheet
Bosch AE4 Data SheetBosch AE4 Data Sheet
Bosch AE4 Data Sheet
 
Bosch AE1 Data Sheet
Bosch AE1 Data SheetBosch AE1 Data Sheet
Bosch AE1 Data Sheet
 
Bosch ACD-IC16K37-50 Data Sheet
Bosch ACD-IC16K37-50 Data SheetBosch ACD-IC16K37-50 Data Sheet
Bosch ACD-IC16K37-50 Data Sheet
 
Bosch ACD-IC2K37-50 Data Sheet
Bosch ACD-IC2K37-50 Data SheetBosch ACD-IC2K37-50 Data Sheet
Bosch ACD-IC2K37-50 Data Sheet
 
Bosch ACA-IC2K26-10 Data Sheet
Bosch ACA-IC2K26-10 Data SheetBosch ACA-IC2K26-10 Data Sheet
Bosch ACA-IC2K26-10 Data Sheet
 
Bosch 9208B Data Sheet
Bosch 9208B Data SheetBosch 9208B Data Sheet
Bosch 9208B Data Sheet
 
Bosch 7110XC Data Sheet
Bosch 7110XC Data SheetBosch 7110XC Data Sheet
Bosch 7110XC Data Sheet
 
Samsung Techwin SNB-1000 Data Sheet
Samsung Techwin SNB-1000 Data SheetSamsung Techwin SNB-1000 Data Sheet
Samsung Techwin SNB-1000 Data Sheet
 
Samsung Techwin SMT-4031 Data Sheet
Samsung Techwin SMT-4031 Data SheetSamsung Techwin SMT-4031 Data Sheet
Samsung Techwin SMT-4031 Data Sheet
 
Samsung Techwin SMT-4023 Data Sheet
Samsung Techwin SMT-4023 Data SheetSamsung Techwin SMT-4023 Data Sheet
Samsung Techwin SMT-4023 Data Sheet
 
Samsung Techwin SMT-3232 Data Sheet
Samsung Techwin SMT-3232 Data SheetSamsung Techwin SMT-3232 Data Sheet
Samsung Techwin SMT-3232 Data Sheet
 

Recently uploaded

APIForce Zurich 5 April Automation LPDG
APIForce Zurich 5 April  Automation LPDGAPIForce Zurich 5 April  Automation LPDG
APIForce Zurich 5 April Automation LPDGMarianaLemus7
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsMark Billinghurst
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr BaganFwdays
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Mark Simos
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Patryk Bandurski
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubKalema Edgar
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebUiPathCommunity
 
Unraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfUnraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfAlex Barbosa Coqueiro
 
Pigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions
 
Beyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry InnovationBeyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry InnovationSafe Software
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Mattias Andersson
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsRizwan Syed
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupFlorian Wilhelm
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsMemoori
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesSinan KOZAK
 
Bluetooth Controlled Car with Arduino.pdf
Bluetooth Controlled Car with Arduino.pdfBluetooth Controlled Car with Arduino.pdf
Bluetooth Controlled Car with Arduino.pdfngoud9212
 
costume and set research powerpoint presentation
costume and set research powerpoint presentationcostume and set research powerpoint presentation
costume and set research powerpoint presentationphoebematthew05
 
Science&tech:THE INFORMATION AGE STS.pdf
Science&tech:THE INFORMATION AGE STS.pdfScience&tech:THE INFORMATION AGE STS.pdf
Science&tech:THE INFORMATION AGE STS.pdfjimielynbastida
 

Recently uploaded (20)

APIForce Zurich 5 April Automation LPDG
APIForce Zurich 5 April  Automation LPDGAPIForce Zurich 5 April  Automation LPDG
APIForce Zurich 5 April Automation LPDG
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR Systems
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding Club
 
Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio Web
 
Unraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfUnraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdf
 
Pigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food Manufacturing
 
Beyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry InnovationBeyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?
 
