DK Cable Junction Boxes
DK Cable Junction Boxes
- 1.5 up to 240 mm²
- Degree of protection IP 54-67
- Cable Junction Boxes are VDE tested in accordance with IEC 60670-22
i
Assembling
videos
16
DK Cable Junction Boxes
Content
Criteria for selecting 18 - 19
Box walls 20
Box walls without knockouts
from 1.5 up to 50 mm2
IP 65
box walls without knockouts, can be drilled individually for customized requirements
- without terminals 33 - 34
- without terminals, for electrical equipment up to 63 A 35 - 36
- Accessories 37 - 39
With or without terminals
from 1.5 up to 240 mm2
IP 65/IP 55
cable entry via metric knockouts
- with terminals for copper conductors 24 - 29
- without terminals 30 - 31
With FIXCONNECT®
plug-in technology for copper conductors
from 1.5 up to 16 mm2
IP 65/IP 55
cable entry via metric knockouts 22
For aluminium- (Alu) and copper (Cu) conductors
from 1.5 up to 240 mm2
IP 65/55
cable entry via metric knockouts
- with terminal blocks for aluminium- (Alu) and copper (Cu) conductors 54 - 60
Cable entry via elastic membranes and integrated M20 thread
up to 4 mm2
IP 55
- without terminals 41
- with terminals for copper conductors 41
Cable entry via cable, cable trunking and conduits
from 1.5 up to 4 mm2
IP 54
- with terminals for copper conductors 43
- without terminals, Accessories 44
Cable entry via elastic membranes
from 1.5 up to 4 mm2
IP 55
- with terminals for copper conductors, grey RAL 7035 46
- without terminals, grey RAL 7035 47
- with terminals for copper conductors, white RAL 9016 48
- without terminals, white RAL 9016, Accessories 49
Cable entry via elastic membranes from the rear and by box walls and lid
from 1.5 up to 2.5 mm2
IP 55
for the clip-on attachment
- with terminals for copper conductors, grey RAL 7035 51
- without terminals, grey RAL 7035 51
- with terminals for copper conductors, white RAL 9016 52
- without terminals, white RAL 9016 52
"Weatherproof" - for outdoor installation - harsh environment and/or outdoor
from 1.5 up to 50 mm2
IP 66
cable/conduit entry via metric knockouts
- with / without terminals, colours grey RAL 7032, black RAL 9011 62 - 69
box walls without knockouts
- without terminals, colours grey RAL 7032, black RAL 901 71 - 74
17
DK Cable Junction Boxes
Content
Additional information and planning tools (e.g. CAD parts libraries)
can be found on the Internet at www.hensel-electric.in
"Waterproof" - for outdoor installation - harsh environment and/or outdoor
from 1,5 up to 10 mm2
cable entry via metric knockouts
- for encapsulating, colours grey RAL 7032, black RAL 9011 NEW
80 - 84
Tested for intrinsic fire resistance
from 0.5 up to 16 mm2
IP 65 / IP 66
- material: duroplast, cable entry via included grommets, IP 65 94 - 95, 101
- material: sheet steel, powder-coated, cable entry via mounted grommets, IP 66 96 - 100, 101
For special applications
from 1.5 up to 25 mm2
IP 55 / IP 65
cable entry via metric knockouts
- for security lighting circuits, with red lid 103
- for equipotential bonding conductors 104
With main line branch terminals
from 25 up to 35 mm2
IP 55 / IP 65
cable/conduit entry via metric knockouts
- with terminal blocks for copper conductors 25 mm² and 35 mm² 106 - 107
With terminal blocks for aluminium- (Alu) and copper conductors (Cu)
from 1.5 up to 4 mm2
IP 65
cable/conduit entry via metric knockouts
- Terminal boxes with terminal blocks 109 - 111
Accessories 113 - 121
"Weatherproof" - for outdoor installation - harsh environment and/or outdoor
from 1.5 up to 50 mm2
IP 66 / IP 65 with UL/CSA approval, (Nema 4X)
box walls without knockouts, can be drilled individually
- without terminals 76 - 77
For offshore / heavy duty applications
from 1.5 up to 35 mm2
IP 66 / IP 67
