Innovative Systems Design and Engineering                                                  www.iiste.org
         ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
         Vol 2, No 3




     Transient analysis of grid-connected wind-driven PMSG, DFIG and
                     SCIG at fixed and variable speeds
                                           Mazen Abdel-Salam (Corresponding author)
                                Electric Engineering Department, Assiut University, Assiut, Egypt
                                                E-mail: mazen2000as@yahoo.com


                                                           Adel Ahmed
                                Electric Engineering Department, Assiut University, Assiut, Egypt
                                                  E-mail: a_ahmed@aun.edu.eg


                                                       Mahmoud Mahrous
                                Electric Engineering Department, Assiut University, Assiut, Egypt
                                             E-mail: mahmoud2006eng@yahoo.com


Abstract
This paper is aimed at presenting transient analysis of a grid-connected wind-driven permanent magnet synchronous
generator (PMSG) at fixed and variable speeds by solving the system describing differential equations. For comparison
purpose, wind-driven squirrel cage (SCIG) and doubly fed (DFIG) induction generators at fixed and variable speeds are
studied using MATLAB/SIMULINK software package. Different from PMSG and DFIG the grid should feed the reactive
losses of transmission lines and transformers at any value of short circuit ratio for SCIG. This increases the dynamic
stability of DFIG and PMSG when compared with SCIG. Under three-phase-to-ground fault and single-phase-to-ground
fault conditions, the time required to recover stability of PMSG wind farm is less than those DFIG and SCIG wind farms
for fixed and variable speeds indicating that PMSG is more stable than of DFIG and of SCIG wind farms.
Keywords: Wind energy; Fixed and variable speed wind turbine; Permanent magnet synchronous generator; Induction
generator; Short circuit ratio.
1.   Introduction
Wind turbine technology has undergone a dramatic transformation during the last 15 years, developing from a fringe
science in the 1970s to the wind turbines of the 2000s utilizing the latest technology in power electronics, aerodynamics
and mechanical drive designs.
Induction generators are more attractive than synchronous generators for wind turbines due to their robust construction, low
cost, low maintenance, long life (more than 50 years) and low power to weight ratio (Bhadra 2005). However the reactive
power management is a major concern, not only to compensate for the reactive power requirements of the wind generator
itself but also to support the system voltage in particular for wind farms based on fixed speed induction generators.
Most wind turbines use induction generators, squirrel cage induction generator (SCIG), doubly-fed-induction-generators
(DFIG) or permanent magnet synchronous generators (PMSG). Currently, DFIG based wind turbines dominate the world
market due to their cost-effective provision of variable-speed operation, as well as the controlling flexibility of
electromagnetic torque and reactive power. However, since its stator and rotor are both connected to the power system, grid
fault ride-through control (on temporal reduction of the grid voltage due to a fault) is difficult for the DFIG, and is a major
challenge for wind turbine manufacturers based on the MATLAB/SIMULINK without stating the system describing
equations (Zhanfeng 2010). In the existing literature, there have recently been several papers dealing with this problem,
mainly focusing on ride-through controller design and transient response analysis based on the system describing equations
after being linearized and models the state variables of the original system states from the nominal operating values (Rahim
2011).
Innovative Systems Design and Engineering                                                      www.iiste.org
          ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
          Vol 2, No 3


The analysis of a configuration consisting wind farm based on conventional fixed speed SCIG has been reported before
(Fischer de Toledo 2005). Improvement of the short-term voltage and rotor stability performance on introducing a
STATCOM was quantified during different types of failure events in the connected power system (three-phase to ground
fault and single-phase to ground fault) using EMTDC/PSCAD digital simulator. Also, the effect of electrical parameters of
the induction generator on the transient voltage stability of a fixed speed wind turbine (FSWT) connected to a simple grid
based on the MATLAB/SIMULINK (Dusonchet 2011).
When compared with induction generators, the PMSG has a smaller physical size and a lower moment of inertia which
means a higher reliability and power density per volume ratio. The electrical losses in the rotor are eliminated on the
expense of high costs for permanent magnet materials and fixed excitation, which cannot be changed according to the
operating point. The model used in this study was developed in the d-q synchronous rotating reference frame (Kesraoui
2010). PMSG based direct driven turbine is connected to the grid by through AC- DC- AC conversion system, modeled and
simulated using MATLAB/SIMULINK (Mittal 2008).
This paper is aimed at presenting a transient analysis model of a grid-connected wind-driven permanent magnet
synchronous generator (PMSG) at fixed and variable speeds by solving the system describing differential equations. The
PMSG is the equivalent generator of many wind-driven synchronous generators operating in a wind farm. For comparison
purpose, wind-driven squirrel cage (SCIG) and doubly fed (DFIG) induction generators running at fixed and variable
speeds are studied using MATLAB/SIMULINK.
Different line connections between the grid and the wind farm with subsequent different short-circuit ratios are studied. The
study extends to include three-phase-to-ground and single-phase-to-ground faults at the point where the wind farm is
connected to the grid. The time required for the wind farm to recover stability is assessed for wind driven PMSG, DFIG
and SCIG.
2. Network
There are a number of possible interconnection structures for wind farms and thus it is not possible to cover every type of
network configuration, load, and interconnection point of the wind farm. Frequently wind parks are connected to weak
systems, as they are typically located far from major load centers and central generation. This reflects itself in defining a
short circuit ratio (SCR) of the interconnection expressed as:
           SCC
 SCR 
           Sbase                                                                                                                (1)

Where
        S base is the rated power of wind farm and SCC or short circuit capacity is the short circuit power delivered from the
grid to a three-phase fault at the wind farm:

         2
       Vbase
 SCC 
       Z line
                                                                                                                                (2)
        Z line                                                                         Vbase
where            is the impedance of the line connecting the grid with wind farm and           is the rated voltage of the grid. For
weak systems the SCR will usually be less than 6 (Abbey 2005).

3.   System modeling
3.1 Grid-connected Wind-driven Permanent Magnet Synchronous Generator (PMSG) System
The block diagram of the system is shown in fig. 1. The system consists of wind-driven PMSG, an AC-DC three phase
bridge rectifier, DC-DC boost converter to fixed the voltage at certain specified value and PWM inverter to interface the
system with the electric utility.
3.1.1 PMSG Modeling
Innovative Systems Design and Engineering                                                         www.iiste.org
          ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
          Vol 2, No 3


The PMSG is described by the following differential equations (Hong-Woo 2010) and (Whei-Min 2011):
  1 d ds
           v ds  Rs ids   e qs
  b dt
                                                                                                                                   (3)
  1 d qs
           v qs  Rs iqs   e ds
  b dt
With

 ds   Ldsids   m
                                                                                                                                   (4)
 qs   Lqsiqs

where    v is the p.u voltage,   Rs
                                      is the p.u resistance, i is the p.u current, e is the p.u stator electrical angular speed, b is

the base angular speed in rad/s, Ls is the p.u stator leakage inductance,  m is the p.u exciter flux of the PMSG, and  is
the p.u flux linkage. The subscripts d and q indicate the direct and quadrature axis components, respectively. The subscripts
s indicates stator quantities. The electrical active and reactive power delivered by the stator are given by

Ps  v dsids  v qsiqs
                                                                                                                                   (5)
Qs  v dsiqs  v qsids

The voltages of phases d, q and 0 are transformed by Park’s transformation (P) to a, b and c variables as follows (Grainger
1994):

  v a       v d 
  v   P 1 v                                                                                                                  (6)
   b         q
  v c 
            v 
               0

                                                      
            cos  d     cos( d  120) cos( d  120)
           2                                          
  P          sin  d    sin( d  120) sin( d  120)                                                                            (7)
           3 1
                               1              1       
             2
                                2              2      
                                                       
3.1.2 Uncontrolled rectifier and DC-DC boost converter
As the wind speed is constantly varying so the PMSG produces variable voltage and variable frequency output. A three-
phase uncontrolled diode rectifier is used to convert the PMSG output AC voltage to DC voltage. The rectifier output
voltage (Vdc) depends on the AC line voltage as expressed (Mohan 1989):

           3 3           3 2
 Vdc            Vm             V LL                                                                                              (8)
                          
Where Vm is the maximum phase voltage and VLL is the rms value of the line-line voltage.
As the PMSG voltage is variable with the wind speed, the DC output voltage of the bridge rectifier is also variable. A boost
DC-DC converter has been used for maintaining the DC output voltage at constant value V do. The relation between the
Innovative Systems Design and Engineering                                                     www.iiste.org
         ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
         Vol 2, No 3


output and input voltages depends on the duty ratio D as expressed by equations (9) and (10), where Ts is the switching
period and ton is the on time of the switch, the switch mode DC-DC converter signal is generated by compared the
triangular wave (its period Ts) with DC wave as shown in fig. 2 (Mohan 1989).
                                    Vdo   1
                                                                                                                           (9)
                                    Vdc 1  D

                                                 t on
                                          D                                                                              (10)
                                                 Ts
The control block diagram consists of a comparator, which compares the actual DC-DC converter output with a reference
value. The error signal is fed to a PI controller passes though a limiter within the controller. The output of the PI controller
used to generate the switching signal.
3.1.3 PWM Inverter
The inverter inverts the DC voltage output to AC voltage with supply frequency in order to connect the wind-driven system
to the grid. The output of the PWM inverter (Mohan 1989) may be expressed as:

             3
   VLL1        maVdo  0.612maVdo                                                                                        (11)
           2 2
       ˆ         ˆ
      Vcontrol V LL
 ma                                                                                                                     (12)
         ˆ
        Vtri    Vdo
         fs
 mf                                                                                                                      (13)
         f1
                                          ˆ
Where ma called the modulation index, V LL is the peak value of the line-line voltage, VLL1 is the fundamental component in
                     ˆ                                                                    ˆ
the output voltage, V is the peak amplitude of the triangular which is kept constant, V
                      tri                                                                        is the peak amplitude of the
                                                                                             control


control signal, mf is the frequency modulation ratio, fs is the switching frequency and f1 is the fundamental component
frequency. It is always desirable to minimize the distortion of the output voltage and current, which change with the
modulation index in linear modulation (ma ≤ 1.0) and over-modulation region (ma > 1). In the linear region (ma ≤ 1.0) the
fundamental- frequency component in the output voltage varies linearly with the amplitude modulation ratio ma as
expressed by equation (12). Also, the harmonics in the inverter output voltage waveform appear as sidebands, centered
around the switching frequency referred to the fundamental and its multiples, that is, around harmonics mf, 2 mf, 3 mf, and
so on (Mohan 1989).
3.1.4 Modeling of grid-connected wind-driven PMSG system using Runge- Kutta Method
The PMSG wind farm connected to a grid is modeled by solving the describing differential equations using runge-kutta
method (Sermutlu 2004) as described by the flow chart of fig. 3.The solution ends up with
the temporal variation of the currents, voltages and active and reactive power.
3.2 Grid-connected Wind-driven Squirrel Cage Induction Generator (SCIG) System
In wind-driven SCIG, the stator winding is connected directly to the grid and the rotor is driven by the wind turbine as
shown in fig. 4. The power captured by the wind turbine is converted into electrical power by the induction generator and is
transmitted to the grid by the stator winding. The pitch angle is controlled in order to limit the generator output power to its
nominal value at high wind speeds. In order to generate power, the induction generator speed must be slightly above the
synchronous speed. The reactive power absorbed by the induction generator is provided by the grid or by some devices like
capacitor banks, SVC, STATCOM or synchronous condenser (Mathworks 2008a). The present transient analysis of the
system is based on MATLAB/SIMULINK simulation for fixed and variable wind speeds.
Innovative Systems Design and Engineering                                                  www.iiste.org
         ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
         Vol 2, No 3


