1
1
FRONT ELEVATION
SCALE: 1/4" = 1'-0"
2
1
LEFT ELEVATION
SCALE: 1/4" = 1'-0"
DRAFTING:
Corvallis CAD Services
P.O. Box 2257
Corvallis, Oregon 97339
Phone: (541) 754-2714
email: ccs@proaxis.com
BUILDER:
email:
Fax:Phone:
PROJECT:
PROJECT LOCATION:
DRAWING STATUS:
SHEET:
PROJECT #:
Elevations
1
1
2
REAR ELEVATION
SCALE: 1/4" = 1'-0"
2
2
RIGHT ELEVATION
SCALE: 1/4" = 1'-0"
DRAFTING:
Corvallis CAD Services
P.O. Box 2257
Corvallis, Oregon 97339
Phone: (541) 754-2714
email: ccs@proaxis.com
BUILDER:
email:
Fax:Phone:
PROJECT:
PROJECT LOCATION:
DRAWING STATUS:
SHEET:
PROJECT #:
Elevations
2
11-7/8" TJI's
@ 16" O.C. (TYP.)
GARAGE SLAB:
6 mil VAPOR BARRIER ON
4" AGGREGATE BASE
4" CONCRETE SLAB ON
VENTILATING
OPENING (TYP.)
16" x 8"
11-7/8" TJI's
@ 16" O.C. (TYP.)
24" x 8" CONC. FTG.
6" PONY WALL ON
(TYP.)
24" x 8" CONC.
8" x 24" STEM WALL
FOOTING (TYP.)
OR ICF EQUIVALENT (TYP.)
CRAWL SPACE
18" x 24" (MIN)
ACCESS
SLOPE
1/8" PER FOOT
33'-4"22'-0"
10'-9"10'-10"
64'-4"
11'-41
2"10'-71
2"
29'-6"25'-10"
64'-4"
2'-0"
3'-2"10'-21
2
"
44'-6"
13'-0" 22'-0"9'-6"
44'-6"
A
6
B
6
B
6
A
6
11'-9"
6'-9"10'-9"12'-0"
11-7/8" TJI's
@ 16" O.C. (TYP.)
18'-8" 3'-4"
9'-0"
9'-0"
16'-6"
THROUGH PONY WALL AS REQ'D.
PROVIDE CRAWL SPACE ACCESS
BLOCK OUT FOR 16'-0" x 8'-0"
OVERHEAD GARAGE DOOR
1
3
FOUNDATION & FLOOR FRAMING PLAN
SCALE: 1/4" = 1'-0"
DRAFTING:
Corvallis CAD Services
P.O. Box 2257
Corvallis, Oregon 97339
Phone: (541) 754-2714
email: ccs@proaxis.com
BUILDER:
email:
Fax:Phone:
PROJECT:
PROJECT LOCATION:
DRAWING STATUS:
SHEET:
PROJECT #:
FoundationandFloorFramingPlan
3
NOTES:
WHERE FOUNDATION DIFFERS
FROM STRUCTURAL ENGINEERING,
ENGINEERING TAKES PRECEDENCE.
SEE STRUCTURAL ENGINEERING
FOR HOLDDOWNS.
FOR CONCRETE WALLS WITH OVER
4'-0" OF UNBALANCED BACKFILL.
SEE STRUCTURAL ENGINEERING
SUBFLOOR AREA: ?? Sq. Ft.
Bath
LINEN
PANTRY
Walk-In
Closet
Garage
COATS
T
TT
Master Bedroom
Kitchen
Den
Great Room
Breakfast Nook
64'-4"
19'-11"22'-0"
8'-2"11'-9"
11'-6"10'-6"
64'-4"
6'-5"25'-9"
2'-8"5'-9"
8'-5"14'-9"
46'-6"
28'-8" 15'-10"
4'-7"3'-6"3'-6"4'-3"4'-8"3'-6"8'-9"3'-6"3'-6"4'-9"
44'-6"2'-0"
5'-0"8'-5"
4'-5"3'-9"4'-8"3'-9"
46'-6"
5'-6"11'-0"5'-6"4'-9"9'-6"3'-6"4'-9"
44'-6"2'-0"
TT ET ET
O
GAS
FIREPLACE
A
6
B
6
B
6
A
6
16'-6"
9'-0"
9'-0"55'-4"
Concrete Patio
A
6
B
6
B
6
11-7/8" TJI's
@ 16" O.C. (TYP.)
1
4
FIRST FLOOR PLAN
SCALE: 1/4" = 1'-0"
DRAFTING:
Corvallis CAD Services
P.O. Box 2257
Corvallis, Oregon 97339
Phone: (541) 754-2714
email: ccs@proaxis.com
BUILDER:
email:
Fax:Phone:
PROJECT:
PROJECT LOCATION:
DRAWING STATUS:
SHEET:
PROJECT #:
FirstFloor&SecondFloorFramingPlan
4FIRST FLOOR AREA: 1,484 Sq. Ft.
GARAGE AREA: 474 Sq. Ft.
TOTAL MAIN FLOOR AREA: 1,958 Sq. Ft.
2