cable entry via metric knockouts
- with / without terminals 86 - 90
box walls without knockouts
- without terminals 91 - 92
Technical Details 123 - 134
18
DK Cable Junction Boxes
Criteria for Selecting
Applications Functions
Branching and
connecting of
copper conduc-
tors
Branching and
connecting of
aluminium and
copper conduc-
tors
 In rooms with dry climate
 In damp and wet environments
 Protected outdoors (refer to technical details)
 On flameable parts of buildings
 In buildings with mainly inflammable materials
 In areas with a high risk of fire
Pages 22-52 Pages 54-60
 Cable trunking installation Pages 43-44
 Intrinsic fire resistance Pages 94-101
 "Waterproof" for encapsulating Pages 80-84
 “Weatherproof”, for outdoor installation (harsh
environment and/or outdoor)
 Improved behaviour in cases of fire
“flame-resistant” and “halogen-free”
Pages 62-74
 Offshore applications Pages 86-92
 Security lighting circuits Page 103
 Equipotential bonding Page 104
 UL Approval Page 76-77
 DNV Approval
 Germanisch Lloyd
 Russian Maritime Register of Shipping
Pages 62-92
PA
19
DK Cable Junction Boxes
Criteria for Selecting
Connecting solid
conductors and
stranded conduc-
tors
Combining multi-
ple control wires
to one control
cable
2 circuits
in one box
Main line branch
terminals
Without terminals Box walls
without
knockouts
Page 54-55
Pages 109-111
Pages 109-111 Pages 43-44
DP 9220,
DP 9221,
DP 9222
Page 106-107 Pages 30-36,
Page 41 DN 2000,
DN 2030,
Page 44, 47
Page 48 DE 9321,
Page 49,
Page 51 DE 9220,
Page 52 DE 9221,
Pages 64-65, 68-69,
71-74, 76-77, 89-92
Page 103 D 9220,
D 9240
Pages 33-36
all Boxes,
Pages 71-74, 76-77
Page 91-92
Pages 43-44
DP 9220,
DP 9221,
DP 9222
Page 44
Pages 64-65
Pages 68-69
Pages 71-74
Pages 71-74
Pages 89-92 Page 91-92
Page 76-77
Pages 64-65, 68-69
Pages 71-74, 89-92
Pages 71-74, 89-92
20
Assignment of box walls:
The assignment of box walls is effected via wall symbols that are
assigned to each product. The individual figures 2 give an indication,
which wall is concerned.
Wand
4
6
5 5
Wall 18
4 x M 25
3 x M 40/50
Wall 19
8 x M 32
4 x M 40/50
Wall 20
2 x M 20
10 x M 25
1 x M 32/40
Wall 21
1 x M 20
4 x M 25
1 x M 32/40
3 x M 40/50
Wall 22
1 x Elastic
membranes
Wall 23
2 x Elastic
membranes
Wall 24
3 x Elastic
membranes
Wall 1
1 x M 20
Wall 2
1 x M 20/25
Wand 3
2 x M 20
Wall 4
2 x M 20/25
Wall 5
1 x M 20/25
1 x M 25/32
Wall 6
2 x M 25/32
Wall 7
2 x M 32
Wall 8
2 x M 32/40
Wall 9
2 x M 40
Wall 10
2 x M 20/25
1 x M 25/32
Wall 11
2 x M 20/25
1 x M 32/40
Wall 12
1 x M 20/25
1 x M 25/32
1 x M 40/50
Wall 13
1 x M 20/25
2 x M 40/50
Wall 14
3 x M 25/32
Wall 15
2 x M 25/32
1 x M 40/50
Wall 16
3 x M 32/40
Wall 17
4 x M 25/32
1 x M 40/50
Wall 25
1 x Removable-
system
Wall 26
2 x Removable-
system
Wall 27
3 x Removable-
system
Wall 28
4 x Removable-
system
DK Cable junction boxes
Box Walls
All box walls are listed in the
fold-out of the coverpages.
Wall 29
1 x M 63
Wall 30
2 x M 50
Wall 31
4 x up to Ø 16 mm
1 x up to Ø 35 mm
21
DK Cable Junction Boxes
with Terminals in Plug-in Technology
Cable Entry via Metric Knockouts
 Plenty of space for the wiring:
Wiring facilities both below the DIN rails
and between the terminals.
 Different conductor types - rigid (r) and
flexible (f) without treatment of conduc-
tors - can be connected in one terminal.
 Conductors can be directly
connected and disconnected with
installed terminal.
 Stainless steel cover screws with quick
fastening metric thread.
Reducing cover fixing time.
 Burning behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 °C,
flame-retardant, self-extinguishing
 Labelling system for circuit description
 Label template on the Internet at
www.hensel-electric.de - in the
’Downloads’ area.
