2. Requirement of dry riser installation
• For residential building height more than 45m but less than
60m, or with basement or commercial building
• Ø100mm dry riser main pipe is for building height
from 10m to 45m
• Ø150mm dry riser main pipe is for building height
from 45m to 60m
Requirement of dry riser installation
•2- way breeching inlet for Ø100mm rising main
•4- way breeching inlet for Ø 150mm rising main
SUBAN MONDAL 2
4323
4. Wet riser tank capacity
• One rising main capacity
= 49 m3
for half hours + 1.1 m3
fire hose reel
• Two rising main capacity
=74 m3
for half hours +1.1 m3
fire hose reel
SUBAN MONDAL 4
4323