                                INSTALLATION AND SETUP GUIDE

GENERAL INFORMATION                                                 WIRING AND INSTALLATION
The ADEMCO 6460S (silver) and 6460W (white) are                     The keypads can be surface mounted directly to a drywall,
addressable Remote Keypads designed for use with                    or to a single- or double-gang electrical box.
Honeywell's ADEMCO series control panels. Addresses are             1. Push the two case release snaps at the bottom of the
set via the keypad keys.                                                keypad with the blade of a medium screwdriver (this will
The keys on the keypad are continuously backlit for                     push in the release snap), then pull that side of the case
convenience.                                                            back away. Refer to Figure 1 for location of the case back
NOTE: If supported, the ADEMCO 6460S and 6460W                          release snaps.
keypads are supervised by the control panel.                        2. Route wiring from the control panel through the opening
                                                                        in the case back.
KEYPAD DISPLAYS AND LEDS                                            3. Mount the case back to a wall or electrical box.
The ADEMCO 6460S and 6460W keypads have the                         4. Wire directly from the keypad’s terminal block to the
following display features:                                             terminal block on the control panel. (See Wiring Table
      • 2-line Alpha Display                                            below).
      • Custom Zone Descriptors
      • Built-in Speaker Sounder                                    NOTE: No more than one wire per terminal may be
      • Dedicated Function Keys                                       connected. If daisy-chained configuration is required,
                                                                      pig-tail wires together so that only one wire is
       • Backlit Display (permanent display backlighting is           terminated under the screw. Use 16-22 AWG wire only!
         an option on some controls; see the control's
         instructions for details).                                 Wiring Table
                                                                         Keypad                                      Control Panel         Wire Color
The following table shows the LEDs and their functions:                   LG                                         Data In               Green
   LED                            Function                                –                                          – Aux Pwr (GND)       Black
 Red         Lights when the system is armed in any mode                  +                                          + Aux. Pwr            Red
 Green       Lights when the system is "ready" to be armed.               MY                                         Data Out              Yellow
                                                                          See the control panel’s Installation and Setup Guide for
                                                                          more complete details.
SPECIAL FUNCTION KEYS                                               5. Reattach the keypad to its case back.
The keypads also feature function keys. These keys may be             A    B                                         C   D
programmed for panic alarms or other special functions
such as macros. See the control's instructions for details.

            Function keys must be held down for at least 2
            seconds to activate an alarm; key pairs are activated
            immediately.
                                                                              ARMED   1           2 ABC   3 DEF
                                                                                        OFF        AWAY     STAY
                                                                              READY
                                                                                      4 GH I      5 JKL   6 MNO
                       Function Keys
                                                                                        MAX        TEST   BYPASS


                                                                                      7PQRS       8 TUV   9 WXYZ
                                                                                      INS TAN T    CODE    CH I ME



                       A or [1] and [6]                                               *   END
                                                                                      R EADY
                                                                                                  0       # NUM


                       B or [6] and [#]
                                                                    NOTE:
                       C or [3] and [#]                             TO REMOVE CASE BACK
                                                                    PUSH IN THE TWO RELEASE
                       D                                            SNAPS LOCATED ALONG THE
                                                                    BOTTOM OF THE KEYPAD
                                                                    AND LIFT UP.
                                                                                                               RELEASE
                                                                                                                 SNAPS
                                                                                                                                                        6460S-001-V1


