ACD-V CO, SMOKE, AND HEAT MULTI-SENSOR
STANDARD FEATURES
 Low profile - only 2.0” high, including base
 Easy and reliable device addressing
 Supports 16 operational modes
 Automatic compensation for sensor contamination
 Built-in fire test feature
 Uses the noise-immune Digital Communication Protocol
(DCP), which utilizes interrupts for fast response to fires
 Two built-in power/alarm LEDs
 Programmable non-polling LEDs
 Non-directional smoke chamber
 Vandal resistant security locking feature
 Removable smoke labyrinth for cleaning or replacement
 10 years CO sensor
SPECIFICATIONS
APPLICATIONS
The Hochiki ACD-V CO, Smoke, and Heat Multi-Sensor is
particularly suited for detecting smoke produced by the wide
range of combustibles found in various applications. Tempera-
ture monitoring is achieved by thermistors placed for optimum
sensitivity. Also, the sensor is suited for detecting deadly lev-
els of carbon monoxide (CO). Hochiki's unique design allows
fast response to flaming/smoldering fires and carbon monox-
ide levels while minimizing nuisance alarms.
OPERATION
To sense smoke, the ACD-V uses a light-emitting diode (LED)
and photodiode compliment. The chamber is designed such
that light emitted by the LED cannot normally reach the
photodiode. In the event of fire, particles of smoke enter the
chamber and scatter the light. As the smoke level increases,
the scattering effect increases, causing more light to hit the
photodiode. The chamber contains a unique design which
allows smoke to enter the chamber while preventing external
light from affecting the photodiode. The photodiode input level
is sampled to sense smoke density. When the smoke density
exceeds a preset threshold the sensor transmits an interrupt
to the fire control panel indicating a fire condition. The fire
alarm control panel can adjust the sensor threshold to com-
pensate for contamination.
The ACD-V heat portion incorporates a highly linear dual
thermistor circuit. A specially designed cover protects the
thermistors while allowing maximum air flow. The ACD-V
supports both fixed-temperature and rate-of-rise sensing. The
fire alarm control panel can adjust the sensor threshold for
different environmental requirements.
The ACD-V carbon monoxide (CO) sensing cell serves the
dual purpose of supplementing smoke detection in combina-
tion with the photodiode arrangement and monitoring color-
less, odorless and deadly carbon monoxide levels for life safe-
ty. When the carbon monoxide exceeds the poisonous levels,
the sensor transmits an interrupt to the control panel indicat-
ing a CO alarm.
Up to 127 devices are permitted on each SLC loop. A sensor
address can be set by a hand-held programming unit. The
sensor mounts to a base and incorporates a locking mecha-
nism for secure installation. The base provides mounting slots
and terminals for field wiring. The sensor incorporates dual
LEDs for easy viewing of sensor status.
Hochiki America Corporation
7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Phone: 714-522-2246 Fax: 714-522-2268
Technical Support: 800-845-6692 or technicalsupport@hochiki.com
Find latest revision at www.hochiki.com
F0210 11/2016 RCK
Operating Voltage 17-41 VDC
Standby Current 450μA
Alarm Current 7.2mA
Transmission Method DCP - Digital Communication Protocol
Maximum Humidity 95% RH Non-Condensing
UL Temperature Range 32°F to 120°F
(0° C to 49° C)
Operating Temperature 14°F to 122°F
Range (-10°C to 50°C)
Sensitivity Range 0.7-4.0%/FT@300FPM
0.7-3.86%/FT@2000FPM
0.7-2.65%/FT@4000FPM
Air Velocity Range 0-4000 fpm
Color & Case Material Bone - ABS Blend
Weight 4.2oz (5.9 oz. with 4” base)
Dimensions 3.9”D x 1.8”H
Recommended Base ASBL
Specifications subject to change without notice. Continued on back.
S1383
PRODUCT LISTINGS
California State
Fire Marshal
Pending
Pending
SENSOR SPACING
Smoke sensor spacing shall be in compliance with NFPA 72. For smooth ceilings and in the absence of specific performance-
based design criteria, the distance between smoke sensors shall not exceed a nominal spacing of 30 ft. (9.1m) or all points on the
ceiling shall have a sensor within a distance equal to or less than 0.7 times the nominal 30 ft. (9.1m) spacing. Sensors shall be
located within a distance of one-half the nominal spacing, measured at right angles from all walls or partitions extending upward
to within the top 15 percent of the ceiling height. For additional instructions see NFPA 72.
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install Hochiki's ACD-V (Multi-Criteria Sensor) as indicated on the plans. The Multi-Criteria
Sensor head and twist lock base is UL Listed and it’s compatible with an UL Listed fire alarm control panel.
The base permits direct interchange with the Hochiki ALG-V, ALK-V/ALK-V2, ALN-V photoelectric type smoke sensors, AIE-EA
ionization type smoke sensor, ATG-EA, ATJ-EA heat sensors and the ACA-V, ACC-V multi-criteria sensor.
The sensitivity of the sensor is capable of being measured by the control panel. The CO sensing element shall provide for 10
years of active usage.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature is
optional and can be implemented when required.
BASES
The ACD-V supports the YBN-NSA-4, HSB-NSA-6, ASB, SCI-B4, SCI-B6 bases as well as the recommended ASBL base when
used for life safety CO sensing. A common mounting base allows sensor interchange and maintains loop continuity when sen-
sors are removed. A simple anti-tamper head locking system is provided which is enabled by removing a small plastic tab on the
back of the sensor. Once locked, the head can be removed using a small diameter screwdriver.
TYPICAL WIRING DIAGRAMS
NOTE: Fire alarm control panel compatibility is required for DCP products. ACD-V are only compatible with the FireNET Plus
Fire alarm control panel DCP communications protocol allows system compo-nents (DCP sensors AIE-EA, ALG-V, ACA-V,
ACC-V, ALK-V, ALN-V, ATJ-EA, ATG-EA, ACD-V, bases and modules) to be used concurrently on a system's SLC (Signaling
Line Circuit).
Hochiki America Corporation ACD-V CO, SMOKE, AND HEAT MULTI-SENSOR Specifications subject to change without notice.
ACD-V CO, SMOKE, AND HEAT MULTI-SENSOR