4
SECOND FLOOR FRAMING PLAN
SCALE: 1/4" = 1'-0"
RIDGE
12:1212:12
12:12
12:1212:12
12:12
RIDGE
12:1212:12
12:12
12:12
12:12
RIDGE
12:1212:12
~2:12
12:12
12:12
Bedroom
Bath
Loft
Bedroom
Linen
22'-0"
3'-6"4'-6"
15'-9"
44'-10"
12'-5"
4'-5"
4'-0"12'-8"
3'-5"4'-6"4'-9"
10'-8"8'-1"9'-9"
28'-6"
44'-10"
8'-11"5'-7"3'-6"11'-4"
A
6
B
6
B
6
2
5
MAIN FLOOR ADDITION PLAN
SCALE: 1/4" = 1'-0"
DRAFTING:
Corvallis CAD Services
P.O. Box 2257
Corvallis, Oregon 97339
Phone: (541) 754-2714
email: ccs@proaxis.com
BUILDER:
email:
Fax:Phone:
PROJECT:
PROJECT LOCATION:
DRAWING STATUS:
SHEET:
PROJECT #:
SecondFloor&RoofPlan
5
NOTE:
ATTIC VENTING AT RIDGE TO BE 50% TO 80%
OF TOTAL ATTIC VENTILATION REQUIRED AND
LOCATED AT LEAST THREE FEET ABOVE
SOFFIT OR EAVE VENTS.
1
5
SECOND FLOOR PLAN
SCALE: 1/4" = 1'-0" SECOND FLOOR AREA: 600 Sq. Ft.
Master Bedroom
BedroomLoft Bath
KitchenGreat Room
BedroomBedroom Closet
Bath
Master Bedroom
Closet Garage
DRAFTING:
Corvallis CAD Services
P.O. Box 2257
Corvallis, Oregon 97339
Phone: (541) 754-2714
email: ccs@proaxis.com
BUILDER:
email:
Fax:Phone:
PROJECT:
PROJECT LOCATION:
DRAWING STATUS:
SHEET:
PROJECT #:
Sections
6
A
6
SECTION A-A
SCALE: 1/4" = 1'-0"
B
6
SECTION B-B
SCALE: 1/4" = 1'-0"
2'-0"
VENTING AT EAVES:
VENTING AT RIDGE:
BLOCKING:
7/16" MIN. WOOD
SHEATHING:
2"x6" STUDS
INTERIOR COVERING:
EXTERIOR FINISH:
INSULATION:
STRUCTURAL PANELS
ROOF FRAMING:
AT 16" O.C.
UNDERLAYMENT:
SUBFLOOR:
3/4" MIN. PLYWOOD
1/2" G.W.B.
FRAMING:
11 7/8" I-JOISTS @ 16" O.C.
INSULATION:
SEE DETAIL 1101 / 6
EXTERIOR FINISH:
(SEE ELEVATIONS)
SHEATHING:
FRAMING:
HOUSE WRAP / DRAINAGE:
SEE DETAIL 1101 / 6
OR APPROVED ALTERNATE
INSULATION:
INTERIOR COVERING:
GREEN GUARD RAINDROP 3D
28-DAY CONCRETE STRENGTH TO BE:
8"
2'-0"
3"
MIN.
CLR.
403
GROUNDING ELECTRODE:
DEPTH:
ASSUMED SOIL BEARING CAPACITY:
FOUNDATION NOTES:
VAPOR BARRIER:
N.T.S.
SITE :
CONTINUOUS FOOTING AT BUILDING EXTERIOR
7
STRUCTURAL ENGINEERING:
WHERE STEM WALL <4'-8" TALL
6"
(MIN.)
1'-0" (MIN.)
2"
(MIN.)
405
N.T.S.7
FOUNDATION DRAINAGE
DISCHARGING:
DRAINAGE NOTES:
FOUNDATION PERIMETER:
CRAWL SPACE LOW POINT:
ROOF DRAINS:
LOCATION:
FINISHED GRADE:
CLR.
8"
2'-0"MIN.
4'-8"MAX.
21
2"
GROUNDING ELECTRODE:
HEIGHT:
CONTINUOUS CONCRETE STEM WALL
FINISHED GRADE AT EXTERIOR :
FOUNDATION NOTES:
404
7 N.T.S.
STRUCTURAL ENGINEERING:
CRAWL SPACE:
VAPOR BARRIER:
WHERE STEM WALL <4'-8" TALL
R-21
ENERGY EFFICIENCY REQUIREMENTS
SCALE: NONE
ADDITIONAL MEASURES:
1101
7
R-30
R-38
R-21
INSULATION:
CEILINGS:
EXTERIOR WALLS:
FLOOR:
FORCED AIR DUCT:
SLAB FLOOR EDGE:
BELOW GRADE WOOD, CONCRETE, OR MASONRY WALLS:
WINDOWS:
SKYLIGHTS:
EXTERIOR DOOR:
BUILDING ENVELOPE:
INTERIOR LOAD-BEARING WALL:
INTERIOR PLUMBING WALL:
(NON-BEARING)
INTERIOR PARTITION WALL:
8"
2'-0"
FOOTING:
PONY WALL:
BOARD UNDER
CONTINUOUS HANDRAIL
1 1/2"x12" MICROLAM STRINGERS
(TYP.)
HANDRAIL
NOSING
3'-0" MIN.
LANDING
MAINTAIN6'-8"(MIN.)
CLEARHEADROOM
30"(MIN.)
4"(MIN.)
RISE
1/2"' GYPSUM WALL
38"(MAX.)
8"(MAX.)
9" (MIN.)
RUN
RADIUS /
BEVEL
9/16" (MAX.)
STAIRS 1 1/4 (MAX.)
1/2" (MAX.)
3/4" (MIN.)
FULL LENGTH OF FLIGHT
5
1
2
"(MIN.)
41
2"(MAX.)
ABOVEHANDRAIL
PROJECTION
AT/BELOWHANDRAIL
HANDRAIL
CONTINUOUS HANDRAIL
2" (MAX.)
OPTIONAL SECOND
HANDRAIL
4" (MIN.), 6 1/4" (MAX.)
3'-0"(MIN.)CLEAR
11
2"(MIN.)
FULL LENGTH OF FLIGHT
TOWALL
INTOSTAIR
HANDRAIL
HANDRAIL
311
2"(MIN.)CLEAR
27"(MIN.)CLEAR
HANDRAIL
CROSS SECTION
HANDRAIL PERIMETER
1 1/4" (MIN.), 2" (MAX.)
HANDRAIL DIAMETER
<4"
< 4"
3'-0"(MIN.)
WALKING SURFACE
DRAFTING:
Corvallis CAD Services
P.O. Box 2257
Corvallis, Oregon 97339
Phone: (541) 754-2714
email: ccs@proaxis.com
BUILDER:
email:
Fax:Phone:
PROJECT:
PROJECT LOCATION:
DRAWING STATUS:
SHEET:
PROJECT #:
WallSectionsandDetails
71
7
TYPICAL EXTERIOR WALL
SCALE: 1" = 1'-0"
TYPICAL EXTERIOR WALL 3
7 SCALE: 1" = 1'-0"
TYPICAL INTERIOR WALL
O
T
E
DOORS & WINDOWS
SINGLE HUNG
DOUBLE HUNG
FIXED
HORIZONTAL SLIDER
OVERHEAD
SH
DH
FXD
HS
O/H
EGRESS WINDOW
OBSCURE WINDOW
TEMPERED WINDOW
ABBREVIATIONS:
PLAN SYMBOLS:
20"
24"
NET CLEAR WIDTH OF OPENING (MIN.):
NET CLEAR HEIGHT OF OPENING (MIN.):
NET CLEAR AREA OF OPENING (MIN.):
SILL WITHIN 44" OF EXT. GRADE:
SILL NOT WITHIN 44" OF EXT. GRADE:
5.0 SF
5.7 SF
44"SILL HEIGHT ABOVE FLOOR (MAX.):
EGRESS WINDOW REQUIREMENTS:
DWELLING / RESIDENCE SEPARATION:
INSTALL 1 3/8" (MIN.) THICK SOLID WOOD, 1 3/8"
(MIN.) THICK SOLID OR HONEYCOMB CORE STEEL
DOOR, OR 20 MINUTE (MIN.) FIRE-RATED DOOR AT
ALL OPENINGS BETWEEN GARAGES AND DWELLING
UNITS. (NOT REQUIRED WHERE AN APPROVED
AUTOMATIC FIRE SPRINKLER SYSTEM IS INSTALLED
IN BOTH THE DWELLING UNIT AND GARAGE).
ALARMS
SMOKE ALARM
CARBON MONOXIDE
SA
CO
SMOKE ALARM
COMB. SMOKE & CARBON MONOXIDE ALARM
ABBREVIATIONS:
PLAN SYMBOLS:
SMOKE ALARMS
CARBON MONOXIDE ALARMS
CARBON MONOXIDE ALARMS TO BE INSTALLED IN
EACH BEDROOM OR WITHIN 15 FEET OF EACH
BEDROOM DOOR.
SMOKE ALARMS TO BE INSTALLED IN EACH
SLEEPING ROOM, AND OUTSIDE EACH SEPARATE
SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
BEDROOMS.
SMOKE ALARMS TO BE INTERCONNECTED SUCH
THAT THE ACTUATION OF ONE ALARM WITHIN A
DWELLING UNIT WILL ACTIVATE ALL OF THE
ALARMS WITHIN THAT DWELLING UNIT.
SINGLE OR DOUBLE HUNGVS
T TEMPERED WINDOW IF R308.4 APPLIES*
2
7 SCALE: 1" = 1'-0"
TYPICAL PONY WALL
SCALE: 1/4" = 1'-0"
TYPICAL STAIR SECTION
7
311.7
SCALE: 1/2" = 1'-0"
TYPICAL HANDRAIL PLAN
7
311.7.7
SCALE: 1/2" = 1'-0"
TYPICAL GUARDRAIL ELEVATION
7
312