22
DK Cable Junction Boxes
with Terminals in Plug-in Technology
Cable Entry via Metric Knockouts
KC 9045
Wall
10
10
6 5
1.5-4 mm², Cu 3~
 FIXCONNECT®
plug-in terminal technology
 5-pole per pole 4 x 1 x 1,5-4 mm² sol/f, terminal technology,
see annex DK Cable junction boxes
 included cable entry: 4 ESM 25, sealing range Ø 9-17 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 32 A
139
119
70
KC 9255
Wall
16
11
8 8
2.5-10 mm², Cu 3~
 FIXCONNECT®
plug-in terminal technology
 5-pole per pole 4 x 1 x 2.5-10 mm² r/f
 included cable entry: 3 ESM 32, sealing range Ø 9-23 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 50 A
98
160
200
KC 9355
Wall
13
13
15 15
2.5-16 mm², Cu 3~
 FIXCONNECT®
plug-in terminal technology
 5-pole per pole 4 x 1 x 2.5-16 mm² r/f
 included cable entry: 3 ESM 40, sealing range Ø 17-30 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 76 A
117260
210
23
DK Cable Junction Boxes
Cable Entry via Metric Knockouts
 Variable terminal mounting
positions (5 positions) and
new terminal technology
 Included accessories as listed:
grommets ESM = IP 55
 Hensel cable junction boxes can in
general also be used in poor
environmental conditions by using
IP 65 cable glands AKM/ASM.
 Stainless steel cover screws with quick
fastening metric thread.
Reducing cover fixing time.
 Burning behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 °C / 960 °C,
flame-retardant, self-extinguishing
 Labelling system for circuit description
 Label template on the Internet at
www.hensel-electric.de - in the
’Downloads’ area.
24
DK Cable Junction Boxes
Cable Entry via Metric Knockouts
D 9025
Wall
3
1
3 3
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 included cable entry: 4 ESM 20, sealing range Ø 6-13 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
5388
88
D 9125
Wall
3
1
3 3
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 included cable entry: 4 ESM 20, sealing range Ø 6-13 mm
 with external fixing
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
5388
88
D 9045
Wall
4
2
4 4
1.5-4 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol,
2 x 6 mm² sol
 included cable entry: 4 ESM 25, sealing range Ø 9-17 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
98 61
98
D 9145
Wall
3
1
3 3
1.5-4 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol,
2 x 6 mm² sol
 included cable entry: 4 ESM 20, sealing range Ø 6-13 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
98 61
98
25
DK Cable Junction Boxes
Cable Entry via Metric Knockouts
K 9065
Wall
10
10
6 5
2.5-6 mm², Cu 3~
 with terminals
 5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol,
2 x 10 mm² sol
 included cable entry: 3 ESM 32, sealing range Ø 9-23 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,5 Nm
139
119
70
K 9105
Wall
14
10
6 6
4-10 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol,
4 x 10 mm² sol, 2 x 16 mm² s
 included cable entry: 3 ESM 32, sealing range Ø 9-23 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 63 A
tightening torque for terminal 2,0 Nm
82167
125
K 9255
Wall
16
11
8 8
10-25 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 10 mm² sol, 4 x 16 mm² s, 4 x 25 mm² s,
2 x 35 mm² s
 included cable entry: 3 ESM 40, sealing range Ø 17-30 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 102 A
tightening torque for terminal 3,0 Nm
98
160
200
K 9502
Wall
12
12
17 17
10-35 mm², Cu 3~
 with terminals
 5-pole per pole 4 x 10 mm² sol, 4 x 16 mm² s, 4 x 25 mm² s,
2 x 35 mm² s
 included cable entry: 3 ESM 40, sealing range Ø 17-30 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 102 A
tightening torque for terminal 3,0 Nm
310
210 117
26
DK Cable Junction Boxes
Cable Entry via Metric Knockouts
K 9504
Wall
12
12
17 17
16-50 mm², Cu 3~
 with terminals
 4-pole per polel 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s,
4 x 50 mm² s
 cable entry via knockouts,
order AKM/ASM separately (refer to index cable entry systems)
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 150 A
tightening torque for terminal 12,0 Nm
310
210 117
K 9505
Wall
12
12
17 17
16-50 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s,
4 x 50 mm² s
 cable entry via knockouts,
order AKM/ASM separately (refer to index cable entry systems)
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 150 A