                                                                                                  Figure 1. Removing the Case Back
SETTING THE KEYPAD ADDRESS                                             FUNCTION KEY LABELS
                                                                       A set of adhesive-backed labels with some typical function
The keypad can either be set for an address of 00-30, or to            symbols (i.e., fire, police, personal emergency, etc.) is
the non-addressable mode (31). The keypad's default                    provided. These labels can be placed on or next to the keys
address is 31.                                                         to identify each key's function for the end user (as
To change the keypad's address, do the following:                      determined by the control panel's capability and
1. Enter address mode: Power up the keypad. Within 60                  programming; see the control's instructions).
   seconds of power-up, press and hold down the [1] and [3]
   keys at the same time for 3 seconds. (If unable to enter
                                                                       OPERATING THE KEYPAD
   address mode, power up and try again.)
                                                                       For operating instructions, see the User Guide for the
   The current keypad address will be displayed, and the
                                                                       control panel used with this keypad.
   cursor will be under the "tens" digit. If 10 seconds have
   passed with no key entry, the keypad automatically exits            SPECIFICATIONS
   address mode. You must power down, power up and                     Physical:       5-9/16"H x 6-3/4"W x 1"D
   start address mode again.
   NOTE: The keypad will not enter address mode if the
                                                                       Displays:       2 x 16 alpha-numeric supertwist LCD,
   panel to which it is connected is in programming mode.
                                                                                       backlit.
2. Set the current address to "00": Press [0] to clear the
   current "tens" digit. The cursor will move to the "ones"
   digit position. Press [0] to clear the current "ones" digit.        Sounder:        Speaker.
   The cursor will move back to the "tens" digit position.
                                                                       Voltage:        12VDC (power-limited)
3. Enter the keypad's address: Enter the proper "tens" digit
   of the keypad's address. The cursor will move to the
                                                                       Current:        150mA in alarm (ARMED LED lit, LCD
   "ones" digit position. Enter the proper "ones" digit of the
                                                                                       backlight and sounder on), reduces to 40mA
   keypad's address. Note that address "31" sets the
                                                                                       when panel is operating in standby mode
   keypad to non-addressable mode.
                                                                                       (backlight off).
4. Exit address mode:
   Press [6] to save the displayed address and exit address            NFPA-72 Compliant.
   mode.
VIEWING THE KEYPAD ADDRESS
Press and hold down the [1] and [3] keys at the same time
for about 3 seconds. The current address is displayed. No
key entry is allowed. Press any key to exit or wait 10
seconds to exit viewing mode.


  REFER TO INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR WARRANTY
  INFORMATION AND LIMITATIONS OF THE ENTIRE ALARM SYSTEM.




                                                2 Corporate Center Drive, Suite 100
                                                 P.O. Box 9040, Melville, NY 11747
                                             Copyright! 2009 Honeywell International Inc.
                                                    www.security.honeywell.com

Ê800-03612rŠ
800-03612 1/09 Rev. C

More Related Content

More from Alarm Grid

Leviton vri10 1 lz product manual and setup guide
Leviton vri10 1 lz product manual and setup guideLeviton vri10 1 lz product manual and setup guide
Leviton vri10 1 lz product manual and setup guide
Alarm Grid
 
Leviton vri06 1 lz product manual and setup guide
Leviton vri06 1 lz product manual and setup guideLeviton vri06 1 lz product manual and setup guide
Leviton vri06 1 lz product manual and setup guide
Alarm Grid
 
Leviton vrf01 1 lz product manual and setup guide
Leviton vrf01 1 lz product manual and setup guideLeviton vrf01 1 lz product manual and setup guide
Leviton vrf01 1 lz product manual and setup guide
Alarm Grid
 
Leviton vre06 1 lz
Leviton vre06 1 lzLeviton vre06 1 lz
Leviton vre06 1 lz
Alarm Grid
 
Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specificationsLeviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
Alarm Grid
 
Leviton vrcz4 1 l, vrcs4-1l, vrcz1-1l, vrcs1-1l and vrmr1-osg product specifi...
Leviton vrcz4 1 l, vrcs4-1l, vrcz1-1l, vrcs1-1l and vrmr1-osg product specifi...Leviton vrcz4 1 l, vrcs4-1l, vrcz1-1l, vrcs1-1l and vrmr1-osg product specifi...
Leviton vrcz4 1 l, vrcs4-1l, vrcz1-1l, vrcs1-1l and vrmr1-osg product specifi...
Alarm Grid
 
