Application GuidesLinear Heat Detection
ALARMlINE
PAGE 1 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
PAGE 2 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Product Overview
Application GuidesLinear Heat Detection
ALARMlINE
Contents
Cable Trays and Racks
Conveyors
Car Parks
Floating Roof Tanks
Sphere and Fixed Roof Tanks
Warehouse Racking
Escalators and Travelators
Tunnels
Thatched Roofs
PAGE 3 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Kidde Alarmline Linear Heat Detection
(LHD) is a cable based system that provides
economical temperature monitoring at the
precise point of risk. The system is reliable,
flexible and has the ability to detect abnormal
temperature variances before it develops into
a fire situation. The comprehensive Alarmline
portfolio consists of both Analogue and
Digital systems, allowing a large range of both
commercial and industrial overheat and fire
risks to be protected, ranging from ambient
temperatures of -40ºC to + 200ºC.
Alarmline cable and its associated controllers
allow integration with many fire alarm and
extinguishing control systems offering a
complete system solution.
The use of ATEX approved junction boxes and
Intrinsically Safe barriers enable the Alarmline
system to be used in hazardous areas.
Linear Heat Detection
ALARMlINE Temperature monitoring
PAGE 4 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Analogue
Alarmline Analogue is a four core cable, which
senses temperature variations by continuously
monitoring the resistance of the specially
doped Negative Temperature Coefficient
(NTC) polymeric insulation. A change in the
temperature produces a relative change in
resistance which is monitored by a dedicated
Alarmline Analogue Controller.
Analogue cable is provided with a selection
of protective outer sheaths to suit various
applications:
Standard (K82017)
Standard protection
Nylon coated (K82021)
Chemical/environmental protection
Bronze braided (K82078)
Mechanical protection
Nylon + Stainless Steel braid (K98166)
Chemical/environmental and mechanical
protection
The Analogue controller (LHD4) provides the
facility to select the temperature at which the
Alarmline system will activate: using a simple
chart (Nomogram). The LWM-1 controller
additionally provides dual functionality to
operate as a fixed temperature heat detector
as well as detecting sudden increases in
temperature i.e. Rate of Rise.
Digital
Alarmline Digital is a twin conductor cable with
temperature sensitive insulation protecting
the inner conductors. Alarmline Digital
operates by melting the internal insulation at a
predetermined temperature, this results in the
conductors short circuiting which provides a
fire alarm signal. Fire and Fault conditions are
provided by continuously monitoring for a short
circuit (Fire) or an open circuit (Fault) state by the
fire alarm panel.
A range of five temperature cables are provided:
H8040N Alarm temperature 63-70ºC
H8045N Alarm temperature 79-95ºC
H8028 Alarm temperature 101-108ºC
H8069 Alarm temperature 177-189ºC
H9650 Alarm temperature 229-251ºC
The digital cables are protected by a range of
outer sheaths nylon, PVC or high temperature
chemical resistant Fluoropolymer to meet
specific application requirements.
Linear Heat Detection
ALARMlINE
PAGE 5 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
System design and installation
The design and installation of the Alarmline
system is unique to every site and application
therefore it is recommended that this work is
only undertaken by trained and competent
persons following the manufacturers guidelines.
How do I choose between Analogue and
Digital cable?
The choice of Alarmline system will depend on a
number of factors including but not limited to:
❚ Nature of the risk
❚ Maximum ambient temperature
❚ Risk of mechanical damage
❚ Chemical resistance
❚ Exposure to the elements
❚ Hazardous area requirements
❚ Interfacing requirements
The following simple questions can provide a
guide to selection:
❚ Is an adjustable alarm setting required on site?
❚ Does the system require detection of rapid
increases in temperature i.e. Rate of Rise
detection?
❚ Is periodic testing of the cables alarm
temperature required?
❚ Are specific system status indications required
local to the risk area?
❚ Do you require specific alarm and fault relay
outputs for each Alarmline detection zone?
❚ Does the application require mechanical
protection of the sensor cable?
If the answer to any of the above questions is yes
then the Alarmline Analogue system would be
the required option.
If the answer to the above questions is no then
an Alarmline Digital system could be considered.
Digital cable additional benefits
❚ Suitable for high and low ambient
temperatures
❚ Suitable for a high temperature alarm
applications: 240ºC
❚ High temperature Fluoropolymer option for
Chemical / UV radiation resistance.
❚ Simple interfacing to existing fire systems.
Temperature monitoring at the precise point of risk
PAGE 6 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Basic installation guidelines
❚ Unless specifically required to monitor surface
temperature, Alarmline should not be in
contact with any material which may act as a
heat sink
❚ Alarmline should be supported at a maximum
of every metre with suitable fixing clips to
prevent sagging in the sensor cable
❚ Neoprene sleeving must be used with metal
fixing clips to prevent the clip from acting as a
heatsink
❚ Alarmline must be supported either side of a
bend
Linear Heat Detection
ALARMlINE
Typical applications include:
❚ Cable trays
❚ Car parks
❚ Conveyors
❚ Escalators
❚ Floating roof tanks
❚ Sphere and fixed roof tanks
❚ Thatched roofs
❚ Tunnels
❚ Warehouse racking
Other typical applications not included in
this guide:
❚ Dust/dirty environments
❚ Pumps
❚ Silos
❚ Transformers
❚ Vehicle engines
For more information on these applications,
please contact Kidde AirSense directly.
PAGE 7 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
The main cause of fires in cable trays is due to
overheating cables caused by over voltage,
short circuit, etc. Cable trays generally consist
of a number of cables running side by side
tightly packed together. Development of a
fire in a single cable can very rapidly spread
to other cables due to the close proximity,
causing severe consequential losses.
Generally cable trays are located in restricted
spaces (service tunnels/vertical risers) making
access difficult and potentially leading to
undetected fire spread therefore early detection
of an overheat condition is necessary to prevent
a major disaster.
Alarmline is ideally suited to this type of
application as it can be installed very close to
the point of risk giving the earliest possible
detection of an overheat condition. Alarmline
is unaffected by the environmental conditions
which may cause false alarms with other
detection types i.e. dust, humidity etc.
Cable Trays and RacksLinear Heat Detection
ALARMlINE
PAGE 8 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Design and installation guidelines
Depending on the configuration of the cable trays or racks, i.e. whether it is
a single run or multiple levels of cable trays, it would generally be necessary
to split the cable trays into smaller detection zones making identification of
the overheat location easier. Zoning can be configured in relation to:
❚ Physical barriers
❚ Defined sections of cable tray or rack
❚ Existing extinguishing zones
The interface used for monitoring Alarmline may be located in the
detection zone or remotely, the latter requiring an interposing cable from
the interface to the detection zone, connected to Alarmline via a suitable
junction box and fire rated cable.
The width of the cable trays will be significant in determining the amount
of Alarmline required to provide the best detection. As a guideline:
❚ A single run of Alarmline will cover a cable tray <600mm wide
❚ Cable trays >600mm wide will require additional runs of Alarmline
Alarmline must be supported at a maximum of one meter spacing and
should be installed no more than 200mm above each cable tray/rack. This
provides maximum operating sensitivity without obstructing access to the
cables. A further run of Alarmline is recommended on the underside of the
bottom tray/rack to protect against any‘debris’fire.
ALARMLINE
‘V’CLIP
Cable Trays and RacksLinear Heat Detection
ALARMlINE
ALARMLINE
PAGE 9 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Conveyor fires are most commonly caused by
friction. This occurs when the roller bearings
used to move the conveyor belt seize and
the rubber conveyor belt rubs against the
seized bearing causing an overheat condition.
This overheat if not detected early can
cause ignition of the fuel being carried on
the conveyor, the conveyor belt and other
adjacent combustibles.
A fire generated by friction, which if allowed to
spread can cause severe damage to the belt, and
the housing containing the conveyor. Alarmline
can be used to provide point of risk detection to
give an early warning of an overheat condition.
Interfacing with other control equipment can
initiate conveyor shut downs and operation of
suppression systems to prevent the spread of
a fire.
Alarmline is particularly suitable as it can be
installed where high levels of dirt, dust, wind and
moisture exist and still be effective. The design
of the conveyor will determine which type of
ConveyorsLinear Heat Detection
ALARMlINE
PAGE 10 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
cable to use, as a minimum the cable will require
mechanical protection but where exposed
to the elements mechanical and chemical
protection would be required.
Design and installation guidelines
The recommended design is to install Alarmline
down each side of the conveyor clipped to the
roller supports to detect an overheat on the
bearings, with a further run under the bed plate
on each side to detect overheat fires caused by
the spillage of product from the conveyor belt.
If the conveyor is enclosed or covered then it
would be recommended to install Alarmline
above the conveyor belt to detect any fires
on a stationary conveyor belt. Other areas of
conveyors which should also be considered for
the use of Alarmline would be the drive motors
and oil filled gear boxes
It is recommended that the conveyors should
be spilt into zones, to limit search areas
and combine with any proposed sprinkler/
suppression systems. The interface used for
monitoring Alarmline may be located in the
detection zone or it may be installed remotely.
If the interface is to be located remotely an
interposing cable from the interface to the
detection zone is required, this is connected
to Alarmline using a suitable junction box and
should be a suitably fire rated cable.
ConveyorsLinear Heat Detection
ALARMlINE
ALARMLINE
BEARINGS
ALARMLINE
PAGE 11 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Multi-storey and underground car parks
have always been vulnerable to fire.
The combustible materials used in the
manufacture of modern passenger vehicles
results in fires that burn more intensely and
generate higher temperatures than ever
before with the opportunity for fire spread
significant. Detection systems in car parks are
often subjected to the elements and possibly
vandalism.
Alarmline is prevalent for this type of application
as it can be installed in environments where
wind, dust and moisture are present; which
can commonly lead to false alarms for other
detection types. Alarmline if installed correctly
is unaffected by temperature variations caused
by seasonal weather conditions and provides a
discrete form of detection.
Car ParksLinear Heat Detection
ALARMlINE
PAGE 12 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Design and installation guidelines
In this application, Alarmline provides area
protection as opposed to point of risk therefore
the design shall follow the guidelines for normal
point type heat detectors regarding maximum
spacing between cable runs and zone size. Due
to the flexibility of Alarmline, it can be run in any
location to provide the best coverage to ensure
all vehicles are adequately protected.
It is recommended in this application that nylon
coated Alarmline is used, which will provide
protection against the elements as well as
hydrocarbons from exhaust fumes.
The interface used for monitoring Alarmline
may be located in the detection zone or it may
be installed remotely. If the interface is to be
located remotely an interposing cable from the
interface to the detection zone is required, this is
connected to Alarmline using a suitable junction