More Related Content

Viewers also liked

Flyer prueba 2014
Flyer prueba 2014Flyer prueba 2014
Flyer prueba 2014PrimeAir
 
Simplex part 3 of 4
Simplex part 3 of 4Simplex part 3 of 4
Simplex part 3 of 4Ed Dansereau
 
Annays alarcón
Annays alarcónAnnays alarcón
Annays alarcón515648
 
人間の成長とユーザエクスペリエンス
人間の成長とユーザエクスペリエンス人間の成長とユーザエクスペリエンス
人間の成長とユーザエクスペリエンスMasaya Ando
 
Architectural Design in Arabic - Book 7 - التصميم المعمارى بالعربى -كتاب 7
Architectural Design in Arabic - Book 7 - التصميم المعمارى بالعربى -كتاب 7Architectural Design in Arabic - Book 7 - التصميم المعمارى بالعربى -كتاب 7
Architectural Design in Arabic - Book 7 - التصميم المعمارى بالعربى -كتاب 7Galala University
 
V trust appraisal market updates
V trust appraisal market updatesV trust appraisal market updates
V trust appraisal market updatesHoem Seiha
 
The Real Story About Marketing Automation
The Real Story About Marketing AutomationThe Real Story About Marketing Automation
The Real Story About Marketing AutomationCheryl Pederzoli
 
Рейтинг новинних ресурсів, січень 2017.
Рейтинг новинних ресурсів, січень 2017.Рейтинг новинних ресурсів, січень 2017.
Рейтинг новинних ресурсів, січень 2017.Watcher
 
講演2 実例に基づくRedmine管理者入門 r2
講演2 実例に基づくRedmine管理者入門 r2講演2 実例に基づくRedmine管理者入門 r2
講演2 実例に基づくRedmine管理者入門 r2Hidehisa Matsutani
 
OpenHCI'14-Day2-鄭鎧尹-UX Culture in a Start-up Company
OpenHCI'14-Day2-鄭鎧尹-UX Culture in a Start-up Company OpenHCI'14-Day2-鄭鎧尹-UX Culture in a Start-up Company
OpenHCI'14-Day2-鄭鎧尹-UX Culture in a Start-up Company OpenHCI
 

Viewers also liked (16)

Flyer prueba 2014
Flyer prueba 2014Flyer prueba 2014
Flyer prueba 2014
 
Motores de graficos
Motores de graficosMotores de graficos
Motores de graficos
 
Presentación: CREANDO COMUNIDAD, UNA ILUSIÓN COMPARTIDA. LIDERAR EL PROYECTO ...
Presentación: CREANDO COMUNIDAD, UNA ILUSIÓN COMPARTIDA. LIDERAR EL PROYECTO ...Presentación: CREANDO COMUNIDAD, UNA ILUSIÓN COMPARTIDA. LIDERAR EL PROYECTO ...
Presentación: CREANDO COMUNIDAD, UNA ILUSIÓN COMPARTIDA. LIDERAR EL PROYECTO ...
 
