Laporan menunjukkan pengukuran penghematan energi setelah pemasangan Somar Integra/Powerboss pada conveyor 7,5 kW. Pengukuran menunjukkan penghematan arus sebesar 32,9-73,32%, penghematan daya 0,422-6,39 kW (21,8-78,54%), dan peningkatan efisiensi aliran daya. Penghematan energi dapat mengurangi biaya listrik dan pemeliharaan serta memperpanjang umur komponen.
1. ANALIZER MEASUREMENT : ENERGY ANALYZER CIRCUTOR AR5-L - CURRENT [ AMPERE ]
WITHOUT SOMAR INTEGRA / POWERBOSS 1.927 A
WITH SOMAR INTEGRA / POWERBOSS 1.293 A
% SAVING 32.90 %
CURRENT [ AMPERE ] RUNNING MEASUREMENT
GRAPHICWITHOUT SOMAR INTEGRA / POWERBOSS ANDWITH SOMAR INTEGRA/POWERBOSS
ENERGYSAVINGREPORT
TYPE OF SI / PBI : PBI 7.5/V220-480
SCHEMATIC CONNECTION : DIRECT ON LINE CONNECTION
EQUIPMENT / MACHINE : CONVEYOR 7,5KW
CUSTOMER : ANTAM POMALA
TESTING INSTRUMENT : CIRCUTOR AR5-L ENERGY ANALYZER
AMPERE SAVING
32.90%
pg. 1
SOMARINTEGRA[POWERBOSS]INSTALLEDATCONVEYER7,5KW
ENERGY TEST - AMPERE RUNNING
PT ENERCON EQUIPMENT COMPANY
Gedung Aldevco II - 4th Floor
Jl. Warung Jati Barat Raya No. 75 Jakarta, Indonesia
T: 62 21 7941182 F: 62 21 7941184 W: www.enercon.co.id E: info@enercon.co.id
2. GRAPHICWITHOUT SOMAR INTEGRA/POWERBOSS ANDWITH SOMAR INTEGRA/POWERBOSS
ANALIZER MEASUREMENT : ENERGY ANALYZER CIRCUTOR AR5-L - CURRENT [ AMPERE]
WITHOUT SOMAR INTEGRA / POWERBOSS 21.136 A
WITH SOMAR INTEGRA / POWERBOSS 5.639 A
% SAVING 73.32%
CURRENT [ AMPERE ] STARTING MEASUREMENT
2
ENERGYSAVINGREPORTSOMARINTEGRA[POWERBOSS]INSTALLEDATCONVEYER7,5KW
TYPE OF SI / PBI : PBI 7.5/V220-480
SCHEMATIC CONNECTION : DIRECT ON LINE CONNECTION
EQUIPMENT / MACHINE : CONVEYOR 7,5KW
CUSTOMER : ANTAM POMALA
TESTING INSTRUMENT : CIRCUTOR AR5-L ENERGY ANALYZER
PT ENERCON EQUIPMENT COMPANY
Gedung Aldevco II - 4th Floor
Jl. Warung Jati Barat Raya No. 75 Jakarta, Indonesia
T: 62 21 7941182 F: 62 21 7941184 W: www.enercon.co.id E: info@enercon.co.id
AMPERE SAVING
73.32%
ENERGY TEST - AMPERE STARTING
3. ANALIZER MEASUREMENT : ENERGY ANALYZER CIRCUTOR AR5-L - KW
WITHOUT SOMAR INTEGRA / POWERBOSS 0.422 KW
WITH SOMAR INTEGRA / POWERBOSS 0.330 KW
% SAVING 21.80%
GRAPHICWITHOUT SOMAR INTEGRA/POWERBOSS ANDWITH SOMAR INTEGRA/POWERBOSS
3
ENERGYSAVINGREPORTSOMARINTEGRA[POWERBOSS]INSTALLEDATCONVEYER7,5KW
TYPE OF SI / PBI : PBI 7.5/V220-480
SCHEMATIC CONNECTION : DIRECT ON LINE CONNECTION
EQUIPMENT / MACHINE : CONVEYOR 7,5KW
CUSTOMER : ANTAM POMALA
TESTING INSTRUMENT : CIRCUTOR AR5-L ENERGY ANALYZER
PT ENERCON EQUIPMENT COMPANY
Gedung Aldevco II - 4th Floor
Jl. Warung Jati Barat Raya No. 75 Jakarta, Indonesia
T: 62 21 7941182 F: 62 21 7941184 W: www.enercon.co.id E: info@enercon.co.id
POWER [ KW] RUNNING MEASUREMENT
ENERGY TEST - KW RUNNING
KW SAVING
21.80%
4. ANALIZER MEASUREMENT : ENERGY ANALYZER CIRCUTOR AR5-L - KW
WITHOUT SOMAR INTEGRA / POWERBOSS 6.390 KW
WITH SOMAR INTEGRA / POWERBOSS 1.371 KW
% SAVING 78.54%
GRAPHICWITHOUT SOMAR INTEGRA/POWERBOSS ANDWITH SOMAR INTEGRA/POWERBOSS
4
ENERGYSAVINGREPORTSOMARINTEGRA[POWERBOSS]INSTALLEDATCONVEYER7,5KW
