TRAINING COURSE COMPLIMENTS CATALOGUETRAINING COURSE COMPLIMENTS CATALOGUETRAINING COURSE COMPLIMENTS CATALOGUETRAINING COURSE COMPLIMENTS CATALOGUE
NX-AIR PNX-AIR MNX-AIR
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 2 25.09.2012
First Line Operation & Maintenance – Training Course
Siemens Vacuum Switchgear Type "NX-Air W / M & P"
Index
INTRO An Introduction to Vacuum Technology
A BRIEF INTRODUCTION TO THE SIEMENS VACUUM CIRCUIT BREAKER MANUFACTURING
PROCESS AND A TECHNICAL OVERVIEW OF THE ARC PRINCIPLE AND DESIGN PHILOSOPHY
BEHIND THE CONCEPT OF "VACUUM ARC INTERRUPTION" AND THE SCIENCE INVOLVED TO
ACHIEVE ONE OF THE HIGHEST GRADES OF TRUE "HIGH QUALITY ELECTRICAL SWITCHING
PRODUCTS" AVAILABLE TODAY…
1. Safety Instructions
2. NX-Air W / M & P Switchgear Description
in an introductory slide-show format
3. NX-Air All Types Descriptive Catalogue
4. NX-Air M & P Contactor Panel
5. NX-Air & NX-Air P Circuit Breaker Panel
6. 3AH & K (new) Vacuum Circuit Breakers
7. Vacuum Circuit Breaker Type: 3AH-1
8. Vacuum Circuit Breaker Type: 3AH-3
9. Vacuum Circuit Breaker Type: 3AH-5
10. Breakers Interrupter Table, Harting plug
description & Breaker-Mech Wiring Dwgs.
11. Sion Circuit Breaker Manual
12. Vacuum Contactor Slideshow
13. 3TL Vacuum Contactors Group Manual
14. 3TL 6 Vacuum Contactor Manual
15. 3TL 8 Vacuum Contactor Manual
16. Vacuum Contactor HR Fuse Types
17. Motorised Racking Manual for NX-Air M
18. Modular Metering & VT Truck Manual
19. Internal Arc Protection Scheme
20. Earthing Switch Operation for NX-Air P
21. Panel, C/B & Contactor Test Sheets
22. Circuit Schematic Drawing of Incomer
23. Circuit Schematic Drawing of Bus-section
24. Circuit Schematic Drawing of Meter Panel
25. Circuit Schematic Drawing of Feeder
26. Circuit Schematic Drawing of Motor Panel
27. Siemens Notepad / Drawing paper
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 3 25.09.2012
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 4 25.09.2012
Vacuum switching technology Arc quenching
During the galvanic separation of the contacts, the current to break produces a metal-vapour
arc discharge. The current flows through this metal-vapour plasma until the next current
zero. Near the current zero, the arc extinguishes. The metal vapour loses its conductivity
after few microseconds already the insulating capability of the contact gap recovers quickly.
To maintain the metal-vapour arc discharge, a specific minimum current is required. If this
minimum current is not reached, it will chop before the natural current zero. To prevent
impermissible switching overvoltages while switching inductive circuits, the chopping current
must be limited to the lowest possible values. Using a special contact material, the chopping
current in vacuum circuit-breakers is just 2 to 3 A. Due to the fast recovery of the contact
gap, the arc is safely quenched even if the contacts are separated right before a state of
"current zero". Therefore, the arcing times in the last pole to clear are 15ms as a maximum.
Depending on the breaking current and the interrupter dimensions, different contact
geometries are used.
Welcome to Siemens Technology
The history of Siemens's manufacture of various types
of circuit breakers recently achieved its first century. In
the past hundred years a very thorough knowledge of
all types of switching devices in every possible type of
medium have been researched, tested and tried.
So, it would be ironic if the technology which we now
call "vacuum" was not discovered during the global
space age. Unlike to normal air or mixtures of nitrogen
and oxygen a vacuum presents the perfect forum for a
safe switching environment being able to minimise
arcing and contact burn.
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 5 25.09.2012
Key to description of parts:
IInntteerrrruupptteerr DDeessiiggnn
The interrupters are of a very compact
design as can be seen in the cross-section
drawing provided. The area or volume of
space occupied within the interrupter is at a
perfect vacuum state. This would be the
same as if switching the contacts in outer-
space, where there is no air, as in
"nitrogen" or "oxygen" which could
contribute in any way to assist with ignition
or explosive tendencies. This compact
design of the Siemens vacuum interrupters
provides a very high switching capacity in
very compact dimensions:
for example: vacuum interrupters for 15
kV/40 kA with housing dimensions of 125
mm diameter by 161 mm length, or for 12
kV/13.1 kA with 68 mm diameter by 115
mm length. A very high QA level has been
achieved in the product market. This quality
assurance is due mainly to Siemens
following the TQM and DIN / ISO 9001
procedures & specifications, which call for
rigorous material, manufacture &
production checking. Every batch is
checked & tested individually before
delivery and only if the QA result is a 100%
pass, are the interrupters released for
delivery. Some of the tests that are
performed include: testing of the
interrupters for assuring the seal of vacuum
sealing, testing for reliable long operation
and long life, environmental protection
involved in the manufacture of these
vacuum interrupters and our guarantee to
only use environmentally compatible
materials, such as copper, ceramics and
high-grade steel. Such, that the
manufacturing processes do not damage
the environment. (e.g. no CFC's are used in
production (this fulfilling the Montreal
agreement); also all the components are
cleaned and kept free from micro-fibres &
contamination in a ultrasonic plant, with the
entire manufacturing line concealed in a
protected atmosphere.
Vacuum interrupters for the medium-voltage range are available from Siemens for all applications on the international market from 1 kV
up to 40.5 kV. Vacuum Interrupters are also used in special design applications where the operational voltage that they are exposed to
is well in excess of 40.5kV, even up to as high as 132kV. When used in these applications the interrupter is immersed in SF6 Gas within
a pressurised chamber, so that the switching of "contacts" are still done within a vacuum inside the interrupter, but therefore in this
application the entire interrupter itself is immersed and insulated by SF6 gas. This type of configuration enables using the same
switching technology in much higher operational voltages.
Applications:
Vacuum interrupters are used in vacuum circuit breakers, vacuum switches, vacuum contactors, transformer tap changers, in circuit
breakers for use in railway applications, auto-reclose switches, and lastly also in special applications such as nuclear fusion.
Introduction to the Vacuum interrupters
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 6 25.09.2012
Inside the Vacuum interrupter - The Manufacturing process
To prove the atmospheric pressure, in 1654 Otto von Guericke
created a vacuum with the Magdeburg hemispheres for the first
time in history. More than 35 years ago, Siemens developed
vacuum switching technology, leading it to series production.
What was then a fundamental innovation has been developed
further to a proven technology, which now has a worldwide
market share of about 70 percent. Vacuum switching
technology from Siemens meets all the requirements placed on
circuit-breakers and contactors in medium-voltage switchgear
up to 40.5 kV, and is now an integral part of many applications
because of its clear advantages.
The Siemens vacuum interrupters are manufactured inside the Siemens Factory in Berlin under various processes. We
will briefly take you on a short journey through this process and discuss some of the important facts of how these
vacuum interrupters are made until they are assembled in the form of a finished product such as a Contactor or vacuum
circuit breaker.
Contact rod processing
In our numerically controlled multi-axis lathes, the raw parts are given
the external contour and the slots of the contact carrier surface in just
one single operation. The fully automatic process reduces the error rate
to a minimum. A constantly high quality characterizes the produced
parts.
Contact material processing
Siemens is the only manufacturer of vacuum interrupters worldwide to
produce the contact material itself. The basic raw materials copper and
chrome are combined to a powerful contact material by means of the
arc-melting procedure. The resulting raw parts are processed to RMF or
AMF contact discs, whereby the slotted AMF discs are de-bured at the
end. All processing steps are electronically recorded for quality
purposes.
Metallography
To fulfil the highest quality demands, samples of the contact material are
examined by metallography. Here, the homogeneity of the contact
material, the quality of the melting process as well as the brazed
connection between the contact material and the contact rod are
checked.
Endurance test for bellows
To enable them to meet the requirements for high endurance in real
practice, the bellows are regularly subjected to an endurance test every
three months. The test is carried out in a fully automatic test cabin with
the travels adjusted to the respective type.
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 7 25.09.2012
Vacuum interrupter assembly under clean-room conditions
After having finished and cleaned the surfaces by electroplating and
performed an optical inspection of the surface consistency of all single
parts, the interrupter is assembled. The high-vacuum solder is applied at
the joints of the components, the parts are aligned, and the interrupters
are fixed. As cleanliness during assembly is especially important, all
operations are done under air-conditioned "clean-room atmospheric"
conditions – in this way we can guarantee a constantly high quality of the
interrupters and maximum possible ratings up to 72 kA according to
IEEE C37.013.
High-vacuum brazing furnace
In the high-vacuum brazing furnace, the joints of the vacuum interrupters
are brazed at temperatures up to 900 °C and a press ure of 10-6 mbar.
Thus, the interrupters fulfil the quality requirement “sealed for lifetime”.
Thanks to the fully automatic production process, the high quality can be
