NEMA Enclosure Types
The purpose of this document is to provide general information on the definitions of
NEMA Enclosure Types to architects, engineers, installers, inspectors and other
interested parties. [For more detailed and complete information, NEMA Standards
Publication 250-2003, “Enclosures for Electrical Equipment (1000 Volts Maximum)”
should be consulted. This Standards Publication as well as all other NEMA publications
are available from IHS @ 800 854-7179 or http://www.global.ihs.com]
Definitions
[from NEMA 250-2003]
In Non-Hazardous Locations, the specific enclosure Types, their applications, and the
environmental conditions they are designed to protect against, when completely and
properly installed, are as follows:
Type 1
Enclosures constructed for indoor use to provide a degree of protection to
personnel against access to hazardous parts and to provide a degree of protection of
the equipment inside the enclosure against ingress of solid foreign objects (falling dirt).
Type 2
Enclosures constructed for indoor use to provide a degree of protection to
personnel against access to hazardous parts; to provide a degree of protection of the
equipment inside the enclosure against ingress of solid foreign objects (falling dirt); and
to provide a degree of protection with respect to harmful effects on the equipment due
to the ingress of water (dripping and light splashing).
Type 3
Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt and windblown dust); to provide a degree of protection with respect to
harmful effects on the equipment due to the ingress of water (rain, sleet, snow); and that
will be undamaged by the external formation of ice on the enclosure.
Type 3R Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt); to provide a degree of protection with respect to harmful effects on the
equipment due to the ingress of water (rain, sleet, snow); and that will be undamaged
by the external formation of ice on the enclosure.
National Electrical Manufacturers Association
1300 N. 17th Street, Suite 1752
Rosslyn, VA 22209

Approved by NEMA Enclosures Section
Nov 2005
Page 1 of 2
NEMA Enclosure Types

Type 3S Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt and windblown dust); to provide a degree of protection with respect to
harmful effects on the equipment due to the ingress of water (rain, sleet, snow); and for
which the external mechanism(s) remain operable when ice laden.
Type 3X Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt and windblown dust); to provide a degree of protection with respect to
harmful effects on the equipment due to the ingress of water (rain, sleet, snow); that
provides an additional level of protection against corrosion and that will be undamaged
by the external formation of ice on the enclosure.
Type 3RX Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt); to provide a degree of protection with respect to harmful effects on the
equipment due to the ingress of water (rain, sleet, snow); that will be undamaged by the
external formation of ice on the enclosure that provides an additional level of protection
against corrosion; and that will be undamaged by the external formation of ice on the
enclosure.
Type 3SX Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt and windblown dust); to provide a degree of protection with respect to
harmful effects on the equipment due to the ingress of water (rain, sleet, snow); that
provides an additional level of protection against corrosion; and for which the external
mechanism(s) remain operable when ice laden.
Type 4
Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt and windblown dust); to provide a degree of protection with respect to
harmful effects on the equipment due to the ingress of water (rain, sleet, snow,
splashing water, and hose directed water); and that will be undamaged by the external
formation of ice on the enclosure.

National Electrical Manufacturers Association
1300 N. 17th Street, Suite 1752
Rosslyn, VA 22209

Approved by NEMA Enclosures Section
November 2005
NEMA Enclosure Types

Type 4X Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(windblown dust); to provide a degree of protection with respect to harmful effects on
the equipment due to the ingress of water (rain, sleet, snow, splashing water, and hose
directed water); that provides an additional level of protection against corrosion; and
that will be undamaged by the external formation of ice on the enclosure.
Type 5
Enclosures constructed for indoor use to provide a degree of protection to
personnel against access to hazardous parts; to provide a degree of protection of the
equipment inside the enclosure against ingress of solid foreign objects (falling dirt and
settling airborne dust, lint, fibers, and flyings); and to provide a degree of protection with
respect to harmful effects on the equipment due to the ingress of water (dripping and
light splashing).
Type 6
Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt); to provide a degree of protection with respect to harmful effects on the
equipment due to the ingress of water (hose directed water and the entry of water
during occasional temporary submersion at a limited depth); and that will be
undamaged by the external formation of ice on the enclosure.
Type 6P Enclosures constructed for either indoor or outdoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt); to provide a degree of protection with respect to harmful effects on the
equipment due to the ingress of water (hose directed water and the entry of water
during prolonged submersion at a limited depth); that provides an additional level of
protection against corrosion and that will be undamaged by the external formation of ice
on the enclosure.
Type 12
Enclosures constructed (without knockouts) for indoor use to provide a
degree of protection to personnel against access to hazardous parts; to provide a
degree of protection of the equipment inside the enclosure against ingress of solid
foreign objects (falling dirt and circulating dust, lint, fibers, and flyings); and to provide a
degree of protection with respect to harmful effects on the equipment due to the ingress
of water (dripping and light splashing).
Type 12K Enclosures constructed (with knockouts) for indoor use to provide a degree
of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against ingress of solid foreign objects
(falling dirt and circulating dust, lint, fibers, and flyings); and to provide a degree of
protection with respect to harmful effects on the equipment due to the ingress of water
(dripping and light splashing).
National Electrical Manufacturers Association
1300 N. 17th Street, Suite 1752
Rosslyn, VA 22209

