ailstorm losses in the U.S.
exceeded $924 million in
2010, according to the
NationalOceanicandAtmos-
pheric Administration.1
For
the second year in a row, the
Dallas-Ft. Worth area suffered a severe hail-
storm in June 2012. Damage estimates pre-
dict the first billion-dollar loss to the insur-
ance companies in a single hailstorm event,
reported the Insurance Council of Texas.2
“This will be up there in the rankings of
Dallas’s worst hailstorm in ten years,” said
Nick Hampshire with the National Weather
Service.3
Massive amounts of roof damage assess-
ments were produced overnight, while some
were still performing work from the previous
year’s storm. Catastrophic losses of this
order of magnitude present the opportuni-
ty to evaluate the performance of different
roofing systems to impact resistance in
a central location. The largest hail was
centered in the Lakewood area of Dallas.
Tile roofs on historic Swiss Avenue were
completely destroyed, as well as thousands
of automobiles and even the greens on the
Lakewood Country Club.
Low-Slope Roofing
Some steep- and low-
slope roofs will show all
of the damage from hail
immediately, although TPO
and PVC roof membranes
do not reveal all of the dam-
age instantly. Pockmarking
with the loss of granules and asphalt-top
coating is easily visible the day the damage
occurs on asphalt shingles and modified-
bitumen cap sheets. Damage to PVC and
TPO membranes underneath the weath-
ering side of the scrim will not breach
the top of the sheet promptly. Differential
movement and thermal cycles will need to
take their course for the damage to surface
visually.4
If the building owner initiates a
claim and the adjuster inspects the roof
immediately, a complete assessment of the
hail damage is not possible.
PVC roof membranes have improved
from the thin-profiled membranes of the
’80s but are still performing poorly for
impact resistance. ASTM Subcommittee
D08.18 is currently working on a revision
for ASTM Standard D6878 titled Standard
Specification for Thermoplastic Polyolefin-
Based Sheet Roofing. The new standard
would ensure that the added thickness
would include more polymeric coating on
16 • In t e r f a c e 	Fe b r u a r y 2013
Photo 1 – Damage to exhaust fan at
modified bitumen roof system.
Photo 2 – Aggregate-surfaced BUR
and modified-bitumen comparison.
the weathering side of the TPO sheet.5
Consideration should be given for
a similar proposal for PVC roofing membranes.
From observing damage to low-slope roofs, it is apparent that aggre-
gate-surfaced BUR and ballasted single-ply roofs performed best in the
worst-hit areas. The heavy flood coat of asphalt and gravel ballast protects
the underlying plies of fiberglass felts in BUR roofs against large hail. The
presence of the large ballast stones above the EPDM membrane presents
a hard “line of defense” from the attacking
hail. On a strip center in the hardest-hit
area, a white granule-surfaced modified-
bitumen roof system showed thousands
of pocked marks, while the aggregate-
surfaced BUR roof adjacent to the white
granule-surfaced modified-bitumen roof
showed no signs of damage to the field of
the roof. All mechanical equipment revealed
equivalent damage, and only minor damage
was observed to the wall and curb flashings
of the aggregate-surfaced BUR roof (Figures
1, 2, 3, and 4).
Fully adhered EPDM membranes have
historically performed well for impact resis-
tance in test laboratories conducted by the
EPDM Roofing Association, National Insti-
tute of Standards and Technology, Under-
writers Laboratory, Factory Mutual, and
ASTM. Using either steel darts or ice
spheres, 60-mil field-aged EPDM samples
were not damaged in 96% of the testing
when impacted with 3-in. hail balls.6
With
the attention of owners drawn towards “cool
roofing,” it’s difficult to find a black EPDM