More Related Content

What's hot

SenseTek Stratos Micra 25 datasheet
SenseTek Stratos Micra 25 datasheetSenseTek Stratos Micra 25 datasheet
SenseTek Stratos Micra 25 datasheetHans Bronkhorst
 
Drager PointGard 2000 Series Gas Detection System
Drager PointGard 2000 Series Gas Detection SystemDrager PointGard 2000 Series Gas Detection System
Drager PointGard 2000 Series Gas Detection SystemFlow-Tech, Inc.
 
Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...
Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...
Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...Hile Controls of Alabama, Inc.
 
Crowcon IRmax Fixed Gas Detector - Spec Sheet
Crowcon IRmax Fixed Gas Detector - Spec SheetCrowcon IRmax Fixed Gas Detector - Spec Sheet
Crowcon IRmax Fixed Gas Detector - Spec SheetThorne & Derrick UK
 
Dräger Polytron 8700 Fixed Gas Detector - Spec Sheet
Dräger Polytron 8700 Fixed Gas Detector - Spec SheetDräger Polytron 8700 Fixed Gas Detector - Spec Sheet
Dräger Polytron 8700 Fixed Gas Detector - Spec SheetThorne & Derrick UK
 
SenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishSenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishHans Bronkhorst
 
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dts
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dtsSenseTek Bandweaver Road Tunnels Linear Heat Detection-dts
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dtsHans Bronkhorst
 
Firelaser-datasheet-SenseTek Glasvezel detectie
Firelaser-datasheet-SenseTek  Glasvezel detectieFirelaser-datasheet-SenseTek  Glasvezel detectie
Firelaser-datasheet-SenseTek Glasvezel detectieHans Bronkhorst
 