constantly reproduced at any time.
X-ray test
The evaluation of the interrupters by means of the X-ray procedure is
used to verify the positions as well as the completeness of the internal
components, and the quality of the brazing points. In this way we ensure
the high quality of our products.
Forming and high-voltage testing of vacuum interrupters
During forming, the definitive internal dielectric strength of the vacuum
interrupter is established with gradually increasing voltage, and this is
verified by a subsequent lightning impulse voltage test. Both operations
are done with higher values than those specified in the standards, as
evidence of the extraordinary quality of the Siemens vacuum
interrupters. This is the prerequisite for a long endurance and a high
availability.
Switching device production
The switching device production is set up as a direct flow production.
Various assemblies are prefabricated in parallel and combined at the
mounting place of the switching device. The flow production reduces the
order lead times and thus the delivery times of the switching devices to a
minimum.
Laser welding
Laser welding provides a completely positive material joint between
individual components – as a prerequisite for highly resistant,
dynamically stress able assemblies such as the operating mechanism
box. Its superiority over conventional welding becomes apparent, above
all, by the fact that no hollows are produced – which would be
susceptible to humidity – and that the material cannot loose shape
anymore. The consequence: a high dimensional accuracy with the
lowest tolerances possible – and thus, reduction of later adjustments to a
minimum.
Stamping and laser cutting
In the pre-production, the steel plates are processed by highly automatic
and highly productive stamping and laser cutting machines – providing
the assured adherence to minimum tolerances, even with high
quantities. The high degree of automation results in a process-safe,
trouble-free production with short lead times, almost without any down
time. Loading, operating and programming is possible with the machine
running, without interrupting the production process.
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 8 25.09.2012
Surface Treatment
Electroplating is used to improve the material surfaces and to protect
them against corrosion. By plating with a second material, the
mechanical and electrical properties of the carrier materials are
sustainably improved. This provides an optimised surface – which is
decisive for a longer service life of the product and its permanently
maintenance-free design.
Final assembly of switching devices
For all switching devices, the individual constructional units are pre-
assembled in parallel. During final assembly, the different constructional
units, the pole structure as well as the operating mechanism box are
combined, and the device is equipped with the order-specific secondary
system. Parallel work operations reduce the production lead time of the
switching device to a minimum – sometimes even short-term customer
requirements can still be implemented.
Final inspection and testing of circuit-breakers
After having passed the routine and high-voltage tests successfully, the
circuit-breakers are inspected at the final testing station to detect visible
sources of faults. The rating plate is not attached until this last visual
inspection has been completed successfully, and then the circuit-breaker
is released for dispatch. To reduce complaints to a minimum, the order is
checked for completeness and conformity before leaving – after all, you
are expecting quality in every detail.
& finally the finished products:
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 9 25.09.2012
The Electro- Magnetic Concept of how a Vacuum Interrupter works:
Definition of a Vacuum Interrupter:
A vacuum interrupter is an operable single contact that has been
homogeneously sealed during its manufacture, in such a way that
the atmosphere within the interrupter, which would normally be
present around the contact surfaces, has been totally withdrawn
or "sucked out" of the inside chamber and then simultaneously
sealed immediately thereafter. In this sealed form there is then no
atmosphere, particles that may be ionized, or any gases present
that may contribute to igniting any type of flame or burning from
an arc around any of these contact surfaces inside the
interrupter. This making it almost impossible for any combustion
or burning to take place during the arcing-time that would usually
occur during an "on" or "off" operation of the circuit breaker.
The interior part of the interrupter is therefore at total vacuum
potential, i.e. equivalent to the conditions that would normally be
found in outer-space. The top pole contact of the interrupter is
usually fixed and the lower contact is the one which moves up
and down to achieve the operation. The interrupters on a circuit
breaker truck are usually 3 that are mounted side by side for the
3 phases usually required for industrial electrical operations on
plants. Vacuum Interrupters are also hugely environmentally
friendly, as they will maintain and contain all their lifetime of
switching gasses and debris, inside their own sealed housing
during their full service lifetime, which can range up to 25 years
pending certain operational circumstances. During operation
vacuum interrupters are also themselves not affected by the
environment, as they have been completely sealed with special
materials such as porcelain.
Philosophy of the -
In radial magnetic-field contacts, the arc burns diffusely until approx. 10 kA (momentary value). Higher currents
burn across a contracted arc. In this case, local overheating of the contacts must be avoided. An additional
magnetic field thus produces this required force, which makes the arc rotate on the arcing rings of the contacts
via the magnetic field generated by the flow of current through the contact tips. Thus, contact erosion at the base
point of the arc is distributed over the entire ring surface at a completely even rate.
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 10 25.09.2012
Philosophy of the -
In axial magnetic-field contacts, the arc remains diffuse, even with high currents due to the axial magnetic-
field. The disc-type contact surfaces are uniformly stressed, and localised melting is avoided. In alternating-
current circuit breakers, the actual function of the quenching system is to de-ionize the contact gap
immediately after current zero. For all conventional quenching systems, this means that the arc must already
be cooled before reaching the minimum quenching distance and the following current zero. Involuntarily, this
increases the arc's power a lot (magnetic component), resulting in it responding better to following the
magnetic field that develops between these two contact surfaces . In the case of vacuum circuit-breakers,
however, the arc is not cooled down. The metal-vapour plasma is highly conductive. This results in a very
small arc voltage ranging between 20 and 200 V. For this reason, and due to the short arcing times, the
energy converted in the contact gap is very low. Because of this relatively low stress, the quenching system
is maintenance-free. In stationary condition, the pressures in the interrupter is very low – less than 10-9 bar,
so that contact distances of just 6 to 20 mm are required to reach a very high dielectric strength. Apart from
circuit-breakers, the vacuum switching technology can also be used in contactors and other type of switches
such as barrel switches. Today, more than 70% of all circuit-breakers installed in medium-voltage systems
are based on vacuum switching technology.
CROSS-SECTIONAL SIDE VIEW OF AN INTERRUPTER
HIGH-SPEED CAMERA SHOTS OF THE "ARC
DISSIPATION" ON A POLE CONTACT SURFACE OPENING
UNDER REAL FULL-LOAD CONDITIONS
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 11 25.09.2012
Maintenance and servicing
Symbols used Operation symbol: Identifies an operation.
Asks the operator to perform an operation.
Result symbol: Identifies the result of an operation.
1.1 General instructions
Independently of the safety instructions given in these operating instructions, the local laws, ordinances,
guidelines and standards for operation of electrical equipment as well as for labour, health and
environmental protection apply, and these are to be complied with, in line with the latest Regulations. All
methodologies & actions applied to any services of the equipment or to repairs are to comply with specified
methods as described and discussed in the Siemens specific procedure relevant to the equipment and parts
in question. All work performed, whether on site or in the works, of whatever nature, must comply with the
ACT.
1.2 The Five Golden Safety Rules of Electrical Engineering
The Five Safety Rules of Electrical Engineering must generally be observed during operation of the products
and components described in these operating instructions:
Isolating.
Securing against reclosing.
Verifying safe isolation from all sources of supply.
Earthing and short-circuiting methods are safe & can withstand kA rating.
Covering, tagging and locking out of all adjacent live parts and shutters.
1.3 Delivery in line with Specifications
The switchgear corresponds to the relevant laws, prescriptions and standards applicable at the time
of delivery. If correctly used, they provide a high degree of safety by means of logical mechanical
interlocks and shockproof metal enclosure of live parts.
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 12 25.09.2012
1.4 Qualified personnel – Training and legalities
Qualified personnel in accordance with these instructions, are persons certified or qualified to undertake this
type of work, either by certification through some form of education, studies, or training, which can be backed
up by a recognized certificate, degree, or letter of appointment. For such persons, or qualified Electrical
Artisans, Technicians and Engineers, that are permitted by their organisations, the National Regulator, or any