Leviton vrcz1 installation manual and setup guide
Leviton vrcz1 installation manual and setup guideLeviton vrcz1 installation manual and setup guide
Leviton vrcz1 installation manual and setup guide
Alarm Grid
 
Leviton vrcs1 1 l
Leviton vrcs1 1 lLeviton vrcs1 1 l
Leviton vrcs1 1 l
Alarm Grid
 
Leviton vp00 r 10z, vp00r-1lz, vp0sr-10z, vp0sr-1lz installation manual and s...
Leviton vp00 r 10z, vp00r-1lz, vp0sr-10z, vp0sr-1lz installation manual and s...Leviton vp00 r 10z, vp00r-1lz, vp0sr-10z, vp0sr-1lz installation manual and s...
Leviton vp00 r 10z, vp00r-1lz, vp0sr-10z, vp0sr-1lz installation manual and s...
Alarm Grid
 
Leviton dimmers, switches and fan speed controllers
Leviton dimmers, switches and fan speed controllersLeviton dimmers, switches and fan speed controllers
Leviton dimmers, switches and fan speed controllers
Alarm Grid
 
Fluorescent dimmer for hi lume or eco-10 ballasts
Fluorescent dimmer for hi lume or eco-10 ballastsFluorescent dimmer for hi lume or eco-10 ballasts
Fluorescent dimmer for hi lume or eco-10 ballasts
Alarm Grid
 
Controlling z wave door locks with the vrc0 p
Controlling z wave door locks with the vrc0 pControlling z wave door locks with the vrc0 p
Controlling z wave door locks with the vrc0 p
Alarm Grid
 
Vizia rf+ collection
Vizia rf+ collectionVizia rf+ collection
Vizia rf+ collection
Alarm Grid
 
Honeywell lynxrchkit-sc-honeywell-lynxyrchkit-hc-honeywell-lynxrchkit-sha-ins...
Honeywell lynxrchkit-sc-honeywell-lynxyrchkit-hc-honeywell-lynxrchkit-sha-ins...Honeywell lynxrchkit-sc-honeywell-lynxyrchkit-hc-honeywell-lynxrchkit-sha-ins...
Honeywell lynxrchkit-sc-honeywell-lynxyrchkit-hc-honeywell-lynxrchkit-sha-ins...
Alarm Grid
 

More from Alarm Grid (20)

Leviton vri10 1 lz product manual and setup guide
Leviton vri10 1 lz product manual and setup guideLeviton vri10 1 lz product manual and setup guide
Leviton vri10 1 lz product manual and setup guide
 
Leviton vri06 1 lz product manual and setup guide
Leviton vri06 1 lz product manual and setup guideLeviton vri06 1 lz product manual and setup guide
Leviton vri06 1 lz product manual and setup guide
 
Leviton vrf01 1 lz product manual and setup guide
Leviton vrf01 1 lz product manual and setup guideLeviton vrf01 1 lz product manual and setup guide
Leviton vrf01 1 lz product manual and setup guide
 
Leviton vre06 1 lz
Leviton vre06 1 lzLeviton vre06 1 lz
Leviton vre06 1 lz
 
Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specificationsLeviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
 
Leviton vrcz4 1 l, vrcs4-1l, vrcz1-1l, vrcs1-1l and vrmr1-osg product specifi...
Leviton vrcz4 1 l, vrcs4-1l, vrcz1-1l, vrcs1-1l and vrmr1-osg product specifi...Leviton vrcz4 1 l, vrcs4-1l, vrcz1-1l, vrcs1-1l and vrmr1-osg product specifi...
Leviton vrcz4 1 l, vrcs4-1l, vrcz1-1l, vrcs1-1l and vrmr1-osg product specifi...
 
