The watchdog : a main component in the protection scheme
Abstract
The watchdog is one of the most important part of the Sepam monitoring system for it notifies the
operator whether the protection functions of the Sepam are in working order. This monitoring system is
based on self-tests. If an internal failure is detected the Sepam is put in standby position. The
watchdog should also be used as a back-up protection in order to maintain primary safety when the
Sepam is in standby position. This shows that the protection relay is useless without a global
protection scheme which takes into account the possibility of a failure of the Sepam. A compromise
has to be found between safety and availability of the electric network regarding the needs of the
plant. As the behavior of the Sepam in standby position is linked with the type of the watchdog, the
choice of this component is crucial.
Index terms – watchdog, monitoring system, standby position, back-up protection, protection scheme,
safety and availability, undervoltage coil, shunt trip coil.
Introduction
The aim of the Sepam relay is to manage electric installation by providing safety and availability of the
installation and the equipment. The protection scheme can be improved with the use of the watchdog.
This simple component is really an important part of the protection plan and can easily provide higher
protection.
Definition of a watchdog
The watchdog contact is a change over contact : the contacts normally closed of the relays are
connected in daisy-chain
m ic r o p r o c e s s o r
r e la y F n
w a t c h d o g
c o n t a c t
a n n u n c ia t o r
p a n e l
r e la y F n
f a u lt
Figure 1 – Watchdog contact
1
Schneider-Electric
Edouard Murat : edouard.murat@schneider-electric.com
Décembre 2005
Version 1.0
The watchdog should be used..
..As a notifying device of the monitoring system
The Sepam relay is equipped with a self monitoring system which is able to detect most internal
failures in protection circuits of the Sepam. This monitoring system is based on self-tests. The
purposes of the self-tests is to detect internal failures that may cause unexpected tripping or non-
tripping. If such a failure is detected by the self-tests, the Sepam is put in standby position. In this
position, all protections functions are turned off in order to avoid any unwanted operation, logic outputs
of the Sepam are open and the watchdog is activated. Please note that some internal failures has no
consequence on protection functions of the Sepam1
.
State of the Relay Watchdog Causes
In standby position activated Internal failure detected
OR
Relay not energized
In working order not activated Relay energized
AND
no internal failure
Fig. 2 – the standby position
The watchdog is an important part of this monitoring system because it indicates if the protections
functions of the Sepam are in working order . If an internal fault is detected by the Sepam, a light of
the Sepam front panel automatically flickers even if the watchdog is not connected to the system. The
fact is that in case of an internal fault of the digital relay, if the watchdog is not properly connected to
the control system, the only way to notice that the relay has failed is to control the front panel of the
relay. The watchdog contact should therefore be connected to the higher level system in order to
generate an efficient alarm and give the state of the relay. For example, a hooter in a plant or a bigger
flickering light can be activated in order to inform the operator.
State of the
Watchdog
contact
No failure
detected
Internal failure detected
Watchdog
properly
connected to the
control system
Protections
functions are in
working order
- Protection functions are out of order
- Sepam in standby position
- The alarm light of the Sepam front panel flickers
- Watchdog contact activates an alarm system operator is
notified that a maintenance operation is required thanks to
the connection to the control system
Watchdog not
connected
Protection
functions are in
working order
- Protection functions are out of order
- Sepam in standby position
- The alarm light of the Sepam front panel flickers
- The need of maintenance is detected only if an operator
controls the front panel of the digital relay
Fig. 3 – the watchdog, a warning system
1
In this case, the Sepam is said to be in downgraded working order : some internal failure has been detected but no protection
function of the Sepam has been affected
2
Schneider-Electric
Edouard Murat : edouard.murat@schneider-electric.com
Décembre 2005
Version 1.0
The first step of maintenance operations is to be kept informed of the state of the device. Thanks to
the watchdog, the maintenance staff is warned of the state of the protection relay and could repair the
faulty device without delay. The use of the watchdog is the main solution because this is often enough
to prevent damage to equipment and to avoid loss of production.
Although the self monitoring system of the Sepam will find most internal failures, some may not be
detected. Those are mainly linked with the different modules of the Sepam such as disconnected
sensitive earth fault current transformers, failure of input / output modules or also faulty analog output
module. Those failures do not concern the relay its self but may have important impacts on the