Vulnerability_Management_GRC_by Sohang Sengupta.pptx
Vulnerability_Management_GRC_by Sohang Sengupta.pptxVulnerability_Management_GRC_by Sohang Sengupta.pptx
Vulnerability_Management_GRC_by Sohang Sengupta.pptx
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL Certs
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project Setup
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial Buildings
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen Frames
 
Bluetooth Controlled Car with Arduino.pdf
Bluetooth Controlled Car with Arduino.pdfBluetooth Controlled Car with Arduino.pdf
Bluetooth Controlled Car with Arduino.pdf
 
costume and set research powerpoint presentation
costume and set research powerpoint presentationcostume and set research powerpoint presentation
costume and set research powerpoint presentation
 
Science&tech:THE INFORMATION AGE STS.pdf
Science&tech:THE INFORMATION AGE STS.pdfScience&tech:THE INFORMATION AGE STS.pdf
Science&tech:THE INFORMATION AGE STS.pdf
 

Edwards Signaling E-NAC Data Sheet

  • 1. Page 1 of 6 D A T A S H E E T S85001-0611 Not to be used for installation purposes. Issue 1 Edwards Signaling Catalog u Intelligent Input-Output Overview Edwards intelligent modules are engineered to deliver high-perfor­ mance features, superb reliability, and unbeatable quality. From control of ancillary equipment, to enhanced signaling functionality, these products add flexibility and powerful options to Edwards Signaling intelligent systems. Designed expressly for small buildings, Edwards Signaling mod- ules are addressable devices that are uniquely identified on the system by means of familiar rotary switches. Once registered, they share data and update status information that determines how the system behaves and how connected devices interact with one another. Unique to Edwards Signaling modules is ground fault detection so precise that it actually pinpoints the specific module where the wiring problem has occurred. This saves hours of troubleshoot- ing and wire tracing. And only Edwards Signaling provides this important feature! The Edwards Signaling family of intelligent modules also offers contractors and installers simple setup and installation, while delivering options that take full advantage of intelligent fire alarm processing. With a microprocessor in each device, intelligence is distributed throughout the system so that command decisions are made instantly at the individual module, rather than bottlenecking at the control panel. This not only speeds event processing, it also makes a more ro- bust and reliable system – so robust, in fact, that when upgrading from a conventional panel to a Edwards Signaling intelligent sys- tem, you can usually use existing wiring – no twisted or shielded cable required! Standard Features • Class A-B Two-Wire Module Acts as an interface between conventional two-wire smoke detectors and the Edwards Signaling control panel. • Analog Class A Single Input Module Used to connect a normally open, alarm, supervisory, or moni- tor type dry contact initiating device circuit to the Edwards Signaling control panel. • Analog Dual Input Module Connects two normally open, alarm, supervisory, or monitor type dry contact initiating device circuits to the Edwards Signal- ing control panel. • Analog Dual Input Waterflow, Supervisory Module Used to connect normally open waterflow alarm and supervi- sory initiating device circuits to the Edwards Signaling control panel. For Class B circuit operation. • Analog SLC Fault Isolator Module Protects a Class A SLC from total collapse due to wire-to-wire short circuits. • Analog NAC Module Connects a supervised output circuit to a signal riser. • Analog Contact Relay Module Provides one Form C dry relay contact and can be configured to provide polarity reversal of its output. • Analog Single Input Mini Module Connects a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit (IDC) to the Edwards Signal- ing control panel. For Class B circuit operation. Intelligent Input-Output Modules Models: E-2WIRE, E-IDC1A, E-IDC2B, E-IDCWS, E-ISO, E-NAC, E-RLY, E-IDC1B
