1. ED34-862 Specifications
2. Specifications
2.1 FXDQ-PB
Slim Ceiling Mounted Duct Type (VE: with Drain Pump, VET without Drain Pump)
Model FXDQ20PBVE (T) FXDQ25PBVE (T) FXDQ32PBVE (T)
kcal/h 2,000 2,500 3,200
★1 Cooling Capacity (19.5°CWB) Btu/h 7,800 9,900 12,600
kW 2.3 2.9 3.7
★2 Cooling Capacity (19.0°CWB) kW 2.2 2.8 3.6
Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D)
Coil (Cross Rows×Stages×Fin Pitch
mm
mm
200×700×620
2×12×1.5
200×700×620
2×12×1.5
200×700×620
3×12×1.5
5
Fin Coil) Face Area m² 0.126 0.126 0.126
Model — — —
Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output × Number W 62×1 62×1 62×1
Fan of Units
Air Flow Rate (HH/H/L) m³/min 8.0/7.2/6.4 8.0/7.2/6.4 8.0/7.2/6.4
★4 External Static Pressure Pa 30-10 30-10 30-10
Drive Direct Drive Direct Drive Direct Drive
Temperature Control Microprocessor Thermostat Microprocessor Thermostat Microprocessor Thermostat
for Cooling and Heating for Cooling and Heating for Cooling and Heating
Sound Absorbing Thermal Insulation Material Foamed Polyethylene Foamed Polyethylene Foamed Polyethylene
Air Filter Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ6.4 (Flare Connection)
Piping Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ12.7 (Flare Connection)
Connections
Drain Pipe mm VP20 VP20 VP20
(External Dia. 26 Internal Dia. 20) (External Dia. 26 Internal Dia. 20) (External Dia. 26 Internal Dia. 20)
Machine Weight (Mass) kg 23 23 23
★5 Sound Pressure Level (HH/H/L) dBA 33/31/29 33/31/29 33/31/29
Safety Devices Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Operation Manual, Operation Manual, Operation Manual,
Installation Manual, Installation Manual, Installation Manual,
Drain Hose, Sealing Pads, Clamps, Drain Hose, Sealing Pads, Clamps, Drain Hose, Sealing Pads, Clamps,
Standard Accessories Washers, Insulation for Fitting, Washers, Insulation for Fitting, Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate, Clamp Metal, Washer Fixing Plate, Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter, Screws for Duct Flanges, Air Filter, Screws for Duct Flanges, Air Filter,
(Product Quality Certificate ★6) (Product Quality Certificate ★6) (Product Quality Certificate ★6)
Drawing No. 3D060921A
Note:
Conversion Formulae
★1 Indoor temp.: 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
★2 Indoor temp.: 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
★4 External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard static pressure”.
(Factory setting is 10 Pa.)
★5 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to be larger than the specified values
due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
★6 FXDQ20 / 25 / 32PBVE only.
7 Refer to page 176 for Fan Motor Input.
Please purchase /PDF Split-Merge on www.verypdf.com to remove this watermark.
FXDQ-PB FXDQ-NB 165
2. Specifications ED34-862
2.2 FXDQ-NB
Slim Ceiling Mounted Duct Type (VE: with Drain Pump, VET without Drain Pump)
Model FXDQ40NBVE(T) FXDQ50NBVE(T) FXDQ63NBVE(T)
kcal/h 4,000 5,000 6,300
★1 Cooling Capacity (19.5°CWB) Btu/h 16,000 19,800 24,900
kW 4.7 5.8 7.3
★2 Cooling Capacity (19.0°CWB) kW 4.5 5.6 7.1
Casing Color Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) mm 200×900×620 200×900×620 200×1100×620
Coil (Cross Rows×Stages×Fin Pitch mm 3×12×1.5 3×12×1.5 3×12×1.5
Fin Coil) Face Area m² 0.176 0.176 0.227
Model — — —
Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output × Number W 62×1 130×1 130×1
Fan of Units
Air Flow Rate (HH/H/L) m³/min 10.5/9.5/8.5 12.5/11.0/10.0 16.5/14.5/13.0
★4 External Static Pressure Pa 44-15 44-15 44-15
Drive Direct Drive Direct Drive Direct Drive
Temperature Control Microprocessor Thermostat Microprocessor Thermostat Microprocessor Thermostat
for Cooling and Heating for Cooling and Heating for Cooling and Heating
Sound Absorbing Thermal Insulation Material Foamed Polyethylene Foamed Polyethylene Foamed Polyethylene
Air Filter Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ9.5 (Flare Connection)
Piping Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ15.9 (Flare Connection)
Connections
Drain Pipe mm VP20 VP20 VP20
(External Dia. 26 Internal Dia. 20) (External Dia. 26 Internal Dia. 20) (External Dia. 26 Internal Dia. 20)
Machine Weight (Mass) kg 27 28 31
★5 Sound Pressure Level (HH/H/L) dBA 34/32/30 35/33/31 36/34/32
Safety Devices Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Operation Manual, Operation Manual, Operation Manual,
Installation Manual, Installation Manual, Installation Manual,
Drain Hose, Sealing Pads, Clamps, Drain Hose, Sealing Pads, Clamps, Drain Hose, Sealing Pads, Clamps,
Standard Accessories Washers, Insulation for Fitting, Washers, Insulation for Fitting, Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate, Clamp Metal, Washer Fixing Plate, Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter, Screws for Duct Flanges, Air Filter, Screws for Duct Flanges, Air Filter,
(Product Quality Certificate ★6) (Product Quality Certificate ★6) (Product Quality Certificate ★6)
Drawing No. 3D060921A
Note:
Conversion Formulae
★1 Indoor temp.: 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
★2 Indoor temp.: 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
★4 External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard static pressure”.
(Factory setting is 15 Pa.)
★5 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to be larger than the specified values
due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
★6 FXDQ40 / 50 / 63NBVE only.
7 Refer to page 176 for Fan Motor Input.
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
166 FXDQ-PB / FXDQ-NB