3.3 Grid-connected Wind-driven Doubly Fed Induction Generator (DFIG) system
In wind-driven doubly-fed induction generator (WTDFIG), Fig. 5 an AC/DC/AC converter connects the rotor of the
generator to the grid. The AC/DC/AC converter is divided into two components: the rotor-side converter (            ) and the
grid-side converter (         ).        and          are Voltage-Sourced Converters that use forced-commutated IGBTs to
synthesize an AC voltage from a DC voltage source. The synthesized AC voltage is of power frequency for                and of
slip frequency for          . A capacitor connected on the DC side acts as the DC voltage source. A coupling inductor L is
used to connect          to the grid. The three-phase rotor winding is connected to        by slip rings and brushes and the
three-phase stator winding is directly connected to the grid. The power captured by the wind turbine is converted into
electrical power by the induction generator and transmitted to the grid by the stator and the rotor windings. The control
system generates pitch angle and voltage command signals Vr and Vgc for                and           respectively in order to
control the wind turbine power comparison against a reference power obtained from the tracking characteristic. A
Proportional-Integral (PI) regulator is used to reduce the power error to zero, while adjusting the DC bus voltage and the
reactive power or the voltage at the grid terminals (Mathworks 2008a). Similar to SCIG system, the present transient
analysis of the DFIG system is based also on MATLAB/SIMULINK simulation for fixed and variable wind speeds.
4. Grid-Connected Wind-driven Systems under study
The one line diagram of the test system employed in this study is shown in Fig. 6 for different types of wind farm.
The wind farm of PMSG consists of 75 units of 1.6 MVA wind turbines. Each wind turbine unit consists of: rotor, gear box,
permanent magnet synchronous generator, uncontrolled converter, DC-DC boost converter, inverter and a 0.69/10.5 kV
transformer as shown in fig. 6a. In the wind farm of SCIG, each wind turbine unit is the same as in PMSG in addition to
shunt capacitors for reactive power compensation, but without uncontrolled converter, DC-DC boost converter and inverter
as shown in fig. 6b. In the wind farm of DFIG, each wind turbine unit is the same as that of PMSG as shown in fig. 6c. In
The representation of the power plant has been made by aggregating all the 75 wind turbines in one equivalent unit. Phase
model is used for wind turbine induction generator (SCIG) and doubly fed induction generator (DFIG) systems (El-Helw
2008).
5. Simulation studies
The grid-connected wind-driven PMSG system is modeled by solving the system differential equations using Runge-Kutta
method by programming the m-file of MATLAB program. Three-phase-to-ground and single-phase-to-ground faults are
applied at the connection bus between the PMSG wind farm and the 115-kV transmission line at t =30 s for a duration of
140ms (as the detection and operation times of the breakers extend to 140 ms) (Fischer de Toledo 2005). For comparison
purpose the same faults are applied at the connection bus between the SCIG and DFIG wind farms and the 115-kV
transmission line at t =30 s for a duration of 140ms and SCR of 16.
5.1 Grid-connected Wind-driven systems at fixed speed
The Grid-connected wind-driven systems of system in Fig. 6 are studied with fixed speed wind turbines at 10 m/s. The
transient behaviour of systems before, during and after three-phase and single-phase to ground faults is studied.
The voltage and the frequency of PMSG are less than the rated voltage and rated frequency of wind farm (690V, 50Hz).
Therefore, the converter and inverter are used to convert the voltage and frequency to rated values.
5.1.1 Three-phase-to-ground fault
A three phase to ground fault is applied at the connection bus (bus 3) between the wind farm and the 115-kV transmission
line (Fig. 6a) at t =30 s for a duration of 140ms. Fig.7 shows the terminal voltage of the PMSG and the input dc voltage to
DC-DC boost converter.
As shown in Fig. 7, the terminal voltage of PMSG before fault is 0.8 p.u (base 690 V) at a frequency of 40 Hz. During fault,
the voltage collapses to zero at 30.25 sec with oscillations before recovering the pre-fault value. The pre-fault value of the
input dc voltage to the converter is 568 V. During fault, the dc voltage reaches zero at 30.75 sec with oscillations before
recovering its pre-fault value.
Figure 8 shows the temporal variations of the speed, voltage, active power and reactive power at Bus 1 for different wind
farms.
As shown in Fig. 8, the time required of PMSG, SCIG and DFIG wind farms to recover their pre-fault values of speed,
Innovative Systems Design and Engineering                                                   www.iiste.org
         ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
         Vol 2, No 3


voltage, active power and reactive power are approximately 0.25 sec, 1.5 sec and 1sec respectively. During fault, the speed
of PMSG wind farm oscillates reaching 1.072p.u, against 1.032 p.u and 1.024 p.u for SCIG and DFIG wind farms,
respectively. Also, the voltage of PMSG wind farm oscillates reaching 3 p.u, against 1.5 p.u and 1.1 p.u for SCIG and
DFIG wind farms, respectively. This concludes that the performance of DFIG is better than SCIG under three-phase-to-
ground fault conditions.
For SCIG, the pre-fault and post-fault values of the speed are equal to 1.015 p.u, which are almost of the same values as
obtained previously using PSCAD simulator calculation (Fischer de Toledo 2005). During the fault, the speed reached 1.03
p.u against 1.06 p.u (Fischer de Toledo 2005). The voltage, the active power and the reactive power have the same trend
during the fault as that reported before (Fischer de Toledo 2005). Generally, the mismatch between the previous and present
calculations of the active and reactive power is nearly negligible and doesn't exceed 0.1%.
5.1.2 Single-phase-to-ground fault
A single phase to ground fault is applied at the connection bus between the wind farm and the 115-kV transmission line at t
=30 s for a duration of 140ms. Fig. 9 shows the three phases terminal voltages of PMSG and the input dc voltage to DC-DC
boost converter.
As shown in Fig. 9, the terminal voltage of PMSG before fault is 0.8 p.u (base 690 V) at a frequency of 40 Hz. During fault,
the voltage of faulted phase (Va) collapses to zero with oscillations before recovering the pre-fault value at 30.25 sec. The
voltage of the other phases (Vb, Vc) decreases to 0.5 p.u with oscillations before recovering the pre-fault value at 30.25 sec.
The pre-fault value of the input dc voltage to converter is 568 V. During fault, the voltage reaches to 250 V with oscillations
before recovering the pre-fault value at 30.75 sec.
Figure.10 shows the temporal variations of the speed, voltage, active power and reactive power at Bus 1 for different wind
farms.
As shown in Fig. 10, , the time required of PMSG, SCIG and DFIG wind farms to recover their pre-fault values of speed,
voltage, active power and reactive power are approximately 0.25 sec, 1.0 sec and 0.5 sec, respectively. During fault, the
speed of PMSG wind farm oscillates reaching 1.1p.u, against 1.02p.u and 1.005p.u for SCIG and DFIG wind farms,
respectively.
The voltage of faulted phase (Va) of PMSG, SCIG and DFIG wind farms decreases to zero while the other phase voltages
(Vb and Vc) of PMSG oscillates reaching 1.01 p.u, against 1.3 p.u and 1.025 p.u for SCIG and DFIG wind farms,
respectively. This concludes that the performance of DFIG is also better than SCIG under single-phase-to-ground fault
conditions.
For SCIG, the pre-fault value of the speed is 1.015 p.u against 1.014 p.u using PSCAD simulator as reported before
(Fischer de Toledo 2005). During the fault, the speed reached 1.018 p.u against 1.03 p.u before (Fischer de Toledo 2005).
After the fault, the speed is 1.015 p.u against 1.02 p.u (Fischer de Toledo 2005). The pre-fault value of the voltage is 1.0 p.u
which is almost of the same value as obtained previously using PSCAD simulator (Fischer de Toledo 2005). After the fault,
the voltage decreased to 0.87 p.u (Fischer de Toledo 2005) against the constant voltage value of 1.0 p.u in the present
calculation. The pre-fault and the post-fault values of the active and reactive power have the same trend as that reported
before (Fischer de Toledo 2005) before, during and after the fault. Generally, the mismatch between the previous and
present calculations of the active and reactive power is nearly negligible and doesn't exceed 0.1%.
5.2 Grid-connected Wind-driven systems at variable speed
The Grid-connected wind-driven systems of system in Fig. 6 are studied with variable speed wind turbines (Abdel-Salam
2011). The transient behaviour of systems before, during and after three-phase and single-phase to ground faults is studied.
During fault, the voltage and the frequency of PMSG are less than the rated values of wind farm (690V, 50Hz).
5.2.1 Three-phase-to-ground fault
A three phase to ground fault is applied at the connection bus (bus 3) between the wind farm and the 115-kV transmission
line at t =30 s for a duration of 140ms. Fig. 11 shows wind speed, the terminal voltage and frequency of PMSG and the
input dc voltage to DC-DC boost converter.
As shown in Fig. 11, the terminal voltage of PMSG before fault changes between 0.6 to 1.2 p.u (base 690 V) at a frequency
of 33 to 42 Hz when the wind speed changes from 8 to 12 m/sec. During fault, the voltage and frequency of PMSG collapse
to zero with oscillations before recovering their pre-fault values at 30.25 sec. The input dc voltage to converter before fault
Innovative Systems Design and Engineering                                                 www.iiste.org
         ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
         Vol 2, No 3


changes between 270 to 610 V. During fault, the dc voltage reaches zero with oscillations before recovering the pre-fault
value at 30.75 sec.
Figure.12 shows the temporal variations of the speed, voltage, active power and reactive power at Bus 1.
As shown in Fig. 12, the speed of PMSG wind farm changes in the range 0.8 to 1.2 p.u against 0.65 to 1.065 p.u for DFIG
wind farm. However, the speed of SCIG wind farm is 1p.u with spike at wind speed changes. Also, the voltage of PMSG
wind farm is value 1 p.u, against 1.0 p.u and 1.05 p.u for SCIG and DFIG wind farms respectively. Moreover, the voltage of
SCIG wind farm spikes at wind speed changes. The time required of PMSG, SCIG and DFIG wind farms to recover their
pre-fault values of speed, voltage, active power and reactive power are approximately 0.25 sec, 1.5 sec and 1sec
respectively. Again, the performance of DFIG is better than that of SCIG at varying wind speed.
5.2.2 Single-phase-to-ground fault
A single phase to ground fault is applied at the connection bus (bus 3) between the wind farm and the 115-kV transmission
line at t =30 s for a duration of 140ms.
Fig. 13 shows the temporal variations of the speed, the voltage, the active power and the reactive power at Bus 1
As shown in Fig. 13, the speed of PMSG wind farm changes in the range 0.8 to 1.2 p.u against 0.65 to 1.065 p.u for DFIG
wind farm. However, the speed of SCIG wind farm is 1p.u with small changes when wind speed changes. Also, the
terminal voltage of PMSG wind farm is 1 p.u against 1.0 p.u and 1.05 p.u for SCIG and DFIG wind farms, respectively.
However, the voltage of SCIG wind farm shows small change when wind speed changes. The times required of PMSG,
SCIG and DFIG wind farms to recover their pre-fault values of speed, voltage, active power and reactive power are
approximately 0.25 sec, 1.0 sec and 0.5 sec, respectively.
Different from SCIG, the PMSG and DFIG are not in need for a fixed capacitor to generate the active power, and the grid
can easily feed the reactive losses of transmission lines and transformer at any value of SCR (SCR ≥ 1). This increases the
dynamic stability of DFIG and PMSG when compared with SCIG. The active power of PMSG is 1 p.u compared to 0.87 p.u
for DFIG and SCIG because some reactive power is absorbed by the IG to generate the active power.
The PMSG has the advantage of generating reactive power 0.43 p.u compared to the SCIG which is in shortage of the
reactive power by 0.365p.u. On the other hand the DFIG absorbs zero reactive power, before fault (Mittal 2009).
During the fault, the speed of PMSG oscillates higher than DFIG and SCIG by approximately 10% due to flux oscillations
required to feed the reactive power. This is because the speed is inversely proportional to flux (Hong-Woo 2010). Also, the
PMSG has higher inertia being of larger weight when compared to DFIG and SCIG with a subsequent lower speed for
PMSG (Mittal 2009).
Due to flux oscillations during fault, the voltage of PMSG oscillates to 3 p.u, which is higher than the corresponding
voltages of DFIG and SCIG.
6. Conclusions
    1) Different from SCIG, the PMSG and DFIG are not in need for a fixed capacitor to generate the active power, and
       the grid can easily feed the reactive losses of transmission lines and transformer at any value of SCR (SCR ≥ 1).
       This increases the dynamic stability of DFIG and PMSG when compared with SCIG.
    2) During fault, the SCIG draws higher reactive power of -3.65p.u against -1.5p.u for the reactive power of DFIG
       and 0p.u for the reactive power of PMSG.
    3) For the three-phase-to-ground fault, the time required to recover stability is approximately 0.25 sec for PMSG
       wind farm compared to 1 sec for DFIG wind farm and 1.5 sec for SCIG wind farm.
    4) For the single-phase-to-ground fault, the time required to recover stability is approximately 0.25 sec for PMSG
       wind farm compared to 0.5 sec for DFIG wind farm and 1.0 sec for SCIG wind farm.
    5) PMSG wind farm is more stable than DFIG and SCIG wind farms because the time required for PMSG wind farm
       to recover the stability is shorter than those of DFIG and SCIG wind farms for fixed and variable speeds.
    6) The performance of DFIG is better than SCIG under three-phase-to-ground fault and single-phase-to-ground fault
       conditions.
7. Appendix
Innovative Systems Design and Engineering                          www.iiste.org
         ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
         Vol 2, No 3