Approved by NEMA Enclosures Section
November 2005
NEMA Enclosure Types

Type 13
Enclosures constructed for indoor use to provide a degree of protection to
personnel against access to hazardous parts; to provide a degree of protection of the
equipment inside the enclosure against ingress of solid foreign objects (falling dirt and
circulating dust, lint, fibers, and flyings); to provide a degree of protection with respect to
harmful effects on the equipment due to the ingress of water (dripping and light
splashing); and to provide a degree of protection against the spraying, splashing, and
seepage of oil and non-corrosive coolants.
Table 1
[From NEMA 250-2003]

Comparison of Specific Applications of Enclosures
for Indoor Nonhazardous Locations
Type of Enclosure
Provides a Degree of Protection Against the
Following Conditions

1*

2*

4

4X

5

6

6P

12

12K

13

Access to hazardous parts

X

X

X

X

X

X

X

X

X

X

Ingress of solid foreign objects (falling dirt)

X

X

X

X

X

X

X

X

X

X

Ingress of water (Dripping and light splashing)

...

X

X

X

X

X

X

X

X

X

Ingress of solid foreign objects (Circulating dust,
lint, fibers, and flyings **)

...

...

X

X

...

X

X

X

X

X

Ingress of solid foreign objects (Settling airborne
dust, lint, fibers, and flyings **)

...

...

X

X

X

X

X

X

X

X

Ingress of water (Hosedown and splashing water)

...

...

X

X

...

X

X

...

...

...

Oil and coolant seepage

...

...

...

..

...

...

...

X

X

X

Oil or coolant spraying and splashing

...

...

...

...

...

...

...

...

...

X

Corrosive agents

...

...

...

X

...

...

X

...

...

...

Ingress of water (Occasional temporary
submersion)

...

...

...

...

...

X

X

...

...

...

Ingress of water (Occasional prolonged
submersion)

...

...

...

...

...

...

X

...

...

...

* These enclosures may be ventilated.
** These fibers and flyings are nonhazardous materials and are not considered Class III type ignitable fibers or
combustible flyings. For Class III type ignitable fibers or combustible flyings see the National Electrical Code,
Article 500.

National Electrical Manufacturers Association
1300 N. 17th Street, Suite 1752
Rosslyn, VA 22209

Approved by NEMA Enclosures Section
November 2005
NEMA Enclosure Types

Table 2
[From NEMA 250-2003]

Comparison of Specific Applications of Enclosures
for Outdoor Nonhazardous Locations
Type of Enclosure
Provides a Degree of Protection Against
the Following Conditions
Access to hazardous parts

3
X

3X
X

3R*
X

3RX*
X

3S
X

3SX
X

4
X

4X
X

6
X

6P
X

Ingress of water (Rain, snow, and sleet **)

X

X

X

X

X

X

X

X

X

X

Sleet ***
Ingress of solid foreign objects (Windblown
dust, lint, fibers, and flyings)
Ingress of water (Hosedown)

...

...

...

...

X

X

...

...

...

...

X

X

...

...

X

X

X

X

X

X

...

...

...

...

...

...

X

X

X

X

Corrosive agents
Ingress of water (Occasional temporary
submersion)
Ingress of water (Occasional prolonged
submersion)

...
...

X
...

...
...

X
...

...
...

X
...

...
...

X
...

...
X

X
X

...

...

...

...

...

...

...

...

...

X

* These enclosures may be ventilated.
** External operating mechanisms are not required to be operable when the enclosure is ice covered.
*** External operating mechanisms are operable when the enclosure is ice covered.

In Hazardous Locations, when completely and properly installed and maintained,
Type 7 and 10 enclosures are designed to contain an internal explosion without causing
an external hazard. Type 8 enclosures are designed to prevent combustion through the
use of oil-immersed equipment. Type 9 enclosures are designed to prevent the ignition
of combustible dust.
Type 7
Enclosures constructed for indoor use in hazardous (classified) locations
classified as Class I, Division 1, Groups A, B, C, or D as defined in NFPA 70.
Type 8
Enclosures constructed for either indoor or outdoor use in hazardous
(classified) locations classified as Class I, Division 1, Groups A, B, C, and D as defined
in NFPA 70.
Type 9
Enclosures constructed for indoor use in hazardous (classified) locations
classified as Class II, Division 1, Groups E, F, or G as defined in NFPA 70.
Type 10
Enclosures constructed to meet the requirements of the Mine Safety and
Health Administration, 30 CFR, Part 18.