box and should be a suitably fire rated cable.
Car ParksLinear Heat Detection
ALARMlINE
ALARMLINE
CONTROL INTERFACE UNIT
ALARMLINE
PAGE 13 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Floating roof tanks are most commonly used
for storing highly flammable products making
them a potential catastrophic fire risk. The
main risk of fire is from the ignition of vapour
escaping from a damaged/worn rim seal. It is
essential that fires are detected at the earliest
possible opportunity to prevent a widespread
fire and activate suitable fire suppression
systems.
With a range of high temperature chemical
resistance cable, Alarmline offers the most cost
effective and reliable method for rim seal fire
protection, it is easy to install close to the rim
seal. Installation of ATEX approved junction boxes
and intrinsically safe barriers/isolators between
Alarmline and the interface unit provides the
necessary protection for hazardous areas.
Design and installation guidelines
The design of each floating roof tank can differ
greatly dependent on the manufacturer therefore
Kidde recommends close liaison with the end
Floating Roof TanksLinear Heat Detection
ALARMlINE
PAGE 14 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
user/site owner during the installation and
design phases.
Where possible the recommendation would
be to use edge clips on the foam dam with
a distance piece to position the Alarmline
cable between the dam and the outer wall
of the tank close to the rim seal. Alarmline
should be supported every metre around the
circumference of the rim seal. A suitable ATEX
approved junction box will be provided on the
roof top for termination of Alarmline. To connect
Alarmline back to the control unit electrical
connections between the tank top and rim are
made using either an automatic cable reeler
or a cable collector with retractable cables to
accommodate the rise and fall of the tank roof.
The interface unit being used to monitor
Alarmline will be located in a non-hazardous
area and to maintain the safety of the system
Alarmline connections to the control unit will
be connected through suitable intrinsically safe
barriers/isolators.
Floating Roof TanksLinear Heat Detection
ALARMlINE
ALARMLINE
JUNCTION BOX
CABLE REELER
PAGE 15 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
The construction layout of tank farms often
results in tanks containing highly flammable
material that are in close proximity to each
other. This makes them a considerable fire risk
with a significant threat of a fire spreading
between tanks.
Alarmline can be installed on the tanks and in
close proximity to monitor the vents, flanges,
gauging points, manholes, and general bund
areas for fire. The system can be linked into a
main fire system to trigger activation of a deluge
water spray/foam system.
Sphere and Fixed Roof TanksLinear Heat Detection
ALARMlINE
PAGE 16 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Design and installation guidelines
The recommended installation of each tank will
vary based on the physical design but each tank
will generally be protected by one continuous
zone of Alarmline.
Alarmline will be terminated in a suitably
certified junction box with interposing fire
rated cabling and connected to the control
unit, located in a safe area. As the tanks will be
located in a hazardous area the cable should
be connected to the control unit via approved
intrinsically safe barriers/isolators.
The clips and fixings for Alarmline will depend
on the physical design of the tank but in most
cases these would need to be fixed to the
surface of the tank using a suitable adhesive.
Sphere and Fixed Roof TanksLinear Heat Detection
ALARMlINE
ALARMLINE ALARMLINE
JUNCTION BOX
JUNCTION BOX
PAGE 17 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Fires in densely packed racking can be
detected with a localised Alarmline detection
system. Alarmline can be installed within the
racking to provide detection very close to the
point of risk, providing a discrete detection
system which is unaffected by the normal
working environment.
Alarmline can be zoned within the racking and
is often used to trigger the pre-action stage of a
sprinkler system to ensure rapid detection and
control of the spread of fire.
Design and installation guidelines
The recommendation is to install Alarmline at
the ceiling and within the rack, fixing it to the
existing shelf supports in a position where it will
not be damaged when loading and unloading
the shelves.
The warehouse and racking can be split in to
zones to reduce the search area and to activate
the relevant sprinkler/suppression system.
Warehouse RackingLinear Heat Detection
ALARMlINE
PAGE 18 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
The interface used for monitoring Alarmline
may be located in the detection zone or it may
be installed remotely. If the interface is to be
located remotely an interposing cable from the
interface to the detection zone is required, this is
connected to Alarmline using a suitable junction
box and fire rated cable.
Freezer warehouses
Where a warehouse is used for cold storage and
operates at low temperatures Alarmline can be
used to provide general area protection. The
design follows the guidelines for point type heat
detectors or installed as‘in-rack’protection. The
following specialist recommendations should
be noted:
❚ Nylon coated cable should be used
❚ Minimum operating temperature:
Digital sensor -65°c
Analogue Sensor -40°C
❚ Minimum installation temperature -11°C
❚ Interface units must be installed in areas with
an ambient temperature above 0°C
Warehouse RackingLinear Heat Detection
ALARMlINE
ALARMLINE
ATTACHED TO CEILING
OR PERMANENTLY
FIXED SHELVING
PAGE 19 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Fires on escalators and travelators can
develop rapidly into a major fire and can
spread because of the continued mechanical
movement. The public nature of this
application means that it is crucial to have the
earliest possible detection system to initiate
emergency procedures.
Alarmline can be installed at the point of risk,
and can protect the following potential fire risks:
❚ Drive motors
❚ Roller bearings
❚ Truss rollers
❚ Dust collector trays
Due to the movement of mechanical parts
it would be recommended that Alarmline
should have mechanical protection; chemical
protection should also be considered due to the
presence of oil and grease.
Design and installation guidelines
Alarmline can be used to protect the roller
trusses and any other moving parts for risk
Escalators and TravelatorsLinear Heat Detection
ALARMlINE
PAGE 20 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
of overheat due to friction. Alarmline should
be installed on both sides of the escalator to
protect the rollers, and at the top and bottom of
the escalator to detect potential fires in the dust
collection trays.
Where necessary the escalator or travelator
can be split into smaller detection zones. If the
Alarmline system is to be used in conjunction
with a suppression system it may be necessary
to install two independent systems to provide
coincidence operation.
Care should be taken when attaching the
Alarmline to the roller bearings to ensure that it
is not damaged by the moving treads of the unit.
The interface used for monitoring Alarmline
may be located in the detection zone or it may
be installed remotely. If the interface is to be
located remotely an interposing cable from the
interface to the detection zone is required, this is
connected to Alarmline using a suitable junction
box and fire rated cable.
ALARMLINE
MOTOR / BEARING
CONTROL INTERFACE UNIT
Escalators and TravelatorsLinear Heat Detection
ALARMlINE
PAGE 21 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Tunnels pose a challenging fire threat due
to their confined structure. Tunnels primarily
offer limited access/egress points, making it
crucial that fires are detected at the earliest
opportunity to enable evacuation and
extinguishing of the fire.
Alarmline detection offers a cost effective
solution that can provide protection for all the
different facets of the tunnel system, with design
capabilities to be compatible with the other
tunnel operating systems.
There are many different potential hazards
within the tunnel environment such as electrical
services, motor vehicle accidents, vehicle load
fires, vehicle fires, fuel fires, etc.
Design and installation guidelines
Specific electrical risks can be protected by
installing Alarmline at the point of risk. The
biggest risk is vehicle fires which can cause
significant problems including intense heat
and thick black toxic smoke making access and
egress difficult.
TunnelsLinear Heat Detection
ALARMlINE
PAGE 22 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
To detect vehicle or fuel fires we would provide
a general area type protection with Alarmline
installed directly over the roadways inside the
tunnel. Alarmline can be split into separate
zones depending on the width and length of
the tunnel. Detection zones could be linked to
suppression systems for localised fire fighting or
ventilation zones to activate extraction systems.
Alarmline can also be used to detect fires in
sumps and drains designed for containment
of fuel or oil spills. These systems can be linked
to a foam suppression system to provide
extinguishing of any fire.
Due to the environmental conditions Alarmline
installed within tunnels should have a nylon
coating.
The interface used for monitoring Alarmline
may be located in the detection zone or it may
be installed remotely. If the interface is to be
located remotely an interposing cable from the
interface to the detection zone is required, this is
connected to Alarmline using a suitable junction
box and should be a suitably fire rated cable
where possible.
TunnelsLinear Heat Detection
ALARMlINE
ALARMLINE
ALARMLINE
PAGE 23 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Thatched roof fires are becoming more
common with the main cause (approximately
90 per cent) being linked to poorly maintained
chimneys.
Fires are due to either hot spots within the
chimney caused by build up of soot and debris
or by cracks in the chimney brickwork causing
hot gases to escape into the thatch layer. This
causes the temperature to rise within the
thatched layer where it eventually reaches a
point of ignition. Thatch layers can be quite
thick which means a fire can be well established
before it is noticed and the fire service
summoned.
Early detection of these increases in temperature
is critical to minimise the amount of damage
that can be caused by a thatched roof fire.
Alarmline Digital cable has been independently
tested and approved for use in this application
by the National Society of Master Thatchers.
Thatched RoofsLinear Heat Detection
ALARMlINE
PAGE 24 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
Design and installation guidelines
To protect against fires caused by heat transfer
from the chimney, Alarmline can be installed
discreetly between the thatch layer and
the brickwork of the chimney to detect any
increases in temperature through the chimney
wall. As Alarmline is a continuous sensor it can
be installed around the chimney stack providing
large area coverage. Installation of two different
temperature cables can provide indication of
a pre-alarm condition followed by an alarm
condition.
It is also possible to install Digital Alarmline
within the thatch itself threading the Alarmline
through the thatch layer at a regular spacing to
detect fires caused by other ignition sources.
Shakespeare’s Globe theatre is one of many
properties which is fitted with such a system.
Digital Alarmline can also be used to provide
detection within the roof space, underneath
the thatch layer the cable can be fixed to the
existing roof struts at regular intervals to provide
Thatched RoofsLinear Heat Detection
ALARMlINE
general area coverage. Alarmline will not be
susceptible to false alarms caused by high levels
of dust typically found in these environments.
Alarmline is compatible with any conventional
fire alarm panel which can be located at a
suitable point within the property to provide
audible and visual warning indications.
Kidde recommend that these systems are only
installed by engineers who are approved to work
in listed and thatched properties.
ALARMLINE
JUNCTION BOX
Kidde AirSense
Thame Park Road, Thame, Oxfordshire OX9 3RT, UK
Tel: +44 (0)1844 265003
Fax: +44 (0)1844 265156
Email: general.enquiries@kiddeuk.co.uk
Web: www.kfp.co.uk
Linear Heat Detection
ALARMlINE
PAGE 25 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE

More Related Content

What's hot

SenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishSenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishHans Bronkhorst
 
System Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data SheetSystem Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data SheetJMAC Supply
 
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...Thorne & Derrick International
 
Kidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NLKidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NLHans Bronkhorst
 
Drager Polytron IR CO2 Fixed Gas Detector - Spec Sheet
Drager Polytron IR CO2 Fixed Gas Detector - Spec SheetDrager Polytron IR CO2 Fixed Gas Detector - Spec Sheet
Drager Polytron IR CO2 Fixed Gas Detector - Spec SheetThorne & Derrick UK
 
Marechal SPeX ATEX Plug & Socket Power Connector - Zones 1, 2 21, 22
Marechal SPeX ATEX Plug & Socket Power Connector - Zones 1, 2 21, 22Marechal SPeX ATEX Plug & Socket Power Connector - Zones 1, 2 21, 22
Marechal SPeX ATEX Plug & Socket Power Connector - Zones 1, 2 21, 22Thorne & Derrick International
 
DEA Security corporate presentation
DEA Security corporate presentationDEA Security corporate presentation
DEA Security corporate presentationDEA Security Srl
 
Andel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
Andel – Leak Detection Cables, Panels, Sensors & Systems - BrochureAndel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
Andel – Leak Detection Cables, Panels, Sensors & Systems - BrochureThorne & Derrick UK
 
Drager Polytron 5310 Fixed Gas Detector - Spec Sheet
Drager Polytron 5310 Fixed Gas Detector - Spec SheetDrager Polytron 5310 Fixed Gas Detector - Spec Sheet
Drager Polytron 5310 Fixed Gas Detector - Spec SheetThorne & Derrick UK
 
Defender 1 0 consumer units
Defender 1 0 consumer unitsDefender 1 0 consumer units
Defender 1 0 consumer unitsContactum
 
Bussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueBussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueThorne & Derrick International
 
Explosion Proof Cable Glands - Prysmian Barrier Glands (424TP) for Lead Sheat...
Explosion Proof Cable Glands - Prysmian Barrier Glands (424TP) for Lead Sheat...Explosion Proof Cable Glands - Prysmian Barrier Glands (424TP) for Lead Sheat...
Explosion Proof Cable Glands - Prysmian Barrier Glands (424TP) for Lead Sheat...Thorne & Derrick International
 
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Thorne & Derrick International
 

What's hot (20)

ACD-V_11-2016 RCK
ACD-V_11-2016 RCKACD-V_11-2016 RCK
ACD-V_11-2016 RCK
 
SenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishSenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet english
 
System Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data SheetSystem Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data Sheet
 
Thermon BSX Self-Regulating Heating Cable
Thermon BSX Self-Regulating Heating CableThermon BSX Self-Regulating Heating Cable
Thermon BSX Self-Regulating Heating Cable
 
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
 
Kidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NLKidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NL
 
Exloc is hj
Exloc is hjExloc is hj
Exloc is hj
 
Drager Polytron IR CO2 Fixed Gas Detector - Spec Sheet
Drager Polytron IR CO2 Fixed Gas Detector - Spec SheetDrager Polytron IR CO2 Fixed Gas Detector - Spec Sheet
Drager Polytron IR CO2 Fixed Gas Detector - Spec Sheet
 
RIVPF_GB_LOCAL
RIVPF_GB_LOCALRIVPF_GB_LOCAL
RIVPF_GB_LOCAL
 
Marechal SPeX ATEX Plug & Socket Power Connector - Zones 1, 2 21, 22
Marechal SPeX ATEX Plug & Socket Power Connector - Zones 1, 2 21, 22Marechal SPeX ATEX Plug & Socket Power Connector - Zones 1, 2 21, 22
Marechal SPeX ATEX Plug & Socket Power Connector - Zones 1, 2 21, 22
 
Dnr
DnrDnr
Dnr
 
Zirconia o2 sensors
Zirconia o2 sensors Zirconia o2 sensors
Zirconia o2 sensors
 
DEA Security corporate presentation
DEA Security corporate presentationDEA Security corporate presentation
DEA Security corporate presentation
 
Andel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
Andel – Leak Detection Cables, Panels, Sensors & Systems - BrochureAndel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
Andel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
 
Drager Polytron 5310 Fixed Gas Detector - Spec Sheet
Drager Polytron 5310 Fixed Gas Detector - Spec SheetDrager Polytron 5310 Fixed Gas Detector - Spec Sheet
Drager Polytron 5310 Fixed Gas Detector - Spec Sheet
 
Defender 1 0 consumer units
Defender 1 0 consumer unitsDefender 1 0 consumer units
Defender 1 0 consumer units
 
Bussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueBussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices Catalogue
 
Explosion Proof Cable Glands - Prysmian Barrier Glands (424TP) for Lead Sheat...
Explosion Proof Cable Glands - Prysmian Barrier Glands (424TP) for Lead Sheat...Explosion Proof Cable Glands - Prysmian Barrier Glands (424TP) for Lead Sheat...
Explosion Proof Cable Glands - Prysmian Barrier Glands (424TP) for Lead Sheat...
 
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
 
A te x wall chart
A te x wall chartA te x wall chart
A te x wall chart
 

Similar to Alarmline application guides

Bandweaver SenseTek conveyor-belt-case-study Lineair Heat Detection
Bandweaver SenseTek conveyor-belt-case-study Lineair Heat DetectionBandweaver SenseTek conveyor-belt-case-study Lineair Heat Detection
Bandweaver SenseTek conveyor-belt-case-study Lineair Heat DetectionHans Bronkhorst
 
Mercer Street Technology - Fire Brochure
Mercer Street Technology - Fire BrochureMercer Street Technology - Fire Brochure
Mercer Street Technology - Fire BrochureAlex Marshall
 
Murco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data SheetMurco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data SheetThorne & Derrick UK
 
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dts
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dtsSenseTek Bandweaver Road Tunnels Linear Heat Detection-dts
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dtsHans Bronkhorst
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Shubham .
 
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptxFIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptxNeerajTiwari965955
 
HR: Safety solutions
HR: Safety solutionsHR: Safety solutions
HR: Safety solutionsClaitec
 
SenseTek Bandweaver Escalator fire-detection-dts
SenseTek Bandweaver Escalator fire-detection-dtsSenseTek Bandweaver Escalator fire-detection-dts
SenseTek Bandweaver Escalator fire-detection-dtsHans Bronkhorst
 
Sugar, grain and milling measurement and inventory control solutions
Sugar, grain and milling measurement and inventory control solutionsSugar, grain and milling measurement and inventory control solutions
Sugar, grain and milling measurement and inventory control solutionsola wesstrom
 
Bandweaver case study_SenseTek EN54-22
Bandweaver case study_SenseTek EN54-22Bandweaver case study_SenseTek EN54-22
Bandweaver case study_SenseTek EN54-22Hans Bronkhorst
 
fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm systemsingh1515
 
Burglar alarm basics-8
Burglar alarm basics-8Burglar alarm basics-8
Burglar alarm basics-8grantlerc
 
Safety technology – Sensors and system solutions from ifm 2016 English
Safety technology – Sensors and system solutions from ifm 2016 EnglishSafety technology – Sensors and system solutions from ifm 2016 English
Safety technology – Sensors and system solutions from ifm 2016 Englishifm electronic gmbh
 
Cc1608 fire systems design guide
Cc1608 fire systems design guideCc1608 fire systems design guide
Cc1608 fire systems design guide1234marvin
 
LLS4 Fuel Level Sensor
LLS4 Fuel Level SensorLLS4 Fuel Level Sensor
LLS4 Fuel Level SensorDmitry Ilyin
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfnipunwijewardhana
 
SenseTek Bandweaver Brochure Branddetectie
SenseTek Bandweaver Brochure BranddetectieSenseTek Bandweaver Brochure Branddetectie
SenseTek Bandweaver Brochure BranddetectieHans Bronkhorst
 

Similar to Alarmline application guides (20)

Bandweaver SenseTek conveyor-belt-case-study Lineair Heat Detection
Bandweaver SenseTek conveyor-belt-case-study Lineair Heat DetectionBandweaver SenseTek conveyor-belt-case-study Lineair Heat Detection
Bandweaver SenseTek conveyor-belt-case-study Lineair Heat Detection
 
Mercer Street Technology - Fire Brochure
Mercer Street Technology - Fire BrochureMercer Street Technology - Fire Brochure
Mercer Street Technology - Fire Brochure
 
Murco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data SheetMurco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data Sheet
 
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dts
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dtsSenseTek Bandweaver Road Tunnels Linear Heat Detection-dts
SenseTek Bandweaver Road Tunnels Linear Heat Detection-dts
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?
 
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptxFIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
 
HR: Safety solutions
HR: Safety solutionsHR: Safety solutions
HR: Safety solutions
 
SenseTek Bandweaver Escalator fire-detection-dts
SenseTek Bandweaver Escalator fire-detection-dtsSenseTek Bandweaver Escalator fire-detection-dts
SenseTek Bandweaver Escalator fire-detection-dts
 
Sugar, grain and milling measurement and inventory control solutions
Sugar, grain and milling measurement and inventory control solutionsSugar, grain and milling measurement and inventory control solutions
Sugar, grain and milling measurement and inventory control solutions
 
Bandweaver case study_SenseTek EN54-22
Bandweaver case study_SenseTek EN54-22Bandweaver case study_SenseTek EN54-22
Bandweaver case study_SenseTek EN54-22
 
fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm system
 
Burglar alarm basics-8
Burglar alarm basics-8Burglar alarm basics-8
Burglar alarm basics-8
 
Safety technology – Sensors and system solutions from ifm 2016 English
Safety technology – Sensors and system solutions from ifm 2016 EnglishSafety technology – Sensors and system solutions from ifm 2016 English
Safety technology – Sensors and system solutions from ifm 2016 English
 
CINT alarm systems
CINT alarm systemsCINT alarm systems
CINT alarm systems
 
Cc1608 fire systems design guide
Cc1608 fire systems design guideCc1608 fire systems design guide
Cc1608 fire systems design guide
 
Systems for mobile machines
Systems for mobile machinesSystems for mobile machines
Systems for mobile machines
 
LLS4 Fuel Level Sensor
LLS4 Fuel Level SensorLLS4 Fuel Level Sensor
LLS4 Fuel Level Sensor
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
 