protection functions. For example, if a core balance current transformer used in order to measure the
sense of the current is linked with the Sepam in the wrong way, it will have impact on all directional
protections. For this reason we recommend periodic testing even when self monitoring is provided.
Considering the frequency of those faults, 5 years between each maintenance operation should
prevent the plant from such problems.
Functions Type of self-test Execution period Fail-safe position
Power supply Detection of processor power supply
outside tolerance range
At time of energizing
and continually
YES
Acquisition of
currents or voltages
Detection of analog channel saturation
Filtering by data signal processing
Test of presence and recognition of
connector
Continually
Continually
At time of energizing
and continually
YES
YES
YES
Processing unit Memory test
Software watchdog
At time of energizing
and continually
YES
YES
UMI Memory test
Software watchdog
At time of energizing
Continually
NO
NO
Logical I/O Test of presence and recognition of
module
At time of energizing
and continually
YES
(1)
RTD inputs Memory test
Software watchdog
Analog conversion test
At time of energizing
Continually
Continually
NO
NO
NO
Analog output Memory test
Software watchdog
At time of energizing
Continually
NO
NO
(1) only when the module is missing or if there are not enough logical inputs
Fig. 4 – The self-tests of the Sepam
3
Schneider-Electric
Edouard Murat : edouard.murat@schneider-electric.com
Décembre 2005
Version 1.0
..As a back-up protection
The watchdog contacts can also be used to provide back-up protection by other relays. The back-up
protection is a brilliant solution in order not to depend only on one Sepam that might be faulty but also
on other Sepam that protect the upstream electric network.
If the protection system is built according to the sate of the art, each fault should be detected by at
least two different protection relays. This can be achieved either by installing 2 different protection
relays on one circuit-breaker (commonly used on transmission systems) or by relying on the upstream
breaker and its protection relay (very common in distribution systems). This basic principle can be
improved by using the following back-up protection system
The back-up protection system is really simple and uses the fact that a protection scheme is
composed of upstream protection relays and downstream protection relays. If the downstream Sepam
relay is in standby position, the protection functions are not in working order. An electric network failure
may happen and damage the power system that should have been protected by the Sepam. The
answer to this problem is to wire the watchdog contact of the downstream Sepam relay with the
protection of the upstream Sepam relay.
An example is described below (Fig. 4.)
Fig. 5 - Example of the use of watchdog contact in a back-up protection
The relay F2 is in working order whereas the relay F1 is in standby position as the watchdog is closed.
Therefore relay F1 does not provide any protection anymore. If a short-circuit occurs in the network
which was protected by F1, the back-up protection F4 will trip the circuit-breaker controlled by
F1thanks to the back-up trip circuit.
Furthermore, any back-up scheme which uses the watchdog contacts of microprocessor relays must
still provide the minimum back-up protection in the case of undetected failures in the relay or circuit-
breaker failure. The protection of a power system using Sepam protection relays is secured, but the
4
Schneider-Electric
Edouard Murat : edouard.murat@schneider-electric.com
Décembre 2005
Version 1.0
power system has to be protected even if the protection function fails. Using the watchdog as a back-
up protection increase the availability and the safety.
Protection scheme
Since many protection functions are included in one device, a reliable protection scheme is very
important in order to protect capital equipment, to protect operating personnel, and to reduce down
time by selectively clearing faults.
Correct operation of the protection circuit including back-up protection may ensure optimal clearance
of the fault but will not in itself prevent a loss of production. In other words good back-up protection
will not fix a bad design.
The reason for extensive damage in installations is not often a faulty protection equipment itself but
how the protection scheme has been designed and implemented.
The protection plan should be designed in order to obtain the best combination of protection and
continuous operation. Any analysis of back-up protection must take into account the complete
protection circuit that consist of the circuit-breaker, the instrument transformers, the auxiliary power
supply, and the relay. Even the most advanced protection relay is useless without a well-designed
protection scheme : if the protection equipment is incorrectly wired and the relays incorrectly set, the
availability and the safety of the power system can not be ensured.
Safety and availability
A protection system has to ensure two main functions :
- To protect the electric installation/components against overloads, and short circuits due to
component failures and therefore to avoid accidents (fires, explosion) that may follow. This
function is linked with safety.
