Consumer Unit
All cables and connections to the consumer unit must be checked and
tested by a qualified electrician. Do not attempt removal or replacement
unless you are absolutely positive you know what you are doing, and
even then the above still applies. It is also an offence to interfere with
the seals on the electricity meter.
The modern consumer unit is the centre, or heart, of the wiring system
in the home. The unit distributes the electricity, via fuses of one kind or
another, to the different circuits in the house. The older fuse wire are
being replaced gradually by their modern equivalent, the MCB or
miniature circuit breaker.
We will deal with the two main types of consumer unit found in the home today . The first one
is a single load fuse board where the power coming in is taken through a double pole switch
to a live buss bar. Each fuse, or MCB, is clipped onto a DIN bar and the "teeth" of the buss
bar are inserted into the MCB's. The cables to the house circuits are connected to the other
side of the MCB's. All of this is explained more thoroughly when we deal with the second type
of unit, which is the split load unit. The photographs are of a split load fuse board. The
ordinary consumer unit is exactly the same in principle without the RCD.
Just as a matter of interest, DIN stands for Deutsche Industrie Norm and, originating in
Germany, is any of a series of technical standards, used Internationally, to designate
electrical connections, film speeds and paper sizes. Shown in the consumer unit casing
above, it is a metal, pressed bar, to which the MCB's clip. They simply push on via a spring
loaded lock at their back.
A split load board is designed for total safety and incorporates an RCD (Residual Current
Device, shown as E in the picture above) as well as the double pole switch (D).
The RCD is not just a manually operated isolating switch, but a very sensitive safety device
which cuts off in fractions of a second if it senses an earth fault. RCDs can be bought in
different current ratings and various sensitivities to current leakage. You will need to check
which ratings are appropriate for your home.
As they are very sensitive, it is not practical to fit one RCD to protect the whole house. If a
fault develops on one circuit, all circuits would be switched off immediately...This would, most
often, leave you in the unnecessary position of having no lights or power. Because of this it
actually contravenes the most recent (16th Edition) wiring regulations. This is easily
prevented by using an RCD in conjunction with a main, double pole isolating switch so that it
protects only some of the more vulnerable circuits. This then becomes a split load consumer
unit and is shown above. The key to this photo is..
A: Neutral terminal block for the main isolating switch side of the unit.
B: Neutral terminal block for RCD side of the unit
C: Earth terminal block (takes both sides of unit)
D: Main double pole isolating switch.
E: Generally 80 - 100 Amp RCD with 100mA (milliamp) sensitivity.
F: Neutral link cable from Main switch to terminal block
G: Live feed from main switch to RCD.
H: Neutral link cable from main terminal block to RCD
I: Neutral link cable from RCD to RCD neutral terminal block.
The use of RCDs is necessary, on two occasions, to meet the wiring regulations. The first of
these is to protect any socket which may be reasonably expected supply equipment outside
the house (Strimmers, lawn mowers, hedge trimmers, pond pumps, sheds, lights etc etc).
This rule pretty much covers every single socket in the house so the ring main should be
placed on the RCD protected side of the consumer unit.
The second condition applies to any circuits where an earth fault current is not sufficient to
blow the fuse, or trip the switch, in the designated time allowance made in the regulations.
This generally applies to higher Amp rated appliances (showers, cookers etc) but it should
always be checked with an electrician as to which circuits need to be placed on the RCD side
of the consumer unit.
The Current ratings which MCBs are designated to deal with are now conforming to the
international equivalent of our old imperial ratings. This standard is called the Renard current
rating and supercedes the imperial ratings as far as MCBs are concerned. A 5 amp fuse can
be replaced with a 6 amp MCB. A 15 amp fuse becomes a 16 amp MCB, a 20 amp fuse can
be a 20 amp MCB, 30 amp fuse = 32 amp
CB and a 45 amp fuse must now be a 40
amp MCB.
M
Top left shows the mains double pole isolating switch and an MCB clipped into place on the
DIN bar. Top right shows two MCBs and the Buss bar. When the MCBs are clipped onto the
DIN bar, the Buss bar is inserted into the live terminal at the bottom of the MCB. When
screwed tight this gives live feed to all the MCBs.
Top left shows the live (K) and neutral (J) coming into the main double pole switch from the
meter. These cables are called tails, and in this instance, with this type of unit, are 16mm
cables. This will vary and you should always check with a qualified electrician. Top left shows
the earth cable from the meter (L). This screws into the earth terminal block.
Top left shows how a circuit cable is introduced to the unit. In this case it is a 2.5mm cable for
the ring main. The live (O) is fixed into the top of an MCB on the RCD side of the unit, while
the neutral (M) goes to the RCD neutral terminal block. The earth (N*) (which has been left
unsheathed for clarity ). Each circuit cable is fed into the consumer unit and connected to an
MCB of the appropriate rating.