SenseTek Bandweaver Brochure Branddetectie
SenseTek Bandweaver Brochure BranddetectieSenseTek Bandweaver Brochure Branddetectie
SenseTek Bandweaver Brochure Branddetectie
 
BRAND FACTORY - SURAT
BRAND FACTORY - SURATBRAND FACTORY - SURAT
BRAND FACTORY - SURAT
 

More from Hans Bronkhorst

Testifire_XTR2_Brochure.pdf
Testifire_XTR2_Brochure.pdfTestifire_XTR2_Brochure.pdf
Testifire_XTR2_Brochure.pdfHans Bronkhorst
 
Testifire_XTR2_Brochure.pdf
Testifire_XTR2_Brochure.pdfTestifire_XTR2_Brochure.pdf
Testifire_XTR2_Brochure.pdfHans Bronkhorst
 
DetectorTesters Testifire XTR2
DetectorTesters Testifire XTR2DetectorTesters Testifire XTR2
DetectorTesters Testifire XTR2Hans Bronkhorst
 
Hoe werkt DTS Glasvezel temperatuurmeting
Hoe werkt DTS Glasvezel temperatuurmetingHoe werkt DTS Glasvezel temperatuurmeting
Hoe werkt DTS Glasvezel temperatuurmetingHans Bronkhorst
 
Glasvezel_branddetectie Datasheet.pdf
Glasvezel_branddetectie Datasheet.pdfGlasvezel_branddetectie Datasheet.pdf
Glasvezel_branddetectie Datasheet.pdfHans Bronkhorst
 
Zonnepalen beveiligen met glasvezelkabel .pdf
Zonnepalen beveiligen met glasvezelkabel .pdfZonnepalen beveiligen met glasvezelkabel .pdf
Zonnepalen beveiligen met glasvezelkabel .pdfHans Bronkhorst
 
Bandweaver_Glasvezel loodsen en pakhuizen LHD.pdf
Bandweaver_Glasvezel loodsen en pakhuizen LHD.pdfBandweaver_Glasvezel loodsen en pakhuizen LHD.pdf
Bandweaver_Glasvezel loodsen en pakhuizen LHD.pdfHans Bronkhorst
 
Bandweaver_FireLaser_glasvezel detectie.pdf
Bandweaver_FireLaser_glasvezel detectie.pdfBandweaver_FireLaser_glasvezel detectie.pdf
Bandweaver_FireLaser_glasvezel detectie.pdfHans Bronkhorst
 
Catalogus Prijslijst 2023 SenseTek.pdf
Catalogus Prijslijst 2023 SenseTek.pdfCatalogus Prijslijst 2023 SenseTek.pdf
Catalogus Prijslijst 2023 SenseTek.pdfHans Bronkhorst
 
SenseTek_Firelaser_Bandweaver_Application-Tunnels-LHD
SenseTek_Firelaser_Bandweaver_Application-Tunnels-LHDSenseTek_Firelaser_Bandweaver_Application-Tunnels-LHD
SenseTek_Firelaser_Bandweaver_Application-Tunnels-LHDHans Bronkhorst
 
SenseTek FireLaser handboek.pdf
SenseTek FireLaser handboek.pdfSenseTek FireLaser handboek.pdf
SenseTek FireLaser handboek.pdfHans Bronkhorst
 
SenseTek DetectorTesters Testifire actie
SenseTek DetectorTesters Testifire actieSenseTek DetectorTesters Testifire actie
SenseTek DetectorTesters Testifire actieHans Bronkhorst
 
SenseTek DTS Distributed Temperature Sensing Bandweaver EN54-22
SenseTek DTS Distributed Temperature Sensing Bandweaver EN54-22SenseTek DTS Distributed Temperature Sensing Bandweaver EN54-22
SenseTek DTS Distributed Temperature Sensing Bandweaver EN54-22Hans Bronkhorst
 
FireFiber TT-Datasheet- SenseTek glasvezelkabel brandbeveiliging
FireFiber TT-Datasheet- SenseTek glasvezelkabel brandbeveiligingFireFiber TT-Datasheet- SenseTek glasvezelkabel brandbeveiliging
FireFiber TT-Datasheet- SenseTek glasvezelkabel brandbeveiligingHans Bronkhorst
 
Firelaser-datasheet-SenseTek Glasvezel detectie
Firelaser-datasheet-SenseTek  Glasvezel detectieFirelaser-datasheet-SenseTek  Glasvezel detectie
Firelaser-datasheet-SenseTek Glasvezel detectieHans Bronkhorst
 
Listec Cbo5 EX versie aansluitbox
Listec Cbo5 EX versie aansluitboxListec Cbo5 EX versie aansluitbox
Listec Cbo5 EX versie aansluitboxHans Bronkhorst
 
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-data
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-dataD List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-data
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-dataHans Bronkhorst
 
SenseTek Stratos Modulaser Handboek
SenseTek Stratos Modulaser HandboekSenseTek Stratos Modulaser Handboek
SenseTek Stratos Modulaser HandboekHans Bronkhorst
 
Smoke Sabre Testgas SenseTek
Smoke Sabre Testgas SenseTekSmoke Sabre Testgas SenseTek
Smoke Sabre Testgas SenseTekHans Bronkhorst
 

More from Hans Bronkhorst (20)

Testifire_XTR2_Brochure.pdf
Testifire_XTR2_Brochure.pdfTestifire_XTR2_Brochure.pdf
Testifire_XTR2_Brochure.pdf
 
Testifire_XTR2_Brochure.pdf
Testifire_XTR2_Brochure.pdfTestifire_XTR2_Brochure.pdf
Testifire_XTR2_Brochure.pdf
 
DetectorTesters Testifire XTR2
DetectorTesters Testifire XTR2DetectorTesters Testifire XTR2
DetectorTesters Testifire XTR2
 
Hoe werkt DTS Glasvezel temperatuurmeting
Hoe werkt DTS Glasvezel temperatuurmetingHoe werkt DTS Glasvezel temperatuurmeting
Hoe werkt DTS Glasvezel temperatuurmeting
 
Glasvezel_branddetectie Datasheet.pdf
Glasvezel_branddetectie Datasheet.pdfGlasvezel_branddetectie Datasheet.pdf
Glasvezel_branddetectie Datasheet.pdf
 
Zonnepalen beveiligen met glasvezelkabel .pdf
Zonnepalen beveiligen met glasvezelkabel .pdfZonnepalen beveiligen met glasvezelkabel .pdf
Zonnepalen beveiligen met glasvezelkabel .pdf
 
Bandweaver_Glasvezel loodsen en pakhuizen LHD.pdf
Bandweaver_Glasvezel loodsen en pakhuizen LHD.pdfBandweaver_Glasvezel loodsen en pakhuizen LHD.pdf
Bandweaver_Glasvezel loodsen en pakhuizen LHD.pdf
 
Bandweaver_FireLaser_glasvezel detectie.pdf
Bandweaver_FireLaser_glasvezel detectie.pdfBandweaver_FireLaser_glasvezel detectie.pdf
Bandweaver_FireLaser_glasvezel detectie.pdf
 
Catalogus Prijslijst 2023 SenseTek.pdf
Catalogus Prijslijst 2023 SenseTek.pdfCatalogus Prijslijst 2023 SenseTek.pdf
Catalogus Prijslijst 2023 SenseTek.pdf
 
SenseTek_Firelaser_Bandweaver_Application-Tunnels-LHD
SenseTek_Firelaser_Bandweaver_Application-Tunnels-LHDSenseTek_Firelaser_Bandweaver_Application-Tunnels-LHD
SenseTek_Firelaser_Bandweaver_Application-Tunnels-LHD
 
Thermische detectie
Thermische detectieThermische detectie
Thermische detectie
 
SenseTek FireLaser handboek.pdf
SenseTek FireLaser handboek.pdfSenseTek FireLaser handboek.pdf
SenseTek FireLaser handboek.pdf
 