National Electrical Manufacturers Association
1300 N. 17th Street, Suite 1752
Rosslyn, VA 22209

Approved by NEMA Enclosures Section
November 2005
NEMA Enclosure Types

Table B-1
[From NEMA 250-2003]

Comparison of Specific Applications of Enclosures
for Indoor Hazardous Locations
(If the installation is outdoors and/or additional protection is required by
Table 1 and Table 2, a combination-type enclosure is required.)
Provides a Degree of Protection Against
Atmospheres Typically Containing
(See NFPA 497M for Complete Listing)

Enclosure Types 7 and
8, Class I Groups **

Enclosure Type 9,
Class II Groups

Class

A

B

C

D

E

F

G

10

Acetylene

I

X

...

...

...

...

...

...

...

Hydrogen, manufactured gas

I

...

X

...

...

...

...

...

...

Diethyl ether, ethylene, cyclopropane

I

...

...

X

...

...

...

...

...

Gasoline, hexane, butane, naphtha, propane,
acetone, toluene, isoprene

I

...

...

...

X

...

...

...

...

Metal dust

II

...

...

...

...

X

...

...

...

Carbon black, coal dust, coke dust

II

...

...

...

...

...

X

...

...

Flour, starch, grain dust

II

...

...

...

...

...

...

X

...

Fibers, flyings *

III

...

...

...

...

...

...

X

...

MSHA

...

...

...

...

...

...

...

X

Methane with or without coal dust

* For Class III type ignitable fibers or combustible flyings see the National Electrical Code, Article 500.
** Due to the characteristics of the gas, vapor, or dust, a product suitable for one Class or Group may not be suitable
for another Class or Group unless marked on the product.

National Electrical Manufacturers Association
1300 N. 17th Street, Suite 1752
Rosslyn, VA 22209

Approved by NEMA Enclosures Section
November 2005
NEMA Enclosure Types

Comparison Between NEMA Enclosure Type Numbers and IEC
Enclosure Classification Designations
IEC Publication 60529 Classification of Degrees of Protection Provided by Enclosures
provides a system for specifying the enclosures of electrical equipment on the basis of the
degree of protection provided by the enclosure. IEC 60529 does not specify degrees of
protection against mechanical damage of equipment, risk of explosions, or conditions
such as moisture (produced for example by condensation), corrosive vapors, fungus, or
vermin. The NEMA Standard for Enclosures for Electrical Equipment does test for
environmental conditions such as corrosion, rust, icing, oil, and coolants. For this reason,
and because the test and evaluations for other characteristics are not identical, the IEC
Enclosure Classification Designations cannot be exactly equated with the enclosure Type
numbers in this Standard.
The IEC designation consists of the letters IP followed by two numerals. The first
characteristic numeral indicates the degree of protection provided by the enclosure with
respect to persons and solid foreign objects entering the enclosure. The second
characteristic numeral indicates the degree of protection provided by the enclosure with
respect to the harmful ingress of water.
Table A-1 provides an equivalent conversion from the enclosure Type numbers in this
Standard to the IEC Enclosure Classification Designations. The enclosure type numbers
meet or exceed the test requirements for the associated IEC Classification; for this reason
Table A-1 cannot be used to convert from IEC Classifications to enclosure Type numbers.

National Electrical Manufacturers Association
1300 N. 17th Street, Suite 1752
Rosslyn, VA 22209

Approved by NEMA Enclosures Section
November 2005
Table A-1
CONVERSION OF NEMA ENCLOSURE TYPE RATINGS
TO IEC 60529 ENCLOSURE CLASSIFICATION DESIGNATIONS (IP)
(Cannot be Used to Convert IEC Classification Designations to NEMA Type Ratings)
IP

IP

First Character

NEMA Enclosure Type
1

3, 3X,
3S, 3SX

2

3R,
3RX

4, 4X

Second Character

5

6

12,
12K, 13

6P

IP0_

IP_0

IP1_

IP_1

IP2_

IP_2

IP3_

IP_3

IP4_

IP_4

IP5_

IP_5

IP6_

IP_6
IP_7
IP_8
A

B

A

B

A

B

A

B

A

B

A

B

A

B

A

B

A

B

A = A shaded block in the “A” column indicates that the NEMA Enclosure Type exceeds the requirements for the respective IEC 60529 IP First
Character Designation. The IP First Character Designation is the protection against access to hazardous parts and solid foreign objects.
B = A shaded block in the “B” column indicates that the NEMA Enclosure Type exceeds the requirements for the respective IEC 60529 IP Second
Character Designation. The IP Second Character Designation is the protection against the ingress of water.
EXAMPLE OF TABLE USE
An IEC IP 45 Enclosure Rating is specified. What NEMA Type Enclosures meet and exceed the IP 45 rating?

National Electrical Manufacturers Association
1300 N. 17th Street, Suite 1752
Rosslyn, VA 22209

Approved by NEMA Enclosures Section
Nov 2005
NEMA Enclosure Types

Referencing the first character, 4, in the IP rating and the row designated “IP4_” in the leftmost column in the table; the blocks in Column “A” for NEMA Types 3,
3X, 3S, 3SX, 4, 4X, 5, 6, 6P, 12, 12K, and 13 are shaded. These NEMA ratings meet and exceed the IEC protection requirements against access to hazardous
parts and solid foreign objects.