Detailed description of input data to model the system in MATLAB/SIMULINK
115 kV Transmission line data:
Length of line = 70 km
R1 =0.0739    ohm/km,   R0 =0.388   ohm/km
X L1 =0.449   ohm/km,    X L 0 =1.522   ohm/km
 X C1 =0.272 Mega ohm-km,       X C0    =0.427 Mega ohm-km
Values: R1, XL1, R0 and XL0 in ohm/km; XC1 and XC0 in Mega ohm-km
The SCIG:
Generator rating: 1.62 MVA (75 units)
Rated RMS line voltage: 690V
Stator resistance: 0.0025 p.u
Cage resistance: 0.0025 p.u
Stator unsaturated leakage reactance: 0.7 p.u
Mutual unsaturated reactance: 3.434
Rotor unsaturated mutual reactance: 0.7 p.u
Frequency: 50
No. of poles pair: 2
Reactive power compensation in the wind farm: 34 MVAr.
The DFIG
Generator rating: 1.62 MVA (75 units)
Rated RMS line voltage: 690V
Stator resistance: 0.0025 p.u
Rotor resistance: 0.0025 p.u
Stator unsaturated leakage reactance: 0.7 p.u
Mutual unsaturated reactance: 3.434
Rotor unsaturated mutual reactance: 0.7 p.u
Frequency: 50
No. of poles pair: 2
The PMSG:
Generator rating: 1.62 MVA (75 units)
Rated RMS line voltage: 690V
d-axis inductance : 0.7 p.u
q-axis inductance: 0.7 p.u
Rotor resistance: 0.0025 p.u
Frequency: 50
No. of poles pair: 4
Each Wind farm transformer:
Rating: 1.6 MVA
Winding voltages: 10.5/0.69
Innovative Systems Design and Engineering                                                   www.iiste.org
         ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
         Vol 2, No 3


Leakage reactance: 0.0626
No-load losses and cooper losses: 0.0017 17 and 0.0002
Magnetizing current: 0.3 68
Step up transformer:
Rating: 150 MVA
Winding voltages: 10.5/115 kV
Leakage reactance: 0.06
No-load losses and cooper losses: 0.0017 and 0.0002
Magnetizing current: 0.3 68
Load connected at the end terminal of the line: 100 MW
System connected at the end terminal of the line:
Short Circuit Power: 2000 MVA, impedance angle 80°
References
Abbey, C., Khodabakhchian, B., Zhou, F., Dennetière, S., Mahseredjian, J., and Joos, G. (2005), “Transient Modeling and
Comparison of Wind Generator Topologies”, Paper No. IPST05, Presented at the International Conference on Power
Systems Transients, June 19-23, Montreal, Canada.
Abdel-Salam, M., Ahmed, A. and Abdel-Sater, M. (2011), "Harmonic Mitigation, Maximum Power Point Tracking and
Dynamic Performance of Variable Speed Grid Connected Wind Turbine", journal of Electric Power Component and
Systems, Vol. 39, pp. 176-190.
Bhadra, SN., Kastha, D. and Banerjee, S. (2005), Wind electrical systems. Oxford: Oxford University, U.K.
Dusonchet, L. and Telaretti, E. (2011), "Effects of electrical and mechanical parameters on the transient voltage stabilityof a
fixed speed wind turbine", Electric Power Systems Research, vol. 81, pp 1308–1316.
EL-Helw, H.M. and Tennakoon, S.B. (2008), “Evaluation of the suitability of a fixed speed wind turbine for large scale
wind farms considering the new UK grid code”, Renewable Energy, vol. 33, pp.1-12.
Fischer de Toledo, P. and Hailian, X. (2005), "WIND FARM IN WEAK GRIDS COMPENSATED WITH STATCOM".
Proceedings of the Nordic wind power conference, Topic 7, Sweden.
Grainger, S.J. and Stevenson, W.D, Jr. (1994), "Power System Analysis", Book, McGraw-Hill, Inc.
Hong-Woo, K., Sung-Soo K. and Hee-Sang, K. (2010), “Modeling and control of PMSG-based variable-speed wind
turbine”, Electric Power Systems Research, vol. 80, pp 46–52.
Kesraoui, M., Bencherouda, O. and Mesbahi, Z., (2010), “Power Control of a PMSG based Wind Turbine System Above
Rated Wind Speed”, International Renewable Energy Congress, November 5-7, Sousse, Tunisia.
Mathworks (2008a) Inc. SimPowerSystems user’s guide, version 7.6. USA: The Mathworks, Inc.
Mittal, R., Sandu, K.S. and Jain, D.K. (2008), “Power Conditioning of Variable Speed Driven PMSG for Wind Energy
Conversion Systems”, 2nd WSEAS/IASME International Conference on RENEWABLE ENERGY SOURCES (RES'08),
October 26-28, Corfu, Greece.
Mittal, R., Sandu, K.S. and Jain, D.K. (2009), "Isolated Operation of Variable Speed Driven PMSG for Wind Energy
Conversion System", IACSIT International Journal of Engineering and Technology, Vol. 1, No.3, August, pp 1793-8236.
Mohan, N., Undeland, T. and Robbins, W. (1989), "power electronics converters, application and design", Book, John wily
and Sons, Inc.
Rahim, A.H.M.A. and Habiballah, I.O. (2011), "DFIG rotor voltage control for system dynamic performance
enhancement", Electric Power Systems Research, vol. 81, pp 503–509.
Sermutlu, E. (2004), "COMPARISON OF RUNGE-KUTTA METHODS OF ORDER 4 AND 5 ON LORENZ
EQUATION", Journal of Arts and Sciences, May.
Innovative Systems Design and Engineering                                           www.iiste.org
        ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
        Vol 2, No 3


Whei-Min, L., Chih-Ming, H., Ting-Chia, O. and Tai-Ming, C. (2011), " Hybrid intelligent control of PMSG wind
generation system using pitch anglecontrol with RBFN", Energy Conversion and Management, vol. 52, pp1244–1251.
Zhanfeng, S., Changliang, X. and Tingna, S. (2010), “Assessing transient response of DFIG based wind turbines during
voltage dips regarding main flux saturation and rotor deep-bar effect”, Applied Energy, vol. 87, pp. 3283–3293.




               Figure 1. Grid-connected Wind-driven Permanent Magnet Synchronous Generator System
Innovative Systems Design and Engineering                                         www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 3



                                L                   Diode

                      Vdc                         Q Co                    Vdo


                                      g        PI
                                           controllers                Vref

         Figure 2. Switch mode DC-DC converter and DC-DC boost converter and its control
Innovative Systems Design and Engineering        www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 3
Innovative Systems Design and Engineering                                          www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 3


                         Figure 3. Flow chart of PMSG system modeling




          Figure 4. Grid-connected Wind-driven Squirrel Cage Induction Generator System




           Figure 5. Grid-connected Wind-driven Doubly-Fed Induction Generator System
Innovative Systems Design and Engineering                     www.iiste.org
ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
Vol 2, No 3




                                           a. PMSG




                                           b. SCIG




                                           c. DFIG
                                    Figure 6. Network model
Innovative Systems Design and Engineering                                                                                                     www.iiste.org
                                ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
                                Vol 2, No 3



                                                    1.5                                                                                1000
                  Terminal voltage of PMSG (p.u)



                                                        1
                                                                                                                                       800

                                                    0.5
                                                                                                                                       600




                                                                                                                             Vdc (V)
                                                        0
                                                                                                                                       400
                                                   -0.5

                                                                                                                                       200
                                                        -1

                                                   -1.5                                                                                       0
                                                      29.5             30      30.5    31         31.5         32                             29.5         30        30.5    31     31.5      32
                                                                               Time (sec)                                                                            Time (sec)

                                                                                  Figure 7. Terminal voltage of PMSG and dc voltage of converter.

                                                                                                                                                   3
                                                                                              PMSG                                                                                     PMSG
                       1.05                                                                   DFIG                                                2.5                                  DFIG
                                                                                              SCIG                                                                                     SCIG
                                                                                                                                                   2
    Speed (p.u)




                                                                                                                                        V (p.u)
                                                    1
                                                                                                                                                  1.5

                                                                                                                                                   1
                       0.95
                                                                                                                                                  0.5

                                         0.9                                                                                                       0
                                                             30             31      32       33           34                                               30            31       32           33
                                                                              Time (sec)                                                                               Time (sec)


                                  1.5                                                                                                             1.5
                                                                                             PMSG                                                                                       PMSG
                                                   1
                                                                                             DFIG                                                                                       DFIG
                                                                                                                                                    1
                                  0.5                                                        SCIG                                                                                       SCIG

                                                   0                                                                                              0.5
    P (p.u)




                                                                                                                                        Q (p.u)




                        -0.5
                                                                                                                                                    0
                                                   -1
                                                                                                                                                  -0.5
                        -1.5

                                                   -2                                                                                              -1
                                                   29.5           30        30.5   31       31.5         32                                         29.5        30     30.5   31       31.5    32
                                                                            Time (sec)                                                                                 Time (sec)

Figure 8. Temporal variations of the speed, the voltage, the active power and the reactive power at Bus 1 for different wind
                                                                                                                    farms.
Innovative Systems Design and Engineering                                                                                                       www.iiste.org
                                            ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
                                            Vol 2, No 3


                                                                 Va                                                                                                              Vb
                                        1                                                                                                      1




                                                                                                          Terminal voltage of PMSG (p.u)
 Terminal voltage of PMSG (p.u)




                                   0.5                                                                                                     0.5



                                        0                                                                                                      0



                                  -0.5                                                                                                     -0.5



                                       -1                                                                                                   -1
                                        29.5         30      30.5    31          31.5        32                                              29.5                 30      30.5    31         31.5      32
                                                             Time (sec)                                                                                                   Time (sec)
                                                               Vc
                                                                                                                                           600
Terminal voltage of PMSG (p.u))




                                       1
                                                                                                                                           500

                                  0.5
                                                                                                                                           400