Leviton vrcz1 installation manual and setup guide
Leviton vrcz1 installation manual and setup guideLeviton vrcz1 installation manual and setup guide
Leviton vrcz1 installation manual and setup guide
 
Leviton vrcs1 1 l
Leviton vrcs1 1 lLeviton vrcs1 1 l
Leviton vrcs1 1 l
 
Leviton vp00 r 10z, vp00r-1lz, vp0sr-10z, vp0sr-1lz installation manual and s...
Leviton vp00 r 10z, vp00r-1lz, vp0sr-10z, vp0sr-1lz installation manual and s...Leviton vp00 r 10z, vp00r-1lz, vp0sr-10z, vp0sr-1lz installation manual and s...
Leviton vp00 r 10z, vp00r-1lz, vp0sr-10z, vp0sr-1lz installation manual and s...
 
Leviton dimmers, switches and fan speed controllers
Leviton dimmers, switches and fan speed controllersLeviton dimmers, switches and fan speed controllers
Leviton dimmers, switches and fan speed controllers
 
Fluorescent dimmer for hi lume or eco-10 ballasts
Fluorescent dimmer for hi lume or eco-10 ballastsFluorescent dimmer for hi lume or eco-10 ballasts
Fluorescent dimmer for hi lume or eco-10 ballasts
 
Controlling z wave door locks with the vrc0 p
Controlling z wave door locks with the vrc0 pControlling z wave door locks with the vrc0 p
Controlling z wave door locks with the vrc0 p
 
Vizia rf+ collection
Vizia rf+ collectionVizia rf+ collection
Vizia rf+ collection
 
Honeywell vista-50p-user-guide
Honeywell vista-50p-user-guideHoneywell vista-50p-user-guide
Honeywell vista-50p-user-guide
 
Honeywell vista-50p-install-guide
Honeywell vista-50p-install-guideHoneywell vista-50p-install-guide
Honeywell vista-50p-install-guide
 
Honeywell vista-50p-connections-summary
Honeywell vista-50p-connections-summaryHoneywell vista-50p-connections-summary
Honeywell vista-50p-connections-summary
 
Honeywell vista-10p-programming-guide
Honeywell vista-10p-programming-guideHoneywell vista-10p-programming-guide
Honeywell vista-10p-programming-guide
 
Honeywell total-connect-video-residential-brochure
Honeywell total-connect-video-residential-brochureHoneywell total-connect-video-residential-brochure
Honeywell total-connect-video-residential-brochure
 
Honeywell lynxrchkit-sc-honeywell-lynxyrchkit-hc-honeywell-lynxrchkit-sha-ins...
Honeywell lynxrchkit-sc-honeywell-lynxyrchkit-hc-honeywell-lynxrchkit-sha-ins...Honeywell lynxrchkit-sc-honeywell-lynxyrchkit-hc-honeywell-lynxrchkit-sha-ins...
Honeywell lynxrchkit-sc-honeywell-lynxyrchkit-hc-honeywell-lynxrchkit-sha-ins...
 
Honeywell l5100-programming-guide
Honeywell l5100-programming-guideHoneywell l5100-programming-guide
Honeywell l5100-programming-guide
 