System Sensor APA151
System Sensor APA151System Sensor APA151
System Sensor APA151JMAC Supply
 
SenseTek Bandweaver Escalator fire-detection-dts
SenseTek Bandweaver Escalator fire-detection-dtsSenseTek Bandweaver Escalator fire-detection-dts
SenseTek Bandweaver Escalator fire-detection-dtsHans Bronkhorst
 
Honeywell 5806w3-data-sheet
Honeywell 5806w3-data-sheetHoneywell 5806w3-data-sheet
Honeywell 5806w3-data-sheetAlarm Grid
 
Edwards Signaling E-HD Data Sheet
Edwards Signaling E-HD Data SheetEdwards Signaling E-HD Data Sheet
Edwards Signaling E-HD Data SheetJMAC Supply
 
Diq s 181 transmitter wtw
Diq s 181 transmitter wtwDiq s 181 transmitter wtw
Diq s 181 transmitter wtwENVIMART
 
Dräger PIR 7000 Fixed Gas Detector - Spec Sheet
Dräger PIR 7000 Fixed Gas Detector - Spec SheetDräger PIR 7000 Fixed Gas Detector - Spec Sheet
Dräger PIR 7000 Fixed Gas Detector - Spec SheetThorne & Derrick UK
 

What's hot (20)

SenseTek Stratos Micra 25 datasheet
SenseTek Stratos Micra 25 datasheetSenseTek Stratos Micra 25 datasheet
SenseTek Stratos Micra 25 datasheet
 
Drager PointGard 2000 Series Gas Detection System
Drager PointGard 2000 Series Gas Detection SystemDrager PointGard 2000 Series Gas Detection System
Drager PointGard 2000 Series Gas Detection System
 
MSR sc2 p3410-a Ethylene-Gas-Sensor-Transmitter
MSR sc2 p3410-a Ethylene-Gas-Sensor-TransmitterMSR sc2 p3410-a Ethylene-Gas-Sensor-Transmitter
MSR sc2 p3410-a Ethylene-Gas-Sensor-Transmitter
 
Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...
Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...
Williamson Infrared Products for Monitoring Smokeless Flares, Pilots, and Fla...
 
Zirconia oxygen sensors (zirconia o2 sensor) o2 s-t2 o2s-fr-t2
Zirconia oxygen sensors (zirconia o2 sensor)   o2 s-t2  o2s-fr-t2Zirconia oxygen sensors (zirconia o2 sensor)   o2 s-t2  o2s-fr-t2
Zirconia oxygen sensors (zirconia o2 sensor) o2 s-t2 o2s-fr-t2
 
Net Safety Monitoring Flame & Gas Detection
Net Safety Monitoring Flame & Gas DetectionNet Safety Monitoring Flame & Gas Detection
Net Safety Monitoring Flame & Gas Detection
 
Crowcon IRmax Fixed Gas Detector - Spec Sheet
Crowcon IRmax Fixed Gas Detector - Spec SheetCrowcon IRmax Fixed Gas Detector - Spec Sheet
Crowcon IRmax Fixed Gas Detector - Spec Sheet
 
Dräger Polytron 8700 Fixed Gas Detector - Spec Sheet
Dräger Polytron 8700 Fixed Gas Detector - Spec SheetDräger Polytron 8700 Fixed Gas Detector - Spec Sheet
Dräger Polytron 8700 Fixed Gas Detector - Spec Sheet
 
SenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishSenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet english
 
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dts
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dtsSenseTek Bandweaver Road Tunnels Linear Heat Detection-dts
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dts
 
Refrigeration Industry Gas Detection Applications
Refrigeration Industry Gas Detection ApplicationsRefrigeration Industry Gas Detection Applications
Refrigeration Industry Gas Detection Applications
 