                                                                                                                 Vdc (V)
                                       0                                                                                                   300

                                                                                                                                           200
                                  -0.5
                                                                                                                                           100

                                       -1                                                                                                      0
                                        29.5        30     30.5    31         31.5      32                                                     29.5                 30        30.5     31      31.5        32
                                                           Time (sec)                                                                                                          Time (sec)
                                                         Figure 9. Three phases terminal voltages of PMSG and the input dc voltage to converter.
                                   1.1
                                                                                                                                                            1.5
                                                                               PMSG                                                                                                                         PMSG
                                                                               DFIG                                                                                                                         DFIG
                                  1.05                                         SCIG                                                                                                                         SCIG

                                                                                                                                                              1
 Speed (p.u)




                                                                                                                                                  V (p.u)




                                        1


                                                                                                                                                            0.5
                                  0.95



                                   0.9
                                     29.5           30      30.5    31        31.5      32                                                                   0
                                                                                                                                                             29.5        30        30.5      31        31.5          32
                                                            Time (sec)                                                                                                              Time (sec)


                                  2                                                                                                                         1.5
                                                                               PMSG                                                                                                                   PMSG
                                                                               DFIG                                                                          1                                        DFIG
                                  1                                            SCIG                                                                                                                   SCIG

                                                                                                                                                            0.5
                                                                                                                                            Q (p.u)
P (p.u)




                                  0
                                                                                                                                                             0

                                  -1
                                                                                                                                                       -0.5


                                  -2                                                                                                                         -1
                                               30            31          32             33                                                                    29.5       30       30.5   31         31.5        32
                                                           Time (sec)                                                                                                             Time (sec)
                          Figure 10. Temporal variations of the speed, the voltage, the active power and the reactive power at Bus 1 for different
                                                                                                  wind farm
Innovative Systems Design and Engineering                                                                                                    www.iiste.org
                         ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
                         Vol 2, No 3



                         15                                                                                                      1.5




                                                                                            Terminal voltage of PMSG (p.u)
                                                                                                                                     1
Wind speed (m/sec)




                                                                                                                                 0.5

                         10                                                                                                          0

                                                                                                                             -0.5

                                                                                                                                     -1

                         5                                                                                                   -1.5
                              0       10    20      30     40        50                                                                   0        10    20      30       40      50
                                            Time (sec)                                                                                                   Time (sec)


                                                                                                                                 700
                         50
                                                                                                                                 600
Frequency of PMSG (Hz)




                         40
                                                                                                                                 500

                         30                                                                                                      400


                                                                                                       Vdc (V)
                                                                                                                                 300
                         20
                                                                                                                                 200
                         10
                                                                                                                                 100

                         0                                                                                                           0
                              0       10    20      30     40        50                                                                   0        10    20      30      40      50
                                            Time (sec0                                                                                                   Time (sec)

                         Figure 11. Wind speed, the terminal voltage and frequency of PMSG and the input dc voltage to converter.

                                                                                                3.5
                         1.4                                     PMSG                                                                                                          PMSG
                                                                 DFIG                                                        3
                                                                                                                                                                               DFIG
                                                                 SCIG                                                                                                          SCIG
                                                                                                2.5
                         1.2
           Speed (p.u)




                                                                                                                             2
                                                                                  V (p.u)




                              1                                                                 1.5

                                                                                                                             1
                         0.8
                                                                                                0.5

                         0.6                                                                                                 0
                                  0    10     20      30        40        50                                                     0            10        20      30        40          50
                                              Time (sec)                                                                                                Time (sec)
Innovative Systems Design and Engineering                                                                                www.iiste.org
               ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online)
               Vol 2, No 3



               1.5                                                                        1.5
                                                     PMSG                                                                                    PMSG
                1                                    DFIG
                                                                                                 1                                           DFIG
               0.5                                   SCIG                                                                                    SCIG

                0                                                                         0.5
   P (p.u)




                                                                             Q (p.u)
              -0.5
                                                                                                 0
                -1
                                                                                       -0.5
              -1.5

                -2                                                                               -1
                     0      10     20      30    40         50                                                  10        20      30        40         50
                                   Time (sec)                                                                              Time (sec)

                         Figure 12. Temporal variations of the speed, voltage, active power and reactive power at Bus 1
              1.6
                                                  PMSG                                                1.5
                                                                                                                                                      PMSG
              1.4                                 DFIG                                                                                                DFIG
                                                  SCIG                                                                                                SCIG
Speed (p.u)




              1.2                                                                                       1




                                                                                            V (p.u)
               1

                                                                                                      0.5
              0.8


              0.6
                    0      10     20      30    40       50                                             0
                                                                                                            0        10      20        30        40          50
                                  Time (sec)                                                                                  Time (sec)



               1.5                                                                                     1
                                                  PMSG                                                                                           PMSG
                    1                             DFIG                                                                                           DFIG
                                                  SCIG                                                                                           SCIG
               0.5
                                                                                                      0.5
                    0
   Q (p.u)




                                                                                       Q (p.u)




              -0.5
                                                                                                       0
                -1

              -1.5

                -2                                                                                -0.5
                  0         10     20      30    40         50                                              0        10     20      30       40         50
                                   Time (sec)                                                                               Time (sec)

               Figure 13. Temporal variations of the speed, the voltage, the active power and the reactive power at Bus 1

More Related Content

What's hot

Wind Power Generation Schemes
Wind Power Generation SchemesWind Power Generation Schemes
Wind Power Generation SchemesVignesh Sekar
 
Wind Turbine Generators
Wind Turbine GeneratorsWind Turbine Generators
Wind Turbine GeneratorsJasjot Singh
 
Design of wind turbine controllers in simulation x jagath_ireshika_bernad_dim...
Design of wind turbine controllers in simulation x jagath_ireshika_bernad_dim...Design of wind turbine controllers in simulation x jagath_ireshika_bernad_dim...
Design of wind turbine controllers in simulation x jagath_ireshika_bernad_dim...Dimuthu Darshana
 
Mtech IEEE Conference Presentation
Mtech IEEE Conference PresentationMtech IEEE Conference Presentation
Mtech IEEE Conference PresentationJanardhan Reddy
 
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...Naila Syed
 
Modeling and simulation of dfig to grid connected wind power generation using...
Modeling and simulation of dfig to grid connected wind power generation using...Modeling and simulation of dfig to grid connected wind power generation using...
Modeling and simulation of dfig to grid connected wind power generation using...IAEME Publication
 
Mfc based doubled fed induction generator in wind energy conversion system
Mfc based doubled fed induction generator in wind energy conversion systemMfc based doubled fed induction generator in wind energy conversion system
Mfc based doubled fed induction generator in wind energy conversion systemnagarajaan
 
Performance of Doubly-Fed Induction Generator by changing various system para...
Performance of Doubly-Fed Induction Generator by changing various system para...Performance of Doubly-Fed Induction Generator by changing various system para...
Performance of Doubly-Fed Induction Generator by changing various system para...AM Publications
 
Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3IAEME Publication
 
Modeling and Analysis of Wind Energy Conversion Systems Using Matlab
Modeling and Analysis of Wind Energy Conversion Systems Using MatlabModeling and Analysis of Wind Energy Conversion Systems Using Matlab
Modeling and Analysis of Wind Energy Conversion Systems Using MatlabIOSR Journals
 
Doubly fed-induction-generator
Doubly fed-induction-generatorDoubly fed-induction-generator
Doubly fed-induction-generatorHarshad Karmarkar
 
DFIG BASED WIND TURBINE
DFIG BASED WIND TURBINEDFIG BASED WIND TURBINE
DFIG BASED WIND TURBINELogu Mani
 
Power electronics in Wind Turbine Systems
Power electronics in Wind Turbine SystemsPower electronics in Wind Turbine Systems
Power electronics in Wind Turbine SystemsManasa K
 
WIND ENERGY CONVERSION SYSTEM KEDARE
WIND ENERGY CONVERSION SYSTEM KEDAREWIND ENERGY CONVERSION SYSTEM KEDARE
WIND ENERGY CONVERSION SYSTEM KEDAREH Janardan Prabhu
 
Control Scheme for a Stand-Alone Wind Energy Conversion System
Control Scheme for a Stand-Alone Wind Energy Conversion SystemControl Scheme for a Stand-Alone Wind Energy Conversion System
Control Scheme for a Stand-Alone Wind Energy Conversion SystemRoja Rani
 
Analysis of PMSG in Wind Integration using T Source Inverter with Simple Boos...
Analysis of PMSG in Wind Integration using T Source Inverter with Simple Boos...Analysis of PMSG in Wind Integration using T Source Inverter with Simple Boos...
Analysis of PMSG in Wind Integration using T Source Inverter with Simple Boos...IJTET Journal
 

What's hot (20)

Wind Power Generation Schemes
Wind Power Generation SchemesWind Power Generation Schemes
Wind Power Generation Schemes
 
Wind Turbine Generators
Wind Turbine GeneratorsWind Turbine Generators
Wind Turbine Generators
 
Design of wind turbine controllers in simulation x jagath_ireshika_bernad_dim...
Design of wind turbine controllers in simulation x jagath_ireshika_bernad_dim...Design of wind turbine controllers in simulation x jagath_ireshika_bernad_dim...
Design of wind turbine controllers in simulation x jagath_ireshika_bernad_dim...
 
Mtech IEEE Conference Presentation
Mtech IEEE Conference PresentationMtech IEEE Conference Presentation
Mtech IEEE Conference Presentation
 
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
Open-End-Winding Permanent Magnet Synchonous Generator for Wind Energy Conver...
 
Modeling and simulation of dfig to grid connected wind power generation using...
Modeling and simulation of dfig to grid connected wind power generation using...Modeling and simulation of dfig to grid connected wind power generation using...
Modeling and simulation of dfig to grid connected wind power generation using...
 
Mfc based doubled fed induction generator in wind energy conversion system
Mfc based doubled fed induction generator in wind energy conversion systemMfc based doubled fed induction generator in wind energy conversion system
Mfc based doubled fed induction generator in wind energy conversion system
 
Performance of Doubly-Fed Induction Generator by changing various system para...
Performance of Doubly-Fed Induction Generator by changing various system para...Performance of Doubly-Fed Induction Generator by changing various system para...
Performance of Doubly-Fed Induction Generator by changing various system para...
 
Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3
 
Modeling and Analysis of Wind Energy Conversion Systems Using Matlab
Modeling and Analysis of Wind Energy Conversion Systems Using MatlabModeling and Analysis of Wind Energy Conversion Systems Using Matlab
Modeling and Analysis of Wind Energy Conversion Systems Using Matlab
 
DFIG_report
DFIG_reportDFIG_report
DFIG_report
 
Doubly fed-induction-generator
Doubly fed-induction-generatorDoubly fed-induction-generator
Doubly fed-induction-generator
 
DFIG BASED WIND TURBINE
DFIG BASED WIND TURBINEDFIG BASED WIND TURBINE
DFIG BASED WIND TURBINE
 
Power electronics in Wind Turbine Systems
Power electronics in Wind Turbine SystemsPower electronics in Wind Turbine Systems
Power electronics in Wind Turbine Systems
 
WIND ENERGY CONVERSION SYSTEM KEDARE
WIND ENERGY CONVERSION SYSTEM KEDAREWIND ENERGY CONVERSION SYSTEM KEDARE
WIND ENERGY CONVERSION SYSTEM KEDARE
 
Pmsg
PmsgPmsg
Pmsg
 
A STAND A
A STAND AA STAND A
A STAND A
 
Control Scheme for a Stand-Alone Wind Energy Conversion System
Control Scheme for a Stand-Alone Wind Energy Conversion SystemControl Scheme for a Stand-Alone Wind Energy Conversion System
Control Scheme for a Stand-Alone Wind Energy Conversion System
 
Analysis of PMSG in Wind Integration using T Source Inverter with Simple Boos...
Analysis of PMSG in Wind Integration using T Source Inverter with Simple Boos...Analysis of PMSG in Wind Integration using T Source Inverter with Simple Boos...
Analysis of PMSG in Wind Integration using T Source Inverter with Simple Boos...
 