form of other legally acceptable appointments, who are similarly familiar with the regulatory requirements and
the safe operational safety requirements of these products and also have the appropriate qualifications for this
"type of work", must also obtain the necessary background knowledge about the transport, installation and
commissioning of these products. Therefore these personnel must have also participated in this training course
for "The first line safety, operation and maintenance" requirements of the Siemens air-insulated medium-voltage
switchgear type "SIMOPRIME".
The aim of this training, is that it provides a firm basis of "safety awareness, knowledge and understanding of
the equipment" in the form of detailed information about the design, operation, installation, testing and
troubleshooting of the SIMOPRIME switchgear. After successful participation, the participants of this training
course get a certificate of Competence to operate and perform the first line maintenance for this "specific" type
of equipment only, as the minimum required training for performing operations on specific electrical apparatus,
or as usually specified under the regulation, the Act or by the D.O.L.
The certificate for this course only authorises the participants to be appointed to "switch" or "operate" the
Siemens "specific" equipment, but then also only after they have fully satisfied the D.O.L., the N.R.S., the Act &
any other regulatory requirements required by the law, to perform "MV switching", within their specific "place of
work", as the authorised or responsible person, and that he or she has been fully trained on all the precautions
and dangers that are associated with this specific process. The certificate of this training will only allow the
operator to switch "Siemens type Simoprime medium voltage switchgear" electrically, provided that he is
certified on HV Regulations, has a letter of appointment to do this switching for and on behalf of his/her
employer, and has been appointed by letter, as the Operational or Responsible person to do such.
The attendee therefore acknowledges and realises, that by signing the attendance register, that it is up to his
"own full responsibility" to ensure his/her understanding of the subject matter, credible certifications to perform
the work and understand and apply the regulatory requirements, that are covered herein, so that at the end of
this course, they do not leave the venue with any remaining questions or uncertainties, to ensure that he or she
has satisfied their every curiosity, or remaining questions that they may have had, in terms of the Safety aspects
of the operations and functions of this equipment.
Siemens cannot be held liable, or will not accept any liability, or responsibility, for the direct or indirect actions
of any customer staff, that are out of, or beyond our control, supervision, or deviate from any regulation, even if
by accident or omission, or even if such procedures may be covered, yet have been misunderstood in this
training course which has been presented. It is the attendees own responsibility at the end of this course to
ensure that all the procedures and legal requirements of the NRS, the Act and any additional safety regulations,
such that may be required by such as even their employer, are all implemented, understood and upheld before
performing any work in the field.
The Completion of this course does not authorize staff to be appointed to do any "Switching". This is a separate
course on offer, which covers the regulations and the Act and is referred to as "High Voltage Switching
Regulations Training". For further information about this training, please contact: Niels Inderbiethen, on cell –
072 287 4525, who will arrange for a quotation for the course to be held either on our, or the clients own
premises.
We wish you a pleasant learning experience in attending this Siemens Training Course…
With our sincere thanks… from all of us… at…
SIEMENS LTD SOUTH AFRICA
Establishing safe conditions first, before the execution of any works
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 13 25.09.2012
Furthermore, qualified personnel must have the following training and authorisation:
Training and instruction or authorisation to switch on, switch off, earth and identify
power circuits and equipment / systems as per the relevant safety standards (and the
recently added new requirements by law, such as HV Reg's & legal appointments)
Training and instruction about the relevant safety standards and the use of
appropriate safety equipment specifically relevant to the equipment they will be
switching (such as this course).
Training in first aid and emergencies behaviour in the event of possible accidents or
evacuation requirements relevant to their specific plant i.e. (plant specific)
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 14 25.09.2012
1.5 Discussion of the features within the 3AH & K (New) operating mechanism.
The operating mechanism is fitted with an integrated mechanical interlock which prevents dangerous
switching conditions or operations from being carried out when the power is on.
The operating mechanism unit is only found on trucks fitted with a circuit-breaker.
The mechanism is fitted with isolating contacts that indicate the breaker position during racking.
Mechanical interlocks are provided to safeguard the operator during racking procedures.
Visual racking control status is provided with graphic representation.
The operating mechanism is fitted with a closing solenoid allowing for remote "close" control.
Mechanical indication of “closing spring charged” indicator can be seen through front of truck cover.
The first shunt release coil, which is also used for remote tripping, is the electrical tripping solenoid which
mechanically pushes against the trip lever that triggers the trip roller bearing.
The mechanism is fitted with an operating cycle counter, which counts every open and then closed
operation as one single operation increment on the counter.
Other solenoids may also be additionally fitted to extend the conditions of the trip operations, these
include under-voltage coils and uniquely driven shunt-trip coils. The circuit-breaker tripping signal can
also be additionally routed through protection relays and logic contacts to extend the desired level of
protection.
The circuit breaker mechanism is fitted with an electrical anti-pumping device which prevents more than
one auto re-closure, when the breaker is switched back on a fault that has still not cleared.
Varistor module fitted for the auxiliary voltage W 60 V, the auxiliary switch has 6NO+6NC contacts.
1.6 Parts of the 3AH5 circuit breaker operating mechanism:
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 15 25.09.2012
1.7 Nameplate:
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 16 25.09.2012
1.8 SION vacuum circuit breaker.
Component Identifications:
Part identification & features of the SION Operating Mechanism.
Component Identifications:
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 17 25.09.2012
Maintenance and servicing
1.9 General Maintenance
The vacuum circuit-breakers / contactors switchgear are maintenance-free within the scope of the
permissible number of operating cycles. Under normal environmental and operating conditions the
maintenance intervals are longer than five years. Built-in equipment such as voltage transformers,
current transformers, relays, meters, protection equipment, etc. must be serviced and maintained as
specified in the associated operating instructions.
Commercially available tools are sufficient for carrying out the maintenance work.
After maintenance, put the equipment again into operation as per the operating instructions.
Carry out maintenance and servicing at shorter intervals (to be specified by the owner) if
there is a lot of dust, or if the air is extremely humid and/or polluted.
Grease main fixed contacts of bushings and fixed contacts of earthing switches as well as
other surfaces exposed to friction (e.g. shutter operating linkage, guide rails) at shorter
intervals (to be specified by the owner): Tin of Long-term 2 grease (8BX1022).
Independently of the regular maintenance, immediately determine the cause of faults and
short circuits and replace any damaged components.
Maintenance intervals
The maintenance intervals described hereafter are a recommendation when the switchgear is
operated under normal environmental conditions. In case of extreme operating conditions the
maintenance intervals must be adjusted accordingly.
Annual maintenance
Carry out general check for damages, dust layers, humidity in the switchpanels, and for partial
discharge noises.
Check whether accessories are complete and in good condition (including the truck).
Maintenance after five years
Operate earthing switches for test.
Clean switchpanels.
Check function of switchpanels and put switchgear again into operation.
Check primary connections of current and voltage transformers.
Check bolted joints (see "Installation", Section 9.2, Page 32).
SAFETY FIRST - Maintenance of vacuum circuit-breaker / vacuum contactor
Preconditions: • Supply voltage switched off
• Circuit-breaker in OPEN position
• Spring not charged
NX-Air_M_P Training Intro Doc Sasol.doc
1006884 - N. Inderbiethen Page 18 25.09.2012
Niels Inderbiethen
Specialist – Technical Support
FAC/ASS ETDPSETA SAQA AcrNo:ATS/12/2838
MCS (Metering) & PTI (Training) Services
SG Services (Smart Grid)
Siemens Southern Africa
IC Sector (Infrastructure & Cities)
Newmarket Street, Northriding
T: +27 10 222 7315
F: +27 86 506 5941
M: +27 72 287 4525
niels.inderbiethen@siemens.com
www.siemens.co.za
- END OF THIS TRAINING ADDENDUM MANUAL -
NNB
(PLEASE REFER TO THE DIFFERENT NX-AIR W, M&P SWITCHGEAR PANEL
DOCUMENTATION FOR A FULL DESCRIPTION OF RACKING IN THE RACKING ORR
MOTORISED RACKING OPERATIONAL PROCEDURES.
ADDITIONAL INFORMATION ON THE CIRCUIT EXAMPLE DRAWINGS FOR THE
CUSTOMERS SWITCHBOARD (SINGLE LINE DRAWINGS AND THE 3AH CIRCUIT
BREAKERS WIRING DIAGRAMS) IS ALSO PROVIDED IN THE LAST SECTIONS,
SECTIONS 22-26 OF THIS MANUAL)