Referencing the second character, 5, in the IP rating and the row designated “IP_5” in the rightmost column in the table; the blocks in Column “B” for NEMA
Types 3, 3X, 3S, 3SX, 4, 4X, 6, and 6P are shaded. These NEMA ratings meet and exceed the IEC requirements for protection against the ingress of water. The
absence of shading in Column “B” beneath the “NEMA Enclosure Type 5” indicates that Type 5 does not meet the IP 45 protection requirements against the
ingress of water. Likewise the absence of shading in Column “B” for NEMA Type 12, 12K and 13 enclosures indicates that these enclosures do not meet the IP
45 requirements for protection against the ingress of water. Only Types 3, 3X, 3S, 3SX, 4, 4X, 6, and 6P have both Column “A” in the “IP4_” row and Column “B”
in the “IP_5” row shaded and could be used in an IP45 application.
The NEMA Enclosure Type 3 not only meets the IP 45 Enclosure Rating, but also exceeds the IEC requirements because the NEMA Type
requires an outdoor corrosion test; a gasket aging test; a dust test; an external icing test; and no water penetration in the rain test. Slight
differences exist between the IEC and NEMA test methods, but the IEC rating permits the penetration of water if “it does not deposit on
insulation parts, or reach live parts.” The IEC rating does not require a corrosion test; gasket aging test; dust test or external icing test. Because
the NEMA ratings include additional test requirements, this table cannot be used to select IP Designations for NEMA rated enclosure
specifications.
IEC 60529 specifies that an enclosure shall only be designated with a stated degree of protection indicated by the first characteristic numeral if it also complies
with all lower degrees of protection. Furthermore IEC 60529 states that an enclosure shall only be designated with a degree of protection indicated by the second
characteristic numeral if it also complies with all lower degrees of protection up to and including the second characteristic numeral 6. An enclosure designated
with a second characteristic numeral 7 or 8 only is considered unsuitable for exposure to water jets (designated by second characteristic numeral 5 or 6) and
need not comply with requirements for numeral 5 or 6 unless it is dual coded. Since the IEC protection requirements become more stringent with increasing IP
character value up through 6, once a NEMA Type rating meets the requirements for an IP designation up through 6, it will also meet the requirements for all
lower IP designations. This is apparent from the shaded areas shown in the table.

National Electrical Manufacturers Association
1300 N. 17th Street, Suite 1752
Rosslyn, VA 22209

Approved by NEMA Enclosures Section
November 2005

More Related Content

What's hot

basic electrical and elctronics devices or equipments used at home
basic electrical and elctronics devices or equipments used at homebasic electrical and elctronics devices or equipments used at home
basic electrical and elctronics devices or equipments used at home
sudhanshu kumar rai
 

What's hot (20)

Earth pit
Earth pitEarth pit
Earth pit
 
Cableado Estructurado
Cableado EstructuradoCableado Estructurado
Cableado Estructurado
 
Electrical Safety and Risk Assessments
Electrical Safety and Risk AssessmentsElectrical Safety and Risk Assessments
Electrical Safety and Risk Assessments
 
Electrical safety slideshare
Electrical safety slideshareElectrical safety slideshare
Electrical safety slideshare
 
Electric instalation operation and training manual
Electric instalation operation and training manualElectric instalation operation and training manual
Electric instalation operation and training manual
 
Insulation coordination.
Insulation coordination.Insulation coordination.
Insulation coordination.
 
monkey menace solution , freedom from monkey problms
monkey  menace solution , freedom from monkey problmsmonkey  menace solution , freedom from monkey problms
monkey menace solution , freedom from monkey problms
 
Mediciones electricas de transformadores Megger
Mediciones electricas de transformadores MeggerMediciones electricas de transformadores Megger
Mediciones electricas de transformadores Megger
 
Electrical safety.ppt trianing
Electrical safety.ppt trianingElectrical safety.ppt trianing
Electrical safety.ppt trianing
 
Calculo de cables_enterrados
Calculo de cables_enterradosCalculo de cables_enterrados
Calculo de cables_enterrados
 
XLPE Land Cable System
XLPE Land Cable SystemXLPE Land Cable System
XLPE Land Cable System
 
Electrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 ComplianceElectrical Safety, Personal Protective Equipment, & Z462 Compliance
Electrical Safety, Personal Protective Equipment, & Z462 Compliance
 
Maintain and repair consumer electronics
Maintain and repair consumer electronicsMaintain and repair consumer electronics
Maintain and repair consumer electronics
 
Electrical Supplies and Materials
Electrical Supplies and MaterialsElectrical Supplies and Materials
Electrical Supplies and Materials
 
Electrical wiring
Electrical wiringElectrical wiring
Electrical wiring
 
NFPA 70E Electrical Safety in the Workplace by Hortica
NFPA 70E  Electrical Safety in the Workplace by HorticaNFPA 70E  Electrical Safety in the Workplace by Hortica
NFPA 70E Electrical Safety in the Workplace by Hortica
 