- To provide power so that electrical equipment can run properly. This function is linked with
availability.
As explained before, a good protection scheme takes into account the possibility of a failure of the
protection relay. Furthermore, it is established that some failures caused more damage to safety than
to availability and vice versa :
- A failure to trip of the protection relay may lead to the destruction of components. This can
start fires which may turn into explosion. This is, of course, always associated with human
risks.
- False trip of a protection relay may trouble the production availability of the installation. This
may lead to a partial or a complete loss (blackout) of the production. This often implies an
important financial loss.
5
Safety of the
system
Availability of
the system
False trip of the
protection relay
Failure to trip of the
protection relay
Fair balance between Safety and
availability
Schneider-Electric
Edouard Murat : edouard.murat@schneider-electric.com
Décembre 2005
Version 1.0
Fig. 6 - Balance between safety and availability
Safety and availability are conflicting requirements: improving the one decreases the other one and
reciprocally. Therefore designing a protection scheme has to be a good compromise between safety
and availability.
The appropriate watchdog
Failures have different impact on the electric network depending on their type, their location, the need
of the plant. It is possible to distinguish two main types : the “safe failures” and “unsafe failures”. It is
really important to note that those two types depend on the need of the plant. It is no sense to talk
about a “safe failure” in a universal point of view.
The protection relay has to ensure availability when “safe failures” occurs and must prevent the power
system from “unsafe states”. As a consequence, the standby position is a main issue and has to be
carefully tackled.
The so-called "safety state" actually depends on the kind of MV application. In most applications the
de-energizing of the system will be the safe state. For instance it is often requested to stop a motor in
case of over-current. But in some specific cases, it will be safer to keep the system energized. For
instance, some safety pumps need to be kept running even in case of MV failure.
This is a problem for manufacturers to address properly requirements of safety and availability. This
issue can be solved by using a temporary "standby" position. In this state, the protection relay is
stopped, and alerts the system for curative maintenance within limited time (24 hours) as showed
below (Fig. 4).
6
Schneider-Electric
Edouard Murat : edouard.murat@schneider-electric.com
Décembre 2005
Version 1.0
Fig. 7 – Example of the use of the temporary "standby" position
In applications where safety is crucial, the system designer will choose a safety-oriented architecture.
In case of a failure detected by self-testing, the system will go in the Safety state, resulting in circuit
tripping. If the safe state of a system is to de-energize it, the use of "under-voltage" coils mode will
ensure safety. In applications where safety and availability have to be balanced, using "shunt trip coils"
may ensure both safety and availability. When self-testing detects a protection relay failure, or when
the power supply is faulty, the watchdog relay is activated, and an upstream protection relay replaces
the downstream faulty protection relay during the fault condition period. Using "shunt trip" coils when
the safe state of a system is to de-energize it will ensure a compromise between safety and
availability.
7
Schneider-Electric
Edouard Murat : edouard.murat@schneider-electric.com
Décembre 2005
Version 1.0
8
PROTECTION IS RUNNUNG
Watchdog linked with the
protection relay
No watchdog linked with
the protection relay
STANDBY POSITION
- a failure was detected by self-
tests
- WD activated
- protection function are turned
off
HAZARDOUS STATE
- protection functions seem to be
working
- protection functions are
actually inoperant
ELECTRIC
NETWOR
K
FAILURE
Watchdog
fulfilled with
undervoltage
coil
Watchdog
fulfilled with
shunt trip coil
SAFE STATE 1
- Circuit breaker is
open
- MV energy is not
more available
SAFE STATE 2
- Circuit breaker is open
- MV energy is not more
available
- Watchdog is activated BACK-UP PROTECTION
- External back-up protection device
activated by watchdog contact
- Without maintenance within 24h,
protection system must be set in safe
state
ACCIDENT
FAILURE OF
PROTECTION RELAY
SAFE STATE 1
- Circuit breaker is
open
- MV energy is not
more available
Watchdog contact
used for back-up
protection
Schneider-Electric
Edouard Murat : edouard.murat@schneider-electric.com
Décembre 2005
Version 1.0
Fig. 8 – The consequences of an electric network failure depend on the state of the relay, the
connection of the watchdog to the control system, the type of the watchdog and the back-up protection
Conclusion
The Sepam relay provides safety and availability of the electric network thanks to its monitoring
system. But the use of the watchdog -carefully chosen before- and the back-up protection increase the
safety and the availability. The protection of an installation or equipment should be considered as a
global system –the protection scheme- and not reduced to the protection relay itself.
9