  • 2. Page 2 of 6 D A T A S H E E T S85001-0611 Not to be used for installation purposes. Issue 1 Warning This module will not operate without electrical power. As fires frequently cause power interruption, you should discuss further safeguards with your local fire protection specialist. This module does not support conventional smoke detectors. Module Addressing Use a screwdriver to adjust the two rotary switches on the front of the module. Set the TENS rotary switch (0 through 12) for the 10s digit and the ONES rotary switch for the 0 through 9 digit. Insert screwdriver here Example: device address 21, set TENS rotary switch to 2 and set the ONES rotary switch to 1. Refer to the Specifications Table for available address numbers. LED operation Modules provide a bicolor LED for status indication. Flashing Green LED Normal Flashing Red LED Active Installation Screw 4-24 screws Module Wall plate Compatible electrical box Mount in a North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box or a standard 4 in. square box 1-1/2 in. (38 mm) deep. Caution Wire in accordance with NFPA 72 and CAN/ ULC-S524. Be sure to observe the polarity of the wires as shown in the diagram. Class A Single Input Module E-IDC1A The Class A Single Input Module is used to connect a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit (IDC) to the Edwards Signaling control panel. The module is designed for Class A circuit operation. The module's device address is set using the two rotary switches located on the front of the module. One device address is re- quired. The device can be preset for alarm or supervisory operation using the slide switch located on the front of the module. The module can also be configured for other device types through front panel programming or the configuration utility. TB2 TB1 (+) (+) (+) (+) RETURN IDC Typical NO Initiating device Style D Class A To next device From previous device SLC out SLC out SLC in SLC in SLC (+) ( ) ( ) ( ) ( ) ( ) Communication line voltage Maximum 20 V peak-to-peak Current Standby Activated 400 μA 500 μA Ground fault impedance 10 k ohm Operating environment Temperature Humidity 32 to 120°F (0 to 49°C) 0 to 93% RH, noncondensing at 90°F (32°C) Storage temperature range –4 to 140°F (–20 to 60°C) Compatible electrical boxes North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box Standard 4 in. square box 1-1/2 in. (38 mm) deep box Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm)  (Sizes 16 and 18 AWG are preferred) Device address 01 to 64 (64 point control panel) 01 to 127 (127 point control panel) Initiating device circuit (IDC) Max. circuit resistance Max. circuit capacitance 50 Ω (25 Ω per wire) 0.1 μF
  • 3. Page 3 of 6 D A T A S H E E T S85001-0611 Not to be used for installation purposes. Issue 1 Class A-B Two-Wire Module E-2WIRE The E-2WIRE module interfaces between conventional two-wire smoke detectors and the Edwards Signaling control panel. It monitors the circuit and smoke detectors, and signals the control panel of any trouble or alarm conditions. The module also regu- lates and supervises the 24 VDC input power. The E-2WIRE is configured to operate as a two-wire alarm device that does not require alarm verification. It can be set for two-wire alarm verified operation through front panel programming or the configuration utility. When using the alarm verification feature of the control panel, do not mix normally open contact initiating devices with two-wire conventional smoke detectors. This module recognizes the CleanMe signal from detectors that support this feature. The device address is set using the two rotary switches located on the front of the module. One device address is required. The E-2WIRE can be set for Class B or Class A operation using the slide switch located on the front of the module. Note: This module cannot be used on a device loop with isolator modules or isolator bases. Dual Input Module E-IDC2B The E-IDC2B connects two normally open, alarm, supervisory, or monitor type dry contact initiating device circuits (IDCs) to the Ed- wards Signaling control panel. This module is designed for Class B circuit operation. The device address is set using the two rotary switches located on the front of the module. Two consecutive addresses are required. The second address is automatically assigned one number higher than the value set on the rotary switches. The E-IDC2B can be preset for alarm or supervisory