Electrical measuring instruments
Electrical measuring instrumentsElectrical measuring instruments
Electrical measuring instruments
 
Safety precautions for electrical appliances
Safety precautions for electrical appliances Safety precautions for electrical appliances
Safety precautions for electrical appliances
 
National electrical code.pptx
National electrical code.pptxNational electrical code.pptx
National electrical code.pptx
 
basic electrical and elctronics devices or equipments used at home
basic electrical and elctronics devices or equipments used at homebasic electrical and elctronics devices or equipments used at home
basic electrical and elctronics devices or equipments used at home
 

Viewers also liked (6)

Nema standards publication mg 2 2001
Nema standards publication mg 2 2001Nema standards publication mg 2 2001
Nema standards publication mg 2 2001
 
Nema symbols
Nema symbolsNema symbols
Nema symbols
 
Ingress protection
Ingress protectionIngress protection
Ingress protection
 
IP (Ingress protection) Ratings
IP (Ingress protection) RatingsIP (Ingress protection) Ratings
IP (Ingress protection) Ratings
 
Electrical earthing
Electrical earthingElectrical earthing
Electrical earthing
 
Electrical grounding and earthing systems
Electrical grounding and earthing systemsElectrical grounding and earthing systems
Electrical grounding and earthing systems
 

Similar to Nema enclosure-types

Similar to Nema enclosure-types (20)

Nema enclosure-types
Nema enclosure-typesNema enclosure-types
Nema enclosure-types
 
Hazardous Classification
Hazardous ClassificationHazardous Classification
Hazardous Classification
 
nema ratings r0
nema ratings r0nema ratings r0
nema ratings r0
 
2 IMPORTANCE OCC SFTY & H.ppt
2 IMPORTANCE OCC SFTY & H.ppt2 IMPORTANCE OCC SFTY & H.ppt
2 IMPORTANCE OCC SFTY & H.ppt
 
Cotainment Building Presentation
Cotainment Building PresentationCotainment Building Presentation
Cotainment Building Presentation
 
impact brochure
impact brochureimpact brochure
impact brochure
 
Lightning protection
Lightning protectionLightning protection
Lightning protection
 
ViVAX Presentation
ViVAX PresentationViVAX Presentation
ViVAX Presentation
 
Safe Series
Safe SeriesSafe Series
Safe Series
 
STI 1221C Data Sheet
STI 1221C Data SheetSTI 1221C Data Sheet
STI 1221C Data Sheet
 
STI 1227 Data Sheet
STI 1227 Data SheetSTI 1227 Data Sheet
STI 1227 Data Sheet
 
STI 1210A Data Sheet
STI 1210A Data SheetSTI 1210A Data Sheet
STI 1210A Data Sheet
 
STI 1221E Data Sheet
STI 1221E Data SheetSTI 1221E Data Sheet
STI 1221E Data Sheet
 
STI 1221A Data Sheet
STI 1221A Data SheetSTI 1221A Data Sheet
STI 1221A Data Sheet
 
STI 1221A4X Data Sheet
STI 1221A4X Data SheetSTI 1221A4X Data Sheet
STI 1221A4X Data Sheet
 
STI 1210B Data Sheet
STI 1210B Data SheetSTI 1210B Data Sheet
STI 1210B Data Sheet
 
STI 1215 Data Sheet
STI 1215 Data SheetSTI 1215 Data Sheet
STI 1215 Data Sheet
 
STI 1212 Data Sheet
STI 1212 Data SheetSTI 1212 Data Sheet
STI 1212 Data Sheet
 
STI 1221B Data Sheet
STI 1221B Data SheetSTI 1221B Data Sheet
STI 1221B Data Sheet
 
STI 1222 Data Sheet
STI 1222 Data SheetSTI 1222 Data Sheet
STI 1222 Data Sheet
 

Recently uploaded

Why Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire businessWhy Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire business
panagenda
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Safe Software
 

Recently uploaded (20)

FWD Group - Insurer Innovation Award 2024
FWD Group - Insurer Innovation Award 2024FWD Group - Insurer Innovation Award 2024
FWD Group - Insurer Innovation Award 2024
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a Fresher
 
Artificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : UncertaintyArtificial Intelligence Chap.5 : Uncertainty
Artificial Intelligence Chap.5 : Uncertainty
 
Why Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire businessWhy Teams call analytics are critical to your entire business
Why Teams call analytics are critical to your entire business
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
 
Corporate and higher education May webinar.pptx
Corporate and higher education May webinar.pptxCorporate and higher education May webinar.pptx
Corporate and higher education May webinar.pptx
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
 
A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?
 
Manulife - Insurer Transformation Award 2024
Manulife - Insurer Transformation Award 2024Manulife - Insurer Transformation Award 2024
Manulife - Insurer Transformation Award 2024
 
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWEREMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt Robison
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
 
Automating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps ScriptAutomating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps Script
 
GenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdfGenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdf
 
Apidays New York 2024 - The value of a flexible API Management solution for O...
Apidays New York 2024 - The value of a flexible API Management solution for O...Apidays New York 2024 - The value of a flexible API Management solution for O...
Apidays New York 2024 - The value of a flexible API Management solution for O...
 
