Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
ย
Genset/ Generator Set 1350KVA
1. General
Genset Type : TNK1350P
Rating : 1080kW / 1350kVA (Prime Power)
: 1200kW / 1500kVA (Standby Power)
Fuel Consumption : 281 l/h (Prime Power), 315 l/h (Standby Power)
Rating Definition
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant
electrical load for limited hours. Limited-Time
Running Power (LTP) is in accordance with
ISO 8528.
Prime Power (PRP):
Applicable for supplying power to varying
electrical load for unlimited hours. Prime
Power (PRP) is in accordance with ISO 8528.
Ten percent overload capability is available in
accordance with ISO 3046, AS 2789,
DIN 6271 and BS 5514.
Engine Data
Type : 4012-46TWG3A
Speed [Rpm] : 1500
Frequency (Hz) : 50
No of cylinders : 12 (in-line)
Displacement [l] : 45.842
Bore/Stroke [mm] : 160 / 190
Compression Ratio : 13 : 1
Governor : Electronic
Oil Capacity [l] : 159
Alternator Data
Type : STAMFORD PI734B
: [3Ph, Single Bearing]
Rated Output [kVA] : 1350
Speed [Rpm] : 1500
Frequency [Hz] : 50
Voltage [V] : 400/230
Insulation : Class H
Protection : IP 23
Specification, picture, dimension may change without notice due to product improvement.
2. Cooling System and Accessories
Radiator Cooling : as Perkins standard
Coolant Capacity [l] : 201
Starting Volt. : 24V
Exhaust System : Industrial / residential exhaust silencer
Baseframe : Steel Channel/Plate construction
Engine and Alternator Mounting : Rubber metal elements
Set of Operation books, consist of : Engine operating instruction
: Certificate of Origin
: Alternator operating instruction
: Genset Test Report
Genset Controller
Genset Dimension and Dry Weight
Open Type
Dimension [LxWxH] : 4550x2010x2520(mm)
Dry Weight : 13030(kg)
Silent Type
Dimension [LxWxH] : 12192x2438x2896(mm)
Dry Weight : 16030kg
PT. Tan Energy Indonesia (TANEKO)
Jl. Prof, DR. Latumenten kav.50
Sentra Latumenten blok. D2, Jakarta 11460
Telp : 62-21 569 58610-14
Email : marketing@taneko.co.id
Website : www.taneko.co.id
According to ISO 8528-5. Continuous Power: No time limitation, plus 10% addictional, power for governing purpose only. Prime Power: Average output โค 80%, no time limitation, plus 5%
addictional power for governing purpose only. Limited Time Running Power: for up to 500 h/year, thereof a maximum of 300 h/year continuous running. In consideration of a generator
efficiency level of 89% - 90% and a power factor of 0.8
DSE7320
Auto Mains (Utility) Failure Control Modules
The DSE7320 is a feature packed Auto Mains (Utility) Failure
Control Module designed to control single diesel or gas gen-
set applications.
KEY FEATURES
-3-phase generator and mains (utility) sensing
-Power monitoring (kW h, kV Ar, kV Ah, kV Ar h)
-Remote communications (RS232 & RS485)
-Configurable inputs/outputs (9/8)
-Fuel usage monitor and low level alarms
-Manual/automatic load transfer.
- Power save mode.
-DSE Configuration Suite PC Software.
-etc
OPEN TYPE SILENT TYPE (Container 40ft)