Simplex part 3 of 4
Simplex part 3 of 4Simplex part 3 of 4
Simplex part 3 of 4
 
Annays alarcón
Annays alarcónAnnays alarcón
Annays alarcón
 
Derechos de autor 2
Derechos de autor 2Derechos de autor 2
Derechos de autor 2
 
Resume
ResumeResume
Resume
 
人間の成長とユーザエクスペリエンス
人間の成長とユーザエクスペリエンス人間の成長とユーザエクスペリエンス
人間の成長とユーザエクスペリエンス
 
PAISAJES DE APRENDIZAJE:
PAISAJES DE APRENDIZAJE:PAISAJES DE APRENDIZAJE:
PAISAJES DE APRENDIZAJE:
 
Architectural Design in Arabic - Book 7 - التصميم المعمارى بالعربى -كتاب 7
Architectural Design in Arabic - Book 7 - التصميم المعمارى بالعربى -كتاب 7Architectural Design in Arabic - Book 7 - التصميم المعمارى بالعربى -كتاب 7
Architectural Design in Arabic - Book 7 - التصميم المعمارى بالعربى -كتاب 7
 
V trust appraisal market updates
V trust appraisal market updatesV trust appraisal market updates
V trust appraisal market updates
 
The Real Story About Marketing Automation
The Real Story About Marketing AutomationThe Real Story About Marketing Automation
The Real Story About Marketing Automation
 
Рейтинг новинних ресурсів, січень 2017.
Рейтинг новинних ресурсів, січень 2017.Рейтинг новинних ресурсів, січень 2017.
Рейтинг новинних ресурсів, січень 2017.
 
講演2 実例に基づくRedmine管理者入門 r2
講演2 実例に基づくRedmine管理者入門 r2講演2 実例に基づくRedmine管理者入門 r2
講演2 実例に基づくRedmine管理者入門 r2
 
Rapporto COE Giornalino Novembre 2013
Rapporto COE Giornalino Novembre 2013 Rapporto COE Giornalino Novembre 2013
Rapporto COE Giornalino Novembre 2013
 
OpenHCI'14-Day2-鄭鎧尹-UX Culture in a Start-up Company
OpenHCI'14-Day2-鄭鎧尹-UX Culture in a Start-up Company OpenHCI'14-Day2-鄭鎧尹-UX Culture in a Start-up Company
OpenHCI'14-Day2-鄭鎧尹-UX Culture in a Start-up Company
 

Similar to 3 Parkview Bldg

Tertiary_Unitec_Proposed_Floorplan
Tertiary_Unitec_Proposed_FloorplanTertiary_Unitec_Proposed_Floorplan
Tertiary_Unitec_Proposed_FloorplanBen Blair
 
Construction Documents Fall 2014
Construction Documents Fall 2014Construction Documents Fall 2014
Construction Documents Fall 2014Martin Pauly
 
Lennar sherwin-williams-architectural-fdp
Lennar sherwin-williams-architectural-fdpLennar sherwin-williams-architectural-fdp
Lennar sherwin-williams-architectural-fdpE'ville Eye
 
At of modern building which create abvolated view
At of modern building which create abvolated viewAt of modern building which create abvolated view
At of modern building which create abvolated viewdreem073
 
Selleck, Matthew NEDF Built Environment Project
Selleck, Matthew NEDF Built Environment Project Selleck, Matthew NEDF Built Environment Project
Selleck, Matthew NEDF Built Environment Project MatthewSelleck1
 
House Shaw Floorplan Final 03
House Shaw Floorplan Final 03House Shaw Floorplan Final 03
House Shaw Floorplan Final 03Terence Botha
 

Similar to 3 Parkview Bldg (8)

Lombard House
Lombard HouseLombard House
Lombard House
 
Tertiary_Unitec_Proposed_Floorplan
Tertiary_Unitec_Proposed_FloorplanTertiary_Unitec_Proposed_Floorplan
Tertiary_Unitec_Proposed_Floorplan
 
Construction Documents Fall 2014
Construction Documents Fall 2014Construction Documents Fall 2014
Construction Documents Fall 2014
 
Lennar sherwin-williams-architectural-fdp
Lennar sherwin-williams-architectural-fdpLennar sherwin-williams-architectural-fdp
Lennar sherwin-williams-architectural-fdp
 
Lombard House
Lombard HouseLombard House
Lombard House
 
At of modern building which create abvolated view
At of modern building which create abvolated viewAt of modern building which create abvolated view
At of modern building which create abvolated view
 
Selleck, Matthew NEDF Built Environment Project
Selleck, Matthew NEDF Built Environment Project Selleck, Matthew NEDF Built Environment Project
Selleck, Matthew NEDF Built Environment Project
 
House Shaw Floorplan Final 03
House Shaw Floorplan Final 03House Shaw Floorplan Final 03
House Shaw Floorplan Final 03
 