operation us- ing the slide switch located on the front of the module. It can also be configured for other device types through front panel program- ming or the configuration utility. Communication line voltage Maximum 20.6 V peak-to-peak Current Standby: 350 μA. Activated: 350 μA Control panel input power 12.4 to 28.3 VDC (not resettable) Smoke power current Standby: 17 mA. Alarm: 58 mA Smoke detector current 3 mA UL compatibility ID 0.0 Ground fault impedance 5 k ohm Operating environment Temperature Humidity 32 to 120°F (0 to 49°C) 0 to 93% RH, noncondensing at 90°F (32°C) Storage temperature –4 to 140°F (–20 to 60°C) Compatible electrical boxes North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box. Standard 4 in. square box 1-1/2 in. (38 mm) deep Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm)  (Sizes 16 and 18 AWG are preferred) Device address 01 to 64 (64 point control panel) 01 to 127 (127 point control panel) Initiating device circuit EOL resistor value Max. circuit resistance Max. circuit capacitance 4.7 kΩ, (P/N: EOL-4.7) 50 Ω (25 Ω per wire) 0.1 μF Style D (Class A) Style B (Class B) Typical initiating device TB2 TB1From previous device To next device From control panel (not resettable) 24 V + 4.7 k Ohm EOLR Used for Class B only SLC out (+) SLC out SLC in SLC in (+) SLC DET. PWR. (+) (+) (+) (+) + + RETURN DET. ( ) ( ) ( ) ( ) ( ) 24 V ( ) 47 EOLR k Ohm 47 EOLR k Ohm IDC2 Style B (Class B) IDC1 Typical NO initiating device TB2 TB1 (+) (+) SLC (+) ( ) ( ) ( ) From previous device To next device SLC out (+) SLC out SLC in SLC in (+) ( ) ( ) Communication line voltage Maximum 20 V peak-to-peak Current Standby Activated 550 μA 725 μA Ground fault impedance 10 k ohm Operating environment Temperature Humidity 32 to 120°F (0 to 49°C) 0 to 93% RH, noncondensing at 90°F (32°C) Storage temperature range –4 to 140°F (–20 to 60°C) Compatible electrical boxes North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box Standard 4 in. square box 1-1/2 in. (38 mm) deep Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm)  (Sizes 16 and 18 AWG are preferred) Device address 01 to 63 (64 point control panel) 01 to 126 (127point control panel) Initiating device circuit (IDC) EOL resistor value Max. circuit resistance Max. circuit capacitance 47 kΩ, (P/N: EOL-47) 50 Ω (25 Ω per wire) 0.1 μF
  • 4. Page 4 of 6 D A T A S H E E T S85001-0611 Not to be used for installation purposes. Issue 1 Dual Input Waterflow, Supervisory Module E-IDCWS • Nonlatching: Configures the module for normally open dry contact initiating devices. When the NO input contact of an initiating device is closed, a supervisory signal is sent to the control panel and the supervisory condition is not latched at the module. • Latching: Configures the module for normally open dry con- tact initiating devices. When the NO input contact of an initiat- ing device is closed, a supervisory signal is sent to the control panel and the supervisory condition is latched at the module. The E-IDCWS connects normally open waterflow alarm and supervisory initiating device circuits (IDCs) to the Edwards Signal- ing control panel. The E-IDCWS is designed for Class B circuit operation. The device address is set using the two rotary switches located on the front of the module. Two consecutive addresses are required. The second address is automatically assigned one number higher that the value set on the rotary switches. The E-IDCWS can operate in the following modes: Waterflow • Alarm latching delayed: Configures the module for use with only nonretarded waterflow alarm switches. When the NO input contact of an initiating device is closed, an alarm is sent to the control panel, which after a 16 second time delay, generates an alarm signal. Supervisory • Supervisory active nonlatching US marketplace • Supervisory active latching Canadian marketplace SLC Fault Isolator Module E-ISO The E-ISO protects a Class A SLC from total collapse due to wire-to-wire short circuits. The module monitors line voltages and opens the SLC when a short is detected. A short is isolated be- tween the two modules located electrically closest to the short. The device address is set using the two rotary switches located on the front of the module. One device address is required. From