Seminar2
Seminar2Seminar2
Seminar2
 

Similar to 15 mazen abdel salam_18

Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...ecij
 
Design And Simulation of Microgrid Control based Wind Power Generation Syst...
Design And Simulation of  Microgrid Control  based Wind Power Generation Syst...Design And Simulation of  Microgrid Control  based Wind Power Generation Syst...
Design And Simulation of Microgrid Control based Wind Power Generation Syst...IRJET Journal
 
Modeling and Control of Gate-Controlled Series Capacitor Interfaced With a DF...
Modeling and Control of Gate-Controlled Series Capacitor Interfaced With a DF...Modeling and Control of Gate-Controlled Series Capacitor Interfaced With a DF...
Modeling and Control of Gate-Controlled Series Capacitor Interfaced With a DF...University of South Carolina
 
Dstatcom based voltage regulator for wind turbine driven self excited indu
Dstatcom based voltage regulator for wind turbine driven self excited induDstatcom based voltage regulator for wind turbine driven self excited indu
Dstatcom based voltage regulator for wind turbine driven self excited induIAEME Publication
 
Inductively coupled distributed static compensator for power quality analysi...
Inductively coupled distributed static compensator for power  quality analysi...Inductively coupled distributed static compensator for power  quality analysi...
Inductively coupled distributed static compensator for power quality analysi...IJECEIAES
 
journal publishing, how to publish research paper, Call For research paper, i...
journal publishing, how to publish research paper, Call For research paper, i...journal publishing, how to publish research paper, Call For research paper, i...
journal publishing, how to publish research paper, Call For research paper, i...IJERD Editor
 
Voltage Oriented Decoupled Control Scheme for DFIG’s Grid Side Converter
Voltage Oriented Decoupled Control Scheme for DFIG’s Grid Side ConverterVoltage Oriented Decoupled Control Scheme for DFIG’s Grid Side Converter
Voltage Oriented Decoupled Control Scheme for DFIG’s Grid Side ConverterTELKOMNIKA JOURNAL
 
Control of DFIG Stator Voltage on Autonomous Micro Hydro Power Plant
Control of DFIG Stator Voltage on Autonomous Micro Hydro Power PlantControl of DFIG Stator Voltage on Autonomous Micro Hydro Power Plant
Control of DFIG Stator Voltage on Autonomous Micro Hydro Power PlantIJPEDS-IAES
 
PERFORMANCE OF MVDC AND MVAC OFFSHORE WIND FARM DISTRIBUTION SYSTEM
PERFORMANCE OF MVDC AND MVAC OFFSHORE WIND FARM DISTRIBUTION SYSTEMPERFORMANCE OF MVDC AND MVAC OFFSHORE WIND FARM DISTRIBUTION SYSTEM
PERFORMANCE OF MVDC AND MVAC OFFSHORE WIND FARM DISTRIBUTION SYSTEMJournal For Research
 

Similar to 15 mazen abdel salam_18 (20)

Control of PMSG based variable speed wind energy conversion system connected ...
Control of PMSG based variable speed wind energy conversion system connected ...Control of PMSG based variable speed wind energy conversion system connected ...
Control of PMSG based variable speed wind energy conversion system connected ...
 
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
 
Design And Simulation of Microgrid Control based Wind Power Generation Syst...
Design And Simulation of  Microgrid Control  based Wind Power Generation Syst...Design And Simulation of  Microgrid Control  based Wind Power Generation Syst...
Design And Simulation of Microgrid Control based Wind Power Generation Syst...
 
Modeling and Control of Gate-Controlled Series Capacitor Interfaced With a DF...
Modeling and Control of Gate-Controlled Series Capacitor Interfaced With a DF...Modeling and Control of Gate-Controlled Series Capacitor Interfaced With a DF...
Modeling and Control of Gate-Controlled Series Capacitor Interfaced With a DF...
 
Fw3410821085
Fw3410821085Fw3410821085
Fw3410821085
 
Dstatcom based voltage regulator for wind turbine driven self excited indu
Dstatcom based voltage regulator for wind turbine driven self excited induDstatcom based voltage regulator for wind turbine driven self excited indu
Dstatcom based voltage regulator for wind turbine driven self excited indu
 
T25102106
T25102106T25102106
T25102106
 
G010234652
G010234652G010234652
G010234652
 
Inductively coupled distributed static compensator for power quality analysi...
Inductively coupled distributed static compensator for power  quality analysi...Inductively coupled distributed static compensator for power  quality analysi...
Inductively coupled distributed static compensator for power quality analysi...
 
Efficient Approach to LVRT Capability of DFIG-Based Wind Turbines under Symme...
Efficient Approach to LVRT Capability of DFIG-Based Wind Turbines under Symme...Efficient Approach to LVRT Capability of DFIG-Based Wind Turbines under Symme...
Efficient Approach to LVRT Capability of DFIG-Based Wind Turbines under Symme...
 
Ar36263268
Ar36263268Ar36263268
Ar36263268
 
journal publishing, how to publish research paper, Call For research paper, i...
journal publishing, how to publish research paper, Call For research paper, i...journal publishing, how to publish research paper, Call For research paper, i...
journal publishing, how to publish research paper, Call For research paper, i...
 
40220140506002
4022014050600240220140506002
40220140506002
 
E010343239
E010343239E010343239
E010343239
 
Voltage Oriented Decoupled Control Scheme for DFIG’s Grid Side Converter
Voltage Oriented Decoupled Control Scheme for DFIG’s Grid Side ConverterVoltage Oriented Decoupled Control Scheme for DFIG’s Grid Side Converter
Voltage Oriented Decoupled Control Scheme for DFIG’s Grid Side Converter
 
Science (1)
Science (1)Science (1)
Science (1)
 
Hr3513381342
Hr3513381342Hr3513381342
Hr3513381342
 
Evaluation of Synchronization and MPPT Algorithms in a DFIG Wind Turbine Cont...
Evaluation of Synchronization and MPPT Algorithms in a DFIG Wind Turbine Cont...Evaluation of Synchronization and MPPT Algorithms in a DFIG Wind Turbine Cont...
Evaluation of Synchronization and MPPT Algorithms in a DFIG Wind Turbine Cont...
 
Control of DFIG Stator Voltage on Autonomous Micro Hydro Power Plant
Control of DFIG Stator Voltage on Autonomous Micro Hydro Power PlantControl of DFIG Stator Voltage on Autonomous Micro Hydro Power Plant
Control of DFIG Stator Voltage on Autonomous Micro Hydro Power Plant
 
PERFORMANCE OF MVDC AND MVAC OFFSHORE WIND FARM DISTRIBUTION SYSTEM
PERFORMANCE OF MVDC AND MVAC OFFSHORE WIND FARM DISTRIBUTION SYSTEMPERFORMANCE OF MVDC AND MVAC OFFSHORE WIND FARM DISTRIBUTION SYSTEM
PERFORMANCE OF MVDC AND MVAC OFFSHORE WIND FARM DISTRIBUTION SYSTEM
 

More from Alexander Decker

Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...Alexander Decker
 
A validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale inA validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale inAlexander Decker
 
A usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websitesA usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websitesAlexander Decker
 
A universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banksA universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banksAlexander Decker
 
A unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized dA unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized dAlexander Decker
 
A trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistanceA trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistanceAlexander Decker
 
A transformational generative approach towards understanding al-istifham
A transformational  generative approach towards understanding al-istifhamA transformational  generative approach towards understanding al-istifham
A transformational generative approach towards understanding al-istifhamAlexander Decker
 
A time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibiaA time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibiaAlexander Decker
 
A therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school childrenA therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school childrenAlexander Decker
 
A theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banksA theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banksAlexander Decker
 
A systematic evaluation of link budget for
A systematic evaluation of link budget forA systematic evaluation of link budget for
A systematic evaluation of link budget forAlexander Decker
 
A synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjabA synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjabAlexander Decker
 
A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...Alexander Decker
 
A survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incrementalA survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incrementalAlexander Decker
 
A survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniquesA survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniquesAlexander Decker
 
A survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo dbA survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo dbAlexander Decker
 
A survey on challenges to the media cloud
A survey on challenges to the media cloudA survey on challenges to the media cloud
A survey on challenges to the media cloudAlexander Decker
 
A survey of provenance leveraged
A survey of provenance leveragedA survey of provenance leveraged
A survey of provenance leveragedAlexander Decker
 
A survey of private equity investments in kenya
A survey of private equity investments in kenyaA survey of private equity investments in kenya
A survey of private equity investments in kenyaAlexander Decker
 
A study to measures the financial health of
A study to measures the financial health ofA study to measures the financial health of
A study to measures the financial health ofAlexander Decker
 

More from Alexander Decker (20)

Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...Abnormalities of hormones and inflammatory cytokines in women affected with p...
Abnormalities of hormones and inflammatory cytokines in women affected with p...
 
A validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale inA validation of the adverse childhood experiences scale in
A validation of the adverse childhood experiences scale in
 
A usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websitesA usability evaluation framework for b2 c e commerce websites
A usability evaluation framework for b2 c e commerce websites
 
A universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banksA universal model for managing the marketing executives in nigerian banks
A universal model for managing the marketing executives in nigerian banks
 
A unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized dA unique common fixed point theorems in generalized d
A unique common fixed point theorems in generalized d
 
A trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistanceA trends of salmonella and antibiotic resistance
A trends of salmonella and antibiotic resistance
 
A transformational generative approach towards understanding al-istifham
A transformational  generative approach towards understanding al-istifhamA transformational  generative approach towards understanding al-istifham
A transformational generative approach towards understanding al-istifham
 
A time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibiaA time series analysis of the determinants of savings in namibia
A time series analysis of the determinants of savings in namibia
 
A therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school childrenA therapy for physical and mental fitness of school children
A therapy for physical and mental fitness of school children
 
A theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banksA theory of efficiency for managing the marketing executives in nigerian banks
A theory of efficiency for managing the marketing executives in nigerian banks
 
A systematic evaluation of link budget for
A systematic evaluation of link budget forA systematic evaluation of link budget for
A systematic evaluation of link budget for
 
A synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjabA synthetic review of contraceptive supplies in punjab
A synthetic review of contraceptive supplies in punjab
 
A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...A synthesis of taylor’s and fayol’s management approaches for managing market...
A synthesis of taylor’s and fayol’s management approaches for managing market...
 
A survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incrementalA survey paper on sequence pattern mining with incremental
A survey paper on sequence pattern mining with incremental
 
A survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniquesA survey on live virtual machine migrations and its techniques
A survey on live virtual machine migrations and its techniques
 
A survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo dbA survey on data mining and analysis in hadoop and mongo db
A survey on data mining and analysis in hadoop and mongo db
 
A survey on challenges to the media cloud
A survey on challenges to the media cloudA survey on challenges to the media cloud
A survey on challenges to the media cloud
 
A survey of provenance leveraged
A survey of provenance leveragedA survey of provenance leveraged
A survey of provenance leveraged
 
A survey of private equity investments in kenya
A survey of private equity investments in kenyaA survey of private equity investments in kenya
A survey of private equity investments in kenya
 
A study to measures the financial health of
A study to measures the financial health ofA study to measures the financial health of
A study to measures the financial health of
 

Recently uploaded

M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.Aaiza Hassan
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLSeo
 
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876dlhescort
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Dave Litwiller
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Roland Driesen
 
RSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors DataRSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors DataExhibitors Data
 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 DelhiCall Girls in Delhi
 
7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...Paul Menig
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageMatteo Carbone
 
HONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsHONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsMichael W. Hawkins
 
Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Roland Driesen
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsP&CO
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst SummitHolger Mueller
 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...Any kyc Account
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxWorkforce Group
 
Best Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaBest Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaShree Krishna Exports
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMRavindra Nath Shukla
 
Understanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key InsightsUnderstanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key Insightsseri bangash
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMANIlamathiKannappan
 

Recently uploaded (20)

M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
 
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
 
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabiunwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...
 
RSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors DataRSA Conference Exhibitor List 2024 - Exhibitors Data
RSA Conference Exhibitor List 2024 - Exhibitors Data
 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
 
7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usage
 
HONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsHONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael Hawkins
 
Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst Summit
 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptx
 
Best Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaBest Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in India
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSM
 
Understanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key InsightsUnderstanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key Insights
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMAN
 

15 mazen abdel salam_18

  • 1. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 Transient analysis of grid-connected wind-driven PMSG, DFIG and SCIG at fixed and variable speeds Mazen Abdel-Salam (Corresponding author) Electric Engineering Department, Assiut University, Assiut, Egypt E-mail: mazen2000as@yahoo.com Adel Ahmed Electric Engineering Department, Assiut University, Assiut, Egypt E-mail: a_ahmed@aun.edu.eg Mahmoud Mahrous Electric Engineering Department, Assiut University, Assiut, Egypt E-mail: mahmoud2006eng@yahoo.com Abstract This paper is aimed at presenting transient analysis of a grid-connected wind-driven permanent magnet synchronous generator (PMSG) at fixed and variable speeds by solving the system describing differential equations. For comparison purpose, wind-driven squirrel cage (SCIG) and doubly fed (DFIG) induction generators at fixed and variable speeds are studied using MATLAB/SIMULINK software package. Different from PMSG and DFIG the grid should feed the reactive losses of transmission lines and transformers at any value of short circuit ratio for SCIG. This increases the dynamic stability of DFIG and PMSG when compared with SCIG. Under three-phase-to-ground fault and single-phase-to-ground fault conditions, the time required to recover stability of PMSG wind farm is less than those DFIG and SCIG wind farms for fixed and variable speeds indicating that PMSG is more stable than of DFIG and of SCIG wind farms. Keywords: Wind energy; Fixed and variable speed wind turbine; Permanent magnet synchronous generator; Induction generator; Short circuit ratio. 1. Introduction Wind turbine technology has undergone a dramatic transformation during the last 15 years, developing from a fringe science in the 1970s to the wind turbines of the 2000s utilizing the latest technology in power electronics, aerodynamics and mechanical drive designs. Induction generators are more attractive than synchronous generators for wind turbines due to their robust construction, low cost, low maintenance, long life (more than 50 years) and low power to weight ratio (Bhadra 2005). However the reactive power management is a major concern, not only to compensate for the reactive power requirements of the wind generator itself but also to support the system voltage in particular for wind farms based on fixed speed induction generators. Most wind turbines use induction generators, squirrel cage induction generator (SCIG), doubly-fed-induction-generators (DFIG) or permanent magnet synchronous generators (PMSG). Currently, DFIG based wind turbines dominate the world market due to their cost-effective provision of variable-speed operation, as well as the controlling flexibility of electromagnetic torque and reactive power. However, since its stator and rotor are both connected to the power system, grid fault ride-through control (on temporal reduction of the grid voltage due to a fault) is difficult for the DFIG, and is a major challenge for wind turbine manufacturers based on the MATLAB/SIMULINK without stating the system describing equations (Zhanfeng 2010). In the existing literature, there have recently been several papers dealing with this problem, mainly focusing on ride-through controller design and transient response analysis based on the system describing equations after being linearized and models the state variables of the original system states from the nominal operating values (Rahim 2011).
  • 2. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 The analysis of a configuration consisting wind farm based on conventional fixed speed SCIG has been reported before (Fischer de Toledo 2005). Improvement of the short-term voltage and rotor stability performance on introducing a STATCOM was quantified during different types of failure events in the connected power system (three-phase to ground fault and single-phase to ground fault) using EMTDC/PSCAD digital simulator. Also, the effect of electrical parameters of the induction generator on the transient voltage stability of a fixed speed wind turbine (FSWT) connected to a simple grid based on the MATLAB/SIMULINK (Dusonchet 2011). When compared with induction generators, the PMSG has a smaller physical size and a lower moment of inertia which means a higher reliability and power density per volume ratio. The electrical losses in the rotor are eliminated on the expense of high costs for permanent magnet materials and fixed excitation, which cannot be changed according to the operating point. The model used in this study was developed in the d-q synchronous rotating reference frame (Kesraoui 2010). PMSG based direct driven turbine is connected to the grid by through AC- DC- AC conversion system, modeled and simulated using MATLAB/SIMULINK (Mittal 2008). This paper is aimed at presenting a transient analysis model of a grid-connected wind-driven permanent magnet synchronous generator (PMSG) at fixed and variable speeds by solving the system describing differential equations. The PMSG is the equivalent generator of many wind-driven synchronous generators operating in a wind farm. For comparison purpose, wind-driven squirrel cage (SCIG) and doubly fed (DFIG) induction generators running at fixed and variable speeds are studied using MATLAB/SIMULINK. Different line connections between the grid and the wind farm with subsequent different short-circuit ratios are studied. The study extends to include three-phase-to-ground and single-phase-to-ground faults at the point where the wind farm is connected to the grid. The time required for the wind farm to recover stability is assessed for wind driven PMSG, DFIG and SCIG. 2. Network There are a number of possible interconnection structures for wind farms and thus it is not possible to cover every type of network configuration, load, and interconnection point of the wind farm. Frequently wind parks are connected to weak systems, as they are typically located far from major load centers and central generation. This reflects itself in defining a short circuit ratio (SCR) of the interconnection expressed as: SCC SCR  Sbase (1) Where S base is the rated power of wind farm and SCC or short circuit capacity is the short circuit power delivered from the grid to a three-phase fault at the wind farm: 2 Vbase SCC  Z line (2) Z line Vbase where is the impedance of the line connecting the grid with wind farm and is the rated voltage of the grid. For weak systems the SCR will usually be less than 6 (Abbey 2005). 3. System modeling 3.1 Grid-connected Wind-driven Permanent Magnet Synchronous Generator (PMSG) System The block diagram of the system is shown in fig. 1. The system consists of wind-driven PMSG, an AC-DC three phase bridge rectifier, DC-DC boost converter to fixed the voltage at certain specified value and PWM inverter to interface the system with the electric utility. 3.1.1 PMSG Modeling
  • 3. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 The PMSG is described by the following differential equations (Hong-Woo 2010) and (Whei-Min 2011): 1 d ds  v ds  Rs ids   e qs  b dt (3) 1 d qs  v qs  Rs iqs   e ds  b dt With  ds   Ldsids   m (4)  qs   Lqsiqs where v is the p.u voltage, Rs is the p.u resistance, i is the p.u current, e is the p.u stator electrical angular speed, b is the base angular speed in rad/s, Ls is the p.u stator leakage inductance,  m is the p.u exciter flux of the PMSG, and  is the p.u flux linkage. The subscripts d and q indicate the direct and quadrature axis components, respectively. The subscripts s indicates stator quantities. The electrical active and reactive power delivered by the stator are given by Ps  v dsids  v qsiqs (5) Qs  v dsiqs  v qsids The voltages of phases d, q and 0 are transformed by Park’s transformation (P) to a, b and c variables as follows (Grainger 1994): v a  v d  v   P 1 v  (6)  b  q v c    v   0   cos  d cos( d  120) cos( d  120) 2  P sin  d sin( d  120) sin( d  120)  (7) 3 1  1 1   2  2 2   3.1.2 Uncontrolled rectifier and DC-DC boost converter As the wind speed is constantly varying so the PMSG produces variable voltage and variable frequency output. A three- phase uncontrolled diode rectifier is used to convert the PMSG output AC voltage to DC voltage. The rectifier output voltage (Vdc) depends on the AC line voltage as expressed (Mohan 1989): 3 3 3 2 Vdc  Vm  V LL (8)   Where Vm is the maximum phase voltage and VLL is the rms value of the line-line voltage. As the PMSG voltage is variable with the wind speed, the DC output voltage of the bridge rectifier is also variable. A boost DC-DC converter has been used for maintaining the DC output voltage at constant value V do. The relation between the
  • 4. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 output and input voltages depends on the duty ratio D as expressed by equations (9) and (10), where Ts is the switching period and ton is the on time of the switch, the switch mode DC-DC converter signal is generated by compared the triangular wave (its period Ts) with DC wave as shown in fig. 2 (Mohan 1989). Vdo 1  (9) Vdc 1  D t on D (10) Ts The control block diagram consists of a comparator, which compares the actual DC-DC converter output with a reference value. The error signal is fed to a PI controller passes though a limiter within the controller. The output of the PI controller used to generate the switching signal. 3.1.3 PWM Inverter The inverter inverts the DC voltage output to AC voltage with supply frequency in order to connect the wind-driven system to the grid. The output of the PWM inverter (Mohan 1989) may be expressed as: 3 VLL1  maVdo  0.612maVdo (11) 2 2 ˆ ˆ Vcontrol V LL ma   (12) ˆ Vtri Vdo fs mf  (13) f1 ˆ Where ma called the modulation index, V LL is the peak value of the line-line voltage, VLL1 is the fundamental component in ˆ ˆ the output voltage, V is the peak amplitude of the triangular which is kept constant, V tri is the peak amplitude of the control control signal, mf is the frequency modulation ratio, fs is the switching frequency and f1 is the fundamental component frequency. It is always desirable to minimize the distortion of the output voltage and current, which change with the modulation index in linear modulation (ma ≤ 1.0) and over-modulation region (ma > 1). In the linear region (ma ≤ 1.0) the fundamental- frequency component in the output voltage varies linearly with the amplitude modulation ratio ma as expressed by equation (12). Also, the harmonics in the inverter output voltage waveform appear as sidebands, centered around the switching frequency referred to the fundamental and its multiples, that is, around harmonics mf, 2 mf, 3 mf, and so on (Mohan 1989). 3.1.4 Modeling of grid-connected wind-driven PMSG system using Runge- Kutta Method The PMSG wind farm connected to a grid is modeled by solving the describing differential equations using runge-kutta method (Sermutlu 2004) as described by the flow chart of fig. 3.The solution ends up with the temporal variation of the currents, voltages and active and reactive power. 3.2 Grid-connected Wind-driven Squirrel Cage Induction Generator (SCIG) System In wind-driven SCIG, the stator winding is connected directly to the grid and the rotor is driven by the wind turbine as shown in fig. 4. The power captured by the wind turbine is converted into electrical power by the induction generator and is transmitted to the grid by the stator winding. The pitch angle is controlled in order to limit the generator output power to its nominal value at high wind speeds. In order to generate power, the induction generator speed must be slightly above the synchronous speed. The reactive power absorbed by the induction generator is provided by the grid or by some devices like capacitor banks, SVC, STATCOM or synchronous condenser (Mathworks 2008a). The present transient analysis of the system is based on MATLAB/SIMULINK simulation for fixed and variable wind speeds.