3 Parkview Bldg

  • 1. 1 1 FRONT ELEVATION SCALE: 1/4" = 1'-0" 2 1 LEFT ELEVATION SCALE: 1/4" = 1'-0" DRAFTING: Corvallis CAD Services P.O. Box 2257 Corvallis, Oregon 97339 Phone: (541) 754-2714 email: ccs@proaxis.com BUILDER: email: Fax:Phone: PROJECT: PROJECT LOCATION: DRAWING STATUS: SHEET: PROJECT #: Elevations 1
  • 2. 1 2 REAR ELEVATION SCALE: 1/4" = 1'-0" 2 2 RIGHT ELEVATION SCALE: 1/4" = 1'-0" DRAFTING: Corvallis CAD Services P.O. Box 2257 Corvallis, Oregon 97339 Phone: (541) 754-2714 email: ccs@proaxis.com BUILDER: email: Fax:Phone: PROJECT: PROJECT LOCATION: DRAWING STATUS: SHEET: PROJECT #: Elevations 2
  • 3. 11-7/8" TJI's @ 16" O.C. (TYP.) GARAGE SLAB: 6 mil VAPOR BARRIER ON 4" AGGREGATE BASE 4" CONCRETE SLAB ON VENTILATING OPENING (TYP.) 16" x 8" 11-7/8" TJI's @ 16" O.C. (TYP.) 24" x 8" CONC. FTG. 6" PONY WALL ON (TYP.) 24" x 8" CONC. 8" x 24" STEM WALL FOOTING (TYP.) OR ICF EQUIVALENT (TYP.) CRAWL SPACE 18" x 24" (MIN) ACCESS SLOPE 1/8" PER FOOT 33'-4"22'-0" 10'-9"10'-10" 64'-4" 11'-41 2"10'-71 2" 29'-6"25'-10" 64'-4" 2'-0" 3'-2"10'-21 2 " 44'-6" 13'-0" 22'-0"9'-6" 44'-6" A 6 B 6 B 6 A 6 11'-9" 6'-9"10'-9"12'-0" 11-7/8" TJI's @ 16" O.C. (TYP.) 18'-8" 3'-4" 9'-0" 9'-0" 16'-6" THROUGH PONY WALL AS REQ'D. PROVIDE CRAWL SPACE ACCESS BLOCK OUT FOR 16'-0" x 8'-0" OVERHEAD GARAGE DOOR 1 3 FOUNDATION & FLOOR FRAMING PLAN SCALE: 1/4" = 1'-0" DRAFTING: Corvallis CAD Services P.O. Box 2257 Corvallis, Oregon 97339 Phone: (541) 754-2714 email: ccs@proaxis.com BUILDER: email: Fax:Phone: PROJECT: PROJECT LOCATION: DRAWING STATUS: SHEET: PROJECT #: FoundationandFloorFramingPlan 3 NOTES: WHERE FOUNDATION DIFFERS FROM STRUCTURAL ENGINEERING, ENGINEERING TAKES PRECEDENCE. SEE STRUCTURAL ENGINEERING FOR HOLDDOWNS. FOR CONCRETE WALLS WITH OVER 4'-0" OF UNBALANCED BACKFILL. SEE STRUCTURAL ENGINEERING SUBFLOOR AREA: ?? Sq. Ft.
  • 4. Bath LINEN PANTRY Walk-In Closet Garage COATS T TT Master Bedroom Kitchen Den Great Room Breakfast Nook 64'-4" 19'-11"22'-0" 8'-2"11'-9" 11'-6"10'-6" 64'-4" 6'-5"25'-9" 2'-8"5'-9" 8'-5"14'-9" 46'-6" 28'-8" 15'-10" 4'-7"3'-6"3'-6"4'-3"4'-8"3'-6"8'-9"3'-6"3'-6"4'-9" 44'-6"2'-0" 5'-0"8'-5" 4'-5"3'-9"4'-8"3'-9" 46'-6" 5'-6"11'-0"5'-6"4'-9"9'-6"3'-6"4'-9" 44'-6"2'-0" TT ET ET O GAS FIREPLACE A 6 B 6 B 6 A 6 16'-6" 9'-0" 9'-0"55'-4" Concrete Patio A 6 B 6 B 6 11-7/8" TJI's @ 16" O.C. (TYP.) 1 4 FIRST FLOOR PLAN SCALE: 1/4" = 1'-0" DRAFTING: Corvallis CAD Services P.O. Box 2257 Corvallis, Oregon 97339 Phone: (541) 754-2714 email: ccs@proaxis.com BUILDER: email: Fax:Phone: PROJECT: PROJECT LOCATION: DRAWING STATUS: SHEET: PROJECT #: FirstFloor&SecondFloorFramingPlan 4FIRST FLOOR AREA: 1,484 Sq. Ft. GARAGE AREA: 474 Sq. Ft. TOTAL MAIN FLOOR AREA: 1,958 Sq. Ft. 2 4 SECOND FLOOR FRAMING PLAN SCALE: 1/4" = 1'-0"