tightening torque for terminal 12,0 Nm
310
210 117
K 7055
Wall
20
20
21 21
16-50 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s,
4 x 50 mm² s
 sealable
 Order cable glands, flanges and other accessories separately as
required
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 150 A
tightening torque for terminal 12,0 Nm
450
300 170
K 9355
Wall
15
15
13 13
16-35 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s,
2 x 50 mm² s
 included cable entry: 3 ESM 40, sealing range Ø 17-30 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 125 A
tightening torque for terminal 12,0 Nm
117
260
210
27
DK Cable Junction Boxes
Cable Entry via Metric Knockouts
K 7004
Wall
20
20
21 21
16-70 mm², Cu 3~
 with terminals
 4-pole per pole 4 x 16-70 mm² s
 sealable
 Order cable glands, flanges and other accessories separately as
required
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 216 A
tightening torque for terminal 10,0 Nm
450
300 170
K 7005
Wall
20
20
21 21
16-70 mm², Cu 3~
 with terminals
 5-pole per polel 4 x 16-70 mm² s
 sealable
 Order cable glands, flanges and other accessories separately as
required
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 216 A
tightening torque for terminal 10,0 Nm
450
300 170
K 1204
Wall
20
20
21 21
16-150 mm², Cu/Alu 3~
 with terminals
 4-pole per pole 2 x 16-150 mm², 4 x 16-70 mm²,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 250 A
tightening torque for terminal 20,0 Nm
450
300 170
28
DK Cable Junction Boxes
Cable Entry via Metric Knockouts
K 1205
Wall
20
20
21 21
16-150 mm², Cu/Alu 3~
 with terminals
 5-pole per pole 2 x 16-150 mm², 4 x 16-70 mm²,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 250 A
tightening torque for terminal 20,0 Nm
450
300 170
K 2404
Wall
20
18
19 19
25-240 mm², Cu/Alu 3~
 with terminals
 4-pole per pole 2 x 25-185/240 mm², 4 x 25-120 mm²,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 400 A
tightening torque for terminal 40,0 Nm
600
300 170
29
DK Cable Junction Boxes
Cable Entry via Metric Knockouts
K 2405
Wall
20
18
19 19
25-240 mm², Cu/Alu 3~
 with terminals
 5-pole per pole 2 x 25-185/240 mm², 4 x 25-120 mm²,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 400 A
tightening torque for terminal 40,0 Nm
600
300 170
30
DK Cable Junction Boxes
Cable Entry via Metric Knockouts
D 9020
Wall
3
1
3 3
 without terminals
 included cable entry: 4 ESM 20, sealing range Ø 6-13 mm
 for normal environment and protected outdoor
5388
88
D 9120
Wall
3
1
3 3
 without terminals
 with external fixing
 included cable entry: 4 ESM 20, sealing range Ø 6-13 mm
 for normal environment and protected outdoor
5388
88
D 9140
Wall
3
1
3 3
 without terminals
 included cable entry: 4 ESM 20, sealing range Ø 6-13 mm
 for normal environment and protected outdoor
98 58
98
D 9040
Wall
4
2
4 4
 without terminals
 included cable entry: 4 ESM 25, sealing range Ø 9-17 mm
 for normal environment and protected outdoor
98 61
98
K 9060
Wall
10
10
6 5
 without terminals
 included cable entry: 3 ESM 32, sealing range Ø 9-23 mm
 for normal environment and protected outdoor
139
119
70
K 9100
Wall
14
10
6 6
 without terminals
 included cable entry: 3 ESM 32, sealing range Ø 9-23 mm
 for normal environment and protected outdoor
82167
125
31
DK Cable Junction Boxes
Cable Entry via Metric Knockouts
K 9250
Wall
16
11
8 8
 without terminals
 included cable entry: 3 ESM 40, sealing range Ø 17-30 mm
 for normal environment and protected outdoor
98
160
200
K 9350
Wall
13
13
15 15
 without terminals
 included cable entry: 3 ESM 40, sealing range Ø 17-30 mm
 for normal environment and protected outdoor
117260
210
K 9500
Wall
12
12
17 17
 without terminals
 cable entry via knockouts, order AKM/ASM separately
(refer to index cable entry systems)
 for normal environment and protected outdoor
310
210 117
32
DK Cable Junction Boxes
Box Walls without Knockouts
Cable entries can be drilled
individually.
 Labelling system for circuit description
 Label template on the Internet at
www.hensel-electric.de - in the
’Downloads’ area.
 Burning behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 °C,
flame-retardant, self-extinguishing
 Stainless steel cover screws with quick
fastening metric thread.
Reducing cover fixing time.
