- 1. XLPE
Australian standard power distribution cable
Construction: Minimum Bending Radius : Temperature Range :
Uncompacted Class 2 stranding, special 10 x cable diameter -40oC to +90oC
X-90 crosslinked Polyethylene (XLPE)
insulation, flame retardant & UV resistant Nominal Voltage:
5V-90 PVC sheath. 600/1000V
Nominal Approx Approx
conductor overall weight
Part No. area mm2 Stranding Ø mm kg/km
3804590 1 x 16 7 x 1.70 9.4 205
3804591 1 x 25 19 x 1.35 11.4 309
3804592 1 x 35 19 x 1.53 12.3 412
3804593 1 x 50 19 x 1.78 13.7 540
3804594 1 x 70 19 x 2.14 15.9 760
3804595 1 x 95 37 x 1.78 17.6 1020
3804596 1 x 120 37 x 2.03 19.6 1270
3804597 1 x 150 37 x 2.25 21.7 1560
3804598 1 x 185 37 x 2.52 24.2 1930
3804599 1 x 240 61 x 2.25 27.2 2510
3804600 1 x 300 61 x 2.52 29.8 3120
3804601 1 x 400 61 x 2.85 33.4 3970
3804602 1 x 500 61 x 3.20 37.5 4980
3804603 1 x 630 127 x 2.52 42 6400
Minimum size of copper earth conductors
AS/NZS 3000
Nominal area active For copper active Nominal area active For copper active Nominal area active For copper active
conductors mm² conductors mm² conductors mm² conductors mm² conductors mm² conductors mm²
1 *1.0 25 6 185 70
1.5 *1.5 35 10 240 95
2.5 2.5 50 16 300 120
4 2.5 70 25 400 ** ≥120
6 2.5 95 25 500 ** ≥120
10 4 120 35 630 ** ≥120
16 6 150 50
* Refer Wiring Rules, AS/NZS 3000 regarding 1.5 earthing conductors.
** A larger earthing conductor may be required to satisfy Clause 5.3.3.1.1