roof to observe in this area following a hail
event. RICOWI did not observe any black
EPDM membranes in its 2011 investigation.
Impact resistance can be improved by
installing a more rigid cover board with a
higher compressive strength. The conven-
Fe b r u a r y 2013	 In t e r f a c e • 17
•	 Clear	polycarbonate	dome	cover	coated	for	UV	resistance
•	 Translucent	and	double	domes	available	when	specified
•	 Fully	gasketed	design	ensures	weathertightness
•	 The	safe	and	reliable	operation	that	you	have		 	
come	to	expect	from	a	Bilco	roof	hatch
To learn more, visit www.bilco.com
or call 800.366.6530
It’s a Roof Hatch... It’s a Skylight...
It’s a Bilco.
Type GS Roof Hatch
All the security and convenience of a roof
hatch with the added benefits of a skylight.
The Worldwide Source for
Specialty Access Products
The natural daylight is ideal for ladder access
roof hatches located in stairwells or closets.
Also	offered	in	sizes	for	staircase	access	and	special	sizes	are	
available	for	unique	access	requirements.
BLC743 Interface GS Ad.indd 1 1/24/12 9:46 AM
Photo 3 – Hail damage to modified roof system.
Photo 4 – Damage to exhaust fan
at aggregate surfaced BUR.
18 • In t e r f a c e 	Fe b r u a r y 2013
tional perlite cover board on hot asphalt-
applied roofing transfers the impact
throughout the roof assembly. A few man-
ufacturers of modified-bitumen roofing offer
a sheet with a 180-gram polyester or fiber-
glass scrim. The enhanced sheet, in a two-
ply application on top of a rigid cover board,
creates a dynamic puncture resistance that
can be covered under some manufacturers’
warranties for up to 4-in. hail.
Steep-Slope Roofing
The frequency of large hail events in the
Dallas-Ft. Worth area is alarming. Roofs
in areas of Coppell, Texas, were totaled
by hail two years in a row, after being
reroofed in 2003 following hail damage.
That’s three roof replacements in nine
years, and concerns have been raised about
the integrity of the decking being com-
promised from the repeated damage from
shingle and underlayment removal. Many
track housing and apartment complexes in
this region have 3/8-in. plywood decking.
The thin decking—coupled with standard
fiberglass-impregnated shingles—are a poor
roof assembly, given the repeated hail-
storms in the area.
RICOWI has yet to complete this year’s
report, although the 2011 Report #1 showed
superior performance of modified-bitumen
shingles. State Farm offers a 21-25% dis-
count on premiums to homeowners who
install impact-resistance (IR) class 4 shin-
gles conforming to UL 2218. Hailstones of
0.25 in. to 2.5 in. diameter revealed surface
impact marks without fractures or minimal
damage on 75% of the IR roofs observed
in the RICOWI 2011 hail investigation.
Standard fiberglass-impregnated asphalt
shingles showed moderate to severe damage
with hailstones 1.25 in. or larger in 93% of
the observations conducted by RICOWI in
2011.7
Stone-coated steel performs well, with
hailstones up to 2.5 in. causing no apparent
damage. Similar results have been reported
with synthetic slate (shingles) and up to
2-in. hail, and metal roofs uniformly “dim-
ple,” causing a more aesthetic issue than a
waterproofing problem (Figure 5). Concrete
and clay tile fare well overall, with 2-in. hail
causing only a few broken tiles; however,
the slate and tile roofs in the Lakewood area
were beat to small pieces from 4-in. hail
(Figure 6). All the roofs were immediately
covered with tarps.	
Economic and Environmental
Impact
The economic impact of a hailstorm is
extremely beneficial to numerous trades,
services, and manufacturing. Supply hous-
es add warehouse, sales, and delivery per-
sonnel. Roofing manufacturing plants add
a second or maybe a third shift. Deposits
in the local banks soar, as do truck sales.
(If only politicians could take credit for the