More Related Content

What's hot

What's hot (20)

Multiple well cathodic protection
Multiple well cathodic protectionMultiple well cathodic protection
Multiple well cathodic protection
 
Basic electrical comp upload1
Basic electrical comp upload1Basic electrical comp upload1
Basic electrical comp upload1
 
Led blinker
Led blinkerLed blinker
Led blinker
 
2k w free energy device don smith
2k w free energy device   don smith2k w free energy device   don smith
2k w free energy device don smith
 
5. resistor and capacitor application
5. resistor and capacitor application5. resistor and capacitor application
5. resistor and capacitor application
 
Components used in electrical installations
Components used in electrical installationsComponents used in electrical installations
Components used in electrical installations
 
Project electronics
Project electronicsProject electronics
Project electronics
 
Electronic bicycle lock
Electronic bicycle lockElectronic bicycle lock
Electronic bicycle lock
 
4.3 transistor
4.3 transistor4.3 transistor
4.3 transistor
 
travelling mobile charger
travelling mobile chargertravelling mobile charger
travelling mobile charger
 
2.3
2.32.3
2.3
 
Basic electronics
Basic electronicsBasic electronics
Basic electronics
 
New electronics slides
New electronics slidesNew electronics slides
New electronics slides
 
Electrical components 8
Electrical components 8Electrical components 8
Electrical components 8
 
Project report on failure of fuse & mcb
Project report on failure of fuse & mcbProject report on failure of fuse & mcb
Project report on failure of fuse & mcb
 
Sensitive intrucer alaram
Sensitive intrucer alaramSensitive intrucer alaram
Sensitive intrucer alaram
 
Basic Electronics
Basic Electronics Basic Electronics
Basic Electronics
 
HELE / TLEelectronics
HELE / TLEelectronicsHELE / TLEelectronics
HELE / TLEelectronics
 
Diode and transistor
Diode and transistorDiode and transistor
Diode and transistor
 
C hapter 2 diode applications
C hapter 2 diode applicationsC hapter 2 diode applications
C hapter 2 diode applications
 

Viewers also liked

Viewers also liked (9)

Build a shed
Build a shedBuild a shed
Build a shed
 
Backyard pond
Backyard pondBackyard pond
Backyard pond
 
Corrugated sheet roofing
Corrugated sheet roofingCorrugated sheet roofing
Corrugated sheet roofing
 
Air bricks
Air bricksAir bricks
Air bricks
 
Fixing to lathe & plaster
Fixing to lathe & plasterFixing to lathe & plaster
Fixing to lathe & plaster
 
Build a brick barbecue
Build a brick barbecueBuild a brick barbecue
Build a brick barbecue
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Build a shower cubicle
Build a shower cubicleBuild a shower cubicle
Build a shower cubicle
 
Uni kl rulesandregulationshandbook7thedition
Uni kl rulesandregulationshandbook7theditionUni kl rulesandregulationshandbook7thedition
Uni kl rulesandregulationshandbook7thedition
 

Similar to Consumer unit

KL1034 Lect2 Electrical wiring.pdf
KL1034 Lect2 Electrical wiring.pdfKL1034 Lect2 Electrical wiring.pdf
KL1034 Lect2 Electrical wiring.pdfSysteDesig
 