33
DK Cable Junction Boxes
Box Walls without Knockouts
D 8020
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 20
 for normal environment and protected outdoor
wall thickness of the bottom part 2,3 mm
5388
88
D 8120
 without terminals
 with external fixing
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 20
 for normal environment and protected outdoor
wall thickness of the bottom part 2,3 mm
5388
88
D 8040
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 20
 for normal environment and protected outdoor
wall thickness of the bottom part 2,3 mm
98 58
98
K 8060
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 32
 for normal environment and protected outdoor
wall thickness of the bottom part 2,6 mm
139
119
70
K 8100
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 32
 for normal environment and protected outdoor
wall thickness of the bottom part 2,8 mm
82167
125
34
DK Cable Junction Boxes
Box Walls without Knockouts
K 8250
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 40
 for normal environment and protected outdoor
wall thickness of the bottom part 3 mm
98
160
200
K 8350
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 50
 for normal environment and protected outdoor
wall thickness of the bottom part 3 mm
117260
210
K 8500
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 50
 for normal environment and protected outdoor
wall thickness of the bottom part 3 mm
310
210 117
35
DK Cable Junction Boxes
Box Walls without Knockouts
K 0100
 with transparent lid
 lid fasteners for tool operation
 box walls without knockouts
 please order DIN rails or mounting plates additionally
 for normal environment and protected outdoor
rated current for electrical devices up to 63 A
wall thickness of the bottom part 3,5 mm
300 170
150
K 0200
 with transparent lid
 lid fasteners for tool operation
 box walls without knockouts
 please order DIN rails or mounting plates additionally
 for normal environment and protected outdoor
rated current for electrical devices up to 63 A
wall thickness of the bottom part 3,5 mm
300 170
300
K 0300
 with transparent lid
 lid fasteners for tool operation
 box walls without knockouts
 please order DIN rails or mounting plates additionally
 for normal environment and protected outdoor
rated current for electrical devices up to 63 A
wall thickness of the bottom part 3,5 mm
300 170
450
K 0400
 with transparent lid
 lid fasteners for tool operation
 box walls without knockouts
 please order DIN rails or mounting plates additionally
 for normal environment and protected outdoor
rated current for electrical devices up to 63 A
wall thickness of the bottom part 3,5 mm
600
300 170
36
DK Cable Junction Boxes
Box Walls without Knockouts
K 0101
 with opaque lid
 lid fasteners for tool operation
 box walls without knockouts
 please order DIN rails or mounting plates additionally
 for normal environment and protected outdoor
rated current for electrical devices up to 63 A
wall thickness of the bottom part 3,5 mm
300 170
150
K 0201
 with opaque lid
 lid fasteners for tool operation
 box walls without knockouts
 please order DIN rails or mounting plates additionally
 for normal environment and protected outdoor
rated current for electrical devices up to 63 A
wall thickness of the bottom part 3,5 mm
300 170
300
K 0301
 with opaque lid
 lid fasteners for tool operation
 box walls without knockouts
 please order DIN rails or mounting plates additionally
 for normal environment and protected outdoor
rated current for electrical devices up to 63 A
wall thickness of the bottom part 3,5 mm
300 170
450
K 0401
 with opaque lid
 lid fasteners for tool operation
 box walls without knockouts
 please order DIN rails or mounting plates additionally
 for normal environment and protected outdoor
rated current for electrical devices up to 63 A
wall thickness of the bottom part 3,5 mm
600
300 170
37
DK Cable Junction Boxes
Empty Boxes
Accessories for Cable Junction Boxes K0x0x
Mi TS 15
DIN rail
length 134 mm
 in accordance with DIN EN 60 715
 for Mi Empty box size 1
 for equipment or terminals with clip-on mounting
 with fixing screws
35
15
134
Mi TS 30
DIN rail
length 284 mm
 in accordance with DIN EN 60 715
 for Mi empty box sizes 1 to 8
 for equipment or terminals with clip-on mounting
 with fixing screws
35
15
284
Mi TS 45
DIN rail
length 434 mm
 in accordance with DIN EN 60 715
 for Mi empty box size 3
 for equipment or terminals with clip-on mounting