More Related Content

What's hot

Safety instrumented systems
Safety instrumented systemsSafety instrumented systems
Safety instrumented systemsMowaten Masry
 
Technical slides tia_portal_v15_en
Technical slides tia_portal_v15_enTechnical slides tia_portal_v15_en
Technical slides tia_portal_v15_enDeepak kumar
 
FIre Fighting Elite Fire hydraulic Calculation As per NFPA Standard
FIre Fighting Elite Fire hydraulic Calculation As per NFPA StandardFIre Fighting Elite Fire hydraulic Calculation As per NFPA Standard
FIre Fighting Elite Fire hydraulic Calculation As per NFPA Standardsureshvsvg
 
Nfpa70 e 2012 hrc no logo
Nfpa70 e 2012 hrc no logoNfpa70 e 2012 hrc no logo
Nfpa70 e 2012 hrc no logoOFFSHC
 
Electrical Risk Management
Electrical Risk ManagementElectrical Risk Management
Electrical Risk Managementguest81e1c7
 
19 Jun 2018 - Hazard Analysis and Functional Safety Compliance
19 Jun 2018 - Hazard Analysis and Functional Safety Compliance 19 Jun 2018 - Hazard Analysis and Functional Safety Compliance
19 Jun 2018 - Hazard Analysis and Functional Safety Compliance Intland Software GmbH
 
27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substationsMugdha Jhanjhote
 
FactoryTalk View SE - Building a Better View
FactoryTalk View SE -  Building a Better ViewFactoryTalk View SE -  Building a Better View
FactoryTalk View SE - Building a Better ViewTony Carrara
 
How Conformal Coating Can Kill
How Conformal Coating Can KillHow Conformal Coating Can Kill
How Conformal Coating Can KillCheryl Tulkoff
 
Siemens Sivacon S8 Info
Siemens Sivacon S8 InfoSiemens Sivacon S8 Info
Siemens Sivacon S8 Infonor52097
 
Frequently Asked Question (FAQ's) on ISO 26262 Functional Safety
Frequently Asked Question (FAQ's)  on ISO 26262 Functional SafetyFrequently Asked Question (FAQ's)  on ISO 26262 Functional Safety
Frequently Asked Question (FAQ's) on ISO 26262 Functional SafetyEmbitel Technologies (I) PVT LTD
 
Day 2: Energy Audit of Air Conditioning And Cooling Systems
Day 2: Energy Audit of Air Conditioning And Cooling Systems Day 2: Energy Audit of Air Conditioning And Cooling Systems
Day 2: Energy Audit of Air Conditioning And Cooling Systems RCREEE
 
BAND IT CABLE TIE | AKBAR TRADING EST | mail@akbartrading.com
BAND IT CABLE TIE | AKBAR TRADING EST | mail@akbartrading.comBAND IT CABLE TIE | AKBAR TRADING EST | mail@akbartrading.com
BAND IT CABLE TIE | AKBAR TRADING EST | mail@akbartrading.comAKBAR TRADING
 

What's hot (20)

Nfpa coods list2
Nfpa coods list2Nfpa coods list2
Nfpa coods list2
 
Sil presentation
Sil presentationSil presentation
Sil presentation
 
Safety instrumented systems
Safety instrumented systemsSafety instrumented systems
Safety instrumented systems
 
Technical slides tia_portal_v15_en
Technical slides tia_portal_v15_enTechnical slides tia_portal_v15_en
Technical slides tia_portal_v15_en
 
FIre Fighting Elite Fire hydraulic Calculation As per NFPA Standard
FIre Fighting Elite Fire hydraulic Calculation As per NFPA StandardFIre Fighting Elite Fire hydraulic Calculation As per NFPA Standard
FIre Fighting Elite Fire hydraulic Calculation As per NFPA Standard
 
Nfpa70 e 2012 hrc no logo
Nfpa70 e 2012 hrc no logoNfpa70 e 2012 hrc no logo
Nfpa70 e 2012 hrc no logo
 
C01 – industry 4 – a revolution simon keogh – siemens
C01 – industry 4 – a revolution   simon keogh – siemensC01 – industry 4 – a revolution   simon keogh – siemens
C01 – industry 4 – a revolution simon keogh – siemens
 
Electrical Risk Management
Electrical Risk ManagementElectrical Risk Management
Electrical Risk Management
 
19 Jun 2018 - Hazard Analysis and Functional Safety Compliance
19 Jun 2018 - Hazard Analysis and Functional Safety Compliance 19 Jun 2018 - Hazard Analysis and Functional Safety Compliance
19 Jun 2018 - Hazard Analysis and Functional Safety Compliance
 
Detailed engineering-design-phase
Detailed engineering-design-phaseDetailed engineering-design-phase
Detailed engineering-design-phase
 
Jornada pci en naves logisticas
Jornada pci en naves logisticasJornada pci en naves logisticas
Jornada pci en naves logisticas
 
Ultrasonic Welding
Ultrasonic WeldingUltrasonic Welding
Ultrasonic Welding
 
27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations
 
FactoryTalk View SE - Building a Better View
FactoryTalk View SE -  Building a Better ViewFactoryTalk View SE -  Building a Better View
FactoryTalk View SE - Building a Better View
 
How Conformal Coating Can Kill
How Conformal Coating Can KillHow Conformal Coating Can Kill
How Conformal Coating Can Kill
 
Siemens Sivacon S8 Info
Siemens Sivacon S8 InfoSiemens Sivacon S8 Info
Siemens Sivacon S8 Info
 
Frequently Asked Question (FAQ's) on ISO 26262 Functional Safety
Frequently Asked Question (FAQ's)  on ISO 26262 Functional SafetyFrequently Asked Question (FAQ's)  on ISO 26262 Functional Safety
Frequently Asked Question (FAQ's) on ISO 26262 Functional Safety
 
Day 2: Energy Audit of Air Conditioning And Cooling Systems
Day 2: Energy Audit of Air Conditioning And Cooling Systems Day 2: Energy Audit of Air Conditioning And Cooling Systems
Day 2: Energy Audit of Air Conditioning And Cooling Systems
 
SF6 circuit breaker
SF6 circuit breakerSF6 circuit breaker
SF6 circuit breaker
 
BAND IT CABLE TIE | AKBAR TRADING EST | mail@akbartrading.com
BAND IT CABLE TIE | AKBAR TRADING EST | mail@akbartrading.comBAND IT CABLE TIE | AKBAR TRADING EST | mail@akbartrading.com
BAND IT CABLE TIE | AKBAR TRADING EST | mail@akbartrading.com
 

Similar to Training Course NX-Air Intro & Safety

Tecnotion Ironless Vacuum Brochure
Tecnotion Ironless Vacuum BrochureTecnotion Ironless Vacuum Brochure
Tecnotion Ironless Vacuum BrochureElectromate
 
ACTOM Distribution Transformers.pdf
ACTOM Distribution Transformers.pdfACTOM Distribution Transformers.pdf
ACTOM Distribution Transformers.pdfThabang3
 
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...Thorne & Derrick International
 
Jmv presentation smart power transmission projects cea
Jmv  presentation  smart power transmission projects  ceaJmv  presentation  smart power transmission projects  cea
Jmv presentation smart power transmission projects ceaMahesh Chandra Manav
 
Worldwide Lightning called as Disaster not as Guest(SACHET)
Worldwide Lightning called as Disaster not as Guest(SACHET)Worldwide Lightning called as Disaster not as Guest(SACHET)
Worldwide Lightning called as Disaster not as Guest(SACHET)Mahesh Chandra Manav
 
Presentation lightning protection system by jmv lps
Presentation lightning protection system by jmv lpsPresentation lightning protection system by jmv lps
Presentation lightning protection system by jmv lpsMahesh Chandra Manav
 
Jmv presentation smart process plant -hurl 2017
Jmv  presentation  smart process plant -hurl 2017Jmv  presentation  smart process plant -hurl 2017
Jmv presentation smart process plant -hurl 2017Mahesh Chandra Manav
 
Pfisterer Connex - Cable Connectors & Systems For Medium Voltage Networks
Pfisterer Connex - Cable Connectors & Systems For Medium Voltage NetworksPfisterer Connex - Cable Connectors & Systems For Medium Voltage Networks
Pfisterer Connex - Cable Connectors & Systems For Medium Voltage NetworksThorne & Derrick UK
 
Solar power pv presentation by jmv lps ltd (2)
Solar power pv presentation by jmv lps ltd (2)Solar power pv presentation by jmv lps ltd (2)
Solar power pv presentation by jmv lps ltd (2)Mahesh Chandra Manav
 