Firelaser-datasheet-SenseTek Glasvezel detectie
Firelaser-datasheet-SenseTek  Glasvezel detectieFirelaser-datasheet-SenseTek  Glasvezel detectie
Firelaser-datasheet-SenseTek Glasvezel detectie
 
D2
D2D2
D2
 
C 9104
C 9104C 9104
C 9104
 
System Sensor APA151
System Sensor APA151System Sensor APA151
System Sensor APA151
 
SenseTek Bandweaver Escalator fire-detection-dts
SenseTek Bandweaver Escalator fire-detection-dtsSenseTek Bandweaver Escalator fire-detection-dts
SenseTek Bandweaver Escalator fire-detection-dts
 
Honeywell 5806w3-data-sheet
Honeywell 5806w3-data-sheetHoneywell 5806w3-data-sheet
Honeywell 5806w3-data-sheet
 
Edwards Signaling E-HD Data Sheet
Edwards Signaling E-HD Data SheetEdwards Signaling E-HD Data Sheet
Edwards Signaling E-HD Data Sheet
 
Diq s 181 transmitter wtw
Diq s 181 transmitter wtwDiq s 181 transmitter wtw
Diq s 181 transmitter wtw
 
Dräger PIR 7000 Fixed Gas Detector - Spec Sheet
Dräger PIR 7000 Fixed Gas Detector - Spec SheetDräger PIR 7000 Fixed Gas Detector - Spec Sheet
Dräger PIR 7000 Fixed Gas Detector - Spec Sheet
 

Similar to ACD-V_11-2016 RCK

Edwards Signaling RB4U Data Sheet
Edwards Signaling RB4U Data SheetEdwards Signaling RB4U Data Sheet
Edwards Signaling RB4U Data SheetJMAC Supply
 
Sensepoint_Pro_pdf.pdf
Sensepoint_Pro_pdf.pdfSensepoint_Pro_pdf.pdf
Sensepoint_Pro_pdf.pdfssuser3e1ce9
 
Crowcon Detective+ Portable Gas Detector - Spec Sheet
Crowcon Detective+ Portable Gas Detector - Spec SheetCrowcon Detective+ Portable Gas Detector - Spec Sheet
Crowcon Detective+ Portable Gas Detector - Spec SheetThorne & Derrick UK
 
fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm systemsingh1515
 
Bluetooth Based Fire Detection and Robust Protection System By Using Arduino
Bluetooth Based Fire Detection and Robust Protection System By Using ArduinoBluetooth Based Fire Detection and Robust Protection System By Using Arduino
Bluetooth Based Fire Detection and Robust Protection System By Using ArduinoIRJET Journal
 
A Project Reports On SMOKE DETECTOR
A Project Reports On SMOKE DETECTORA Project Reports On SMOKE DETECTOR
A Project Reports On SMOKE DETECTORAnn Wera
 
Refrigeration brochure sept 2012 (2)
Refrigeration brochure sept 2012 (2)Refrigeration brochure sept 2012 (2)
Refrigeration brochure sept 2012 (2)a1-cbiss
 
Dräger X-am 1700 Portable Gas Detector - Spec Sheet
Dräger X-am 1700 Portable Gas Detector - Spec SheetDräger X-am 1700 Portable Gas Detector - Spec Sheet
Dräger X-am 1700 Portable Gas Detector - Spec SheetThorne & Derrick UK
 
ATIs-D1Ex-IR-Combustible-Gas-Transmitter-Product-Literature.pdf
ATIs-D1Ex-IR-Combustible-Gas-Transmitter-Product-Literature.pdfATIs-D1Ex-IR-Combustible-Gas-Transmitter-Product-Literature.pdf
ATIs-D1Ex-IR-Combustible-Gas-Transmitter-Product-Literature.pdfENVIMART
 
Drager Polytron IR CO2 Fixed Gas Detector - Spec Sheet
Drager Polytron IR CO2 Fixed Gas Detector - Spec SheetDrager Polytron IR CO2 Fixed Gas Detector - Spec Sheet
Drager Polytron IR CO2 Fixed Gas Detector - Spec SheetThorne & Derrick UK
 