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot TakeoffStrategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
Polkadot JAM Slides - Token2049 - By Dr. Gavin Wood
Polkadot JAM Slides - Token2049 - By Dr. Gavin WoodPolkadot JAM Slides - Token2049 - By Dr. Gavin Wood
Polkadot JAM Slides - Token2049 - By Dr. Gavin Wood
 
AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024
 

Nema enclosure-types

  • 1. NEMA Enclosure Types The purpose of this document is to provide general information on the definitions of NEMA Enclosure Types to architects, engineers, installers, inspectors and other interested parties. [For more detailed and complete information, NEMA Standards Publication 250-2003, “Enclosures for Electrical Equipment (1000 Volts Maximum)” should be consulted. This Standards Publication as well as all other NEMA publications are available from IHS @ 800 854-7179 or http://www.global.ihs.com] Definitions [from NEMA 250-2003] In Non-Hazardous Locations, the specific enclosure Types, their applications, and the environmental conditions they are designed to protect against, when completely and properly installed, are as follows: Type 1 Enclosures constructed for indoor use to provide a degree of protection to personnel against access to hazardous parts and to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt). Type 2 Enclosures constructed for indoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt); and to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (dripping and light splashing). Type 3 Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); and that will be undamaged by the external formation of ice on the enclosure. Type 3R Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); and that will be undamaged by the external formation of ice on the enclosure. National Electrical Manufacturers Association 1300 N. 17th Street, Suite 1752 Rosslyn, VA 22209 Approved by NEMA Enclosures Section Nov 2005 Page 1 of 2
  • 2. NEMA Enclosure Types Type 3S Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); and for which the external mechanism(s) remain operable when ice laden. Type 3X Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); that provides an additional level of protection against corrosion and that will be undamaged by the external formation of ice on the enclosure. Type 3RX Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); that will be undamaged by the external formation of ice on the enclosure that provides an additional level of protection against corrosion; and that will be undamaged by the external formation of ice on the enclosure. Type 3SX Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); that provides an additional level of protection against corrosion; and for which the external mechanism(s) remain operable when ice laden. Type 4 Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow, splashing water, and hose directed water); and that will be undamaged by the external formation of ice on the enclosure. National Electrical Manufacturers Association 1300 N. 17th Street, Suite 1752 Rosslyn, VA 22209 Approved by NEMA Enclosures Section November 2005
  • 3. NEMA Enclosure Types Type 4X Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow, splashing water, and hose directed water); that provides an additional level of protection against corrosion; and that will be undamaged by the external formation of ice on the enclosure. Type 5 Enclosures constructed for indoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and settling airborne dust, lint, fibers, and flyings); and to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (dripping and light splashing). Type 6 Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (hose directed water and the entry of water during occasional temporary submersion at a limited depth); and that will be undamaged by the external formation of ice on the enclosure. Type 6P Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (hose directed water and the entry of water during prolonged submersion at a limited depth); that provides an additional level of protection against corrosion and that will be undamaged by the external formation of ice on the enclosure. Type 12 Enclosures constructed (without knockouts) for indoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and circulating dust, lint, fibers, and flyings); and to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (dripping and light splashing). Type 12K Enclosures constructed (with knockouts) for indoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and circulating dust, lint, fibers, and flyings); and to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (dripping and light splashing). National Electrical Manufacturers Association 1300 N. 17th Street, Suite 1752 Rosslyn, VA 22209 Approved by NEMA Enclosures Section November 2005