Honeywell 6460-install-guide

  • 1. 800-03612 1/09 Rev. C 6460S/6460W ADEMCO 6460S/6460W REMOTE KEYPAD INSTALLATION AND SETUP GUIDE GENERAL INFORMATION WIRING AND INSTALLATION The ADEMCO 6460S (silver) and 6460W (white) are The keypads can be surface mounted directly to a drywall, addressable Remote Keypads designed for use with or to a single- or double-gang electrical box. Honeywell's ADEMCO series control panels. Addresses are 1. Push the two case release snaps at the bottom of the set via the keypad keys. keypad with the blade of a medium screwdriver (this will The keys on the keypad are continuously backlit for push in the release snap), then pull that side of the case convenience. back away. Refer to Figure 1 for location of the case back NOTE: If supported, the ADEMCO 6460S and 6460W release snaps. keypads are supervised by the control panel. 2. Route wiring from the control panel through the opening in the case back. KEYPAD DISPLAYS AND LEDS 3. Mount the case back to a wall or electrical box. The ADEMCO 6460S and 6460W keypads have the 4. Wire directly from the keypad’s terminal block to the following display features: terminal block on the control panel. (See Wiring Table • 2-line Alpha Display below). • Custom Zone Descriptors • Built-in Speaker Sounder NOTE: No more than one wire per terminal may be • Dedicated Function Keys connected. If daisy-chained configuration is required, pig-tail wires together so that only one wire is • Backlit Display (permanent display backlighting is terminated under the screw. Use 16-22 AWG wire only! an option on some controls; see the control's instructions for details). Wiring Table Keypad Control Panel Wire Color The following table shows the LEDs and their functions: LG Data In Green LED Function – – Aux Pwr (GND) Black Red Lights when the system is armed in any mode + + Aux. Pwr Red Green Lights when the system is "ready" to be armed. MY Data Out Yellow See the control panel’s Installation and Setup Guide for more complete details. SPECIAL FUNCTION KEYS 5. Reattach the keypad to its case back. The keypads also feature function keys. These keys may be A B C D programmed for panic alarms or other special functions such as macros. See the control's instructions for details. Function keys must be held down for at least 2 seconds to activate an alarm; key pairs are activated immediately. ARMED 1 2 ABC 3 DEF OFF AWAY STAY READY 4 GH I 5 JKL 6 MNO Function Keys MAX TEST BYPASS 7PQRS 8 TUV 9 WXYZ INS TAN T CODE CH I ME A or [1] and [6] * END R EADY 0 # NUM B or [6] and [#] NOTE: C or [3] and [#] TO REMOVE CASE BACK PUSH IN THE TWO RELEASE D SNAPS LOCATED ALONG THE BOTTOM OF THE KEYPAD AND LIFT UP. RELEASE SNAPS 6460S-001-V1 Figure 1. Removing the Case Back
  • 2. SETTING THE KEYPAD ADDRESS FUNCTION KEY LABELS A set of adhesive-backed labels with some typical function The keypad can either be set for an address of 00-30, or to symbols (i.e., fire, police, personal emergency, etc.) is the non-addressable mode (31). The keypad's default provided. These labels can be placed on or next to the keys address is 31. to identify each key's function for the end user (as To change the keypad's address, do the following: determined by the control panel's capability and 1. Enter address mode: Power up the keypad. Within 60 programming; see the control's instructions). seconds of power-up, press and hold down the [1] and [3] keys at the same time for 3 seconds. (If unable to enter OPERATING THE KEYPAD address mode, power up and try again.) For operating instructions, see the User Guide for the The current keypad address will be displayed, and the control panel used with this keypad. cursor will be under the "tens" digit. If 10 seconds have passed with no key entry, the keypad automatically exits SPECIFICATIONS address mode. You must power down, power up and Physical: 5-9/16"H x 6-3/4"W x 1"D start address mode again. NOTE: The keypad will not enter address mode if the Displays: 2 x 16 alpha-numeric supertwist LCD, panel to which it is connected is in programming mode. backlit. 2. Set the current address to "00": Press [0] to clear the current "tens" digit. The cursor will move to the "ones" digit position. Press [0] to clear the current "ones" digit. Sounder: Speaker. The cursor will move back to the "tens" digit position. Voltage: 12VDC (power-limited) 3. Enter the keypad's address: Enter the proper "tens" digit of the keypad's address. The cursor will move to the Current: 150mA in alarm (ARMED LED lit, LCD "ones" digit position. Enter the proper "ones" digit of the backlight and sounder on), reduces to 40mA keypad's address. Note that address "31" sets the when panel is operating in standby mode keypad to non-addressable mode. (backlight off). 4. Exit address mode: Press [6] to save the displayed address and exit address NFPA-72 Compliant. mode. VIEWING THE KEYPAD ADDRESS Press and hold down the [1] and [3] keys at the same time for about 3 seconds. The current address is displayed. No key entry is allowed. Press any key to exit or wait 10 seconds to exit viewing mode. REFER TO INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE ALARM SYSTEM. 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright! 2009 Honeywell International Inc. www.security.honeywell.com Ê800-03612rŠ 800-03612 1/09 Rev. C