Hệ thống quan trắc khí thải tự động - Tư vấn: 0938-564-123
Hệ thống quan trắc khí thải tự động - Tư vấn: 0938-564-123Hệ thống quan trắc khí thải tự động - Tư vấn: 0938-564-123
Hệ thống quan trắc khí thải tự động - Tư vấn: 0938-564-123Lâm Nguyễn Hoàng
 
Brosur Total Station Sokkia Cx series
Brosur Total Station Sokkia Cx seriesBrosur Total Station Sokkia Cx series
Brosur Total Station Sokkia Cx seriesRega Surveyor
 
Dräger X-am 5600 Portable Gas Detector - Spec Sheet
Dräger X-am 5600 Portable Gas Detector - Spec SheetDräger X-am 5600 Portable Gas Detector - Spec Sheet
Dräger X-am 5600 Portable Gas Detector - Spec SheetThorne & Derrick UK
 
GCEM4000 insitu gas analyser codel datasheet
GCEM4000 insitu gas analyser codel datasheetGCEM4000 insitu gas analyser codel datasheet
GCEM4000 insitu gas analyser codel datasheetENVIMART
 
SenseTek Stratos HSSD2 datasheet
SenseTek Stratos HSSD2 datasheetSenseTek Stratos HSSD2 datasheet
SenseTek Stratos HSSD2 datasheetHans Bronkhorst
 

Similar to ACD-V_11-2016 RCK (20)

GfG_G888_
GfG_G888_GfG_G888_
GfG_G888_
 
Edwards Signaling RB4U Data Sheet
Edwards Signaling RB4U Data SheetEdwards Signaling RB4U Data Sheet
Edwards Signaling RB4U Data Sheet
 
Sensepoint_Pro_pdf.pdf
Sensepoint_Pro_pdf.pdfSensepoint_Pro_pdf.pdf
Sensepoint_Pro_pdf.pdf
 
C 9103
C 9103C 9103
C 9103
 
Crowcon Detective+ Portable Gas Detector - Spec Sheet
Crowcon Detective+ Portable Gas Detector - Spec SheetCrowcon Detective+ Portable Gas Detector - Spec Sheet
Crowcon Detective+ Portable Gas Detector - Spec Sheet
 
fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm system
 
Bluetooth Based Fire Detection and Robust Protection System By Using Arduino
Bluetooth Based Fire Detection and Robust Protection System By Using ArduinoBluetooth Based Fire Detection and Robust Protection System By Using Arduino
Bluetooth Based Fire Detection and Robust Protection System By Using Arduino
 
A Project Reports On SMOKE DETECTOR
A Project Reports On SMOKE DETECTORA Project Reports On SMOKE DETECTOR
A Project Reports On SMOKE DETECTOR
 
Refrigeration brochure sept 2012 (2)
Refrigeration brochure sept 2012 (2)Refrigeration brochure sept 2012 (2)
Refrigeration brochure sept 2012 (2)
 
Co1224
Co1224Co1224
Co1224
 
Dräger X-am 1700 Portable Gas Detector - Spec Sheet
Dräger X-am 1700 Portable Gas Detector - Spec SheetDräger X-am 1700 Portable Gas Detector - Spec Sheet
Dräger X-am 1700 Portable Gas Detector - Spec Sheet
 
ATIs-D1Ex-IR-Combustible-Gas-Transmitter-Product-Literature.pdf
ATIs-D1Ex-IR-Combustible-Gas-Transmitter-Product-Literature.pdfATIs-D1Ex-IR-Combustible-Gas-Transmitter-Product-Literature.pdf
ATIs-D1Ex-IR-Combustible-Gas-Transmitter-Product-Literature.pdf
 
Drager Polytron IR CO2 Fixed Gas Detector - Spec Sheet
Drager Polytron IR CO2 Fixed Gas Detector - Spec SheetDrager Polytron IR CO2 Fixed Gas Detector - Spec Sheet
Drager Polytron IR CO2 Fixed Gas Detector - Spec Sheet
 