sudden jobs created by inclement weather,
they might get reelected every year.)
Although the economic impact to some
trades may be beneficial, there is a down-
side. In the chaos, unscrupulous start-up
contractors and scam artists converge on
the public. White-collar thieves have col-
lected insurance checks and disappeared,
leaving homeowners with no roofs or funds
to replace them. Others have received slop-
py workmanship that does not reveal itself
until heavy rains months later. Few manda-
tory roof inspections are performed in any
Photo 5 – Damage to copper
standing seam.
Photo 6 – Damage to concrete tile.
municipality in North Texas on residential
roofs. How can this industry go unchecked?
Professional roofing contractors belonging
to the Roofing Contractors Association of
Texas (RCAT) have taken the liberty of insti-
tuting a registration of their membership in
an attempt to bring stability and to educate
the public without governmental involve-
ment. The United Association of Storm
Restoration Contractors is a nonprofit orga-
nization dedicated to informing homeown-
ers in order to prevent contractor fraud.
Another downside to the economic
impact is the obvious increase in insurance
premiums. In recent years, insurance com-
panies have raised deductibles dramatically
in hail-prone areas to combat losses.
As for the environmental impact of past
error and waste in the industry, look in the
landfills. There are several companies in the
Dallas-Ft. Worth area offering the service of
recycling of asphalt shingles. Manufacturer
sponsorship, along with contractor partic-
ipation, is vital to promote the responsible
disposal of asphalt roofing products. Savvy
contractors should showcase the recycling
of the roofing debris in their bids to home-
owners. Roof consultants should consider
including recycling in specifications.
Not all roof coverings are included
in this article, just the roofs this author
encountered during the 2012 Dallas-Ft.
Worth hailstorm. When specifying a roof
system in this region, it would be prudent
to consider impact resistance along with all
the factors it takes to design a successful
roofing system.
References
1.	 National Oceanic and Atmospheric
Administration.
2.	 Insurance Council of Texas.
3.	 Dallas Morning News, June 2011.
4.	 Lyle D. Hogan, FRCI, PE, “A Proposal
for Uniformly Assessing Hail Dam-
age to Roofs,” Interface, RCI, Inc.,
October 2006.
5.	Walter Rossiter, “Many Standards
Impacted by Recent Actions of ASTM
Technical Committee D08 on Roofing
and Waterproofing,” Interface, RCI,
Inc., August 2012.
6.	 Jim D. Koontz, RRC, PE; and Thomas
W. Hutchinson, FRCI, RRC, AIA, CSI;
“Hail Impact Testing of EPDM Roof
Assemblies,” Proceedings of the RCI
24th International Convention and
Trade Show, March 12-17, 2009.
7.	 RICOWI, Inc., Hailstorm Investigation
Dallas/Ft. Worth, May 24, 2011.
American Hydrotech, Inc. 303 East Ohio | Chicago, IL 60611 | 800.877.6125 | www.hydrotechusa.com
© 2013 Monolithic Membrane 6125 is a registered trademark of American Hydrotech, Inc.
Monolithic Membrane 6125, the original rubberized
asphalt membrane, has been entrusted with keeping
high profile structures across the country and around
the globe watertight for 50 years. More than 2
billion square feet of membrane is still performing
today as it did the day it was installed.
50 YEARS OF PROVEN PERFORMANCE - MONOLITHIC MEMBRANE 6125®
RCI-50-Half-Horiztonal.indd 1 12/11/2012 5:15:41 PM
Fe b r u a r y 2013	 In t e r f a c e • 19
Keith Simmons has been a Registered Roof Observer for
DryTec Moisture Protection Technologies for the past seven
years. Prior to that, he was a roofing contractor in the North
Texas area for 23 years. He has evaluated hail damage events
from 1982, 1988, 1992, 1995, 2003, 2011, and 2012.
Keith Simmons, RRO