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit CatalogueFlexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit CatalogueThorne & Derrick International
 
INTEGRATION OF SENSORS WITH KUKA ROBOT
INTEGRATION OF SENSORS WITH KUKA ROBOTINTEGRATION OF SENSORS WITH KUKA ROBOT
INTEGRATION OF SENSORS WITH KUKA ROBOTKirtimaan Srivastava
 
Hybrid battery +solar pv grid tie power project presentation by jmv lps
Hybrid battery +solar pv grid tie power project presentation by jmv lpsHybrid battery +solar pv grid tie power project presentation by jmv lps
Hybrid battery +solar pv grid tie power project presentation by jmv lpsMahesh Chandra Manav
 
Jmv presentation smart process plant (fertilizer)
Jmv  presentation  smart process  plant (fertilizer)Jmv  presentation  smart process  plant (fertilizer)
Jmv presentation smart process plant (fertilizer)Mahesh Chandra Manav
 
IRJET- Design, Modeling and Analysis of a Vacuum Chamber for High Speed T...
IRJET-  	  Design, Modeling and Analysis of a Vacuum Chamber for High Speed T...IRJET-  	  Design, Modeling and Analysis of a Vacuum Chamber for High Speed T...
IRJET- Design, Modeling and Analysis of a Vacuum Chamber for High Speed T...IRJET Journal
 

Similar to Training Course NX-Air Intro & Safety (20)

Training Adobe
Training AdobeTraining Adobe
Training Adobe
 
Tecnotion Ironless Vacuum Brochure
Tecnotion Ironless Vacuum BrochureTecnotion Ironless Vacuum Brochure
Tecnotion Ironless Vacuum Brochure
 
ACTOM Distribution Transformers.pdf
ACTOM Distribution Transformers.pdfACTOM Distribution Transformers.pdf
ACTOM Distribution Transformers.pdf
 
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
Flexicon Flexible Conduit Solutions and Fittings for Hazardous Area - Low Fir...
 
Jmv presentation smart power transmission projects cea
Jmv  presentation  smart power transmission projects  ceaJmv  presentation  smart power transmission projects  cea
Jmv presentation smart power transmission projects cea
 
Worldwide Lightning called as Disaster not as Guest(SACHET)
Worldwide Lightning called as Disaster not as Guest(SACHET)Worldwide Lightning called as Disaster not as Guest(SACHET)
Worldwide Lightning called as Disaster not as Guest(SACHET)
 
Presentation lightning protection system by jmv lps
Presentation lightning protection system by jmv lpsPresentation lightning protection system by jmv lps
Presentation lightning protection system by jmv lps
 
Jmv presentation smart process plant -hurl 2017
Jmv  presentation  smart process plant -hurl 2017Jmv  presentation  smart process plant -hurl 2017
Jmv presentation smart process plant -hurl 2017
 
Pfisterer Connex - Cable Connectors & Systems For Medium Voltage Networks
Pfisterer Connex - Cable Connectors & Systems For Medium Voltage NetworksPfisterer Connex - Cable Connectors & Systems For Medium Voltage Networks
Pfisterer Connex - Cable Connectors & Systems For Medium Voltage Networks
 
Epcos 5
Epcos 5Epcos 5
Epcos 5
 
Solar power pv presentation by jmv lps ltd (2)
Solar power pv presentation by jmv lps ltd (2)Solar power pv presentation by jmv lps ltd (2)
Solar power pv presentation by jmv lps ltd (2)
 
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit CatalogueFlexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
Flexicon Flexible Conduit - Hazardous Areas ATEX Conduit Catalogue
 
Standing type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unitStanding type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unit
 
Standing type GIS RMU
Standing type GIS RMUStanding type GIS RMU
Standing type GIS RMU
 
INTEGRATION OF SENSORS WITH KUKA ROBOT
INTEGRATION OF SENSORS WITH KUKA ROBOTINTEGRATION OF SENSORS WITH KUKA ROBOT
INTEGRATION OF SENSORS WITH KUKA ROBOT
 
Kaizenreport
KaizenreportKaizenreport
Kaizenreport
 
Product Catalogue
Product CatalogueProduct Catalogue
Product Catalogue
 
Hybrid battery +solar pv grid tie power project presentation by jmv lps
Hybrid battery +solar pv grid tie power project presentation by jmv lpsHybrid battery +solar pv grid tie power project presentation by jmv lps
Hybrid battery +solar pv grid tie power project presentation by jmv lps
 
Jmv presentation smart process plant (fertilizer)
Jmv  presentation  smart process  plant (fertilizer)Jmv  presentation  smart process  plant (fertilizer)
Jmv presentation smart process plant (fertilizer)
 
IRJET- Design, Modeling and Analysis of a Vacuum Chamber for High Speed T...
IRJET-  	  Design, Modeling and Analysis of a Vacuum Chamber for High Speed T...IRJET-  	  Design, Modeling and Analysis of a Vacuum Chamber for High Speed T...
IRJET- Design, Modeling and Analysis of a Vacuum Chamber for High Speed T...
 

More from Niels Inderbiethen

Equipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
Equipment Audits for LV, MV, HV for annual mandatory record keeping by NielsEquipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
Equipment Audits for LV, MV, HV for annual mandatory record keeping by NielsNiels Inderbiethen
 
Example of Substation Maintenance & Assessment Audits for Training - Niels In...
Example of Substation Maintenance & Assessment Audits for Training - Niels In...Example of Substation Maintenance & Assessment Audits for Training - Niels In...
Example of Substation Maintenance & Assessment Audits for Training - Niels In...Niels Inderbiethen
 
NX Air also Any other MV Training Index
NX Air also Any other MV Training IndexNX Air also Any other MV Training Index
NX Air also Any other MV Training IndexNiels Inderbiethen
 
ACTON Panel Door Design & Layout
ACTON Panel Door Design & LayoutACTON Panel Door Design & Layout
ACTON Panel Door Design & LayoutNiels Inderbiethen
 
Niels rfi publication_for_eskom-low_res
Niels rfi publication_for_eskom-low_resNiels rfi publication_for_eskom-low_res
Niels rfi publication_for_eskom-low_resNiels Inderbiethen
 
AS_TD_en_SAFE-Audit-Tools_1304
AS_TD_en_SAFE-Audit-Tools_1304AS_TD_en_SAFE-Audit-Tools_1304
AS_TD_en_SAFE-Audit-Tools_1304Niels Inderbiethen
 
Niels NX Air & Simoprime Product Trainer Certification
Niels NX Air & Simoprime Product Trainer CertificationNiels NX Air & Simoprime Product Trainer Certification
Niels NX Air & Simoprime Product Trainer CertificationNiels Inderbiethen
 
Niels SETA_SAQA Facilitator Accreditation
Niels SETA_SAQA Facilitator AccreditationNiels SETA_SAQA Facilitator Accreditation
Niels SETA_SAQA Facilitator AccreditationNiels Inderbiethen
 
Niels SETA_SAQA Electrical Assessor Accreditation
Niels SETA_SAQA Electrical Assessor AccreditationNiels SETA_SAQA Electrical Assessor Accreditation
Niels SETA_SAQA Electrical Assessor AccreditationNiels Inderbiethen
 

More from Niels Inderbiethen (10)

Equipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
Equipment Audits for LV, MV, HV for annual mandatory record keeping by NielsEquipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
Equipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
 
Example of Substation Maintenance & Assessment Audits for Training - Niels In...
Example of Substation Maintenance & Assessment Audits for Training - Niels In...Example of Substation Maintenance & Assessment Audits for Training - Niels In...
Example of Substation Maintenance & Assessment Audits for Training - Niels In...
 