Switchgear.pptx
Switchgear.pptxSwitchgear.pptx
Switchgear.pptxsatabdi8
 
buildinggroupppt-130512115915-phpapp02.pptx
buildinggroupppt-130512115915-phpapp02.pptxbuildinggroupppt-130512115915-phpapp02.pptx
buildinggroupppt-130512115915-phpapp02.pptxNirmalSivarajan3
 
Failure of fuse & mcb
Failure of fuse & mcbFailure of fuse & mcb
Failure of fuse & mcbsachin singh
 
Invisible broken wire detector
Invisible broken wire detectorInvisible broken wire detector
Invisible broken wire detectorRITESH D. PATIL
 
Electronics 01
Electronics 01Electronics 01
Electronics 01snakeaye
 
Wiring devices for illumination
Wiring devices for illuminationWiring devices for illumination
Wiring devices for illuminationSurendra Tamang
 
Switchyard final
Switchyard finalSwitchyard final
Switchyard finalHAIDER ALI
 
Mains operated under voltage over voltage trip switch
Mains operated under voltage over voltage trip switchMains operated under voltage over voltage trip switch
Mains operated under voltage over voltage trip switchEdgefxkits & Solutions
 
Electrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBElectrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBMANOJ964697
 
Water level indicator by bhushan kumbhalkar
Water level indicator by  bhushan kumbhalkarWater level indicator by  bhushan kumbhalkar
Water level indicator by bhushan kumbhalkarBhushan Kumbhalkar
 
protection scheme of a grid substation prsentation
protection scheme of a grid substation prsentationprotection scheme of a grid substation prsentation
protection scheme of a grid substation prsentationabu jubayer
 
Electrical protective devices ec
Electrical protective devices ecElectrical protective devices ec
Electrical protective devices ectrg12345
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentationKamal Mittal
 

Similar to Consumer unit (20)

KL1034 Lect2 Electrical wiring.pdf
KL1034 Lect2 Electrical wiring.pdfKL1034 Lect2 Electrical wiring.pdf
KL1034 Lect2 Electrical wiring.pdf
 
Electrical Installations
Electrical InstallationsElectrical Installations
Electrical Installations
 
Switchgear.pptx
Switchgear.pptxSwitchgear.pptx
Switchgear.pptx
 
Mcb, rccb, elcb
Mcb, rccb, elcbMcb, rccb, elcb
Mcb, rccb, elcb
 
buildinggroupppt-130512115915-phpapp02.pptx
buildinggroupppt-130512115915-phpapp02.pptxbuildinggroupppt-130512115915-phpapp02.pptx
buildinggroupppt-130512115915-phpapp02.pptx
 
Failure of fuse & mcb
Failure of fuse & mcbFailure of fuse & mcb
Failure of fuse & mcb
 
Invisible broken wire detector
Invisible broken wire detectorInvisible broken wire detector
Invisible broken wire detector
 
Electrical System.ppsx
Electrical System.ppsxElectrical System.ppsx
Electrical System.ppsx
 
Electronics 01
Electronics 01Electronics 01
Electronics 01
 
Wiring devices for illumination
Wiring devices for illuminationWiring devices for illumination
Wiring devices for illumination
 
Switchyard final
Switchyard finalSwitchyard final
Switchyard final
 
homewiring.pdf
homewiring.pdfhomewiring.pdf
homewiring.pdf
 
Mains operated under voltage over voltage trip switch
Mains operated under voltage over voltage trip switchMains operated under voltage over voltage trip switch
Mains operated under voltage over voltage trip switch
 
avi
aviavi
avi
 
Bee presentation
Bee presentationBee presentation
Bee presentation
 
Electrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBElectrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCB
 
Water level indicator by bhushan kumbhalkar
Water level indicator by  bhushan kumbhalkarWater level indicator by  bhushan kumbhalkar
Water level indicator by bhushan kumbhalkar
 
protection scheme of a grid substation prsentation
protection scheme of a grid substation prsentationprotection scheme of a grid substation prsentation
protection scheme of a grid substation prsentation
 
Electrical protective devices ec
Electrical protective devices ecElectrical protective devices ec
Electrical protective devices ec
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 

More from Zulaiha Amaria

More from Zulaiha Amaria (20)