More Related Content

What's hot

The Mallett Deep Energy Retrofit
The Mallett Deep Energy RetrofitThe Mallett Deep Energy Retrofit
The Mallett Deep Energy RetrofitEnergy Circle
 
Premium Plastisol Finishes for Metal Building Components
Premium Plastisol Finishes for Metal Building ComponentsPremium Plastisol Finishes for Metal Building Components
Premium Plastisol Finishes for Metal Building ComponentsKen Madren
 
Dow Corning & Wintech Riverlight Case Study
Dow Corning & Wintech Riverlight Case StudyDow Corning & Wintech Riverlight Case Study
Dow Corning & Wintech Riverlight Case StudyWintech
 
Linear Systems - Expansion and Movement Joints
Linear Systems - Expansion and Movement JointsLinear Systems - Expansion and Movement Joints
Linear Systems - Expansion and Movement JointsAli Asgar Raja
 
White Paper_Bin Roof Maintenance
White Paper_Bin Roof MaintenanceWhite Paper_Bin Roof Maintenance
White Paper_Bin Roof MaintenanceJack Kenney
 
GEODOMAS_STRUCTURAL_GLAZING_FAÇADE
GEODOMAS_STRUCTURAL_GLAZING_FAÇADEGEODOMAS_STRUCTURAL_GLAZING_FAÇADE
GEODOMAS_STRUCTURAL_GLAZING_FAÇADEGeodomas Engineering
 
Moving Towards More Energy Efficient Wood Frame Building Enclosures
Moving Towards More Energy Efficient Wood Frame Building EnclosuresMoving Towards More Energy Efficient Wood Frame Building Enclosures
Moving Towards More Energy Efficient Wood Frame Building EnclosuresRDH Building Science
 
Dynamic Shells 2009 International P P S Large Size
Dynamic Shells 2009  International    P P S Large SizeDynamic Shells 2009  International    P P S Large Size
Dynamic Shells 2009 International P P S Large SizeMK
 
4ftbsys EEF catalogue
4ftbsys EEF catalogue4ftbsys EEF catalogue
4ftbsys EEF catalogueLeads Facade
 

What's hot (11)

The Mallett Deep Energy Retrofit
The Mallett Deep Energy RetrofitThe Mallett Deep Energy Retrofit
The Mallett Deep Energy Retrofit
 
Premium Plastisol Finishes for Metal Building Components
Premium Plastisol Finishes for Metal Building ComponentsPremium Plastisol Finishes for Metal Building Components
Premium Plastisol Finishes for Metal Building Components
 
Dow Corning & Wintech Riverlight Case Study
Dow Corning & Wintech Riverlight Case StudyDow Corning & Wintech Riverlight Case Study
Dow Corning & Wintech Riverlight Case Study
 
Linear Systems - Expansion and Movement Joints
Linear Systems - Expansion and Movement JointsLinear Systems - Expansion and Movement Joints
Linear Systems - Expansion and Movement Joints
 
White Paper_Bin Roof Maintenance
White Paper_Bin Roof MaintenanceWhite Paper_Bin Roof Maintenance
White Paper_Bin Roof Maintenance
 
GEODOMAS_STRUCTURAL_GLAZING_FAÇADE
GEODOMAS_STRUCTURAL_GLAZING_FAÇADEGEODOMAS_STRUCTURAL_GLAZING_FAÇADE
GEODOMAS_STRUCTURAL_GLAZING_FAÇADE
 
Moving Towards More Energy Efficient Wood Frame Building Enclosures
Moving Towards More Energy Efficient Wood Frame Building EnclosuresMoving Towards More Energy Efficient Wood Frame Building Enclosures
Moving Towards More Energy Efficient Wood Frame Building Enclosures
 
Atlanta Sample Home Inspection Report
Atlanta Sample Home Inspection ReportAtlanta Sample Home Inspection Report
Atlanta Sample Home Inspection Report
 
Dynamic Shells 2009 International P P S Large Size
Dynamic Shells 2009  International    P P S Large SizeDynamic Shells 2009  International    P P S Large Size
Dynamic Shells 2009 International P P S Large Size
 
4ftbsys EEF catalogue
4ftbsys EEF catalogue4ftbsys EEF catalogue
4ftbsys EEF catalogue
 
Answers
AnswersAnswers
Answers
 

Viewers also liked

Viewers also liked (11)

UNCCD Short Guide for Chairs
UNCCD Short Guide for ChairsUNCCD Short Guide for Chairs
UNCCD Short Guide for Chairs
 
Simmons Nov 2014
Simmons Nov 2014Simmons Nov 2014
Simmons Nov 2014
 
Madres de plaza de Mayo
Madres de plaza de MayoMadres de plaza de Mayo
Madres de plaza de Mayo
 
Quiet woods counseling
Quiet woods counselingQuiet woods counseling
Quiet woods counseling
 
Defense PPT
Defense PPTDefense PPT
Defense PPT
 
Serendipity
SerendipitySerendipity
Serendipity
 
Defense ppt
Defense pptDefense ppt
Defense ppt
 
UNCCD CSOs Guide
UNCCD CSOs GuideUNCCD CSOs Guide
UNCCD CSOs Guide
 
Supercapacitor module applications for customers
Supercapacitor module applications for customersSupercapacitor module applications for customers
Supercapacitor module applications for customers
 