NX Air also Any other MV Training Index
NX Air also Any other MV Training IndexNX Air also Any other MV Training Index
NX Air also Any other MV Training Index
 
ACTON Panel Door Design & Layout
ACTON Panel Door Design & LayoutACTON Panel Door Design & Layout
ACTON Panel Door Design & Layout
 
Niels rfi publication_for_eskom-low_res
Niels rfi publication_for_eskom-low_resNiels rfi publication_for_eskom-low_res
Niels rfi publication_for_eskom-low_res
 
AS_TD_en_SAFE-Audit-Tools_1304
AS_TD_en_SAFE-Audit-Tools_1304AS_TD_en_SAFE-Audit-Tools_1304
AS_TD_en_SAFE-Audit-Tools_1304
 
Niels NX Air & Simoprime Product Trainer Certification
Niels NX Air & Simoprime Product Trainer CertificationNiels NX Air & Simoprime Product Trainer Certification
Niels NX Air & Simoprime Product Trainer Certification
 
20130207111028094
2013020711102809420130207111028094
20130207111028094
 
Niels SETA_SAQA Facilitator Accreditation
Niels SETA_SAQA Facilitator AccreditationNiels SETA_SAQA Facilitator Accreditation
Niels SETA_SAQA Facilitator Accreditation
 
Niels SETA_SAQA Electrical Assessor Accreditation
Niels SETA_SAQA Electrical Assessor AccreditationNiels SETA_SAQA Electrical Assessor Accreditation
Niels SETA_SAQA Electrical Assessor Accreditation
 