  • 4. NEMA Enclosure Types Type 13 Enclosures constructed for indoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and circulating dust, lint, fibers, and flyings); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (dripping and light splashing); and to provide a degree of protection against the spraying, splashing, and seepage of oil and non-corrosive coolants. Table 1 [From NEMA 250-2003] Comparison of Specific Applications of Enclosures for Indoor Nonhazardous Locations Type of Enclosure Provides a Degree of Protection Against the Following Conditions 1* 2* 4 4X 5 6 6P 12 12K 13 Access to hazardous parts X X X X X X X X X X Ingress of solid foreign objects (falling dirt) X X X X X X X X X X Ingress of water (Dripping and light splashing) ... X X X X X X X X X Ingress of solid foreign objects (Circulating dust, lint, fibers, and flyings **) ... ... X X ... X X X X X Ingress of solid foreign objects (Settling airborne dust, lint, fibers, and flyings **) ... ... X X X X X X X X Ingress of water (Hosedown and splashing water) ... ... X X ... X X ... ... ... Oil and coolant seepage ... ... ... .. ... ... ... X X X Oil or coolant spraying and splashing ... ... ... ... ... ... ... ... ... X Corrosive agents ... ... ... X ... ... X ... ... ... Ingress of water (Occasional temporary submersion) ... ... ... ... ... X X ... ... ... Ingress of water (Occasional prolonged submersion) ... ... ... ... ... ... X ... ... ... * These enclosures may be ventilated. ** These fibers and flyings are nonhazardous materials and are not considered Class III type ignitable fibers or combustible flyings. For Class III type ignitable fibers or combustible flyings see the National Electrical Code, Article 500. National Electrical Manufacturers Association 1300 N. 17th Street, Suite 1752 Rosslyn, VA 22209 Approved by NEMA Enclosures Section November 2005
  • 5. NEMA Enclosure Types Table 2 [From NEMA 250-2003] Comparison of Specific Applications of Enclosures for Outdoor Nonhazardous Locations Type of Enclosure Provides a Degree of Protection Against the Following Conditions Access to hazardous parts 3 X 3X X 3R* X 3RX* X 3S X 3SX X 4 X 4X X 6 X 6P X Ingress of water (Rain, snow, and sleet **) X X X X X X X X X X Sleet *** Ingress of solid foreign objects (Windblown dust, lint, fibers, and flyings) Ingress of water (Hosedown) ... ... ... ... X X ... ... ... ... X X ... ... X X X X X X ... ... ... ... ... ... X X X X Corrosive agents Ingress of water (Occasional temporary submersion) Ingress of water (Occasional prolonged submersion) ... ... X ... ... ... X ... ... ... X ... ... ... X ... ... X X X ... ... ... ... ... ... ... ... ... X * These enclosures may be ventilated. ** External operating mechanisms are not required to be operable when the enclosure is ice covered. *** External operating mechanisms are operable when the enclosure is ice covered. In Hazardous Locations, when completely and properly installed and maintained, Type 7 and 10 enclosures are designed to contain an internal explosion without causing an external hazard. Type 8 enclosures are designed to prevent combustion through the use of oil-immersed equipment. Type 9 enclosures are designed to prevent the ignition of combustible dust. Type 7 Enclosures constructed for indoor use in hazardous (classified) locations classified as Class I, Division 1, Groups A, B, C, or D as defined in NFPA 70. Type 8 Enclosures constructed for either indoor or outdoor use in hazardous (classified) locations classified as Class I, Division 1, Groups A, B, C, and D as defined in NFPA 70. Type 9 Enclosures constructed for indoor use in hazardous (classified) locations classified as Class II, Division 1, Groups E, F, or G as defined in NFPA 70. Type 10 Enclosures constructed to meet the requirements of the Mine Safety and Health Administration, 30 CFR, Part 18. National Electrical Manufacturers Association 1300 N. 17th Street, Suite 1752 Rosslyn, VA 22209 Approved by NEMA Enclosures Section November 2005
  • 6. NEMA Enclosure Types Table B-1 [From NEMA 250-2003] Comparison of Specific Applications of Enclosures for Indoor Hazardous Locations (If the installation is outdoors and/or additional protection is required by Table 1 and Table 2, a combination-type enclosure is required.) Provides a Degree of Protection Against Atmospheres Typically Containing (See NFPA 497M for Complete Listing) Enclosure Types 7 and 8, Class I Groups ** Enclosure Type 9, Class II Groups Class A B C D E F G 10 Acetylene I X ... ... ... ... ... ... ... Hydrogen, manufactured gas I ... X ... ... ... ... ... ... Diethyl ether, ethylene, cyclopropane I ... ... X ... ... ... ... ... Gasoline, hexane, butane, naphtha, propane, acetone, toluene, isoprene I ... ... ... X ... ... ... ... Metal dust II ... ... ... ... X ... ... ... Carbon black, coal dust, coke dust II ... ... ... ... ... X ... ... Flour, starch, grain dust II ... ... ... ... ... ... X ... Fibers, flyings * III ... ... ... ... ... ... X ... MSHA ... ... ... ... ... ... ... X Methane with or without coal dust * For Class III type ignitable fibers or combustible flyings see the National Electrical Code, Article 500. ** Due to the characteristics of the gas, vapor, or dust, a product suitable for one Class or Group may not be suitable for another Class or Group unless marked on the product. National Electrical Manufacturers Association 1300 N. 17th Street, Suite 1752 Rosslyn, VA 22209 Approved by NEMA Enclosures Section November 2005
