2. 2
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
•One fan = Several dwellings
•Outside the dwellings
• Multi flat residential buildings
3. 3
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• Portfolio overview
HAT VTR VCR
Three products existing, each of them is declined in several versions
All projects needs are covered
4. 4
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• Airflows & pressures
HAT VTR VCR
Number of models 7 2 4
Max airflow (m3/h) 1500 700 3500
Max Pressure (Pa) 140 140 140 to 400
5. 5
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• Airflows & pressures
Airflow (m3/h)
Pressure (Pa)
VCR
0 700 1100 3500
140
400
VTR HAT
HAT
VTR
6. 6
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• Acoustic settings
HAT VTR VCR
Number of models 7 2 4
Max sound pressure
level Lp @ 3 m (dB(A))
Please refer to technical lefleafts
Max power
consumption (W/m3/h)
1701 1701 4001
1These values are given for the maximum speed rotation of the motor, which is not representative of the real consumption that
is always lower in real conditions (for more details, see our datasheets)
7. 7
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• Installation
HAT VTR VCR
Installation Outdoor Outdoor Outdoor and indoor
Orientation Horizontal Horizontal
Horizontal & vertical (only
inside)
Airflow orientation Horizontal Vertical Horizontal
Vibration isolator
Embedded into the fan base
(to be ordered separately)
Under the EC-motor -
Localisation New and refurbished buildings
New & renovation ; residential
and non residential buildings
8. 8
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• Maintenance
In case of maintenance the motor is
protected by the top cover
Top cover can be dismounted by unscrewing
4 screws
Impeller can be cleaned very easily
9. 9
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• Operating
Electronic commutation motor for minimal consumption with
permanent magnets
The electronic commutation motor used here offers an
optimum consumption all the time. Associated to the pressure
control device, it automatically adjusts the consumed power
to the requested airflow, while maintaining a constant
pressure.
10. 10
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• Pressure control
Standard codes are classified in two ways according to the existing regulation :
MD HD
400140
11. 11
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• MD – Manual Drive regulation
Fan speed potentiometer
(0 to 100% of the fan power)
Fan control connectors
(0-10V signal)
Fan power supply connectors
Power supply wires
12. 12
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• HD – Hygro dynamic regulation
Pressure setting (0-140Pa)
Power supply wires Pressure sensors
(HD)
Fan power supply connectors
Fan control connectors
(0-10V signal)
13. 13
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• Main competitive advantages
•Low energy consumption: EC motor associated with an automatic
pressure control device for HD versions
•Sturdiness and reliability: galvanized steel sheet construction
•Easy to install: a wide range for different installation place
•DCV compatible: built-in automatic pressure control device to optimize
DCV performance.
•Silent: acoustic foam and motor’s isolation to prevent vibrations
•Easy to maintain: the access to the impeller is optimized
•Pioneering square design : HAT square shape is under patent
14. 14
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• Accessories & Fan bases for HAT
1st step : chose the correct fan base for HAT fans (SBC)
Acoustic fan base is not included with HAT : must be ordered separately
How to chose the correct fan base ? Based on the fan name
2nd step : Chose the correct acoustic duct (SAS which are recommanded with SBC
base) or (SNS) (optionnal)
15. 15
SBC-250-160-C-EX
SBC-250-200-C-EX
SBC-250-250-C-EX
RANGE : MECHANICAL EXHAUST VENTILATION COLLECTIVE TREATMENT
• Acoustic fan bases for HAT
B, C and D are
the size of the fan
base
SBC-250-100-B-EX
SBC-250-125-B-EX
SBC-250-160-B-EX
SBC-250-200-B-EX
HAT-100-B HAT-125-B HAT-160-B
Ød : Duct diameter Ød : Duct diameter
HAT-160-C HAT-200-C HAT-250-C