Training Course NX-Air Intro & Safety

  • 1. © TRAINING COURSE COMPLIMENTS CATALOGUETRAINING COURSE COMPLIMENTS CATALOGUETRAINING COURSE COMPLIMENTS CATALOGUETRAINING COURSE COMPLIMENTS CATALOGUE NX-AIR PNX-AIR MNX-AIR
  • 2. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 2 25.09.2012 First Line Operation & Maintenance – Training Course Siemens Vacuum Switchgear Type "NX-Air W / M & P" Index INTRO An Introduction to Vacuum Technology A BRIEF INTRODUCTION TO THE SIEMENS VACUUM CIRCUIT BREAKER MANUFACTURING PROCESS AND A TECHNICAL OVERVIEW OF THE ARC PRINCIPLE AND DESIGN PHILOSOPHY BEHIND THE CONCEPT OF "VACUUM ARC INTERRUPTION" AND THE SCIENCE INVOLVED TO ACHIEVE ONE OF THE HIGHEST GRADES OF TRUE "HIGH QUALITY ELECTRICAL SWITCHING PRODUCTS" AVAILABLE TODAY… 1. Safety Instructions 2. NX-Air W / M & P Switchgear Description in an introductory slide-show format 3. NX-Air All Types Descriptive Catalogue 4. NX-Air M & P Contactor Panel 5. NX-Air & NX-Air P Circuit Breaker Panel 6. 3AH & K (new) Vacuum Circuit Breakers 7. Vacuum Circuit Breaker Type: 3AH-1 8. Vacuum Circuit Breaker Type: 3AH-3 9. Vacuum Circuit Breaker Type: 3AH-5 10. Breakers Interrupter Table, Harting plug description & Breaker-Mech Wiring Dwgs. 11. Sion Circuit Breaker Manual 12. Vacuum Contactor Slideshow 13. 3TL Vacuum Contactors Group Manual 14. 3TL 6 Vacuum Contactor Manual 15. 3TL 8 Vacuum Contactor Manual 16. Vacuum Contactor HR Fuse Types 17. Motorised Racking Manual for NX-Air M 18. Modular Metering & VT Truck Manual 19. Internal Arc Protection Scheme 20. Earthing Switch Operation for NX-Air P 21. Panel, C/B & Contactor Test Sheets 22. Circuit Schematic Drawing of Incomer 23. Circuit Schematic Drawing of Bus-section 24. Circuit Schematic Drawing of Meter Panel 25. Circuit Schematic Drawing of Feeder 26. Circuit Schematic Drawing of Motor Panel 27. Siemens Notepad / Drawing paper
  • 3. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 3 25.09.2012
  • 4. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 4 25.09.2012 Vacuum switching technology Arc quenching During the galvanic separation of the contacts, the current to break produces a metal-vapour arc discharge. The current flows through this metal-vapour plasma until the next current zero. Near the current zero, the arc extinguishes. The metal vapour loses its conductivity after few microseconds already the insulating capability of the contact gap recovers quickly. To maintain the metal-vapour arc discharge, a specific minimum current is required. If this minimum current is not reached, it will chop before the natural current zero. To prevent impermissible switching overvoltages while switching inductive circuits, the chopping current must be limited to the lowest possible values. Using a special contact material, the chopping current in vacuum circuit-breakers is just 2 to 3 A. Due to the fast recovery of the contact gap, the arc is safely quenched even if the contacts are separated right before a state of "current zero". Therefore, the arcing times in the last pole to clear are 15ms as a maximum. Depending on the breaking current and the interrupter dimensions, different contact geometries are used. Welcome to Siemens Technology The history of Siemens's manufacture of various types of circuit breakers recently achieved its first century. In the past hundred years a very thorough knowledge of all types of switching devices in every possible type of medium have been researched, tested and tried. So, it would be ironic if the technology which we now call "vacuum" was not discovered during the global space age. Unlike to normal air or mixtures of nitrogen and oxygen a vacuum presents the perfect forum for a safe switching environment being able to minimise arcing and contact burn.
  • 5. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 5 25.09.2012 Key to description of parts: IInntteerrrruupptteerr DDeessiiggnn The interrupters are of a very compact design as can be seen in the cross-section drawing provided. The area or volume of space occupied within the interrupter is at a perfect vacuum state. This would be the same as if switching the contacts in outer- space, where there is no air, as in "nitrogen" or "oxygen" which could contribute in any way to assist with ignition or explosive tendencies. This compact design of the Siemens vacuum interrupters provides a very high switching capacity in very compact dimensions: for example: vacuum interrupters for 15 kV/40 kA with housing dimensions of 125 mm diameter by 161 mm length, or for 12 kV/13.1 kA with 68 mm diameter by 115 mm length. A very high QA level has been achieved in the product market. This quality assurance is due mainly to Siemens following the TQM and DIN / ISO 9001 procedures & specifications, which call for rigorous material, manufacture & production checking. Every batch is checked & tested individually before delivery and only if the QA result is a 100% pass, are the interrupters released for delivery. Some of the tests that are performed include: testing of the interrupters for assuring the seal of vacuum sealing, testing for reliable long operation and long life, environmental protection involved in the manufacture of these vacuum interrupters and our guarantee to only use environmentally compatible materials, such as copper, ceramics and high-grade steel. Such, that the manufacturing processes do not damage the environment. (e.g. no CFC's are used in production (this fulfilling the Montreal agreement); also all the components are cleaned and kept free from micro-fibres & contamination in a ultrasonic plant, with the entire manufacturing line concealed in a protected atmosphere. Vacuum interrupters for the medium-voltage range are available from Siemens for all applications on the international market from 1 kV up to 40.5 kV. Vacuum Interrupters are also used in special design applications where the operational voltage that they are exposed to is well in excess of 40.5kV, even up to as high as 132kV. When used in these applications the interrupter is immersed in SF6 Gas within a pressurised chamber, so that the switching of "contacts" are still done within a vacuum inside the interrupter, but therefore in this application the entire interrupter itself is immersed and insulated by SF6 gas. This type of configuration enables using the same switching technology in much higher operational voltages. Applications: Vacuum interrupters are used in vacuum circuit breakers, vacuum switches, vacuum contactors, transformer tap changers, in circuit breakers for use in railway applications, auto-reclose switches, and lastly also in special applications such as nuclear fusion. Introduction to the Vacuum interrupters
  • 6. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 6 25.09.2012 Inside the Vacuum interrupter - The Manufacturing process To prove the atmospheric pressure, in 1654 Otto von Guericke created a vacuum with the Magdeburg hemispheres for the first time in history. More than 35 years ago, Siemens developed vacuum switching technology, leading it to series production. What was then a fundamental innovation has been developed further to a proven technology, which now has a worldwide market share of about 70 percent. Vacuum switching technology from Siemens meets all the requirements placed on circuit-breakers and contactors in medium-voltage switchgear up to 40.5 kV, and is now an integral part of many applications because of its clear advantages. The Siemens vacuum interrupters are manufactured inside the Siemens Factory in Berlin under various processes. We will briefly take you on a short journey through this process and discuss some of the important facts of how these vacuum interrupters are made until they are assembled in the form of a finished product such as a Contactor or vacuum circuit breaker. Contact rod processing In our numerically controlled multi-axis lathes, the raw parts are given the external contour and the slots of the contact carrier surface in just one single operation. The fully automatic process reduces the error rate to a minimum. A constantly high quality characterizes the produced parts. Contact material processing Siemens is the only manufacturer of vacuum interrupters worldwide to produce the contact material itself. The basic raw materials copper and chrome are combined to a powerful contact material by means of the arc-melting procedure. The resulting raw parts are processed to RMF or AMF contact discs, whereby the slotted AMF discs are de-bured at the end. All processing steps are electronically recorded for quality purposes. Metallography To fulfil the highest quality demands, samples of the contact material are examined by metallography. Here, the homogeneity of the contact material, the quality of the melting process as well as the brazed connection between the contact material and the contact rod are checked. Endurance test for bellows To enable them to meet the requirements for high endurance in real practice, the bellows are regularly subjected to an endurance test every three months. The test is carried out in a fully automatic test cabin with the travels adjusted to the respective type.
  • 7. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 7 25.09.2012 Vacuum interrupter assembly under clean-room conditions After having finished and cleaned the surfaces by electroplating and performed an optical inspection of the surface consistency of all single parts, the interrupter is assembled. The high-vacuum solder is applied at the joints of the components, the parts are aligned, and the interrupters are fixed. As cleanliness during assembly is especially important, all operations are done under air-conditioned "clean-room atmospheric" conditions – in this way we can guarantee a constantly high quality of the interrupters and maximum possible ratings up to 72 kA according to IEEE C37.013. High-vacuum brazing furnace In the high-vacuum brazing furnace, the joints of the vacuum interrupters are brazed at temperatures up to 900 °C and a press ure of 10-6 mbar. Thus, the interrupters fulfil the quality requirement “sealed for lifetime”. Thanks to the fully automatic production process, the high quality can be constantly reproduced at any time. X-ray test The evaluation of the interrupters by means of the X-ray procedure is used to verify the positions as well as the completeness of the internal components, and the quality of the brazing points. In this way we ensure the high quality of our products. Forming and high-voltage testing of vacuum interrupters During forming, the definitive internal dielectric strength of the vacuum interrupter is established with gradually increasing voltage, and this is verified by a subsequent lightning impulse voltage test. Both operations are done with higher values than those specified in the standards, as evidence of the extraordinary quality of the Siemens vacuum interrupters. This is the prerequisite for a long endurance and a high availability. Switching device production The switching device production is set up as a direct flow production. Various assemblies are prefabricated in parallel and combined at the mounting place of the switching device. The flow production reduces the order lead times and thus the delivery times of the switching devices to a minimum. Laser welding Laser welding provides a completely positive material joint between individual components – as a prerequisite for highly resistant, dynamically stress able assemblies such as the operating mechanism box. Its superiority over conventional welding becomes apparent, above all, by the fact that no hollows are produced – which would be susceptible to humidity – and that the material cannot loose shape anymore. The consequence: a high dimensional accuracy with the lowest tolerances possible – and thus, reduction of later adjustments to a minimum. Stamping and laser cutting In the pre-production, the steel plates are processed by highly automatic and highly productive stamping and laser cutting machines – providing the assured adherence to minimum tolerances, even with high quantities. The high degree of automation results in a process-safe, trouble-free production with short lead times, almost without any down time. Loading, operating and programming is possible with the machine running, without interrupting the production process.
  • 8. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 8 25.09.2012 Surface Treatment Electroplating is used to improve the material surfaces and to protect them against corrosion. By plating with a second material, the mechanical and electrical properties of the carrier materials are sustainably improved. This provides an optimised surface – which is decisive for a longer service life of the product and its permanently maintenance-free design. Final assembly of switching devices For all switching devices, the individual constructional units are pre- assembled in parallel. During final assembly, the different constructional units, the pole structure as well as the operating mechanism box are combined, and the device is equipped with the order-specific secondary system. Parallel work operations reduce the production lead time of the switching device to a minimum – sometimes even short-term customer requirements can still be implemented. Final inspection and testing of circuit-breakers After having passed the routine and high-voltage tests successfully, the circuit-breakers are inspected at the final testing station to detect visible sources of faults. The rating plate is not attached until this last visual inspection has been completed successfully, and then the circuit-breaker is released for dispatch. To reduce complaints to a minimum, the order is checked for completeness and conformity before leaving – after all, you are expecting quality in every detail. & finally the finished products:
  • 9. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 9 25.09.2012 The Electro- Magnetic Concept of how a Vacuum Interrupter works: Definition of a Vacuum Interrupter: A vacuum interrupter is an operable single contact that has been homogeneously sealed during its manufacture, in such a way that the atmosphere within the interrupter, which would normally be present around the contact surfaces, has been totally withdrawn or "sucked out" of the inside chamber and then simultaneously sealed immediately thereafter. In this sealed form there is then no atmosphere, particles that may be ionized, or any gases present that may contribute to igniting any type of flame or burning from an arc around any of these contact surfaces inside the interrupter. This making it almost impossible for any combustion or burning to take place during the arcing-time that would usually occur during an "on" or "off" operation of the circuit breaker. The interior part of the interrupter is therefore at total vacuum potential, i.e. equivalent to the conditions that would normally be found in outer-space. The top pole contact of the interrupter is usually fixed and the lower contact is the one which moves up and down to achieve the operation. The interrupters on a circuit breaker truck are usually 3 that are mounted side by side for the 3 phases usually required for industrial electrical operations on plants. Vacuum Interrupters are also hugely environmentally friendly, as they will maintain and contain all their lifetime of switching gasses and debris, inside their own sealed housing during their full service lifetime, which can range up to 25 years pending certain operational circumstances. During operation vacuum interrupters are also themselves not affected by the environment, as they have been completely sealed with special materials such as porcelain. Philosophy of the - In radial magnetic-field contacts, the arc burns diffusely until approx. 10 kA (momentary value). Higher currents burn across a contracted arc. In this case, local overheating of the contacts must be avoided. An additional magnetic field thus produces this required force, which makes the arc rotate on the arcing rings of the contacts via the magnetic field generated by the flow of current through the contact tips. Thus, contact erosion at the base point of the arc is distributed over the entire ring surface at a completely even rate.