Social media ecosystem presentation
Social media ecosystem presentationSocial media ecosystem presentation
Social media ecosystem presentation
 
SMARTboard
SMARTboardSMARTboard
SMARTboard
 

Similar to Simmons Feb 13

Bilal Hamm Writing sample
Bilal Hamm Writing sampleBilal Hamm Writing sample
Bilal Hamm Writing sampleBilal N. Hamm
 
Asv 21st century tile roofs 2008-10-vandewater
Asv 21st century tile roofs 2008-10-vandewaterAsv 21st century tile roofs 2008-10-vandewater
Asv 21st century tile roofs 2008-10-vandewaterCool Roof Innovations
 
Part 3.Ul Fs Power Point Pdf
Part 3.Ul Fs Power Point PdfPart 3.Ul Fs Power Point Pdf
Part 3.Ul Fs Power Point Pdfccseerc
 
Nano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower StallNano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower StallIndustrial Solutions USA
 
Metal Roofs by Drawdy Roofing
Metal Roofs by Drawdy RoofingMetal Roofs by Drawdy Roofing
Metal Roofs by Drawdy RoofingVince Dettore
 
Green Roofing Picture Portfolio
Green Roofing Picture PortfolioGreen Roofing Picture Portfolio
Green Roofing Picture Portfolioharleyguy
 
RCMA Reflective Coatings One-Pager
RCMA Reflective Coatings One-PagerRCMA Reflective Coatings One-Pager
RCMA Reflective Coatings One-PagerChelsea Ritchie
 
Commercial Flat Roofing: Components and Damage Assessment
Commercial Flat Roofing: Components and Damage AssessmentCommercial Flat Roofing: Components and Damage Assessment
Commercial Flat Roofing: Components and Damage AssessmentDenis Koval
 
New Aia Hurricane 2007
New Aia Hurricane 2007New Aia Hurricane 2007
New Aia Hurricane 2007jbgask
 
INDUSTRIAL PRESSURE WASHING DETROIT, MI.pptx
INDUSTRIAL PRESSURE WASHING DETROIT, MI.pptxINDUSTRIAL PRESSURE WASHING DETROIT, MI.pptx
INDUSTRIAL PRESSURE WASHING DETROIT, MI.pptxMarcusColin
 
white_green_booklet
white_green_bookletwhite_green_booklet
white_green_bookletTim Kikot
 
Technical Paper No 2
Technical Paper No 2Technical Paper No 2
Technical Paper No 2Jerry Solov
 
12 Roof Edge Tips & Tricks
12 Roof Edge Tips & Tricks12 Roof Edge Tips & Tricks
12 Roof Edge Tips & TricksMetal-Era
 
Part one audio demonstration
Part one audio demonstrationPart one audio demonstration
Part one audio demonstrationAdrian Haberhauer
 
Soil Issues for Residential Construction in Texas
Soil  Issues for Residential Construction in TexasSoil  Issues for Residential Construction in Texas
Soil Issues for Residential Construction in TexasWayne Caswell
 

Similar to Simmons Feb 13 (20)

SAAH MAR 2014
SAAH MAR 2014SAAH MAR 2014
SAAH MAR 2014
 
Bilal Hamm Writing sample
Bilal Hamm Writing sampleBilal Hamm Writing sample
Bilal Hamm Writing sample
 
Asv 21st century tile roofs 2008-10-vandewater
Asv 21st century tile roofs 2008-10-vandewaterAsv 21st century tile roofs 2008-10-vandewater
Asv 21st century tile roofs 2008-10-vandewater
 
Acrylic Roofing
Acrylic  Roofing Acrylic  Roofing
Acrylic Roofing
 
Part 3.Ul Fs Power Point Pdf
Part 3.Ul Fs Power Point PdfPart 3.Ul Fs Power Point Pdf
Part 3.Ul Fs Power Point Pdf
 
CIB Publication 405
CIB Publication 405CIB Publication 405
CIB Publication 405
 
Nano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower StallNano-Clear Protects Concrete Block in Shower Stall
Nano-Clear Protects Concrete Block in Shower Stall
 
Metal Roofs by Drawdy Roofing
Metal Roofs by Drawdy RoofingMetal Roofs by Drawdy Roofing
Metal Roofs by Drawdy Roofing
 