 with fixing screws
35
15
434
Mi TS 60
DIN rail
length 584 mm
 in accordance with DIN EN 60 715
 for Mi empty box sizes 4 and 8
 for equipment or terminals with clip-on mounting
 with fixing screws 35
15
584
Mi MP 1
Mounting plate
W 259 x H 115 mm
 material thickness 4 mm
 for Mi-Empty boxes sizes 1, 2, 3, 4
 with fixing screws
259
115
Mi MP 2
Mounting plate
W 265 x H 265 mm
 material thickness 4 mm
 for Mi-Empty boxes sizes 2 to 8
 with fixing screws
265
265
38
DK Cable Junction Boxes
Empty Boxes
Accessories for Cable Junction Boxes K0x0x
Mi MP 3
Mounting plate
W 265 x H 415 mm
 material thickness 4 mm
 for Mi-Empty boxes sizes 3, 4
 with fixing screws
415
265
Mi MP 4
Mounting plate
W 265 x H 565 mm
 material thickness 4 mm
 for Mi-Empty boxes sizes 4, 8
 with fixing screws
565
265
Mi PL 2
Sealing cap
 2 sealing caps for converting the lid fasteners
Mi SR 4
Conversion set
for manual operation on tool operation
 4 fastening covers
Mi SN 4
Conversion set
for converting lid fasteners from tool to
manual operation
 4 manual actuators
39
DK Cable Junction Boxes
Empty Boxes
Accessories for Cable Junction Boxes K0x0x
Mi DV 01
Locking device insertion
 only in connection with Mi PL 2, Mi SR 4 or Mi SN 4
Mi ZS 11
Lid lock
with locking device I
 Is being used instead of fasteners for hand or tool operation in
order to prevent unauthorised opening of the lids
 consisting of: cylinder lock, keys, locking device insertion, dust
cover
Mi ZS 12
Lid lock
with locking device II
 Is being used instead of fasteners for hand or tool operation in
order to prevent unauthorised opening of the lids
 consisting of: cylinder lock, keys, locking device insertion, dust
cover
Mi DR 04
Lid fastener for tool operation
triangle 8 mm
 is used instead of fasteners for hand- or tool operation, in order to
make unauthorized opening of lids more difficult
 4 locking devices with triangle 8 mm and key
DS 1
Triangular key 8 mm
Mi AL 40
4 stainless steel external brackets
 for external fixing of enclosures
40
DK Cable Junction Boxes
Cable Entry via Elastic Membranes and Integrated M 20 Thread
 IP 55 with cable entry via
elastic membranes.
 IP 65 with ADM 20 cable gland without
locknut. The gland is secured by an
integrated M 20 thread.
 Captive cover screws with
quick-release lock.
 Burning behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 °C,
flame-retardant, self-extinguishing
41
DK Cable Junction boxes
Cable Entry via Elastic Membranes and Integrated M 20 Thread
DN 2035
Wall
3
3
3 3
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 cable entry via elastic membranes and integrated M 20 thread
 8 elastic membranes, closed, sealing range Ø 3-12 mm
 included cable entry: 3 ADM 20, sealing range Ø 6,5-13,5 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
5185
85
DN 2005
Wall
3
3
3 3
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 cable entry via elastic membranes and integrated M 20 thread
 8 elastic membranes, closed, sealing range Ø 3-12 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
5185
85
DN 2030
Wall
3
3
3 3
 without terminals
 cable entry via elastic membranes and integrated M 20 thread
 8 elastic membranes, closed, sealing range Ø 3-12 mm
 included cable entry: 3 ADM 20, sealing range Ø 6,5-13,5 mm
5185
85
DN 2000
Wall
3
3
3 3
 without terminals
 cable entry via elastic membranes and integrated M 20 thread
 8 elastic membranes, closed, sealing range Ø 3-12 mm
 for normal environment and protected outdoor
518585
ADM 20
ISO thread M 20 x 1.5
 sealing range Ø 6,5-13,5 mm
 with strain relief
 for indoor - normal environment and (or) protected outdoor installation
 ambient temperature - 25° to + 35° C
 glow wire test IEC 60 695-2-11: 750° C
tightening torque 2,0 Nm
42
DK Cable Junction Boxes
Cable Entry via Knockouts
for Cable Trunking and Conduit Installation
 Simply cut out cable trunking wall
to the required width.
 The cables can be inserted from the
front! No threading of cables neccessary!
 Supplied accessory grommets
DPS 02 = IP 54
 The clean installation solution for cable
trunking!
 Removable trunking adapters
for connection of cable trunkings
to junction boxes.
 Stainless steel cover screws with quick
fastening metric thread.
Reducing cover fixing time.
 Burning behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 °C,
flame-retardant, self-extinguishing
 Labelling system for circuit description
 Label template on the Internet at
www.hensel-electric.de - in the
’Downloads’ area.