SenseTek DetectorTesters Testifire actie
SenseTek DetectorTesters Testifire actieSenseTek DetectorTesters Testifire actie
SenseTek DetectorTesters Testifire actie
 
SenseTek DTS Distributed Temperature Sensing Bandweaver EN54-22
SenseTek DTS Distributed Temperature Sensing Bandweaver EN54-22SenseTek DTS Distributed Temperature Sensing Bandweaver EN54-22
SenseTek DTS Distributed Temperature Sensing Bandweaver EN54-22
 
FireFiber TT-Datasheet- SenseTek glasvezelkabel brandbeveiliging
FireFiber TT-Datasheet- SenseTek glasvezelkabel brandbeveiligingFireFiber TT-Datasheet- SenseTek glasvezelkabel brandbeveiliging
FireFiber TT-Datasheet- SenseTek glasvezelkabel brandbeveiliging
 
Firelaser-datasheet-SenseTek Glasvezel detectie
Firelaser-datasheet-SenseTek  Glasvezel detectieFirelaser-datasheet-SenseTek  Glasvezel detectie
Firelaser-datasheet-SenseTek Glasvezel detectie
 
Listec Cbo5 EX versie aansluitbox
Listec Cbo5 EX versie aansluitboxListec Cbo5 EX versie aansluitbox
Listec Cbo5 EX versie aansluitbox
 
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-data
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-dataD List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-data
D List 835-SEC-15-Sensor-Control-Unit-d-listcontroller-technical-data
 
SenseTek Stratos Modulaser Handboek
SenseTek Stratos Modulaser HandboekSenseTek Stratos Modulaser Handboek
SenseTek Stratos Modulaser Handboek
 
Smoke Sabre Testgas SenseTek
Smoke Sabre Testgas SenseTekSmoke Sabre Testgas SenseTek
Smoke Sabre Testgas SenseTek
 

Recently uploaded

Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Miguel Araújo
 
Automating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps ScriptAutomating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps Scriptwesley chun
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfEnterprise Knowledge
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking MenDelhi Call girls
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Enterprise Knowledge
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesSinan KOZAK
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Igalia
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024The Digital Insurer
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreternaman860154
 
Slack Application Development 101 Slides
Slack Application Development 101 SlidesSlack Application Development 101 Slides
Slack Application Development 101 Slidespraypatel2
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdfhans926745
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)Gabriella Davis
 
Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101Paola De la Torre
 
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxFactors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxKatpro Technologies
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationMichael W. Hawkins
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking MenDelhi Call girls
 
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure serviceWhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure servicePooja Nehwal
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptxHampshireHUG
 
Top 5 Benefits OF Using Muvi Live Paywall For Live Streams
Top 5 Benefits OF Using Muvi Live Paywall For Live StreamsTop 5 Benefits OF Using Muvi Live Paywall For Live Streams
Top 5 Benefits OF Using Muvi Live Paywall For Live StreamsRoshan Dwivedi
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024Results
 

Recently uploaded (20)

Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
Automating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps ScriptAutomating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps Script
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen Frames
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreter
 
Slack Application Development 101 Slides
Slack Application Development 101 SlidesSlack Application Development 101 Slides
Slack Application Development 101 Slides
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101
 
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxFactors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
 
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure serviceWhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
 
Top 5 Benefits OF Using Muvi Live Paywall For Live Streams
Top 5 Benefits OF Using Muvi Live Paywall For Live StreamsTop 5 Benefits OF Using Muvi Live Paywall For Live Streams
Top 5 Benefits OF Using Muvi Live Paywall For Live Streams
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024
 