Green Roofing Picture Portfolio
Green Roofing Picture PortfolioGreen Roofing Picture Portfolio
Green Roofing Picture Portfolio
 
RCMA Reflective Coatings One-Pager
RCMA Reflective Coatings One-PagerRCMA Reflective Coatings One-Pager
RCMA Reflective Coatings One-Pager
 
Commercial Flat Roofing: Components and Damage Assessment
Commercial Flat Roofing: Components and Damage AssessmentCommercial Flat Roofing: Components and Damage Assessment
Commercial Flat Roofing: Components and Damage Assessment
 
New Aia Hurricane 2007
New Aia Hurricane 2007New Aia Hurricane 2007
New Aia Hurricane 2007
 
INDUSTRIAL PRESSURE WASHING DETROIT, MI.pptx
INDUSTRIAL PRESSURE WASHING DETROIT, MI.pptxINDUSTRIAL PRESSURE WASHING DETROIT, MI.pptx
INDUSTRIAL PRESSURE WASHING DETROIT, MI.pptx
 
Roof maintenance
Roof maintenanceRoof maintenance
Roof maintenance
 
RoofWhiteningSummary
RoofWhiteningSummaryRoofWhiteningSummary
RoofWhiteningSummary
 
white_green_booklet
white_green_bookletwhite_green_booklet
white_green_booklet
 
Technical Paper No 2
Technical Paper No 2Technical Paper No 2
Technical Paper No 2
 
12 Roof Edge Tips & Tricks
12 Roof Edge Tips & Tricks12 Roof Edge Tips & Tricks
12 Roof Edge Tips & Tricks
 
Part one audio demonstration
Part one audio demonstrationPart one audio demonstration
Part one audio demonstration
 
Soil Issues for Residential Construction in Texas
Soil  Issues for Residential Construction in TexasSoil  Issues for Residential Construction in Texas
Soil Issues for Residential Construction in Texas
 