  • 5. RIDGE 12:1212:12 12:12 12:1212:12 12:12 RIDGE 12:1212:12 12:12 12:12 12:12 RIDGE 12:1212:12 ~2:12 12:12 12:12 Bedroom Bath Loft Bedroom Linen 22'-0" 3'-6"4'-6" 15'-9" 44'-10" 12'-5" 4'-5" 4'-0"12'-8" 3'-5"4'-6"4'-9" 10'-8"8'-1"9'-9" 28'-6" 44'-10" 8'-11"5'-7"3'-6"11'-4" A 6 B 6 B 6 2 5 MAIN FLOOR ADDITION PLAN SCALE: 1/4" = 1'-0" DRAFTING: Corvallis CAD Services P.O. Box 2257 Corvallis, Oregon 97339 Phone: (541) 754-2714 email: ccs@proaxis.com BUILDER: email: Fax:Phone: PROJECT: PROJECT LOCATION: DRAWING STATUS: SHEET: PROJECT #: SecondFloor&RoofPlan 5 NOTE: ATTIC VENTING AT RIDGE TO BE 50% TO 80% OF TOTAL ATTIC VENTILATION REQUIRED AND LOCATED AT LEAST THREE FEET ABOVE SOFFIT OR EAVE VENTS. 1 5 SECOND FLOOR PLAN SCALE: 1/4" = 1'-0" SECOND FLOOR AREA: 600 Sq. Ft.
  • 6. Master Bedroom BedroomLoft Bath KitchenGreat Room BedroomBedroom Closet Bath Master Bedroom Closet Garage DRAFTING: Corvallis CAD Services P.O. Box 2257 Corvallis, Oregon 97339 Phone: (541) 754-2714 email: ccs@proaxis.com BUILDER: email: Fax:Phone: PROJECT: PROJECT LOCATION: DRAWING STATUS: SHEET: PROJECT #: Sections 6 A 6 SECTION A-A SCALE: 1/4" = 1'-0" B 6 SECTION B-B SCALE: 1/4" = 1'-0"
  • 7. 2'-0" VENTING AT EAVES: VENTING AT RIDGE: BLOCKING: 7/16" MIN. WOOD SHEATHING: 2"x6" STUDS INTERIOR COVERING: EXTERIOR FINISH: INSULATION: STRUCTURAL PANELS ROOF FRAMING: AT 16" O.C. UNDERLAYMENT: SUBFLOOR: 3/4" MIN. PLYWOOD 1/2" G.W.B. FRAMING: 11 7/8" I-JOISTS @ 16" O.C. INSULATION: SEE DETAIL 1101 / 6 EXTERIOR FINISH: (SEE ELEVATIONS) SHEATHING: FRAMING: HOUSE WRAP / DRAINAGE: SEE DETAIL 1101 / 6 OR APPROVED ALTERNATE INSULATION: INTERIOR COVERING: GREEN GUARD RAINDROP 3D 28-DAY CONCRETE STRENGTH TO BE: 8" 2'-0" 3" MIN. CLR. 403 GROUNDING ELECTRODE: DEPTH: ASSUMED SOIL BEARING CAPACITY: FOUNDATION NOTES: VAPOR BARRIER: N.T.S. SITE : CONTINUOUS FOOTING AT BUILDING EXTERIOR 7 STRUCTURAL ENGINEERING: WHERE STEM WALL <4'-8" TALL 6" (MIN.) 1'-0" (MIN.) 2" (MIN.) 405 N.T.S.7 FOUNDATION DRAINAGE DISCHARGING: DRAINAGE NOTES: FOUNDATION PERIMETER: CRAWL SPACE LOW POINT: ROOF DRAINS: LOCATION: FINISHED GRADE: CLR. 8" 2'-0"MIN. 4'-8"MAX. 21 2" GROUNDING ELECTRODE: HEIGHT: CONTINUOUS CONCRETE STEM WALL FINISHED GRADE AT EXTERIOR : FOUNDATION NOTES: 404 7 N.T.S. STRUCTURAL ENGINEERING: CRAWL SPACE: VAPOR BARRIER: WHERE STEM WALL <4'-8" TALL R-21 ENERGY EFFICIENCY REQUIREMENTS SCALE: NONE ADDITIONAL MEASURES: 1101 7 R-30 R-38 R-21 INSULATION: CEILINGS: EXTERIOR WALLS: FLOOR: FORCED AIR DUCT: SLAB FLOOR EDGE: BELOW GRADE WOOD, CONCRETE, OR MASONRY WALLS: WINDOWS: SKYLIGHTS: EXTERIOR DOOR: BUILDING ENVELOPE: INTERIOR LOAD-BEARING WALL: INTERIOR PLUMBING WALL: (NON-BEARING) INTERIOR PARTITION WALL: 8" 2'-0" FOOTING: PONY WALL: BOARD UNDER CONTINUOUS HANDRAIL 1 1/2"x12" MICROLAM STRINGERS (TYP.) HANDRAIL NOSING 3'-0" MIN. LANDING MAINTAIN6'-8"(MIN.) CLEARHEADROOM 30"(MIN.) 4"(MIN.) RISE 1/2"' GYPSUM WALL 38"(MAX.) 8"(MAX.) 9" (MIN.) RUN RADIUS / BEVEL 9/16" (MAX.) STAIRS 1 1/4 (MAX.) 1/2" (MAX.) 3/4" (MIN.) FULL LENGTH OF FLIGHT 5 1 2 "(MIN.) 41 2"(MAX.) ABOVEHANDRAIL PROJECTION AT/BELOWHANDRAIL HANDRAIL CONTINUOUS HANDRAIL 2" (MAX.) OPTIONAL SECOND HANDRAIL 4" (MIN.), 6 1/4" (MAX.) 3'-0"(MIN.)CLEAR 11 2"(MIN.) FULL LENGTH OF FLIGHT TOWALL INTOSTAIR HANDRAIL HANDRAIL 311 2"(MIN.)CLEAR 27"(MIN.)CLEAR HANDRAIL CROSS SECTION HANDRAIL PERIMETER 1 1/4" (MIN.), 2" (MAX.) HANDRAIL DIAMETER <4" < 4" 3'-0"(MIN.) WALKING SURFACE DRAFTING: Corvallis CAD Services P.O. Box 2257 Corvallis, Oregon 97339 Phone: (541) 754-2714 email: ccs@proaxis.com BUILDER: email: Fax:Phone: PROJECT: PROJECT LOCATION: DRAWING STATUS: SHEET: PROJECT #: WallSectionsandDetails 71 7 TYPICAL EXTERIOR WALL SCALE: 1" = 1'-0" TYPICAL EXTERIOR WALL 3 7 SCALE: 1" = 1'-0" TYPICAL INTERIOR WALL O T E DOORS & WINDOWS SINGLE HUNG DOUBLE HUNG FIXED HORIZONTAL SLIDER OVERHEAD SH DH FXD HS O/H EGRESS WINDOW OBSCURE WINDOW TEMPERED WINDOW ABBREVIATIONS: PLAN SYMBOLS: 20" 24" NET CLEAR WIDTH OF OPENING (MIN.): NET CLEAR HEIGHT OF OPENING (MIN.): NET CLEAR AREA OF OPENING (MIN.): SILL WITHIN 44" OF EXT. GRADE: SILL NOT WITHIN 44" OF EXT. GRADE: 5.0 SF 5.7 SF 44"SILL HEIGHT ABOVE FLOOR (MAX.): EGRESS WINDOW REQUIREMENTS: DWELLING / RESIDENCE SEPARATION: INSTALL 1 3/8" (MIN.) THICK SOLID WOOD, 1 3/8" (MIN.) THICK SOLID OR HONEYCOMB CORE STEEL DOOR, OR 20 MINUTE (MIN.) FIRE-RATED DOOR AT ALL OPENINGS BETWEEN GARAGES AND DWELLING UNITS. (NOT REQUIRED WHERE AN APPROVED AUTOMATIC FIRE SPRINKLER SYSTEM IS INSTALLED IN BOTH THE DWELLING UNIT AND GARAGE). ALARMS SMOKE ALARM CARBON MONOXIDE SA CO SMOKE ALARM COMB. SMOKE & CARBON MONOXIDE ALARM ABBREVIATIONS: PLAN SYMBOLS: SMOKE ALARMS CARBON MONOXIDE ALARMS CARBON MONOXIDE ALARMS TO BE INSTALLED IN EACH BEDROOM OR WITHIN 15 FEET OF EACH BEDROOM DOOR. SMOKE ALARMS TO BE INSTALLED IN EACH SLEEPING ROOM, AND OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOMS. SMOKE ALARMS TO BE INTERCONNECTED SUCH THAT THE ACTUATION OF ONE ALARM WITHIN A DWELLING UNIT WILL ACTIVATE ALL OF THE ALARMS WITHIN THAT DWELLING UNIT. SINGLE OR DOUBLE HUNGVS T TEMPERED WINDOW IF R308.4 APPLIES* 2 7 SCALE: 1" = 1'-0" TYPICAL PONY WALL SCALE: 1/4" = 1'-0" TYPICAL STAIR SECTION 7 311.7 SCALE: 1/2" = 1'-0" TYPICAL HANDRAIL PLAN 7 311.7.7 SCALE: 1/2" = 1'-0" TYPICAL GUARDRAIL ELEVATION 7 312