  • 10. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 10 25.09.2012 Philosophy of the - In axial magnetic-field contacts, the arc remains diffuse, even with high currents due to the axial magnetic- field. The disc-type contact surfaces are uniformly stressed, and localised melting is avoided. In alternating- current circuit breakers, the actual function of the quenching system is to de-ionize the contact gap immediately after current zero. For all conventional quenching systems, this means that the arc must already be cooled before reaching the minimum quenching distance and the following current zero. Involuntarily, this increases the arc's power a lot (magnetic component), resulting in it responding better to following the magnetic field that develops between these two contact surfaces . In the case of vacuum circuit-breakers, however, the arc is not cooled down. The metal-vapour plasma is highly conductive. This results in a very small arc voltage ranging between 20 and 200 V. For this reason, and due to the short arcing times, the energy converted in the contact gap is very low. Because of this relatively low stress, the quenching system is maintenance-free. In stationary condition, the pressures in the interrupter is very low – less than 10-9 bar, so that contact distances of just 6 to 20 mm are required to reach a very high dielectric strength. Apart from circuit-breakers, the vacuum switching technology can also be used in contactors and other type of switches such as barrel switches. Today, more than 70% of all circuit-breakers installed in medium-voltage systems are based on vacuum switching technology. CROSS-SECTIONAL SIDE VIEW OF AN INTERRUPTER HIGH-SPEED CAMERA SHOTS OF THE "ARC DISSIPATION" ON A POLE CONTACT SURFACE OPENING UNDER REAL FULL-LOAD CONDITIONS
  • 11. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 11 25.09.2012 Maintenance and servicing Symbols used Operation symbol: Identifies an operation. Asks the operator to perform an operation. Result symbol: Identifies the result of an operation. 1.1 General instructions Independently of the safety instructions given in these operating instructions, the local laws, ordinances, guidelines and standards for operation of electrical equipment as well as for labour, health and environmental protection apply, and these are to be complied with, in line with the latest Regulations. All methodologies & actions applied to any services of the equipment or to repairs are to comply with specified methods as described and discussed in the Siemens specific procedure relevant to the equipment and parts in question. All work performed, whether on site or in the works, of whatever nature, must comply with the ACT. 1.2 The Five Golden Safety Rules of Electrical Engineering The Five Safety Rules of Electrical Engineering must generally be observed during operation of the products and components described in these operating instructions: Isolating. Securing against reclosing. Verifying safe isolation from all sources of supply. Earthing and short-circuiting methods are safe & can withstand kA rating. Covering, tagging and locking out of all adjacent live parts and shutters. 1.3 Delivery in line with Specifications The switchgear corresponds to the relevant laws, prescriptions and standards applicable at the time of delivery. If correctly used, they provide a high degree of safety by means of logical mechanical interlocks and shockproof metal enclosure of live parts.
  • 12. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 12 25.09.2012 1.4 Qualified personnel – Training and legalities Qualified personnel in accordance with these instructions, are persons certified or qualified to undertake this type of work, either by certification through some form of education, studies, or training, which can be backed up by a recognized certificate, degree, or letter of appointment. For such persons, or qualified Electrical Artisans, Technicians and Engineers, that are permitted by their organisations, the National Regulator, or any form of other legally acceptable appointments, who are similarly familiar with the regulatory requirements and the safe operational safety requirements of these products and also have the appropriate qualifications for this "type of work", must also obtain the necessary background knowledge about the transport, installation and commissioning of these products. Therefore these personnel must have also participated in this training course for "The first line safety, operation and maintenance" requirements of the Siemens air-insulated medium-voltage switchgear type "SIMOPRIME". The aim of this training, is that it provides a firm basis of "safety awareness, knowledge and understanding of the equipment" in the form of detailed information about the design, operation, installation, testing and troubleshooting of the SIMOPRIME switchgear. After successful participation, the participants of this training course get a certificate of Competence to operate and perform the first line maintenance for this "specific" type of equipment only, as the minimum required training for performing operations on specific electrical apparatus, or as usually specified under the regulation, the Act or by the D.O.L. The certificate for this course only authorises the participants to be appointed to "switch" or "operate" the Siemens "specific" equipment, but then also only after they have fully satisfied the D.O.L., the N.R.S., the Act & any other regulatory requirements required by the law, to perform "MV switching", within their specific "place of work", as the authorised or responsible person, and that he or she has been fully trained on all the precautions and dangers that are associated with this specific process. The certificate of this training will only allow the operator to switch "Siemens type Simoprime medium voltage switchgear" electrically, provided that he is certified on HV Regulations, has a letter of appointment to do this switching for and on behalf of his/her employer, and has been appointed by letter, as the Operational or Responsible person to do such. The attendee therefore acknowledges and realises, that by signing the attendance register, that it is up to his "own full responsibility" to ensure his/her understanding of the subject matter, credible certifications to perform the work and understand and apply the regulatory requirements, that are covered herein, so that at the end of this course, they do not leave the venue with any remaining questions or uncertainties, to ensure that he or she has satisfied their every curiosity, or remaining questions that they may have had, in terms of the Safety aspects of the operations and functions of this equipment. Siemens cannot be held liable, or will not accept any liability, or responsibility, for the direct or indirect actions of any customer staff, that are out of, or beyond our control, supervision, or deviate from any regulation, even if by accident or omission, or even if such procedures may be covered, yet have been misunderstood in this training course which has been presented. It is the attendees own responsibility at the end of this course to ensure that all the procedures and legal requirements of the NRS, the Act and any additional safety regulations, such that may be required by such as even their employer, are all implemented, understood and upheld before performing any work in the field. The Completion of this course does not authorize staff to be appointed to do any "Switching". This is a separate course on offer, which covers the regulations and the Act and is referred to as "High Voltage Switching Regulations Training". For further information about this training, please contact: Niels Inderbiethen, on cell – 072 287 4525, who will arrange for a quotation for the course to be held either on our, or the clients own premises. We wish you a pleasant learning experience in attending this Siemens Training Course… With our sincere thanks… from all of us… at… SIEMENS LTD SOUTH AFRICA Establishing safe conditions first, before the execution of any works
  • 13. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 13 25.09.2012 Furthermore, qualified personnel must have the following training and authorisation: Training and instruction or authorisation to switch on, switch off, earth and identify power circuits and equipment / systems as per the relevant safety standards (and the recently added new requirements by law, such as HV Reg's & legal appointments) Training and instruction about the relevant safety standards and the use of appropriate safety equipment specifically relevant to the equipment they will be switching (such as this course). Training in first aid and emergencies behaviour in the event of possible accidents or evacuation requirements relevant to their specific plant i.e. (plant specific)
  • 14. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 14 25.09.2012 1.5 Discussion of the features within the 3AH & K (New) operating mechanism. The operating mechanism is fitted with an integrated mechanical interlock which prevents dangerous switching conditions or operations from being carried out when the power is on. The operating mechanism unit is only found on trucks fitted with a circuit-breaker. The mechanism is fitted with isolating contacts that indicate the breaker position during racking. Mechanical interlocks are provided to safeguard the operator during racking procedures. Visual racking control status is provided with graphic representation. The operating mechanism is fitted with a closing solenoid allowing for remote "close" control. Mechanical indication of “closing spring charged” indicator can be seen through front of truck cover. The first shunt release coil, which is also used for remote tripping, is the electrical tripping solenoid which mechanically pushes against the trip lever that triggers the trip roller bearing. The mechanism is fitted with an operating cycle counter, which counts every open and then closed operation as one single operation increment on the counter. Other solenoids may also be additionally fitted to extend the conditions of the trip operations, these include under-voltage coils and uniquely driven shunt-trip coils. The circuit-breaker tripping signal can also be additionally routed through protection relays and logic contacts to extend the desired level of protection. The circuit breaker mechanism is fitted with an electrical anti-pumping device which prevents more than one auto re-closure, when the breaker is switched back on a fault that has still not cleared. Varistor module fitted for the auxiliary voltage W 60 V, the auxiliary switch has 6NO+6NC contacts. 1.6 Parts of the 3AH5 circuit breaker operating mechanism:
  • 15. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 15 25.09.2012 1.7 Nameplate:
  • 16. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 16 25.09.2012 1.8 SION vacuum circuit breaker. Component Identifications: Part identification & features of the SION Operating Mechanism. Component Identifications:
  • 17. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 17 25.09.2012 Maintenance and servicing 1.9 General Maintenance The vacuum circuit-breakers / contactors switchgear are maintenance-free within the scope of the permissible number of operating cycles. Under normal environmental and operating conditions the maintenance intervals are longer than five years. Built-in equipment such as voltage transformers, current transformers, relays, meters, protection equipment, etc. must be serviced and maintained as specified in the associated operating instructions. Commercially available tools are sufficient for carrying out the maintenance work. After maintenance, put the equipment again into operation as per the operating instructions. Carry out maintenance and servicing at shorter intervals (to be specified by the owner) if there is a lot of dust, or if the air is extremely humid and/or polluted. Grease main fixed contacts of bushings and fixed contacts of earthing switches as well as other surfaces exposed to friction (e.g. shutter operating linkage, guide rails) at shorter intervals (to be specified by the owner): Tin of Long-term 2 grease (8BX1022). Independently of the regular maintenance, immediately determine the cause of faults and short circuits and replace any damaged components. Maintenance intervals The maintenance intervals described hereafter are a recommendation when the switchgear is operated under normal environmental conditions. In case of extreme operating conditions the maintenance intervals must be adjusted accordingly. Annual maintenance Carry out general check for damages, dust layers, humidity in the switchpanels, and for partial discharge noises. Check whether accessories are complete and in good condition (including the truck). Maintenance after five years Operate earthing switches for test. Clean switchpanels. Check function of switchpanels and put switchgear again into operation. Check primary connections of current and voltage transformers. Check bolted joints (see "Installation", Section 9.2, Page 32). SAFETY FIRST - Maintenance of vacuum circuit-breaker / vacuum contactor Preconditions: • Supply voltage switched off • Circuit-breaker in OPEN position • Spring not charged
  • 18. NX-Air_M_P Training Intro Doc Sasol.doc 1006884 - N. Inderbiethen Page 18 25.09.2012 Niels Inderbiethen Specialist – Technical Support FAC/ASS ETDPSETA SAQA AcrNo:ATS/12/2838 MCS (Metering) & PTI (Training) Services SG Services (Smart Grid) Siemens Southern Africa IC Sector (Infrastructure & Cities) Newmarket Street, Northriding T: +27 10 222 7315 F: +27 86 506 5941 M: +27 72 287 4525 niels.inderbiethen@siemens.com www.siemens.co.za - END OF THIS TRAINING ADDENDUM MANUAL - NNB (PLEASE REFER TO THE DIFFERENT NX-AIR W, M&P SWITCHGEAR PANEL DOCUMENTATION FOR A FULL DESCRIPTION OF RACKING IN THE RACKING ORR MOTORISED RACKING OPERATIONAL PROCEDURES. ADDITIONAL INFORMATION ON THE CIRCUIT EXAMPLE DRAWINGS FOR THE CUSTOMERS SWITCHBOARD (SINGLE LINE DRAWINGS AND THE 3AH CIRCUIT BREAKERS WIRING DIAGRAMS) IS ALSO PROVIDED IN THE LAST SECTIONS, SECTIONS 22-26 OF THIS MANUAL)