Simmons Feb 13

  • 1. H ailstorm losses in the U.S. exceeded $924 million in 2010, according to the NationalOceanicandAtmos- pheric Administration.1 For the second year in a row, the Dallas-Ft. Worth area suffered a severe hail- storm in June 2012. Damage estimates pre- dict the first billion-dollar loss to the insur- ance companies in a single hailstorm event, reported the Insurance Council of Texas.2 “This will be up there in the rankings of Dallas’s worst hailstorm in ten years,” said Nick Hampshire with the National Weather Service.3 Massive amounts of roof damage assess- ments were produced overnight, while some were still performing work from the previous year’s storm. Catastrophic losses of this order of magnitude present the opportuni- ty to evaluate the performance of different roofing systems to impact resistance in a central location. The largest hail was centered in the Lakewood area of Dallas. Tile roofs on historic Swiss Avenue were completely destroyed, as well as thousands of automobiles and even the greens on the Lakewood Country Club. Low-Slope Roofing Some steep- and low- slope roofs will show all of the damage from hail immediately, although TPO and PVC roof membranes do not reveal all of the dam- age instantly. Pockmarking with the loss of granules and asphalt-top coating is easily visible the day the damage occurs on asphalt shingles and modified- bitumen cap sheets. Damage to PVC and TPO membranes underneath the weath- ering side of the scrim will not breach the top of the sheet promptly. Differential movement and thermal cycles will need to take their course for the damage to surface visually.4 If the building owner initiates a claim and the adjuster inspects the roof immediately, a complete assessment of the hail damage is not possible. PVC roof membranes have improved from the thin-profiled membranes of the ’80s but are still performing poorly for impact resistance. ASTM Subcommittee D08.18 is currently working on a revision for ASTM Standard D6878 titled Standard Specification for Thermoplastic Polyolefin- Based Sheet Roofing. The new standard would ensure that the added thickness would include more polymeric coating on 16 • In t e r f a c e Fe b r u a r y 2013 Photo 1 – Damage to exhaust fan at modified bitumen roof system. Photo 2 – Aggregate-surfaced BUR and modified-bitumen comparison.
  • 2. the weathering side of the TPO sheet.5 Consideration should be given for a similar proposal for PVC roofing membranes. From observing damage to low-slope roofs, it is apparent that aggre- gate-surfaced BUR and ballasted single-ply roofs performed best in the worst-hit areas. The heavy flood coat of asphalt and gravel ballast protects the underlying plies of fiberglass felts in BUR roofs against large hail. The presence of the large ballast stones above the EPDM membrane presents a hard “line of defense” from the attacking hail. On a strip center in the hardest-hit area, a white granule-surfaced modified- bitumen roof system showed thousands of pocked marks, while the aggregate- surfaced BUR roof adjacent to the white granule-surfaced modified-bitumen roof showed no signs of damage to the field of the roof. All mechanical equipment revealed equivalent damage, and only minor damage was observed to the wall and curb flashings of the aggregate-surfaced BUR roof (Figures 1, 2, 3, and 4). Fully adhered EPDM membranes have historically performed well for impact resis- tance in test laboratories conducted by the EPDM Roofing Association, National Insti- tute of Standards and Technology, Under- writers Laboratory, Factory Mutual, and ASTM. Using either steel darts or ice spheres, 60-mil field-aged EPDM samples were not damaged in 96% of the testing when impacted with 3-in. hail balls.6 With the attention of owners drawn towards “cool roofing,” it’s difficult to find a black EPDM roof to observe in this area following a hail event. RICOWI did not observe any black EPDM membranes in its 2011 investigation. Impact resistance can be improved by installing a more rigid cover board with a higher compressive strength. The conven- Fe b r u a r y 2013 In t e r f a c e • 17 • Clear polycarbonate dome cover coated for UV resistance • Translucent and double domes available when specified • Fully gasketed design ensures weathertightness • The safe and reliable operation that you have come to expect from a Bilco roof hatch To learn more, visit www.bilco.com or call 800.366.6530 It’s a Roof Hatch... It’s a Skylight... It’s a Bilco. Type GS Roof Hatch All the security and convenience of a roof hatch with the added benefits of a skylight. The Worldwide Source for Specialty Access Products The natural daylight is ideal for ladder access roof hatches located in stairwells or closets. Also offered in sizes for staircase access and special sizes are available for unique access requirements. BLC743 Interface GS Ad.indd 1 1/24/12 9:46 AM Photo 3 – Hail damage to modified roof system. Photo 4 – Damage to exhaust fan at aggregate surfaced BUR.