More Related Content

What's hot

Equipments in switchyard and its protection
Equipments in switchyard and its protectionEquipments in switchyard and its protection
Equipments in switchyard and its protectionJayashree Behera
 
Industrial electrician coursr book soft copy
Industrial electrician coursr book soft copy Industrial electrician coursr book soft copy
Industrial electrician coursr book soft copy Ramesh Meti
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSPartha Parida
 
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATIONRELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATIONMd Sarowar Alam
 
400 KV GSS HEERAPURA, JAIPUR
400 KV GSS HEERAPURA, JAIPUR400 KV GSS HEERAPURA, JAIPUR
400 KV GSS HEERAPURA, JAIPURsahid raja khan
 
High Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating ProceduresHigh Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating ProceduresLiving Online
 
Protection Relays Numbering (ANSI)
Protection Relays Numbering (ANSI)Protection Relays Numbering (ANSI)
Protection Relays Numbering (ANSI)AHMED MOHAMED HEGAB
 
Madan mohan malaviya
Madan mohan malaviyaMadan mohan malaviya
Madan mohan malaviyaAnuj Bansal
 
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,
Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,Sameer Kumar
 
Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)
Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)
Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)Hazem El-Henawy
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgearmichaeljmack
 
132kv substation inplant training seminar
132kv substation inplant training seminar132kv substation inplant training seminar
132kv substation inplant training seminarShrikant Bhansali
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersSARAVANAN A
 
protection scheme of a grid substation prsentation
protection scheme of a grid substation prsentationprotection scheme of a grid substation prsentation
protection scheme of a grid substation prsentationabu jubayer
 
Nbr 15749 malha de aterramento
Nbr 15749   malha de aterramentoNbr 15749   malha de aterramento
Nbr 15749 malha de aterramentoRaphael Silva
 
Motor Control Centre
Motor Control CentreMotor Control Centre
Motor Control Centresalehkhan
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1Md Irshad Ahmad
 

What's hot (20)

capacitors
capacitorscapacitors
capacitors
 
Equipments in switchyard and its protection
Equipments in switchyard and its protectionEquipments in switchyard and its protection
Equipments in switchyard and its protection
 
Industrial electrician coursr book soft copy
Industrial electrician coursr book soft copy Industrial electrician coursr book soft copy
Industrial electrician coursr book soft copy
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
 
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATIONRELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATION
 
400 KV GSS HEERAPURA, JAIPUR
400 KV GSS HEERAPURA, JAIPUR400 KV GSS HEERAPURA, JAIPUR
400 KV GSS HEERAPURA, JAIPUR
 
High Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating ProceduresHigh Voltage Electrical Compliance and Safety Operating Procedures
High Voltage Electrical Compliance and Safety Operating Procedures
 
Protection Relays Numbering (ANSI)
Protection Relays Numbering (ANSI)Protection Relays Numbering (ANSI)
Protection Relays Numbering (ANSI)
 
Buchholz relay
Buchholz relayBuchholz relay
Buchholz relay
 
Madan mohan malaviya
Madan mohan malaviyaMadan mohan malaviya
Madan mohan malaviya
 
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,
Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,
 
Switchyard
SwitchyardSwitchyard
Switchyard
 
Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)
Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)
Moulded Case Circuit Breaker (Mccb) & air circuit breaker (acb)
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
132kv substation inplant training seminar
132kv substation inplant training seminar132kv substation inplant training seminar
132kv substation inplant training seminar
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
protection scheme of a grid substation prsentation
protection scheme of a grid substation prsentationprotection scheme of a grid substation prsentation
protection scheme of a grid substation prsentation
 
Nbr 15749 malha de aterramento
Nbr 15749   malha de aterramentoNbr 15749   malha de aterramento
Nbr 15749 malha de aterramento
 
Motor Control Centre
Motor Control CentreMotor Control Centre
Motor Control Centre
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1
 

Viewers also liked

Fce speaking overview_activity
Fce speaking overview_activityFce speaking overview_activity
Fce speaking overview_activityelenainforb
 
Derecho de familia. inseminacion artifici al. sentencia 1456. enviar
Derecho de familia. inseminacion artifici al. sentencia 1456.  enviarDerecho de familia. inseminacion artifici al. sentencia 1456.  enviar
Derecho de familia. inseminacion artifici al. sentencia 1456. enviarLUIS HERNANDEZ
 
legalizacion de la marihuana en mexico
legalizacion de la marihuana en mexico legalizacion de la marihuana en mexico
legalizacion de la marihuana en mexico Alee Vazquez
 
Poder ciudadano
Poder ciudadanoPoder ciudadano
Poder ciudadanoMayeila
 
Elogic Magento development presentation
Elogic Magento development presentationElogic Magento development presentation
Elogic Magento development presentationPaul Okhrem
 
Amity University Social Media
Amity University   Social MediaAmity University   Social Media
Amity University Social MediaDipankar Sarkar
 
Santa Ana School.pptx
Santa Ana School.pptxSanta Ana School.pptx
Santa Ana School.pptxsofiathoma
 
Closing the Loop - Technology Implementations
Closing the Loop - Technology ImplementationsClosing the Loop - Technology Implementations
Closing the Loop - Technology ImplementationsCASRAI
 
Amity University | Government Recognitions
Amity University | Government RecognitionsAmity University | Government Recognitions
Amity University | Government RecognitionsAmity New York
 

Viewers also liked (14)

Global KTech Corporate Deck
Global KTech Corporate DeckGlobal KTech Corporate Deck
Global KTech Corporate Deck
 