Alarmline application guides

  • 1. Application GuidesLinear Heat Detection ALARMlINE PAGE 1 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE
  • 2. PAGE 2 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Product Overview Application GuidesLinear Heat Detection ALARMlINE Contents Cable Trays and Racks Conveyors Car Parks Floating Roof Tanks Sphere and Fixed Roof Tanks Warehouse Racking Escalators and Travelators Tunnels Thatched Roofs
  • 3. PAGE 3 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Kidde Alarmline Linear Heat Detection (LHD) is a cable based system that provides economical temperature monitoring at the precise point of risk. The system is reliable, flexible and has the ability to detect abnormal temperature variances before it develops into a fire situation. The comprehensive Alarmline portfolio consists of both Analogue and Digital systems, allowing a large range of both commercial and industrial overheat and fire risks to be protected, ranging from ambient temperatures of -40ºC to + 200ºC. Alarmline cable and its associated controllers allow integration with many fire alarm and extinguishing control systems offering a complete system solution. The use of ATEX approved junction boxes and Intrinsically Safe barriers enable the Alarmline system to be used in hazardous areas. Linear Heat Detection ALARMlINE Temperature monitoring
  • 4. PAGE 4 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Analogue Alarmline Analogue is a four core cable, which senses temperature variations by continuously monitoring the resistance of the specially doped Negative Temperature Coefficient (NTC) polymeric insulation. A change in the temperature produces a relative change in resistance which is monitored by a dedicated Alarmline Analogue Controller. Analogue cable is provided with a selection of protective outer sheaths to suit various applications: Standard (K82017) Standard protection Nylon coated (K82021) Chemical/environmental protection Bronze braided (K82078) Mechanical protection Nylon + Stainless Steel braid (K98166) Chemical/environmental and mechanical protection The Analogue controller (LHD4) provides the facility to select the temperature at which the Alarmline system will activate: using a simple chart (Nomogram). The LWM-1 controller additionally provides dual functionality to operate as a fixed temperature heat detector as well as detecting sudden increases in temperature i.e. Rate of Rise. Digital Alarmline Digital is a twin conductor cable with temperature sensitive insulation protecting the inner conductors. Alarmline Digital operates by melting the internal insulation at a predetermined temperature, this results in the conductors short circuiting which provides a fire alarm signal. Fire and Fault conditions are provided by continuously monitoring for a short circuit (Fire) or an open circuit (Fault) state by the fire alarm panel. A range of five temperature cables are provided: H8040N Alarm temperature 63-70ºC H8045N Alarm temperature 79-95ºC H8028 Alarm temperature 101-108ºC H8069 Alarm temperature 177-189ºC H9650 Alarm temperature 229-251ºC The digital cables are protected by a range of outer sheaths nylon, PVC or high temperature chemical resistant Fluoropolymer to meet specific application requirements. Linear Heat Detection ALARMlINE
  • 5. PAGE 5 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE System design and installation The design and installation of the Alarmline system is unique to every site and application therefore it is recommended that this work is only undertaken by trained and competent persons following the manufacturers guidelines. How do I choose between Analogue and Digital cable? The choice of Alarmline system will depend on a number of factors including but not limited to: ❚ Nature of the risk ❚ Maximum ambient temperature ❚ Risk of mechanical damage ❚ Chemical resistance ❚ Exposure to the elements ❚ Hazardous area requirements ❚ Interfacing requirements The following simple questions can provide a guide to selection: ❚ Is an adjustable alarm setting required on site? ❚ Does the system require detection of rapid increases in temperature i.e. Rate of Rise detection? ❚ Is periodic testing of the cables alarm temperature required? ❚ Are specific system status indications required local to the risk area? ❚ Do you require specific alarm and fault relay outputs for each Alarmline detection zone? ❚ Does the application require mechanical protection of the sensor cable? If the answer to any of the above questions is yes then the Alarmline Analogue system would be the required option. If the answer to the above questions is no then an Alarmline Digital system could be considered. Digital cable additional benefits ❚ Suitable for high and low ambient temperatures ❚ Suitable for a high temperature alarm applications: 240ºC ❚ High temperature Fluoropolymer option for Chemical / UV radiation resistance. ❚ Simple interfacing to existing fire systems. Temperature monitoring at the precise point of risk
  • 6. PAGE 6 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Basic installation guidelines ❚ Unless specifically required to monitor surface temperature, Alarmline should not be in contact with any material which may act as a heat sink ❚ Alarmline should be supported at a maximum of every metre with suitable fixing clips to prevent sagging in the sensor cable ❚ Neoprene sleeving must be used with metal fixing clips to prevent the clip from acting as a heatsink ❚ Alarmline must be supported either side of a bend Linear Heat Detection ALARMlINE Typical applications include: ❚ Cable trays ❚ Car parks ❚ Conveyors ❚ Escalators ❚ Floating roof tanks ❚ Sphere and fixed roof tanks ❚ Thatched roofs ❚ Tunnels ❚ Warehouse racking Other typical applications not included in this guide: ❚ Dust/dirty environments ❚ Pumps ❚ Silos ❚ Transformers ❚ Vehicle engines For more information on these applications, please contact Kidde AirSense directly.
  • 7. PAGE 7 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE The main cause of fires in cable trays is due to overheating cables caused by over voltage, short circuit, etc. Cable trays generally consist of a number of cables running side by side tightly packed together. Development of a fire in a single cable can very rapidly spread to other cables due to the close proximity, causing severe consequential losses. Generally cable trays are located in restricted spaces (service tunnels/vertical risers) making access difficult and potentially leading to undetected fire spread therefore early detection of an overheat condition is necessary to prevent a major disaster. Alarmline is ideally suited to this type of application as it can be installed very close to the point of risk giving the earliest possible detection of an overheat condition. Alarmline is unaffected by the environmental conditions which may cause false alarms with other detection types i.e. dust, humidity etc. Cable Trays and RacksLinear Heat Detection ALARMlINE
  • 8. PAGE 8 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Design and installation guidelines Depending on the configuration of the cable trays or racks, i.e. whether it is a single run or multiple levels of cable trays, it would generally be necessary to split the cable trays into smaller detection zones making identification of the overheat location easier. Zoning can be configured in relation to: ❚ Physical barriers ❚ Defined sections of cable tray or rack ❚ Existing extinguishing zones The interface used for monitoring Alarmline may be located in the detection zone or remotely, the latter requiring an interposing cable from the interface to the detection zone, connected to Alarmline via a suitable junction box and fire rated cable. The width of the cable trays will be significant in determining the amount of Alarmline required to provide the best detection. As a guideline: ❚ A single run of Alarmline will cover a cable tray <600mm wide ❚ Cable trays >600mm wide will require additional runs of Alarmline Alarmline must be supported at a maximum of one meter spacing and should be installed no more than 200mm above each cable tray/rack. This provides maximum operating sensitivity without obstructing access to the cables. A further run of Alarmline is recommended on the underside of the bottom tray/rack to protect against any‘debris’fire. ALARMLINE ‘V’CLIP Cable Trays and RacksLinear Heat Detection ALARMlINE ALARMLINE
  • 9. PAGE 9 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Conveyor fires are most commonly caused by friction. This occurs when the roller bearings used to move the conveyor belt seize and the rubber conveyor belt rubs against the seized bearing causing an overheat condition. This overheat if not detected early can cause ignition of the fuel being carried on the conveyor, the conveyor belt and other adjacent combustibles. A fire generated by friction, which if allowed to spread can cause severe damage to the belt, and the housing containing the conveyor. Alarmline can be used to provide point of risk detection to give an early warning of an overheat condition. Interfacing with other control equipment can initiate conveyor shut downs and operation of suppression systems to prevent the spread of a fire. Alarmline is particularly suitable as it can be installed where high levels of dirt, dust, wind and moisture exist and still be effective. The design of the conveyor will determine which type of ConveyorsLinear Heat Detection ALARMlINE
  • 10. PAGE 10 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE cable to use, as a minimum the cable will require mechanical protection but where exposed to the elements mechanical and chemical protection would be required. Design and installation guidelines The recommended design is to install Alarmline down each side of the conveyor clipped to the roller supports to detect an overheat on the bearings, with a further run under the bed plate on each side to detect overheat fires caused by the spillage of product from the conveyor belt. If the conveyor is enclosed or covered then it would be recommended to install Alarmline above the conveyor belt to detect any fires on a stationary conveyor belt. Other areas of conveyors which should also be considered for the use of Alarmline would be the drive motors and oil filled gear boxes It is recommended that the conveyors should be spilt into zones, to limit search areas and combine with any proposed sprinkler/ suppression systems. The interface used for monitoring Alarmline may be located in the detection zone or it may be installed remotely. If the interface is to be located remotely an interposing cable from the interface to the detection zone is required, this is connected to Alarmline using a suitable junction box and should be a suitably fire rated cable. ConveyorsLinear Heat Detection ALARMlINE ALARMLINE BEARINGS ALARMLINE
  • 11. PAGE 11 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Multi-storey and underground car parks have always been vulnerable to fire. The combustible materials used in the manufacture of modern passenger vehicles results in fires that burn more intensely and generate higher temperatures than ever before with the opportunity for fire spread significant. Detection systems in car parks are often subjected to the elements and possibly vandalism. Alarmline is prevalent for this type of application as it can be installed in environments where wind, dust and moisture are present; which can commonly lead to false alarms for other detection types. Alarmline if installed correctly is unaffected by temperature variations caused by seasonal weather conditions and provides a discrete form of detection. Car ParksLinear Heat Detection ALARMlINE
  • 12. PAGE 12 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Design and installation guidelines In this application, Alarmline provides area protection as opposed to point of risk therefore the design shall follow the guidelines for normal point type heat detectors regarding maximum spacing between cable runs and zone size. Due to the flexibility of Alarmline, it can be run in any location to provide the best coverage to ensure all vehicles are adequately protected. It is recommended in this application that nylon coated Alarmline is used, which will provide protection against the elements as well as hydrocarbons from exhaust fumes. The interface used for monitoring Alarmline may be located in the detection zone or it may be installed remotely. If the interface is to be located remotely an interposing cable from the interface to the detection zone is required, this is connected to Alarmline using a suitable junction box and should be a suitably fire rated cable. Car ParksLinear Heat Detection ALARMlINE ALARMLINE CONTROL INTERFACE UNIT ALARMLINE
