Earth testing was conducted on the 125kVA camp DG system using the three probe method as per IS:3043. Earth resistance readings were taken at four locations around the three DG pits, with readings ranging from 36.4 to 63.6 ohms with a voltage of 0.5 to 0.7 volts applied. Two 125kVA DGs from Sudhir Power Ltd were listed with serial numbers.