21 x lighting points
12 x double 10 A socket-outlets
1 x 15 A socket-outlet
1 x 230 V, 6.0 kW oven
1 x 230 V, 2.4 kW insta...
Load       Description      Current       Calculation   Demand
Group       of load         allowance                   cur...
Load       Description      Current       Calculation   Demand
Group       of load         allowance                   cur...
Load       Description      Current       Calculation   Demand
Group       of load         allowance                   cur...
Load       Description      Current       Calculation   Demand
Group       of load         allowance                   cur...
Load       Description      Current       Calculation   Demand
Group       of load         allowance                   cur...
Load       Description      Current       Calculation   Demand
Group       of load         allowance                   cur...
Load       Description      Current       Calculation   Demand
Group       of load         allowance                   cur...
4.1.1 Example Single
4.1.1 Example Single
4.1.1 Example Single
4.1.1 Example Single
4.1.1 Example Single
4.1.1 Example Single
4.1.1 Example Single
Upcoming SlideShare
Loading in …5
×

4.1.1 Example Single

537 views

Published on

Published in: Travel, Business
0 Comments
0 Likes
Statistics
Notes
  • Be the first to comment

  • Be the first to like this

No Downloads
Views
Total views
537
On SlideShare
0
From Embeds
0
Number of Embeds
3
Actions
Shares
0
Downloads
2
Comments
0
Likes
0
Embeds 0
No embeds

No notes for slide

4.1.1 Example Single

  1. 1. 21 x lighting points 12 x double 10 A socket-outlets 1 x 15 A socket-outlet 1 x 230 V, 6.0 kW oven 1 x 230 V, 2.4 kW instantaneous water heater
  2. 2. Load Description Current Calculation Demand Group of load allowance current (column 1) (given list) per unit (Amps) (column 2) 21 lighting 3A 3+2 5.0 A (i) points 12 double 10 A (1st 20) 10 + 5 15.0 outlets 5 A (next 20) B (i) (equivalent 24 sockets) 15 single-phase 10 A None 10.0 B (ii) outlets 50% (6000 / 240) x 12.5 C Oven rating (or x 0.5) 0.5 E Instantaneous 33.3 % (2400 / 240) x 3.33 HWS (or x 0.33) 0.33 Total demand current = 45.83 A
  3. 3. Load Description Current Calculation Demand Group of load allowance current (column 1) (given list) per unit (Amps) (column 2) 21 lighting 3A 3+2 5.0 A (i) points 12 double 10 A (1st 20) 10 + 5 15.0 outlets 5 A (next 20) B (i) (equivalent 24 sockets) 15 single-phase 10 A None 10.0 B (ii) outlets 50% (6000 / 240) x 12.5 C Oven rating (or x 0.5) 0.5 E Instantaneous 33.3 % (2400 / 240) x 3.33 HWS (or x 0.33) 0.33 Total demand current = 45.83 A
  4. 4. Load Description Current Calculation Demand Group of load allowance current (column 1) (given list) per unit (Amps) (column 2) 21 lighting 3A 3+2 5.0 A (i) points 12 double 10 A (1st 20) 10 + 5 15.0 outlets 5 A (next 20) B (i) (equivalent 24 sockets) 15 single-phase 10 A None 10.0 B (ii) outlets 50% (6000 / 240) x 12.5 C Oven rating (or x 0.5) 0.5 E Instantaneous 33.3 % (2400 / 240) x 3.33 HWS (or x 0.33) 0.33 Total demand current = 45.83 A
  5. 5. Load Description Current Calculation Demand Group of load allowance current (column 1) (given list) per unit (Amps) (column 2) 21 lighting 3A 3+2 5.0 A (i) points 12 double 10 A (1st 20) 10 + 5 15.0 outlets 5 A (next 20) B (i) (equivalent 24 sockets) 15 single-phase 10 A None 10.0 B (ii) outlets 50% (6000 / 240) x 12.5 C Oven rating (or x 0.5) 0.5 E Instantaneous 33.3 % (2400 / 240) x 3.33 HWS (or x 0.33) 0.33 Total demand current = 45.83 A
  6. 6. Load Description Current Calculation Demand Group of load allowance current (column 1) (given list) per unit (Amps) (column 2) 21 lighting 3A 3+2 5.0 A (i) points 12 double 10 A (1st 20) 10 + 5 15.0 outlets 5 A (next 20) B (i) (equivalent 24 sockets) 15 single-phase 10 A None 10.0 B (ii) outlets 50% (6000 / 240) x 12.5 C Oven rating (or x 0.5) 0.5 E Instantaneous 33.3 % (2400 / 240) x 3.33 HWS (or x 0.33) 0.33 Total demand current = 45.83 A
  7. 7. Load Description Current Calculation Demand Group of load allowance current (column 1) (given list) per unit (Amps) (column 2) 21 lighting 3A 3+2 5.0 A (i) points 12 double 10 A (1st 20) 10 + 5 15.0 outlets 5 A (next 20) B (i) (equivalent 24 sockets) 15 single-phase 10 A None 10.0 B (ii) outlets 50% (6000 / 240) x 12.5 C Oven rating (or x 0.5) 0.5 E Instantaneous 33.3 % (2400 / 240) x 3.33 HWS (or x 0.33) 0.33 Total demand current = 45.83 A
  8. 8. Load Description Current Calculation Demand Group of load allowance current (column 1) (given list) per unit (Amps) (column 2) 21 lighting 3A 3+2 5.0 A (i) points 12 double 10 A (1st 20) 10 + 5 15.0 outlets 5 A (next 20) B (i) (equivalent 24 sockets) 15 single-phase 10 A None 10.0 B (ii) outlets 50% (6000 / 240) x 12.5 C Oven rating (or x 0.5) 0.5 E Instantaneous 33.3 % (2400 / 240) x 3.33 HWS (or x 0.33) 0.33 Total demand current = 45.83 A

×