  • 13. PAGE 13 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Floating roof tanks are most commonly used for storing highly flammable products making them a potential catastrophic fire risk. The main risk of fire is from the ignition of vapour escaping from a damaged/worn rim seal. It is essential that fires are detected at the earliest possible opportunity to prevent a widespread fire and activate suitable fire suppression systems. With a range of high temperature chemical resistance cable, Alarmline offers the most cost effective and reliable method for rim seal fire protection, it is easy to install close to the rim seal. Installation of ATEX approved junction boxes and intrinsically safe barriers/isolators between Alarmline and the interface unit provides the necessary protection for hazardous areas. Design and installation guidelines The design of each floating roof tank can differ greatly dependent on the manufacturer therefore Kidde recommends close liaison with the end Floating Roof TanksLinear Heat Detection ALARMlINE
  • 14. PAGE 14 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE user/site owner during the installation and design phases. Where possible the recommendation would be to use edge clips on the foam dam with a distance piece to position the Alarmline cable between the dam and the outer wall of the tank close to the rim seal. Alarmline should be supported every metre around the circumference of the rim seal. A suitable ATEX approved junction box will be provided on the roof top for termination of Alarmline. To connect Alarmline back to the control unit electrical connections between the tank top and rim are made using either an automatic cable reeler or a cable collector with retractable cables to accommodate the rise and fall of the tank roof. The interface unit being used to monitor Alarmline will be located in a non-hazardous area and to maintain the safety of the system Alarmline connections to the control unit will be connected through suitable intrinsically safe barriers/isolators. Floating Roof TanksLinear Heat Detection ALARMlINE ALARMLINE JUNCTION BOX CABLE REELER
  • 15. PAGE 15 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE The construction layout of tank farms often results in tanks containing highly flammable material that are in close proximity to each other. This makes them a considerable fire risk with a significant threat of a fire spreading between tanks. Alarmline can be installed on the tanks and in close proximity to monitor the vents, flanges, gauging points, manholes, and general bund areas for fire. The system can be linked into a main fire system to trigger activation of a deluge water spray/foam system. Sphere and Fixed Roof TanksLinear Heat Detection ALARMlINE
  • 16. PAGE 16 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Design and installation guidelines The recommended installation of each tank will vary based on the physical design but each tank will generally be protected by one continuous zone of Alarmline. Alarmline will be terminated in a suitably certified junction box with interposing fire rated cabling and connected to the control unit, located in a safe area. As the tanks will be located in a hazardous area the cable should be connected to the control unit via approved intrinsically safe barriers/isolators. The clips and fixings for Alarmline will depend on the physical design of the tank but in most cases these would need to be fixed to the surface of the tank using a suitable adhesive. Sphere and Fixed Roof TanksLinear Heat Detection ALARMlINE ALARMLINE ALARMLINE JUNCTION BOX JUNCTION BOX
  • 17. PAGE 17 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Fires in densely packed racking can be detected with a localised Alarmline detection system. Alarmline can be installed within the racking to provide detection very close to the point of risk, providing a discrete detection system which is unaffected by the normal working environment. Alarmline can be zoned within the racking and is often used to trigger the pre-action stage of a sprinkler system to ensure rapid detection and control of the spread of fire. Design and installation guidelines The recommendation is to install Alarmline at the ceiling and within the rack, fixing it to the existing shelf supports in a position where it will not be damaged when loading and unloading the shelves. The warehouse and racking can be split in to zones to reduce the search area and to activate the relevant sprinkler/suppression system. Warehouse RackingLinear Heat Detection ALARMlINE
  • 18. PAGE 18 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE The interface used for monitoring Alarmline may be located in the detection zone or it may be installed remotely. If the interface is to be located remotely an interposing cable from the interface to the detection zone is required, this is connected to Alarmline using a suitable junction box and fire rated cable. Freezer warehouses Where a warehouse is used for cold storage and operates at low temperatures Alarmline can be used to provide general area protection. The design follows the guidelines for point type heat detectors or installed as‘in-rack’protection. The following specialist recommendations should be noted: ❚ Nylon coated cable should be used ❚ Minimum operating temperature: Digital sensor -65°c Analogue Sensor -40°C ❚ Minimum installation temperature -11°C ❚ Interface units must be installed in areas with an ambient temperature above 0°C Warehouse RackingLinear Heat Detection ALARMlINE ALARMLINE ATTACHED TO CEILING OR PERMANENTLY FIXED SHELVING
  • 19. PAGE 19 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Fires on escalators and travelators can develop rapidly into a major fire and can spread because of the continued mechanical movement. The public nature of this application means that it is crucial to have the earliest possible detection system to initiate emergency procedures. Alarmline can be installed at the point of risk, and can protect the following potential fire risks: ❚ Drive motors ❚ Roller bearings ❚ Truss rollers ❚ Dust collector trays Due to the movement of mechanical parts it would be recommended that Alarmline should have mechanical protection; chemical protection should also be considered due to the presence of oil and grease. Design and installation guidelines Alarmline can be used to protect the roller trusses and any other moving parts for risk Escalators and TravelatorsLinear Heat Detection ALARMlINE
  • 20. PAGE 20 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE of overheat due to friction. Alarmline should be installed on both sides of the escalator to protect the rollers, and at the top and bottom of the escalator to detect potential fires in the dust collection trays. Where necessary the escalator or travelator can be split into smaller detection zones. If the Alarmline system is to be used in conjunction with a suppression system it may be necessary to install two independent systems to provide coincidence operation. Care should be taken when attaching the Alarmline to the roller bearings to ensure that it is not damaged by the moving treads of the unit. The interface used for monitoring Alarmline may be located in the detection zone or it may be installed remotely. If the interface is to be located remotely an interposing cable from the interface to the detection zone is required, this is connected to Alarmline using a suitable junction box and fire rated cable. ALARMLINE MOTOR / BEARING CONTROL INTERFACE UNIT Escalators and TravelatorsLinear Heat Detection ALARMlINE
  • 21. PAGE 21 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Tunnels pose a challenging fire threat due to their confined structure. Tunnels primarily offer limited access/egress points, making it crucial that fires are detected at the earliest opportunity to enable evacuation and extinguishing of the fire. Alarmline detection offers a cost effective solution that can provide protection for all the different facets of the tunnel system, with design capabilities to be compatible with the other tunnel operating systems. There are many different potential hazards within the tunnel environment such as electrical services, motor vehicle accidents, vehicle load fires, vehicle fires, fuel fires, etc. Design and installation guidelines Specific electrical risks can be protected by installing Alarmline at the point of risk. The biggest risk is vehicle fires which can cause significant problems including intense heat and thick black toxic smoke making access and egress difficult. TunnelsLinear Heat Detection ALARMlINE
  • 22. PAGE 22 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE To detect vehicle or fuel fires we would provide a general area type protection with Alarmline installed directly over the roadways inside the tunnel. Alarmline can be split into separate zones depending on the width and length of the tunnel. Detection zones could be linked to suppression systems for localised fire fighting or ventilation zones to activate extraction systems. Alarmline can also be used to detect fires in sumps and drains designed for containment of fuel or oil spills. These systems can be linked to a foam suppression system to provide extinguishing of any fire. Due to the environmental conditions Alarmline installed within tunnels should have a nylon coating. The interface used for monitoring Alarmline may be located in the detection zone or it may be installed remotely. If the interface is to be located remotely an interposing cable from the interface to the detection zone is required, this is connected to Alarmline using a suitable junction box and should be a suitably fire rated cable where possible. TunnelsLinear Heat Detection ALARMlINE ALARMLINE ALARMLINE
  • 23. PAGE 23 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Thatched roof fires are becoming more common with the main cause (approximately 90 per cent) being linked to poorly maintained chimneys. Fires are due to either hot spots within the chimney caused by build up of soot and debris or by cracks in the chimney brickwork causing hot gases to escape into the thatch layer. This causes the temperature to rise within the thatched layer where it eventually reaches a point of ignition. Thatch layers can be quite thick which means a fire can be well established before it is noticed and the fire service summoned. Early detection of these increases in temperature is critical to minimise the amount of damage that can be caused by a thatched roof fire. Alarmline Digital cable has been independently tested and approved for use in this application by the National Society of Master Thatchers. Thatched RoofsLinear Heat Detection ALARMlINE
  • 24. PAGE 24 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE Design and installation guidelines To protect against fires caused by heat transfer from the chimney, Alarmline can be installed discreetly between the thatch layer and the brickwork of the chimney to detect any increases in temperature through the chimney wall. As Alarmline is a continuous sensor it can be installed around the chimney stack providing large area coverage. Installation of two different temperature cables can provide indication of a pre-alarm condition followed by an alarm condition. It is also possible to install Digital Alarmline within the thatch itself threading the Alarmline through the thatch layer at a regular spacing to detect fires caused by other ignition sources. Shakespeare’s Globe theatre is one of many properties which is fitted with such a system. Digital Alarmline can also be used to provide detection within the roof space, underneath the thatch layer the cable can be fixed to the existing roof struts at regular intervals to provide Thatched RoofsLinear Heat Detection ALARMlINE general area coverage. Alarmline will not be susceptible to false alarms caused by high levels of dust typically found in these environments. Alarmline is compatible with any conventional fire alarm panel which can be located at a suitable point within the property to provide audible and visual warning indications. Kidde recommend that these systems are only installed by engineers who are approved to work in listed and thatched properties. ALARMLINE JUNCTION BOX
  • 25. Kidde AirSense Thame Park Road, Thame, Oxfordshire OX9 3RT, UK Tel: +44 (0)1844 265003 Fax: +44 (0)1844 265156 Email: general.enquiries@kiddeuk.co.uk Web: www.kfp.co.uk Linear Heat Detection ALARMlINE PAGE 25 ZOOM PRINT EXITCONTENTSHOMECONTACT KIDDE AIRSENSE