Fce speaking overview_activity
Fce speaking overview_activityFce speaking overview_activity
Fce speaking overview_activity
 
Derecho de familia. inseminacion artifici al. sentencia 1456. enviar
Derecho de familia. inseminacion artifici al. sentencia 1456.  enviarDerecho de familia. inseminacion artifici al. sentencia 1456.  enviar
Derecho de familia. inseminacion artifici al. sentencia 1456. enviar
 
legalizacion de la marihuana en mexico
legalizacion de la marihuana en mexico legalizacion de la marihuana en mexico
legalizacion de la marihuana en mexico
 
C astelao
C astelaoC astelao
C astelao
 
Poder ciudadano
Poder ciudadanoPoder ciudadano
Poder ciudadano
 
What’s happening
What’s happeningWhat’s happening
What’s happening
 
Youtwitface
YoutwitfaceYoutwitface
Youtwitface
 
Elogic Magento development presentation
Elogic Magento development presentationElogic Magento development presentation
Elogic Magento development presentation
 
Amity University Social Media
Amity University   Social MediaAmity University   Social Media
Amity University Social Media
 
Santa Ana School.pptx
Santa Ana School.pptxSanta Ana School.pptx
Santa Ana School.pptx
 
Closing the Loop - Technology Implementations
Closing the Loop - Technology ImplementationsClosing the Loop - Technology Implementations
Closing the Loop - Technology Implementations
 
Hypofractionation in breast cancer
Hypofractionation in breast cancerHypofractionation in breast cancer
Hypofractionation in breast cancer
 
Amity University | Government Recognitions
Amity University | Government RecognitionsAmity University | Government Recognitions
Amity University | Government Recognitions
 

Similar to The watchdog is a main component in the protection scheme

FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONPower System Operation
 
Fault detection consequence
Fault detection consequenceFault detection consequence
Fault detection consequenceMahbub Rashid
 
RUGGEDCOM RPS1300 accessories
RUGGEDCOM RPS1300 accessoriesRUGGEDCOM RPS1300 accessories
RUGGEDCOM RPS1300 accessoriesashwini reliserv
 
Commander sx user guide
Commander sx user guideCommander sx user guide
Commander sx user guideToàn Huỳnh
 
Zipato alarm, security module
Zipato alarm, security moduleZipato alarm, security module
Zipato alarm, security moduleDomotica daVinci
 
Summary_of_Safety_and_Transport_Instructions_EN.pdf
Summary_of_Safety_and_Transport_Instructions_EN.pdfSummary_of_Safety_and_Transport_Instructions_EN.pdf
Summary_of_Safety_and_Transport_Instructions_EN.pdfMarioUrbanoRamirezHu
 
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdfH15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdfEMERSON EDUARDO RODRIGUES
 
IRJET- Smart Production Line Industry 4.0 - Leak Testing for Fuel Tank
IRJET-  	  Smart Production Line Industry 4.0 - Leak Testing for Fuel TankIRJET-  	  Smart Production Line Industry 4.0 - Leak Testing for Fuel Tank
IRJET- Smart Production Line Industry 4.0 - Leak Testing for Fuel TankIRJET Journal
 
Switchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptxSwitchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptxLoitaFredy
 
S5 135 155 U System Manual
S5 135 155 U System ManualS5 135 155 U System Manual
S5 135 155 U System Manualguest4315c00
 

Similar to The watchdog is a main component in the protection scheme (20)

FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
Fault detection consequence
Fault detection consequenceFault detection consequence
Fault detection consequence
 
RUGGEDCOM RPS1300 accessories
RUGGEDCOM RPS1300 accessoriesRUGGEDCOM RPS1300 accessories
RUGGEDCOM RPS1300 accessories
 
Commander sx user guide
Commander sx user guideCommander sx user guide
Commander sx user guide
 
Basics of railway principles
Basics of railway principlesBasics of railway principles
Basics of railway principles
 
Protective relaying
Protective relayingProtective relaying
Protective relaying
 
Zipato alarm, security module
Zipato alarm, security moduleZipato alarm, security module
Zipato alarm, security module
 
Tracer1210rn Tracer1215rn manual from Ultisolar New Energy
Tracer1210rn Tracer1215rn manual from Ultisolar New EnergyTracer1210rn Tracer1215rn manual from Ultisolar New Energy
Tracer1210rn Tracer1215rn manual from Ultisolar New Energy
 
PPT.pptx
PPT.pptxPPT.pptx
PPT.pptx
 
Summary_of_Safety_and_Transport_Instructions_EN.pdf
Summary_of_Safety_and_Transport_Instructions_EN.pdfSummary_of_Safety_and_Transport_Instructions_EN.pdf
Summary_of_Safety_and_Transport_Instructions_EN.pdf
 