43
DK Cable Junction Boxes
Cable Entry via Knockouts
for Cable Trunking and Conduit Installation
DP 9025
Wall
26
25
26 26
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 for cable trunking and conduit installation
 included cable entry: 4 DPS 02, sealing range Ø 10-13,5 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
5088
88
DP 9221
Wall
28
27
27 27
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 for cable trunking and conduit installation
 included cable entry: 7 DPS 02, sealing range Ø 10-13,5 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
50139
119
DP 9222
Wall
28
27
27 27
1.5-2.5 mm², Cu 3~
 with 2 terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 for cable trunking and conduit installation
 included cable entry: 7 DPS 02, sealing range Ø 10-13,5 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
50139
119
DPC 9225
Wall
28
27
27 27
1.5-2.5 mm², Cu 3~
 FIXCONNECT®
plug-in terminal technology
 5-pole per pole 4 x 1 x 1.5-2.5 mm² sol/f, terminal technology,
see annex DK Cable junction boxes
 for cable trunking and conduit installation
 included cable entry: 4 DPS 02, sealing range Ø 10-13,5 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 32 A
50139
119
44
DK Cable Junction Boxes
Cable Entry via Knockouts
for Cable Trunking and Conduit Installation
DP 9020
Wall
26
25
26 26
 without terminals
 for cable trunking and conduit installation
 included cable entry: 4 DPS 02, sealing range Ø 10-13,5 mm
 for normal environment and protected outdoor
5088
88
DP 9220
Wall
28
27
27 27
 without terminals
 for cable trunking and conduit installation
 included cable entry: 7 DPS 02, sealing range Ø 10-13,5 mm
 for normal environment and protected outdoor
50139
119
DPS 02
Removable grommet
 degree of protection: IP 54 sealing range Ø 10-13.5 mm
 for retrofitting
 for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225
ERA 20
Removable conduit adapter
 degree of protection: IP 54 sealing range Ø 10-13.5 mm
 for wiring conduits M 20
 for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225
EKA 20
Removable trunking adapter
 degree of protection: IP 54 sealing range Ø 10-13.5 mm
 for mini trunking up to 20 x 20 mm
 for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225
45
DK Cable Junction Boxes
Cable Entry via Elastic Membranes
 No punching tool required - insert the
conductor and it‘s done
 Degree of protection IP 55
 Grommet supplied for sealing membra-
nes in case of modifications.
 Box wall with 3 cable entries  Stainless steel cover screws with quick
fastening metric thread.
Reducing cover fixing time.
 Burning behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 °C,
flame-retardant, self-extinguishing
 Labelling system for circuit description
 Label template on the Internet at
www.hensel-electric.de - in the
’Downloads’ area.
46
DK Cable Junction Boxes
Cable Entry via Elastic Membranes
DE 9325
Wall
24
24
23 23
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-16 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
4788
88
DE 9345
Wall
24
24
23 23
1.5-4 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol,
2 x 6 mm² sol
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-18 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
98
98 52
DE 9335
Wall
24
24
23 23
1.5-4 mm², Cu 3~
 terminals with wire protection
 5-pole per pole 4 x 1.5 mm² sol/s/f, 4 x 2.5 mm² sol/s/f,
2 x 4 mm² sol/s/f
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-16 mm
 with cable retention (2 pc.) for cable tie up to 6.5 mm width
 for normal environment and protected outdoor
rated insulation voltage AC/DC 500 V
rated current 32 A
tightening torque for terminal 0,8 Nm
Dismantling length 6 mm
4788
88
47
DK Cable Junction Boxes
Cable Entry via Elastic Membranes
DE 9320
Wall
24
24
23 23
 without terminals
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-16 mm
 for normal environment and protected outdoor
4788
88
DE 9340
Wall
24
24
23 23
 without terminals
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-18 mm
 for normal environment and protected outdoor
98
98 52
DE 9330
Wall
24
24
23 23
 without terminals
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-16 mm
 with cable retention (2 pc.) for cable tie up to 6.5 mm width
 for normal environment and protected outdoor
4788
88
DE 9350
Wall
24
24
23 23
 without terminals
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-18 mm
 with cable retention (2 pc.) for cable tie up to 6.5 mm width
 for normal environment and protected outdoor 98
98 52
48
DK Cable Junction Boxes
Cable Entry via Elastic Membranes