  • 7. NEMA Enclosure Types Comparison Between NEMA Enclosure Type Numbers and IEC Enclosure Classification Designations IEC Publication 60529 Classification of Degrees of Protection Provided by Enclosures provides a system for specifying the enclosures of electrical equipment on the basis of the degree of protection provided by the enclosure. IEC 60529 does not specify degrees of protection against mechanical damage of equipment, risk of explosions, or conditions such as moisture (produced for example by condensation), corrosive vapors, fungus, or vermin. The NEMA Standard for Enclosures for Electrical Equipment does test for environmental conditions such as corrosion, rust, icing, oil, and coolants. For this reason, and because the test and evaluations for other characteristics are not identical, the IEC Enclosure Classification Designations cannot be exactly equated with the enclosure Type numbers in this Standard. The IEC designation consists of the letters IP followed by two numerals. The first characteristic numeral indicates the degree of protection provided by the enclosure with respect to persons and solid foreign objects entering the enclosure. The second characteristic numeral indicates the degree of protection provided by the enclosure with respect to the harmful ingress of water. Table A-1 provides an equivalent conversion from the enclosure Type numbers in this Standard to the IEC Enclosure Classification Designations. The enclosure type numbers meet or exceed the test requirements for the associated IEC Classification; for this reason Table A-1 cannot be used to convert from IEC Classifications to enclosure Type numbers. National Electrical Manufacturers Association 1300 N. 17th Street, Suite 1752 Rosslyn, VA 22209 Approved by NEMA Enclosures Section November 2005
  • 8. Table A-1 CONVERSION OF NEMA ENCLOSURE TYPE RATINGS TO IEC 60529 ENCLOSURE CLASSIFICATION DESIGNATIONS (IP) (Cannot be Used to Convert IEC Classification Designations to NEMA Type Ratings) IP IP First Character NEMA Enclosure Type 1 3, 3X, 3S, 3SX 2 3R, 3RX 4, 4X Second Character 5 6 12, 12K, 13 6P IP0_ IP_0 IP1_ IP_1 IP2_ IP_2 IP3_ IP_3 IP4_ IP_4 IP5_ IP_5 IP6_ IP_6 IP_7 IP_8 A B A B A B A B A B A B A B A B A B A = A shaded block in the “A” column indicates that the NEMA Enclosure Type exceeds the requirements for the respective IEC 60529 IP First Character Designation. The IP First Character Designation is the protection against access to hazardous parts and solid foreign objects. B = A shaded block in the “B” column indicates that the NEMA Enclosure Type exceeds the requirements for the respective IEC 60529 IP Second Character Designation. The IP Second Character Designation is the protection against the ingress of water. EXAMPLE OF TABLE USE An IEC IP 45 Enclosure Rating is specified. What NEMA Type Enclosures meet and exceed the IP 45 rating? National Electrical Manufacturers Association 1300 N. 17th Street, Suite 1752 Rosslyn, VA 22209 Approved by NEMA Enclosures Section Nov 2005
  • 9. NEMA Enclosure Types Referencing the first character, 4, in the IP rating and the row designated “IP4_” in the leftmost column in the table; the blocks in Column “A” for NEMA Types 3, 3X, 3S, 3SX, 4, 4X, 5, 6, 6P, 12, 12K, and 13 are shaded. These NEMA ratings meet and exceed the IEC protection requirements against access to hazardous parts and solid foreign objects. Referencing the second character, 5, in the IP rating and the row designated “IP_5” in the rightmost column in the table; the blocks in Column “B” for NEMA Types 3, 3X, 3S, 3SX, 4, 4X, 6, and 6P are shaded. These NEMA ratings meet and exceed the IEC requirements for protection against the ingress of water. The absence of shading in Column “B” beneath the “NEMA Enclosure Type 5” indicates that Type 5 does not meet the IP 45 protection requirements against the ingress of water. Likewise the absence of shading in Column “B” for NEMA Type 12, 12K and 13 enclosures indicates that these enclosures do not meet the IP 45 requirements for protection against the ingress of water. Only Types 3, 3X, 3S, 3SX, 4, 4X, 6, and 6P have both Column “A” in the “IP4_” row and Column “B” in the “IP_5” row shaded and could be used in an IP45 application. The NEMA Enclosure Type 3 not only meets the IP 45 Enclosure Rating, but also exceeds the IEC requirements because the NEMA Type requires an outdoor corrosion test; a gasket aging test; a dust test; an external icing test; and no water penetration in the rain test. Slight differences exist between the IEC and NEMA test methods, but the IEC rating permits the penetration of water if “it does not deposit on insulation parts, or reach live parts.” The IEC rating does not require a corrosion test; gasket aging test; dust test or external icing test. Because the NEMA ratings include additional test requirements, this table cannot be used to select IP Designations for NEMA rated enclosure specifications. IEC 60529 specifies that an enclosure shall only be designated with a stated degree of protection indicated by the first characteristic numeral if it also complies with all lower degrees of protection. Furthermore IEC 60529 states that an enclosure shall only be designated with a degree of protection indicated by the second characteristic numeral if it also complies with all lower degrees of protection up to and including the second characteristic numeral 6. An enclosure designated with a second characteristic numeral 7 or 8 only is considered unsuitable for exposure to water jets (designated by second characteristic numeral 5 or 6) and need not comply with requirements for numeral 5 or 6 unless it is dual coded. Since the IEC protection requirements become more stringent with increasing IP character value up through 6, once a NEMA Type rating meets the requirements for an IP designation up through 6, it will also meet the requirements for all lower IP designations. This is apparent from the shaded areas shown in the table. National Electrical Manufacturers Association 1300 N. 17th Street, Suite 1752 Rosslyn, VA 22209 Approved by NEMA Enclosures Section November 2005