previous device To next device TB2 SLC OUT SLC IN (+) (+) ( ) ( ) ( ) ( ) Communication line voltage Maximum 20 V peak-to-peak Current Standby Activated 175 μA 200 μA Ground fault impedance 10 k ohm Maximum circuit resistance between isolators 6 ohm Operating environment Temperature Humidity 32 to 120°F (0 to 49°C) 0 to 93% RH, noncondensing at 90°F (32°C) Storage temperature range –4 to 140°F (–20 to 60°C) Compatible electrical boxes North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box Standard 4 in. square box 1-1/2 in. (38 mm) deep Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm)  (Sizes 16 and 18 AWG are preferred) Module address 01 to 64 (64 point control panel) 01 to 127 (127 point control panel) Typical NO Waterflow Switch 47 EOLR k Ohm 47 EOLR k Ohm SUP. Style B (Class B) W/FLOW Typical NO Supervisory/ Tamper Switch TB2 TB1 (+) (+) SLC (+) ( ) ( ) ( ) From previous device To next device SLC out (+) SLC out SLC in SLC in (+) ( ) ( ) Communication line voltage Maximum 20 V peak-to-peak Current Standby Activated 550 μA 725μA Ground fault impedance 10 k ohm Operating environment Temperature Humidity 32 to 120°F (0 to 49°C) 0 to 93% RH Storage temperature range –4 to 140°F (–20 to 60°C) Compatible electrical boxes North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box Standard 4 in. square box 1-1/2 in. (38 mm) deep Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm)  (Sizes 16 and 18 AWG are preferred) Device address 01 to 63 (64 point control panel) 01 to 126 (127 point control panel) Initiating device circuit (IDC) EOL resistor value Max. circuit resistance Max. circuit capacitance 47 kΩ, (P/N: EOL-47) 50 Ω (25 Ω per wire) 0.1 μF
  • 5. Page 5 of 6 D A T A S H E E T S85001-0611 Not to be used for installation purposes. Issue 1 NAC Module E-NAC The E-NAC connects a supervised output circuit to a signal riser. The output wiring is monitored for open and short circuits. A short circuit causes the module to inhibit the activation of the audible/ visual signal circuit so the riser is not connected to the wiring fault. Upon command from the control panel, the module connects the output circuit to the riser input. The output circuit energizes a riser to operate polarized audible and visual signals. The module can be used for connection of a Class A or Class B (with EOL) output notification appliance circuit (NAC). The E-NAC module is configured to operate as a Continuous Silenceable device type from the factory. It can also be configured for other device types, such as Genesis (for synchronization of Edwards Genesis series strobes) through front panel programming or the configuration utility. Genesis Audible/Visual/Silence: Used with Genesis and En- hanced Integrity horns and strobes. Signals maintain synchroniza- tion per UL 1971. For Genesis devices, this configuration allows connected horns to be silenced while strobes on the same two- wire circuit continue to flash until the panel is reset.From listed power supply [4] 24 VDC (+) 24 VDC Circuit wired same as diagram above Style Z (Class A) Style Z (Class A) Style Y (Class B) Style Y (Class B) Typical bell circuit Typical horn or strobe circuit TB2 TB1 + + - - + + - - + + - - RETURNNAC PWR. IN NACSLC (+) (+) From previous device To next device SLC out (+) SLC out SLC in SLC in (+) ( ) ( ) ( ) ( ) ( ) ( ) ( ) 47 k Ohm ELOR used for Class B only 47 k Ohm ELOR used for Class B only Communication line voltage Maximum 20 V peak-to-peak Current Standby Activated 350 μA 200 μA Ground fault impedance 10 k ohm Operating environment Temperature Humidity 32 to 120°F (0 to 49°C) 0 to 93% RH, noncondensing at 90°F (32°C) Output ratings Circuit current EOL resistor value 24 VDC at 2 A max. 47 kΩ UL listed Storage temperature range –4 to 140°F (–20 to 60°C) Compatible electrical boxes North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box Standard 4 in. square box 1-1/2 in. (38 mm) deep Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm)  (Sizes 16 and 18 AWG are preferred) Device address (one address required) 01 to 64 (64 point control panel) 01 to 127 (127 point control panel) Communication line voltage Maximum 20 V peak-to-peak Current Standby Activated 125 µA 125 µA Contact ratings (pilot duty) 30 VDC 125 VAC 2 A 0.5A resistive