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdfH15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
 
IRJET- Smart Production Line Industry 4.0 - Leak Testing for Fuel Tank
IRJET-  	  Smart Production Line Industry 4.0 - Leak Testing for Fuel TankIRJET-  	  Smart Production Line Industry 4.0 - Leak Testing for Fuel Tank
IRJET- Smart Production Line Industry 4.0 - Leak Testing for Fuel Tank
 
PSG UNIT I.pdf
PSG UNIT I.pdfPSG UNIT I.pdf
PSG UNIT I.pdf
 
Switchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptxSwitchgear and Protection Engineering Lecture 01.pptx
Switchgear and Protection Engineering Lecture 01.pptx
 
Et601 chapter1 ayu
Et601  chapter1 ayuEt601  chapter1 ayu
Et601 chapter1 ayu
 
Spam 20
Spam 20Spam 20
Spam 20
 
S5 135 155 U System Manual
S5 135 155 U System ManualS5 135 155 U System Manual
S5 135 155 U System Manual
 
Mg90 j102 xxxx
Mg90 j102 xxxxMg90 j102 xxxx
Mg90 j102 xxxx
 
Ethernet mg90 j102
Ethernet mg90 j102Ethernet mg90 j102
Ethernet mg90 j102
 
Lecture 4
Lecture 4Lecture 4
Lecture 4
 

The watchdog is a main component in the protection scheme

  • 1. Schneider-Electric Edouard Murat : edouard.murat@schneider-electric.com Décembre 2005 Version 1.0 The watchdog : a main component in the protection scheme Abstract The watchdog is one of the most important part of the Sepam monitoring system for it notifies the operator whether the protection functions of the Sepam are in working order. This monitoring system is based on self-tests. If an internal failure is detected the Sepam is put in standby position. The watchdog should also be used as a back-up protection in order to maintain primary safety when the Sepam is in standby position. This shows that the protection relay is useless without a global protection scheme which takes into account the possibility of a failure of the Sepam. A compromise has to be found between safety and availability of the electric network regarding the needs of the plant. As the behavior of the Sepam in standby position is linked with the type of the watchdog, the choice of this component is crucial. Index terms – watchdog, monitoring system, standby position, back-up protection, protection scheme, safety and availability, undervoltage coil, shunt trip coil. Introduction The aim of the Sepam relay is to manage electric installation by providing safety and availability of the installation and the equipment. The protection scheme can be improved with the use of the watchdog. This simple component is really an important part of the protection plan and can easily provide higher protection. Definition of a watchdog The watchdog contact is a change over contact : the contacts normally closed of the relays are connected in daisy-chain m ic r o p r o c e s s o r r e la y F n w a t c h d o g c o n t a c t a n n u n c ia t o r p a n e l r e la y F n f a u lt Figure 1 – Watchdog contact 1
  • 2. Schneider-Electric Edouard Murat : edouard.murat@schneider-electric.com Décembre 2005 Version 1.0 The watchdog should be used.. ..As a notifying device of the monitoring system The Sepam relay is equipped with a self monitoring system which is able to detect most internal failures in protection circuits of the Sepam. This monitoring system is based on self-tests. The purposes of the self-tests is to detect internal failures that may cause unexpected tripping or non- tripping. If such a failure is detected by the self-tests, the Sepam is put in standby position. In this position, all protections functions are turned off in order to avoid any unwanted operation, logic outputs of the Sepam are open and the watchdog is activated. Please note that some internal failures has no consequence on protection functions of the Sepam1 . State of the Relay Watchdog Causes In standby position activated Internal failure detected OR Relay not energized In working order not activated Relay energized AND no internal failure Fig. 2 – the standby position The watchdog is an important part of this monitoring system because it indicates if the protections functions of the Sepam are in working order . If an internal fault is detected by the Sepam, a light of the Sepam front panel automatically flickers even if the watchdog is not connected to the system. The fact is that in case of an internal fault of the digital relay, if the watchdog is not properly connected to the control system, the only way to notice that the relay has failed is to control the front panel of the relay. The watchdog contact should therefore be connected to the higher level system in order to generate an efficient alarm and give the state of the relay. For example, a hooter in a plant or a bigger flickering light can be activated in order to inform the operator. State of the Watchdog contact No failure detected Internal failure detected Watchdog properly connected to the control system Protections functions are in working order - Protection functions are out of order - Sepam in standby position - The alarm light of the Sepam front panel flickers - Watchdog contact activates an alarm system operator is notified that a maintenance operation is required thanks to the connection to the control system Watchdog not connected Protection functions are in working order - Protection functions are out of order - Sepam in standby position - The alarm light of the Sepam front panel flickers - The need of maintenance is detected only if an operator controls the front panel of the digital relay Fig. 3 – the watchdog, a warning system 1 In this case, the Sepam is said to be in downgraded working order : some internal failure has been detected but no protection function of the Sepam has been affected 2