Application of disciplinary system
Application of disciplinary systemApplication of disciplinary system
Application of disciplinary system
 
girl culture dictionary
girl culture dictionarygirl culture dictionary
girl culture dictionary
 
Wiring a ring main
Wiring a ring mainWiring a ring main
Wiring a ring main
 
Waterproof your roof
Waterproof your roofWaterproof your roof
Waterproof your roof
 
Wallpapering techniques
Wallpapering techniquesWallpapering techniques
Wallpapering techniques
 
Wallpaper stripping
Wallpaper strippingWallpaper stripping
Wallpaper stripping
 
Wallpaper a ceiling
Wallpaper a ceilingWallpaper a ceiling
Wallpaper a ceiling
 
Wall tiling
Wall tilingWall tiling
Wall tiling
 
Wainscotting
WainscottingWainscotting
Wainscotting
 
Upvc fascia
Upvc fasciaUpvc fascia
Upvc fascia
 
Tow dolly plans
Tow dolly plansTow dolly plans
Tow dolly plans
 
Timber decking
Timber deckingTimber decking
Timber decking
 
Timber cutting hand saws
Timber cutting hand sawsTimber cutting hand saws
Timber cutting hand saws
 
Size conversion charts
Size conversion chartsSize conversion charts
Size conversion charts
 
Shelving and storage
Shelving and storageShelving and storage
Shelving and storage
 
Safe diy
Safe diySafe diy
Safe diy
 
Replacing a brick
Replacing a brickReplacing a brick
Replacing a brick
 
Replace broken tiles
Replace broken tilesReplace broken tiles
Replace broken tiles
 
Repairing a dripping tap
Repairing a dripping tapRepairing a dripping tap
Repairing a dripping tap
 
Renovating wood
Renovating woodRenovating wood
Renovating wood
 

Recently uploaded

B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptxB.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptxpriyanshujha201
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayNZSG
 
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876dlhescort
 
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...allensay1
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...rajveerescorts2022
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...lizamodels9
 
Organizational Transformation Lead with Culture
Organizational Transformation Lead with CultureOrganizational Transformation Lead with Culture
Organizational Transformation Lead with CultureSeta Wicaksana
 
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...amitlee9823
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxWorkforce Group
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptxnandhinijagan9867
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Roland Driesen
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsP&CO
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageMatteo Carbone
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...amitlee9823
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLSeo
 
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdfDr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdfAdmir Softic
 
John Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfJohn Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfAmzadHosen3
 
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...amitlee9823
 
Business Model Canvas (BMC)- A new venture concept
Business Model Canvas (BMC)-  A new venture conceptBusiness Model Canvas (BMC)-  A new venture concept
Business Model Canvas (BMC)- A new venture conceptP&CO
 

Recently uploaded (20)

B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptxB.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
 
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabiunwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 May
 
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
 
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
Call Girls Service In Old Town Dubai ((0551707352)) Old Town Dubai Call Girl ...
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
 
Organizational Transformation Lead with Culture
Organizational Transformation Lead with CultureOrganizational Transformation Lead with Culture
Organizational Transformation Lead with Culture
 
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptx
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptx
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usage
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
 
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdfDr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
 
John Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfJohn Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdf
 
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
 
Business Model Canvas (BMC)- A new venture concept
Business Model Canvas (BMC)-  A new venture conceptBusiness Model Canvas (BMC)-  A new venture concept
Business Model Canvas (BMC)- A new venture concept
 