  • 5. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 3.3 Grid-connected Wind-driven Doubly Fed Induction Generator (DFIG) system In wind-driven doubly-fed induction generator (WTDFIG), Fig. 5 an AC/DC/AC converter connects the rotor of the generator to the grid. The AC/DC/AC converter is divided into two components: the rotor-side converter ( ) and the grid-side converter ( ). and are Voltage-Sourced Converters that use forced-commutated IGBTs to synthesize an AC voltage from a DC voltage source. The synthesized AC voltage is of power frequency for and of slip frequency for . A capacitor connected on the DC side acts as the DC voltage source. A coupling inductor L is used to connect to the grid. The three-phase rotor winding is connected to by slip rings and brushes and the three-phase stator winding is directly connected to the grid. The power captured by the wind turbine is converted into electrical power by the induction generator and transmitted to the grid by the stator and the rotor windings. The control system generates pitch angle and voltage command signals Vr and Vgc for and respectively in order to control the wind turbine power comparison against a reference power obtained from the tracking characteristic. A Proportional-Integral (PI) regulator is used to reduce the power error to zero, while adjusting the DC bus voltage and the reactive power or the voltage at the grid terminals (Mathworks 2008a). Similar to SCIG system, the present transient analysis of the DFIG system is based also on MATLAB/SIMULINK simulation for fixed and variable wind speeds. 4. Grid-Connected Wind-driven Systems under study The one line diagram of the test system employed in this study is shown in Fig. 6 for different types of wind farm. The wind farm of PMSG consists of 75 units of 1.6 MVA wind turbines. Each wind turbine unit consists of: rotor, gear box, permanent magnet synchronous generator, uncontrolled converter, DC-DC boost converter, inverter and a 0.69/10.5 kV transformer as shown in fig. 6a. In the wind farm of SCIG, each wind turbine unit is the same as in PMSG in addition to shunt capacitors for reactive power compensation, but without uncontrolled converter, DC-DC boost converter and inverter as shown in fig. 6b. In the wind farm of DFIG, each wind turbine unit is the same as that of PMSG as shown in fig. 6c. In The representation of the power plant has been made by aggregating all the 75 wind turbines in one equivalent unit. Phase model is used for wind turbine induction generator (SCIG) and doubly fed induction generator (DFIG) systems (El-Helw 2008). 5. Simulation studies The grid-connected wind-driven PMSG system is modeled by solving the system differential equations using Runge-Kutta method by programming the m-file of MATLAB program. Three-phase-to-ground and single-phase-to-ground faults are applied at the connection bus between the PMSG wind farm and the 115-kV transmission line at t =30 s for a duration of 140ms (as the detection and operation times of the breakers extend to 140 ms) (Fischer de Toledo 2005). For comparison purpose the same faults are applied at the connection bus between the SCIG and DFIG wind farms and the 115-kV transmission line at t =30 s for a duration of 140ms and SCR of 16. 5.1 Grid-connected Wind-driven systems at fixed speed The Grid-connected wind-driven systems of system in Fig. 6 are studied with fixed speed wind turbines at 10 m/s. The transient behaviour of systems before, during and after three-phase and single-phase to ground faults is studied. The voltage and the frequency of PMSG are less than the rated voltage and rated frequency of wind farm (690V, 50Hz). Therefore, the converter and inverter are used to convert the voltage and frequency to rated values. 5.1.1 Three-phase-to-ground fault A three phase to ground fault is applied at the connection bus (bus 3) between the wind farm and the 115-kV transmission line (Fig. 6a) at t =30 s for a duration of 140ms. Fig.7 shows the terminal voltage of the PMSG and the input dc voltage to DC-DC boost converter. As shown in Fig. 7, the terminal voltage of PMSG before fault is 0.8 p.u (base 690 V) at a frequency of 40 Hz. During fault, the voltage collapses to zero at 30.25 sec with oscillations before recovering the pre-fault value. The pre-fault value of the input dc voltage to the converter is 568 V. During fault, the dc voltage reaches zero at 30.75 sec with oscillations before recovering its pre-fault value. Figure 8 shows the temporal variations of the speed, voltage, active power and reactive power at Bus 1 for different wind farms. As shown in Fig. 8, the time required of PMSG, SCIG and DFIG wind farms to recover their pre-fault values of speed,
  • 6. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 voltage, active power and reactive power are approximately 0.25 sec, 1.5 sec and 1sec respectively. During fault, the speed of PMSG wind farm oscillates reaching 1.072p.u, against 1.032 p.u and 1.024 p.u for SCIG and DFIG wind farms, respectively. Also, the voltage of PMSG wind farm oscillates reaching 3 p.u, against 1.5 p.u and 1.1 p.u for SCIG and DFIG wind farms, respectively. This concludes that the performance of DFIG is better than SCIG under three-phase-to- ground fault conditions. For SCIG, the pre-fault and post-fault values of the speed are equal to 1.015 p.u, which are almost of the same values as obtained previously using PSCAD simulator calculation (Fischer de Toledo 2005). During the fault, the speed reached 1.03 p.u against 1.06 p.u (Fischer de Toledo 2005). The voltage, the active power and the reactive power have the same trend during the fault as that reported before (Fischer de Toledo 2005). Generally, the mismatch between the previous and present calculations of the active and reactive power is nearly negligible and doesn't exceed 0.1%. 5.1.2 Single-phase-to-ground fault A single phase to ground fault is applied at the connection bus between the wind farm and the 115-kV transmission line at t =30 s for a duration of 140ms. Fig. 9 shows the three phases terminal voltages of PMSG and the input dc voltage to DC-DC boost converter. As shown in Fig. 9, the terminal voltage of PMSG before fault is 0.8 p.u (base 690 V) at a frequency of 40 Hz. During fault, the voltage of faulted phase (Va) collapses to zero with oscillations before recovering the pre-fault value at 30.25 sec. The voltage of the other phases (Vb, Vc) decreases to 0.5 p.u with oscillations before recovering the pre-fault value at 30.25 sec. The pre-fault value of the input dc voltage to converter is 568 V. During fault, the voltage reaches to 250 V with oscillations before recovering the pre-fault value at 30.75 sec. Figure.10 shows the temporal variations of the speed, voltage, active power and reactive power at Bus 1 for different wind farms. As shown in Fig. 10, , the time required of PMSG, SCIG and DFIG wind farms to recover their pre-fault values of speed, voltage, active power and reactive power are approximately 0.25 sec, 1.0 sec and 0.5 sec, respectively. During fault, the speed of PMSG wind farm oscillates reaching 1.1p.u, against 1.02p.u and 1.005p.u for SCIG and DFIG wind farms, respectively. The voltage of faulted phase (Va) of PMSG, SCIG and DFIG wind farms decreases to zero while the other phase voltages (Vb and Vc) of PMSG oscillates reaching 1.01 p.u, against 1.3 p.u and 1.025 p.u for SCIG and DFIG wind farms, respectively. This concludes that the performance of DFIG is also better than SCIG under single-phase-to-ground fault conditions. For SCIG, the pre-fault value of the speed is 1.015 p.u against 1.014 p.u using PSCAD simulator as reported before (Fischer de Toledo 2005). During the fault, the speed reached 1.018 p.u against 1.03 p.u before (Fischer de Toledo 2005). After the fault, the speed is 1.015 p.u against 1.02 p.u (Fischer de Toledo 2005). The pre-fault value of the voltage is 1.0 p.u which is almost of the same value as obtained previously using PSCAD simulator (Fischer de Toledo 2005). After the fault, the voltage decreased to 0.87 p.u (Fischer de Toledo 2005) against the constant voltage value of 1.0 p.u in the present calculation. The pre-fault and the post-fault values of the active and reactive power have the same trend as that reported before (Fischer de Toledo 2005) before, during and after the fault. Generally, the mismatch between the previous and present calculations of the active and reactive power is nearly negligible and doesn't exceed 0.1%. 5.2 Grid-connected Wind-driven systems at variable speed The Grid-connected wind-driven systems of system in Fig. 6 are studied with variable speed wind turbines (Abdel-Salam 2011). The transient behaviour of systems before, during and after three-phase and single-phase to ground faults is studied. During fault, the voltage and the frequency of PMSG are less than the rated values of wind farm (690V, 50Hz). 5.2.1 Three-phase-to-ground fault A three phase to ground fault is applied at the connection bus (bus 3) between the wind farm and the 115-kV transmission line at t =30 s for a duration of 140ms. Fig. 11 shows wind speed, the terminal voltage and frequency of PMSG and the input dc voltage to DC-DC boost converter. As shown in Fig. 11, the terminal voltage of PMSG before fault changes between 0.6 to 1.2 p.u (base 690 V) at a frequency of 33 to 42 Hz when the wind speed changes from 8 to 12 m/sec. During fault, the voltage and frequency of PMSG collapse to zero with oscillations before recovering their pre-fault values at 30.25 sec. The input dc voltage to converter before fault