  • 3. 18 • In t e r f a c e Fe b r u a r y 2013 tional perlite cover board on hot asphalt- applied roofing transfers the impact throughout the roof assembly. A few man- ufacturers of modified-bitumen roofing offer a sheet with a 180-gram polyester or fiber- glass scrim. The enhanced sheet, in a two- ply application on top of a rigid cover board, creates a dynamic puncture resistance that can be covered under some manufacturers’ warranties for up to 4-in. hail. Steep-Slope Roofing The frequency of large hail events in the Dallas-Ft. Worth area is alarming. Roofs in areas of Coppell, Texas, were totaled by hail two years in a row, after being reroofed in 2003 following hail damage. That’s three roof replacements in nine years, and concerns have been raised about the integrity of the decking being com- promised from the repeated damage from shingle and underlayment removal. Many track housing and apartment complexes in this region have 3/8-in. plywood decking. The thin decking—coupled with standard fiberglass-impregnated shingles—are a poor roof assembly, given the repeated hail- storms in the area. RICOWI has yet to complete this year’s report, although the 2011 Report #1 showed superior performance of modified-bitumen shingles. State Farm offers a 21-25% dis- count on premiums to homeowners who install impact-resistance (IR) class 4 shin- gles conforming to UL 2218. Hailstones of 0.25 in. to 2.5 in. diameter revealed surface impact marks without fractures or minimal damage on 75% of the IR roofs observed in the RICOWI 2011 hail investigation. Standard fiberglass-impregnated asphalt shingles showed moderate to severe damage with hailstones 1.25 in. or larger in 93% of the observations conducted by RICOWI in 2011.7 Stone-coated steel performs well, with hailstones up to 2.5 in. causing no apparent damage. Similar results have been reported with synthetic slate (shingles) and up to 2-in. hail, and metal roofs uniformly “dim- ple,” causing a more aesthetic issue than a waterproofing problem (Figure 5). Concrete and clay tile fare well overall, with 2-in. hail causing only a few broken tiles; however, the slate and tile roofs in the Lakewood area were beat to small pieces from 4-in. hail (Figure 6). All the roofs were immediately covered with tarps. Economic and Environmental Impact The economic impact of a hailstorm is extremely beneficial to numerous trades, services, and manufacturing. Supply hous- es add warehouse, sales, and delivery per- sonnel. Roofing manufacturing plants add a second or maybe a third shift. Deposits in the local banks soar, as do truck sales. (If only politicians could take credit for the sudden jobs created by inclement weather, they might get reelected every year.) Although the economic impact to some trades may be beneficial, there is a down- side. In the chaos, unscrupulous start-up contractors and scam artists converge on the public. White-collar thieves have col- lected insurance checks and disappeared, leaving homeowners with no roofs or funds to replace them. Others have received slop- py workmanship that does not reveal itself until heavy rains months later. Few manda- tory roof inspections are performed in any Photo 5 – Damage to copper standing seam. Photo 6 – Damage to concrete tile.
  • 4. municipality in North Texas on residential roofs. How can this industry go unchecked? Professional roofing contractors belonging to the Roofing Contractors Association of Texas (RCAT) have taken the liberty of insti- tuting a registration of their membership in an attempt to bring stability and to educate the public without governmental involve- ment. The United Association of Storm Restoration Contractors is a nonprofit orga- nization dedicated to informing homeown- ers in order to prevent contractor fraud. Another downside to the economic impact is the obvious increase in insurance premiums. In recent years, insurance com- panies have raised deductibles dramatically in hail-prone areas to combat losses. As for the environmental impact of past error and waste in the industry, look in the landfills. There are several companies in the Dallas-Ft. Worth area offering the service of recycling of asphalt shingles. Manufacturer sponsorship, along with contractor partic- ipation, is vital to promote the responsible disposal of asphalt roofing products. Savvy contractors should showcase the recycling of the roofing debris in their bids to home- owners. Roof consultants should consider including recycling in specifications. Not all roof coverings are included in this article, just the roofs this author encountered during the 2012 Dallas-Ft. Worth hailstorm. When specifying a roof system in this region, it would be prudent to consider impact resistance along with all the factors it takes to design a successful roofing system. References 1. National Oceanic and Atmospheric Administration. 2. Insurance Council of Texas. 3. Dallas Morning News, June 2011. 4. Lyle D. Hogan, FRCI, PE, “A Proposal for Uniformly Assessing Hail Dam- age to Roofs,” Interface, RCI, Inc., October 2006. 5. Walter Rossiter, “Many Standards Impacted by Recent Actions of ASTM Technical Committee D08 on Roofing and Waterproofing,” Interface, RCI, Inc., August 2012. 6. Jim D. Koontz, RRC, PE; and Thomas W. Hutchinson, FRCI, RRC, AIA, CSI; “Hail Impact Testing of EPDM Roof Assemblies,” Proceedings of the RCI 24th International Convention and Trade Show, March 12-17, 2009. 7. RICOWI, Inc., Hailstorm Investigation Dallas/Ft. Worth, May 24, 2011. American Hydrotech, Inc. 303 East Ohio | Chicago, IL 60611 | 800.877.6125 | www.hydrotechusa.com © 2013 Monolithic Membrane 6125 is a registered trademark of American Hydrotech, Inc. Monolithic Membrane 6125, the original rubberized asphalt membrane, has been entrusted with keeping high profile structures across the country and around the globe watertight for 50 years. More than 2 billion square feet of membrane is still performing today as it did the day it was installed. 50 YEARS OF PROVEN PERFORMANCE - MONOLITHIC MEMBRANE 6125® RCI-50-Half-Horiztonal.indd 1 12/11/2012 5:15:41 PM Fe b r u a r y 2013 In t e r f a c e • 19 Keith Simmons has been a Registered Roof Observer for DryTec Moisture Protection Technologies for the past seven years. Prior to that, he was a roofing contractor in the North Texas area for 23 years. He has evaluated hail damage events from 1982, 1988, 1992, 1995, 2003, 2011, and 2012. Keith Simmons, RRO