Consumer unit

  • 1. Consumer Unit All cables and connections to the consumer unit must be checked and tested by a qualified electrician. Do not attempt removal or replacement unless you are absolutely positive you know what you are doing, and even then the above still applies. It is also an offence to interfere with the seals on the electricity meter. The modern consumer unit is the centre, or heart, of the wiring system in the home. The unit distributes the electricity, via fuses of one kind or another, to the different circuits in the house. The older fuse wire are being replaced gradually by their modern equivalent, the MCB or miniature circuit breaker. We will deal with the two main types of consumer unit found in the home today . The first one is a single load fuse board where the power coming in is taken through a double pole switch to a live buss bar. Each fuse, or MCB, is clipped onto a DIN bar and the "teeth" of the buss bar are inserted into the MCB's. The cables to the house circuits are connected to the other side of the MCB's. All of this is explained more thoroughly when we deal with the second type of unit, which is the split load unit. The photographs are of a split load fuse board. The ordinary consumer unit is exactly the same in principle without the RCD. Just as a matter of interest, DIN stands for Deutsche Industrie Norm and, originating in Germany, is any of a series of technical standards, used Internationally, to designate electrical connections, film speeds and paper sizes. Shown in the consumer unit casing above, it is a metal, pressed bar, to which the MCB's clip. They simply push on via a spring loaded lock at their back. A split load board is designed for total safety and incorporates an RCD (Residual Current Device, shown as E in the picture above) as well as the double pole switch (D).
  • 2. The RCD is not just a manually operated isolating switch, but a very sensitive safety device which cuts off in fractions of a second if it senses an earth fault. RCDs can be bought in different current ratings and various sensitivities to current leakage. You will need to check which ratings are appropriate for your home. As they are very sensitive, it is not practical to fit one RCD to protect the whole house. If a fault develops on one circuit, all circuits would be switched off immediately...This would, most often, leave you in the unnecessary position of having no lights or power. Because of this it actually contravenes the most recent (16th Edition) wiring regulations. This is easily prevented by using an RCD in conjunction with a main, double pole isolating switch so that it protects only some of the more vulnerable circuits. This then becomes a split load consumer unit and is shown above. The key to this photo is.. A: Neutral terminal block for the main isolating switch side of the unit. B: Neutral terminal block for RCD side of the unit C: Earth terminal block (takes both sides of unit) D: Main double pole isolating switch. E: Generally 80 - 100 Amp RCD with 100mA (milliamp) sensitivity. F: Neutral link cable from Main switch to terminal block G: Live feed from main switch to RCD. H: Neutral link cable from main terminal block to RCD I: Neutral link cable from RCD to RCD neutral terminal block. The use of RCDs is necessary, on two occasions, to meet the wiring regulations. The first of these is to protect any socket which may be reasonably expected supply equipment outside the house (Strimmers, lawn mowers, hedge trimmers, pond pumps, sheds, lights etc etc). This rule pretty much covers every single socket in the house so the ring main should be placed on the RCD protected side of the consumer unit. The second condition applies to any circuits where an earth fault current is not sufficient to blow the fuse, or trip the switch, in the designated time allowance made in the regulations. This generally applies to higher Amp rated appliances (showers, cookers etc) but it should always be checked with an electrician as to which circuits need to be placed on the RCD side of the consumer unit. The Current ratings which MCBs are designated to deal with are now conforming to the international equivalent of our old imperial ratings. This standard is called the Renard current rating and supercedes the imperial ratings as far as MCBs are concerned. A 5 amp fuse can be replaced with a 6 amp MCB. A 15 amp fuse becomes a 16 amp MCB, a 20 amp fuse can be a 20 amp MCB, 30 amp fuse = 32 amp CB and a 45 amp fuse must now be a 40 amp MCB. M
  • 3. Top left shows the mains double pole isolating switch and an MCB clipped into place on the DIN bar. Top right shows two MCBs and the Buss bar. When the MCBs are clipped onto the DIN bar, the Buss bar is inserted into the live terminal at the bottom of the MCB. When screwed tight this gives live feed to all the MCBs. Top left shows the live (K) and neutral (J) coming into the main double pole switch from the meter. These cables are called tails, and in this instance, with this type of unit, are 16mm cables. This will vary and you should always check with a qualified electrician. Top left shows the earth cable from the meter (L). This screws into the earth terminal block.
  • 4. Top left shows how a circuit cable is introduced to the unit. In this case it is a 2.5mm cable for the ring main. The live (O) is fixed into the top of an MCB on the RCD side of the unit, while the neutral (M) goes to the RCD neutral terminal block. The earth (N*) (which has been left unsheathed for clarity ). Each circuit cable is fed into the consumer unit and connected to an MCB of the appropriate rating.