  • 7. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 changes between 270 to 610 V. During fault, the dc voltage reaches zero with oscillations before recovering the pre-fault value at 30.75 sec. Figure.12 shows the temporal variations of the speed, voltage, active power and reactive power at Bus 1. As shown in Fig. 12, the speed of PMSG wind farm changes in the range 0.8 to 1.2 p.u against 0.65 to 1.065 p.u for DFIG wind farm. However, the speed of SCIG wind farm is 1p.u with spike at wind speed changes. Also, the voltage of PMSG wind farm is value 1 p.u, against 1.0 p.u and 1.05 p.u for SCIG and DFIG wind farms respectively. Moreover, the voltage of SCIG wind farm spikes at wind speed changes. The time required of PMSG, SCIG and DFIG wind farms to recover their pre-fault values of speed, voltage, active power and reactive power are approximately 0.25 sec, 1.5 sec and 1sec respectively. Again, the performance of DFIG is better than that of SCIG at varying wind speed. 5.2.2 Single-phase-to-ground fault A single phase to ground fault is applied at the connection bus (bus 3) between the wind farm and the 115-kV transmission line at t =30 s for a duration of 140ms. Fig. 13 shows the temporal variations of the speed, the voltage, the active power and the reactive power at Bus 1 As shown in Fig. 13, the speed of PMSG wind farm changes in the range 0.8 to 1.2 p.u against 0.65 to 1.065 p.u for DFIG wind farm. However, the speed of SCIG wind farm is 1p.u with small changes when wind speed changes. Also, the terminal voltage of PMSG wind farm is 1 p.u against 1.0 p.u and 1.05 p.u for SCIG and DFIG wind farms, respectively. However, the voltage of SCIG wind farm shows small change when wind speed changes. The times required of PMSG, SCIG and DFIG wind farms to recover their pre-fault values of speed, voltage, active power and reactive power are approximately 0.25 sec, 1.0 sec and 0.5 sec, respectively. Different from SCIG, the PMSG and DFIG are not in need for a fixed capacitor to generate the active power, and the grid can easily feed the reactive losses of transmission lines and transformer at any value of SCR (SCR ≥ 1). This increases the dynamic stability of DFIG and PMSG when compared with SCIG. The active power of PMSG is 1 p.u compared to 0.87 p.u for DFIG and SCIG because some reactive power is absorbed by the IG to generate the active power. The PMSG has the advantage of generating reactive power 0.43 p.u compared to the SCIG which is in shortage of the reactive power by 0.365p.u. On the other hand the DFIG absorbs zero reactive power, before fault (Mittal 2009). During the fault, the speed of PMSG oscillates higher than DFIG and SCIG by approximately 10% due to flux oscillations required to feed the reactive power. This is because the speed is inversely proportional to flux (Hong-Woo 2010). Also, the PMSG has higher inertia being of larger weight when compared to DFIG and SCIG with a subsequent lower speed for PMSG (Mittal 2009). Due to flux oscillations during fault, the voltage of PMSG oscillates to 3 p.u, which is higher than the corresponding voltages of DFIG and SCIG. 6. Conclusions 1) Different from SCIG, the PMSG and DFIG are not in need for a fixed capacitor to generate the active power, and the grid can easily feed the reactive losses of transmission lines and transformer at any value of SCR (SCR ≥ 1). This increases the dynamic stability of DFIG and PMSG when compared with SCIG. 2) During fault, the SCIG draws higher reactive power of -3.65p.u against -1.5p.u for the reactive power of DFIG and 0p.u for the reactive power of PMSG. 3) For the three-phase-to-ground fault, the time required to recover stability is approximately 0.25 sec for PMSG wind farm compared to 1 sec for DFIG wind farm and 1.5 sec for SCIG wind farm. 4) For the single-phase-to-ground fault, the time required to recover stability is approximately 0.25 sec for PMSG wind farm compared to 0.5 sec for DFIG wind farm and 1.0 sec for SCIG wind farm. 5) PMSG wind farm is more stable than DFIG and SCIG wind farms because the time required for PMSG wind farm to recover the stability is shorter than those of DFIG and SCIG wind farms for fixed and variable speeds. 6) The performance of DFIG is better than SCIG under three-phase-to-ground fault and single-phase-to-ground fault conditions. 7. Appendix
  • 8. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 Detailed description of input data to model the system in MATLAB/SIMULINK 115 kV Transmission line data: Length of line = 70 km R1 =0.0739 ohm/km, R0 =0.388 ohm/km X L1 =0.449 ohm/km, X L 0 =1.522 ohm/km X C1 =0.272 Mega ohm-km, X C0 =0.427 Mega ohm-km Values: R1, XL1, R0 and XL0 in ohm/km; XC1 and XC0 in Mega ohm-km The SCIG: Generator rating: 1.62 MVA (75 units) Rated RMS line voltage: 690V Stator resistance: 0.0025 p.u Cage resistance: 0.0025 p.u Stator unsaturated leakage reactance: 0.7 p.u Mutual unsaturated reactance: 3.434 Rotor unsaturated mutual reactance: 0.7 p.u Frequency: 50 No. of poles pair: 2 Reactive power compensation in the wind farm: 34 MVAr. The DFIG Generator rating: 1.62 MVA (75 units) Rated RMS line voltage: 690V Stator resistance: 0.0025 p.u Rotor resistance: 0.0025 p.u Stator unsaturated leakage reactance: 0.7 p.u Mutual unsaturated reactance: 3.434 Rotor unsaturated mutual reactance: 0.7 p.u Frequency: 50 No. of poles pair: 2 The PMSG: Generator rating: 1.62 MVA (75 units) Rated RMS line voltage: 690V d-axis inductance : 0.7 p.u q-axis inductance: 0.7 p.u Rotor resistance: 0.0025 p.u Frequency: 50 No. of poles pair: 4 Each Wind farm transformer: Rating: 1.6 MVA Winding voltages: 10.5/0.69
  • 9. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 Leakage reactance: 0.0626 No-load losses and cooper losses: 0.0017 17 and 0.0002 Magnetizing current: 0.3 68 Step up transformer: Rating: 150 MVA Winding voltages: 10.5/115 kV Leakage reactance: 0.06 No-load losses and cooper losses: 0.0017 and 0.0002 Magnetizing current: 0.3 68 Load connected at the end terminal of the line: 100 MW System connected at the end terminal of the line: Short Circuit Power: 2000 MVA, impedance angle 80° References Abbey, C., Khodabakhchian, B., Zhou, F., Dennetière, S., Mahseredjian, J., and Joos, G. (2005), “Transient Modeling and Comparison of Wind Generator Topologies”, Paper No. IPST05, Presented at the International Conference on Power Systems Transients, June 19-23, Montreal, Canada. Abdel-Salam, M., Ahmed, A. and Abdel-Sater, M. (2011), "Harmonic Mitigation, Maximum Power Point Tracking and Dynamic Performance of Variable Speed Grid Connected Wind Turbine", journal of Electric Power Component and Systems, Vol. 39, pp. 176-190. Bhadra, SN., Kastha, D. and Banerjee, S. (2005), Wind electrical systems. Oxford: Oxford University, U.K. Dusonchet, L. and Telaretti, E. (2011), "Effects of electrical and mechanical parameters on the transient voltage stabilityof a fixed speed wind turbine", Electric Power Systems Research, vol. 81, pp 1308–1316. EL-Helw, H.M. and Tennakoon, S.B. (2008), “Evaluation of the suitability of a fixed speed wind turbine for large scale wind farms considering the new UK grid code”, Renewable Energy, vol. 33, pp.1-12. Fischer de Toledo, P. and Hailian, X. (2005), "WIND FARM IN WEAK GRIDS COMPENSATED WITH STATCOM". Proceedings of the Nordic wind power conference, Topic 7, Sweden. Grainger, S.J. and Stevenson, W.D, Jr. (1994), "Power System Analysis", Book, McGraw-Hill, Inc. Hong-Woo, K., Sung-Soo K. and Hee-Sang, K. (2010), “Modeling and control of PMSG-based variable-speed wind turbine”, Electric Power Systems Research, vol. 80, pp 46–52. Kesraoui, M., Bencherouda, O. and Mesbahi, Z., (2010), “Power Control of a PMSG based Wind Turbine System Above Rated Wind Speed”, International Renewable Energy Congress, November 5-7, Sousse, Tunisia. Mathworks (2008a) Inc. SimPowerSystems user’s guide, version 7.6. USA: The Mathworks, Inc. Mittal, R., Sandu, K.S. and Jain, D.K. (2008), “Power Conditioning of Variable Speed Driven PMSG for Wind Energy Conversion Systems”, 2nd WSEAS/IASME International Conference on RENEWABLE ENERGY SOURCES (RES'08), October 26-28, Corfu, Greece. Mittal, R., Sandu, K.S. and Jain, D.K. (2009), "Isolated Operation of Variable Speed Driven PMSG for Wind Energy Conversion System", IACSIT International Journal of Engineering and Technology, Vol. 1, No.3, August, pp 1793-8236. Mohan, N., Undeland, T. and Robbins, W. (1989), "power electronics converters, application and design", Book, John wily and Sons, Inc. Rahim, A.H.M.A. and Habiballah, I.O. (2011), "DFIG rotor voltage control for system dynamic performance enhancement", Electric Power Systems Research, vol. 81, pp 503–509. Sermutlu, E. (2004), "COMPARISON OF RUNGE-KUTTA METHODS OF ORDER 4 AND 5 ON LORENZ EQUATION", Journal of Arts and Sciences, May.
  • 10. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 Whei-Min, L., Chih-Ming, H., Ting-Chia, O. and Tai-Ming, C. (2011), " Hybrid intelligent control of PMSG wind generation system using pitch anglecontrol with RBFN", Energy Conversion and Management, vol. 52, pp1244–1251. Zhanfeng, S., Changliang, X. and Tingna, S. (2010), “Assessing transient response of DFIG based wind turbines during voltage dips regarding main flux saturation and rotor deep-bar effect”, Applied Energy, vol. 87, pp. 3283–3293. Figure 1. Grid-connected Wind-driven Permanent Magnet Synchronous Generator System
  • 11. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 L Diode Vdc Q Co Vdo g PI controllers Vref Figure 2. Switch mode DC-DC converter and DC-DC boost converter and its control
  • 12. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3
  • 13. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 Figure 3. Flow chart of PMSG system modeling Figure 4. Grid-connected Wind-driven Squirrel Cage Induction Generator System Figure 5. Grid-connected Wind-driven Doubly-Fed Induction Generator System
  • 14. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 a. PMSG b. SCIG c. DFIG Figure 6. Network model
  • 15. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 1.5 1000 Terminal voltage of PMSG (p.u) 1 800 0.5 600 Vdc (V) 0 400 -0.5 200 -1 -1.5 0 29.5 30 30.5 31 31.5 32 29.5 30 30.5 31 31.5 32 Time (sec) Time (sec) Figure 7. Terminal voltage of PMSG and dc voltage of converter. 3 PMSG PMSG 1.05 DFIG 2.5 DFIG SCIG SCIG 2 Speed (p.u) V (p.u) 1 1.5 1 0.95 0.5 0.9 0 30 31 32 33 34 30 31 32 33 Time (sec) Time (sec) 1.5 1.5 PMSG PMSG 1 DFIG DFIG 1 0.5 SCIG SCIG 0 0.5 P (p.u) Q (p.u) -0.5 0 -1 -0.5 -1.5 -2 -1 29.5 30 30.5 31 31.5 32 29.5 30 30.5 31 31.5 32 Time (sec) Time (sec) Figure 8. Temporal variations of the speed, the voltage, the active power and the reactive power at Bus 1 for different wind farms.
  • 16. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 Va Vb 1 1 Terminal voltage of PMSG (p.u) Terminal voltage of PMSG (p.u) 0.5 0.5 0 0 -0.5 -0.5 -1 -1 29.5 30 30.5 31 31.5 32 29.5 30 30.5 31 31.5 32 Time (sec) Time (sec) Vc 600 Terminal voltage of PMSG (p.u)) 1 500 0.5 400 Vdc (V) 0 300 200 -0.5 100 -1 0 29.5 30 30.5 31 31.5 32 29.5 30 30.5 31 31.5 32 Time (sec) Time (sec) Figure 9. Three phases terminal voltages of PMSG and the input dc voltage to converter. 1.1 1.5 PMSG PMSG DFIG DFIG 1.05 SCIG SCIG 1 Speed (p.u) V (p.u) 1 0.5 0.95 0.9 29.5 30 30.5 31 31.5 32 0 29.5 30 30.5 31 31.5 32 Time (sec) Time (sec) 2 1.5 PMSG PMSG DFIG 1 DFIG 1 SCIG SCIG 0.5 Q (p.u) P (p.u) 0 0 -1 -0.5 -2 -1 30 31 32 33 29.5 30 30.5 31 31.5 32 Time (sec) Time (sec) Figure 10. Temporal variations of the speed, the voltage, the active power and the reactive power at Bus 1 for different wind farm
  • 17. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 15 1.5 Terminal voltage of PMSG (p.u) 1 Wind speed (m/sec) 0.5 10 0 -0.5 -1 5 -1.5 0 10 20 30 40 50 0 10 20 30 40 50 Time (sec) Time (sec) 700 50 600 Frequency of PMSG (Hz) 40 500 30 400 Vdc (V) 300 20 200 10 100 0 0 0 10 20 30 40 50 0 10 20 30 40 50 Time (sec0 Time (sec) Figure 11. Wind speed, the terminal voltage and frequency of PMSG and the input dc voltage to converter. 3.5 1.4 PMSG PMSG DFIG 3 DFIG SCIG SCIG 2.5 1.2 Speed (p.u) 2 V (p.u) 1 1.5 1 0.8 0.5 0.6 0 0 10 20 30 40 50 0 10 20 30 40 50 Time (sec) Time (sec)
  • 18. Innovative Systems Design and Engineering www.iiste.org ISSN 2222-1727 (Paper) ISSN 2222-2871 (Online) Vol 2, No 3 1.5 1.5 PMSG PMSG 1 DFIG 1 DFIG 0.5 SCIG SCIG 0 0.5 P (p.u) Q (p.u) -0.5 0 -1 -0.5 -1.5 -2 -1 0 10 20 30 40 50 10 20 30 40 50 Time (sec) Time (sec) Figure 12. Temporal variations of the speed, voltage, active power and reactive power at Bus 1 1.6 PMSG 1.5 PMSG 1.4 DFIG DFIG SCIG SCIG Speed (p.u) 1.2 1 V (p.u) 1 0.5 0.8 0.6 0 10 20 30 40 50 0 0 10 20 30 40 50 Time (sec) Time (sec) 1.5 1 PMSG PMSG 1 DFIG DFIG SCIG SCIG 0.5 0.5 0 Q (p.u) Q (p.u) -0.5 0 -1 -1.5 -2 -0.5 0 10 20 30 40 50 0 10 20 30 40 50 Time (sec) Time (sec) Figure 13. Temporal variations of the speed, the voltage, the active power and the reactive power at Bus 1