load 60 W or 62.5 VA max. Relay type Form C, programmable Operating environment Temperature Humidity 32 to 120°F (0 to 49°C) 0 to 93% RH, noncondensing at 90°F (32°C) Storage temperature range –4 to 140°F (–20 to 60°C) Compatible electrical boxes North American 4 inch square x 2-1/2 in. (64 mm) deep 1 gang box North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box Standard 4 in. square box 1-1/2 in. (38 mm) deep box Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm)  (Sizes 16 and 18 AWG are preferred) Module address (one address required) 01 to 64 (64 point control panel) 01 to 127 (127 point control panel) Contact Relay Module E-RLY The E-RLY provides one Form C dry relay contact. It can also be configured to provide polarity reversal of its output. The E-RLY can be used to control external appliances or shut down equipment. The E-RLY is wired according to its operation. It is configured to op- erate as a relay nonsilence device type, and can function as either a control relay or polarity reversal relay, depending on how it is wired. Control relay function: Provides one Form C dry relay contact. Polarity reversal relay function: Provides polarity reversal of its output. Note: Additional device types are available through front panel programming or the configuration utility. Refer to applicable control panel technical reference manual. TB2 TB1From previous device SLC in (+) SLC out (+) SLC in SLC out To next device Normally open Common Not used Normally closed SLC (+) (NC) (NO) (C) ( ) ( ) ( )
  • 6. Page 6 of 6 D A T A S H E E T S85001-0611 Not to be used for installation purposes. Issue 1 09-06-13 Contact us... Phone: 1-800-336-4206 Web: www.edwardssignaling.com Edwards Signaling is an EDWARDS brand. 3 Farm Glen Boulevard Farmington, CT 06032 In Canada, contact Chubb Edwards... Email: inquiries@chubbedwards.com Web: www.chubbedwards.com © 2013 UTC Fire & Security Americas Corporation, Inc. All rights reserved. Specifications subject to change without notice. Edwards is part of UTC Climate, Controls & Security, a unit of United Technologies Corporation. Ordering Information Model Description Ship Weight E-IDC1A Analog Class A Single Input Module 0.50 lbs. (0.23 kg.) E-IDC1B Analog Single Input Mini Module 0.34 lbs. (0.15 kg.) E-2WIRE Analog Class A-B Two-Wire Module 0.50 lbs. (0.23 kg.) E-IDC2B Analog Dual Input Module 0.50 lbs. (0.23 kg.) E-2IDCWS Analog Dual Input Waterflow-Supervisory Module 0.50 lbs. (0.23 kg.) E-NAC Analog NAC Module 0.50 lbs. (0.23 kg.) E-RLY Analog Contact Relay Module 0.50 lbs. (0.23 kg.) E-ISO Analog SLC Fault Isolator Module 0.50 lbs. (0.23 kg.) Communication line voltage Maximum 20 V peak-to-peak Current Standby Activated 350 μA 500 μA Ground fault impedance 10 k ohm Operating environment Temperature Humidity 32 to 120°F (0 to 49°C) 0 to 93% RH, noncondensing at 90°F (32°C) Storage temperature range –4 to 140°F (–20 to 60°C) Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm)  (Sizes 16 and 18 AWG are preferred) Device address (two addresses required) 01 to 64 (64 point control panel) 01 to 127 (127 point control panel) Initiating device circuit (IDC) EOL resistor value Max. circuit resistance Max. circuit capacitance 47 kΩ, (P/N: EOL-47) 50 Ω (25 Ω per wire) 0.1 μF Single Input Mini Module E-IDC1B The E-IDC1B connects a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit (IDC) to the Edwards Signaling control panel. This module is for Class B circuit operation. The device address is set using the two rotary switches located on the front of the module. One device address is required. The module is configured to operate as an alarm latching device type from the factory. When the NO contact of an initiating device is closed, an alarm signal is sent to the control panel and the alarm condition is latched at the module. Additional device types are available through front panel programming or the configuration util- ity. Refer to applicable control panel technical reference manual. Red (+) IDC (+) Orange IDC Yellow 01 2 3 4 5 6 12 11 10 9 87 0 9 1 2 3 4 5 6 7 8 47 EOLR k Ohm Typical NO initiating device From previous device SLC in SLC out Wire nut SLC in (+) SLC out (+) To next device Style B (Class B) Black( ) ( ) ( ) ( ) Insert screwdriver here LEDs on reverse side