  • 3. Schneider-Electric Edouard Murat : edouard.murat@schneider-electric.com Décembre 2005 Version 1.0 The first step of maintenance operations is to be kept informed of the state of the device. Thanks to the watchdog, the maintenance staff is warned of the state of the protection relay and could repair the faulty device without delay. The use of the watchdog is the main solution because this is often enough to prevent damage to equipment and to avoid loss of production. Although the self monitoring system of the Sepam will find most internal failures, some may not be detected. Those are mainly linked with the different modules of the Sepam such as disconnected sensitive earth fault current transformers, failure of input / output modules or also faulty analog output module. Those failures do not concern the relay its self but may have important impacts on the protection functions. For example, if a core balance current transformer used in order to measure the sense of the current is linked with the Sepam in the wrong way, it will have impact on all directional protections. For this reason we recommend periodic testing even when self monitoring is provided. Considering the frequency of those faults, 5 years between each maintenance operation should prevent the plant from such problems. Functions Type of self-test Execution period Fail-safe position Power supply Detection of processor power supply outside tolerance range At time of energizing and continually YES Acquisition of currents or voltages Detection of analog channel saturation Filtering by data signal processing Test of presence and recognition of connector Continually Continually At time of energizing and continually YES YES YES Processing unit Memory test Software watchdog At time of energizing and continually YES YES UMI Memory test Software watchdog At time of energizing Continually NO NO Logical I/O Test of presence and recognition of module At time of energizing and continually YES (1) RTD inputs Memory test Software watchdog Analog conversion test At time of energizing Continually Continually NO NO NO Analog output Memory test Software watchdog At time of energizing Continually NO NO (1) only when the module is missing or if there are not enough logical inputs Fig. 4 – The self-tests of the Sepam 3
  • 4. Schneider-Electric Edouard Murat : edouard.murat@schneider-electric.com Décembre 2005 Version 1.0 ..As a back-up protection The watchdog contacts can also be used to provide back-up protection by other relays. The back-up protection is a brilliant solution in order not to depend only on one Sepam that might be faulty but also on other Sepam that protect the upstream electric network. If the protection system is built according to the sate of the art, each fault should be detected by at least two different protection relays. This can be achieved either by installing 2 different protection relays on one circuit-breaker (commonly used on transmission systems) or by relying on the upstream breaker and its protection relay (very common in distribution systems). This basic principle can be improved by using the following back-up protection system The back-up protection system is really simple and uses the fact that a protection scheme is composed of upstream protection relays and downstream protection relays. If the downstream Sepam relay is in standby position, the protection functions are not in working order. An electric network failure may happen and damage the power system that should have been protected by the Sepam. The answer to this problem is to wire the watchdog contact of the downstream Sepam relay with the protection of the upstream Sepam relay. An example is described below (Fig. 4.) Fig. 5 - Example of the use of watchdog contact in a back-up protection The relay F2 is in working order whereas the relay F1 is in standby position as the watchdog is closed. Therefore relay F1 does not provide any protection anymore. If a short-circuit occurs in the network which was protected by F1, the back-up protection F4 will trip the circuit-breaker controlled by F1thanks to the back-up trip circuit. Furthermore, any back-up scheme which uses the watchdog contacts of microprocessor relays must still provide the minimum back-up protection in the case of undetected failures in the relay or circuit- breaker failure. The protection of a power system using Sepam protection relays is secured, but the 4
  • 5. Schneider-Electric Edouard Murat : edouard.murat@schneider-electric.com Décembre 2005 Version 1.0 power system has to be protected even if the protection function fails. Using the watchdog as a back- up protection increase the availability and the safety. Protection scheme Since many protection functions are included in one device, a reliable protection scheme is very important in order to protect capital equipment, to protect operating personnel, and to reduce down time by selectively clearing faults. Correct operation of the protection circuit including back-up protection may ensure optimal clearance of the fault but will not in itself prevent a loss of production. In other words good back-up protection will not fix a bad design. The reason for extensive damage in installations is not often a faulty protection equipment itself but how the protection scheme has been designed and implemented. The protection plan should be designed in order to obtain the best combination of protection and continuous operation. Any analysis of back-up protection must take into account the complete protection circuit that consist of the circuit-breaker, the instrument transformers, the auxiliary power supply, and the relay. Even the most advanced protection relay is useless without a well-designed protection scheme : if the protection equipment is incorrectly wired and the