Hệ thống quan trắc khí thải tự động - Tư vấn: 0938-564-123
Hệ thống quan trắc khí thải tự động - Tư vấn: 0938-564-123Hệ thống quan trắc khí thải tự động - Tư vấn: 0938-564-123
Hệ thống quan trắc khí thải tự động - Tư vấn: 0938-564-123
 
Brosur Total Station Sokkia Cx series
Brosur Total Station Sokkia Cx seriesBrosur Total Station Sokkia Cx series
Brosur Total Station Sokkia Cx series
 
Dräger X-am 5600 Portable Gas Detector - Spec Sheet
Dräger X-am 5600 Portable Gas Detector - Spec SheetDräger X-am 5600 Portable Gas Detector - Spec Sheet
Dräger X-am 5600 Portable Gas Detector - Spec Sheet
 
In Situ Oxygen Transmitter For Combustion Monitoring
In Situ Oxygen Transmitter For Combustion MonitoringIn Situ Oxygen Transmitter For Combustion Monitoring
In Situ Oxygen Transmitter For Combustion Monitoring
 
GCEM4000 insitu gas analyser codel datasheet
GCEM4000 insitu gas analyser codel datasheetGCEM4000 insitu gas analyser codel datasheet
GCEM4000 insitu gas analyser codel datasheet
 
SenseTek Stratos HSSD2 datasheet
SenseTek Stratos HSSD2 datasheetSenseTek Stratos HSSD2 datasheet
SenseTek Stratos HSSD2 datasheet
 
Novasulf HG400 H2S analyser
Novasulf HG400 H2S analyserNovasulf HG400 H2S analyser
Novasulf HG400 H2S analyser
 