TYPE OF SI / PBI : PBI 7.5/V220-480
SCHEMATIC CONNECTION : DIRECT ON LINE CONNECTION
EQUIPMENT / MACHINE : CONVEYOR 7,5KW
CUSTOMER : ANTAM POMALA
TESTING INSTRUMENT : CIRCUTOR AR5-L ENERGY ANALYZER
PT ENERCON EQUIPMENT COMPANY
Gedung Aldevco II - 4th Floor
Jl. Warung Jati Barat Raya No. 75 Jakarta, Indonesia
T: 62 21 7941182 F: 62 21 7941184 W: www.enercon.co.id E: info@enercon.co.id
POWER [ KW ] STARTING MEASUREMENT
KW SAVING
78.54%
ENERGY TEST - KW STARTING
5. GRAPHICWITHOUT SOMAR INTEGRA/POWERBOSS ANDWITH SOMAR INTEGRA/POWERBOSS
5
ENERGYSAVINGREPORTSOMARINTEGRA[POWERBOSS]INSTALLEDATCONVEYER7,5KW
TYPE OF SI / PBI : PBI 7.5/V220-480
SCHEMATIC CONNECTION : DIRECT ON LINE CONNECTION
EQUIPMENT / MACHINE : CONVEYOR 7,5KW
CUSTOMER : ANTAM POMALA
TESTING INSTRUMENT : CIRCUTOR AR5-L ENERGY ANALYZER
PT ENERCON EQUIPMENT COMPANY
Gedung Aldevco II - 4th Floor
Jl. Warung Jati Barat Raya No. 75 Jakarta, Indonesia
T: 62 21 7941182 F: 62 21 7941184 W: www.enercon.co.id E: info@enercon.co.id
POWER FACTOR [ PF ] RUNNING MEASUREMENT
ENERGY TEST - PF RUNNING
6. 6
ENERGYSAVINGREPORTSOMARINTEGRA[POWERBOSS]INSTALLEDATCONVEYER7,5KW
TYPE OF SI / PBI : PBI 7.5/V220-480
SCHEMATIC CONNECTION : DIRECT ON LINE CONNECTION
EQUIPMENT / MACHINE : CONVEYOR 7,5KW
CUSTOMER : ANTAM POMALA
TESTING INSTRUMENT : CIRCUTOR AR5-L ENERGY ANALYZER
PT ENERCON EQUIPMENT COMPANY
Gedung Aldevco II - 4th Floor
Jl. Warung Jati Barat Raya No. 75 Jakarta, Indonesia
T: 62 21 7941182 F: 62 21 7941184 W: www.enercon.co.id E: info@enercon.co.id
K E S I M P U L A N
•KW SAVING
Efisiensi KW akan mengurangi nilai pemakaian KWH (energy listrik) oleh
motor utama, sehingga mengurangi biaya pengeluaran tagihan listrik untuk
motor tersebut.
•KVAR SAVING
Efisiensi KVAR akan mengurangi panas yang timbul akibat adanya losses/
kehilangan daya motor, sehingga dengan berkurangnya KVAR akan
memperpanjang faktor lifetime dari motor dan perbaikan Power factor.
•KVA SAVING
Motor & Peralatan lainnya yang berhubungan (cables, fuses, contactors dan
overloads) akan dialiri oleh arus current yang lebih kecil sehingga tidak akan
mudah rusak dan akan mengurangi biaya maintenance serta mengurangi
biaya beban pinalti KVA (KVA Dis-insentif).
Bagi konsumen yang menggunakan sumber listrik (Power Plant) sendiri atau
generator dengan bahan bakar solar, maka KVA saving ini akan mengurangi
konsumsi pemakaian solar pada saat offload dan meningkatkan kemampuan
generator tersebut untuk beroperasi.
Keuntungan lain yang didapatkan dengan dipasangnya sSOMAR INTEGRA /
POWERBOSS, antara lain:
•Soft Start & Soft Stop
Proses Start & Stop motor akan lebih halus bila dibandingkan dengan
instalasi motor yang hanya menggunakan Direct on line dan star-delta.
Efeknya adalah tiadanya hentakan saat starting dan proses stop yang tiba-
tiba sehingga komponen mekanikal motor akan lebih tahan lama.
•3 Phase Protector
Bila terjadi hilangnya salah satu phase power listrik, maka Powerboss akan
bekerja secara otomatis untuk memutuskan aliran listrik ke motor agar motor
tidak terbakar akibat overload/over