relays incorrectly set, the availability and the safety of the power system can not be ensured. Safety and availability A protection system has to ensure two main functions : - To protect the electric installation/components against overloads, and short circuits due to component failures and therefore to avoid accidents (fires, explosion) that may follow. This function is linked with safety. - To provide power so that electrical equipment can run properly. This function is linked with availability. As explained before, a good protection scheme takes into account the possibility of a failure of the protection relay. Furthermore, it is established that some failures caused more damage to safety than to availability and vice versa : - A failure to trip of the protection relay may lead to the destruction of components. This can start fires which may turn into explosion. This is, of course, always associated with human risks. - False trip of a protection relay may trouble the production availability of the installation. This may lead to a partial or a complete loss (blackout) of the production. This often implies an important financial loss. 5 Safety of the system Availability of the system False trip of the protection relay Failure to trip of the protection relay Fair balance between Safety and availability
  • 6. Schneider-Electric Edouard Murat : edouard.murat@schneider-electric.com Décembre 2005 Version 1.0 Fig. 6 - Balance between safety and availability Safety and availability are conflicting requirements: improving the one decreases the other one and reciprocally. Therefore designing a protection scheme has to be a good compromise between safety and availability. The appropriate watchdog Failures have different impact on the electric network depending on their type, their location, the need of the plant. It is possible to distinguish two main types : the “safe failures” and “unsafe failures”. It is really important to note that those two types depend on the need of the plant. It is no sense to talk about a “safe failure” in a universal point of view. The protection relay has to ensure availability when “safe failures” occurs and must prevent the power system from “unsafe states”. As a consequence, the standby position is a main issue and has to be carefully tackled. The so-called "safety state" actually depends on the kind of MV application. In most applications the de-energizing of the system will be the safe state. For instance it is often requested to stop a motor in case of over-current. But in some specific cases, it will be safer to keep the system energized. For instance, some safety pumps need to be kept running even in case of MV failure. This is a problem for manufacturers to address properly requirements of safety and availability. This issue can be solved by using a temporary "standby" position. In this state, the protection relay is stopped, and alerts the system for curative maintenance within limited time (24 hours) as showed below (Fig. 4). 6
  • 7. Schneider-Electric Edouard Murat : edouard.murat@schneider-electric.com Décembre 2005 Version 1.0 Fig. 7 – Example of the use of the temporary "standby" position In applications where safety is crucial, the system designer will choose a safety-oriented architecture. In case of a failure detected by self-testing, the system will go in the Safety state, resulting in circuit tripping. If the safe state of a system is to de-energize it, the use of "under-voltage" coils mode will ensure safety. In applications where safety and availability have to be balanced, using "shunt trip coils" may ensure both safety and availability. When self-testing detects a protection relay failure, or when the power supply is faulty, the watchdog relay is activated, and an upstream protection relay replaces the downstream faulty protection relay during the fault condition period. Using "shunt trip" coils when the safe state of a system is to de-energize it will ensure a compromise between safety and availability. 7
  • 8. Schneider-Electric Edouard Murat : edouard.murat@schneider-electric.com Décembre 2005 Version 1.0 8 PROTECTION IS RUNNUNG Watchdog linked with the protection relay No watchdog linked with the protection relay STANDBY POSITION - a failure was detected by self- tests - WD activated - protection function are turned off HAZARDOUS STATE - protection functions seem to be working - protection functions are actually inoperant ELECTRIC NETWOR K FAILURE Watchdog fulfilled with undervoltage coil Watchdog fulfilled with shunt trip coil SAFE STATE 1 - Circuit breaker is open - MV energy is not more available SAFE STATE 2 - Circuit breaker is open - MV energy is not more available - Watchdog is activated BACK-UP PROTECTION - External back-up protection device activated by watchdog contact - Without maintenance within 24h, protection system must be set in safe state ACCIDENT FAILURE OF PROTECTION RELAY SAFE STATE 1 - Circuit breaker is open - MV energy is not more available Watchdog contact used for back-up protection
  • 9. Schneider-Electric Edouard Murat : edouard.murat@schneider-electric.com Décembre 2005 Version 1.0 Fig. 8 – The consequences of an electric network failure depend on the state of the relay, the connection of the watchdog to the control system, the type of the watchdog and the back-up protection Conclusion The Sepam relay provides safety and availability of the electric network thanks to its monitoring system. But the use of the watchdog -carefully chosen before- and the back-up protection increase the safety and the availability. The protection of an installation or equipment should be considered as a global system –the protection scheme- and not reduced to the protection relay itself. 9