ACD-V_11-2016 RCK

  • 1. ACD-V CO, SMOKE, AND HEAT MULTI-SENSOR STANDARD FEATURES  Low profile - only 2.0” high, including base  Easy and reliable device addressing  Supports 16 operational modes  Automatic compensation for sensor contamination  Built-in fire test feature  Uses the noise-immune Digital Communication Protocol (DCP), which utilizes interrupts for fast response to fires  Two built-in power/alarm LEDs  Programmable non-polling LEDs  Non-directional smoke chamber  Vandal resistant security locking feature  Removable smoke labyrinth for cleaning or replacement  10 years CO sensor SPECIFICATIONS APPLICATIONS The Hochiki ACD-V CO, Smoke, and Heat Multi-Sensor is particularly suited for detecting smoke produced by the wide range of combustibles found in various applications. Tempera- ture monitoring is achieved by thermistors placed for optimum sensitivity. Also, the sensor is suited for detecting deadly lev- els of carbon monoxide (CO). Hochiki's unique design allows fast response to flaming/smoldering fires and carbon monox- ide levels while minimizing nuisance alarms. OPERATION To sense smoke, the ACD-V uses a light-emitting diode (LED) and photodiode compliment. The chamber is designed such that light emitted by the LED cannot normally reach the photodiode. In the event of fire, particles of smoke enter the chamber and scatter the light. As the smoke level increases, the scattering effect increases, causing more light to hit the photodiode. The chamber contains a unique design which allows smoke to enter the chamber while preventing external light from affecting the photodiode. The photodiode input level is sampled to sense smoke density. When the smoke density exceeds a preset threshold the sensor transmits an interrupt to the fire control panel indicating a fire condition. The fire alarm control panel can adjust the sensor threshold to com- pensate for contamination. The ACD-V heat portion incorporates a highly linear dual thermistor circuit. A specially designed cover protects the thermistors while allowing maximum air flow. The ACD-V supports both fixed-temperature and rate-of-rise sensing. The fire alarm control panel can adjust the sensor threshold for different environmental requirements. The ACD-V carbon monoxide (CO) sensing cell serves the dual purpose of supplementing smoke detection in combina- tion with the photodiode arrangement and monitoring color- less, odorless and deadly carbon monoxide levels for life safe- ty. When the carbon monoxide exceeds the poisonous levels, the sensor transmits an interrupt to the control panel indicat- ing a CO alarm. Up to 127 devices are permitted on each SLC loop. A sensor address can be set by a hand-held programming unit. The sensor mounts to a base and incorporates a locking mecha- nism for secure installation. The base provides mounting slots and terminals for field wiring. The sensor incorporates dual LEDs for easy viewing of sensor status. Hochiki America Corporation 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268 Phone: 714-522-2246 Fax: 714-522-2268 Technical Support: 800-845-6692 or technicalsupport@hochiki.com Find latest revision at www.hochiki.com F0210 11/2016 RCK Operating Voltage 17-41 VDC Standby Current 450μA Alarm Current 7.2mA Transmission Method DCP - Digital Communication Protocol Maximum Humidity 95% RH Non-Condensing UL Temperature Range 32°F to 120°F (0° C to 49° C) Operating Temperature 14°F to 122°F Range (-10°C to 50°C) Sensitivity Range 0.7-4.0%/FT@300FPM 0.7-3.86%/FT@2000FPM 0.7-2.65%/FT@4000FPM Air Velocity Range 0-4000 fpm Color & Case Material Bone - ABS Blend Weight 4.2oz (5.9 oz. with 4” base) Dimensions 3.9”D x 1.8”H Recommended Base ASBL Specifications subject to change without notice. Continued on back. S1383 PRODUCT LISTINGS California State Fire Marshal Pending Pending
  • 2. SENSOR SPACING Smoke sensor spacing shall be in compliance with NFPA 72. For smooth ceilings and in the absence of specific performance- based design criteria, the distance between smoke sensors shall not exceed a nominal spacing of 30 ft. (9.1m) or all points on the ceiling shall have a sensor within a distance equal to or less than 0.7 times the nominal 30 ft. (9.1m) spacing. Sensors shall be located within a distance of one-half the nominal spacing, measured at right angles from all walls or partitions extending upward to within the top 15 percent of the ceiling height. For additional instructions see NFPA 72. ENGINEERING SPECIFICATIONS The contractor shall furnish and install Hochiki's ACD-V (Multi-Criteria Sensor) as indicated on the plans. The Multi-Criteria Sensor head and twist lock base is UL Listed and it’s compatible with an UL Listed fire alarm control panel. The base permits direct interchange with the Hochiki ALG-V, ALK-V/ALK-V2, ALN-V photoelectric type smoke sensors, AIE-EA ionization type smoke sensor, ATG-EA, ATJ-EA heat sensors and the ACA-V, ACC-V multi-criteria sensor. The sensitivity of the sensor is capable of being measured by the control panel. The CO sensing element shall provide for 10 years of active usage. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature is optional and can be implemented when required. BASES The ACD-V supports the YBN-NSA-4, HSB-NSA-6, ASB, SCI-B4, SCI-B6 bases as well as the recommended ASBL base when used for life safety CO sensing. A common mounting base allows sensor interchange and maintains loop continuity when sen- sors are removed. A simple anti-tamper head locking system is provided which is enabled by removing a small plastic tab on the back of the sensor. Once locked, the head can be removed using a small diameter screwdriver. TYPICAL WIRING DIAGRAMS NOTE: Fire alarm control panel compatibility is required for DCP products. ACD-V are only compatible with the FireNET Plus Fire alarm control panel DCP communications protocol allows system compo-nents (DCP sensors AIE-EA, ALG-V, ACA-V, ACC-V, ALK-V, ALN-V, ATJ-EA, ATG-EA, ACD-V, bases and modules) to be used concurrently on a system's SLC (Signaling Line Circuit). Hochiki America Corporation ACD-V CO, SMOKE, AND HEAT MULTI-SENSOR Specifications subject to change without notice. ACD-V CO, SMOKE, AND HEAT MULTI-SENSOR