DE 9326
Wall
24
24
23 23
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-16 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
4788
88
DE 9346
Wall
24
24
23 23
1.5-4 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol,
2 x 6 mm² sol
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-18 mm
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
98
98 52
DE 9336
Wall
24
24
23 23
1.5-2.5 mm², Cu 3~
 terminals with wire protection
 5-pole per pole 4 x 1.5 mm² sol/s/f, 4 x 2.5 mm² sol/s/f,
2 x 4 mm² sol/s/f
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-16 mm
 with cable retention (2 pc.) for cable tie up to 6.5 mm width
 for normal environment and protected outdoor
rated insulation voltage AC/DC 500 V
rated current 32 A
tightening torque for terminal 0,8 Nm
Dismantling length 11 mm
4788
88
DE 9321
Wall
24
24
23 23
 without terminals
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-16 mm
 for normal environment and protected outdoor
4788
88
49
DK Cable Junction Boxes
Cable Entry via Elastic Membranes
DE 9341
Wall
24
24
23 23
 without terminals
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-18 mm
 for normal environment and protected outdoor
98
98 52
DE 9331
Wall
24
24
23 23
 without terminals
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-16 mm
 with cable retention (2 pc.) for cable tie up to 6.5 mm width
 for normal environment and protected outdoor
4788
88
DE 9351
Wall
24
24
23 23
 without terminals
 10 elastic membranes, closed cable entries,
sealing range Ø 6.5-18 mm
 with cable retention (2 pc.) for cable tie up to 6.5 mm width
 for normal environment and protected outdoor
98
98 52
KHR 01
Cable retention
for cable diameter 6,5 - 14 mm
 set with 10 x 6 cable rentention rings
 30 pieces for cable diameter 6,5 - 10 mm
 30 pieces for cable diameter 10 - 14 mm
KHR 02
Cable retention
for cable diameter 10 - 16 mm
 set with 10 x 6 cable rentention rings
 30 pieces for cable diameter 10 - 14 mm
 30 pieces for cable diameter 13 - 16 mm
DK ZE 10
Cable retention
 set with 10 pieces
 for fixing in the bottom part of DK-cable junction boxes
 cable retention with cable clip up to 6.5 mm
50
DK Cable Junction Boxes
Cable Entry via Elastic Membranes
in Bottom and Box Walls
 Cable entry from the rear via elastic
membranes in the bottom
 Lid for clip-on attachment.
Reducing cover fixing time
 Flexible elastic membranes -
no cable glands required.
Push through and tight!
 Cable entry via elastic membranes
in box walls
 Burning behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 °C,
flame-retardant, self-extinguishing
51
DK Cable Junction Boxes
Cable Entry via Elastic Membranes
in Bottom and Box Walls
DE 9225
Wall
23
23
24 24
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 box walls with 10 elastic membranes, closed, sealing range Ø
3-14 mm, bottom with 2 elastic membranes, closed
 lid with clip-on attachment
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
53
76
76
DE 9220
Wall
23
23
24 24
 without terminals
 box walls with 10 elastic membranes, closed, sealing range Ø
3-14 mm, bottom with 2 elastic membranes, closed
 lid with clip-on attachment
 with cable retention (2 pc.) for cable tie up to 6.5 mm width
 for normal environment and protected outdoor
53
76
76
DK ZE 10
Cable retention
 set with 10 pieces
 for fixing in the bottom part of DK-cable junction boxes
 cable retention with cable clip up to 6.5 mm
KHR 01
Cable retention
for cable diameter 6,5 - 14 mm
 set with 10 x 6 cable rentention rings
 30 pieces for cable diameter 6,5 - 10 mm
 30 pieces for cable diameter 10 - 14 mm
KHR 02
Cable retention
for cable diameter 10 - 16 mm
 set with 10 x 6 cable rentention rings
 30 pieces for cable diameter 10 - 14 mm
 30 pieces for cable diameter 13 - 16 mm
DE MB 10
Assembly bracket
 external brackets 10 units
 material: thermoplastics
 for quick installation of cable junction boxes DE 922. and DN 20..
70
55
10 6ø6
18
10
6
52
DK Cable Junction Boxes
Cable Entry via Elastic Membranes
in Bottom and Box Walls
DE 9226
Wall
23
23
24 24
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 box walls with 10 elastic membranes, closed, sealing range Ø
3-14 mm, bottom with 2 elastic membranes, closed
 lid with clip-on attachment
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
53
76
76
DE 9221
Wall
23
23
24 24
 without terminals
 box walls with 10 elastic membranes, closed, sealing range Ø
3-14 mm, bottom with 2 elastic membranes, closed
 lid with clip-on attachment
 with cable retention (2 pc.) for cable tie up to 6.5 mm width
 for normal environment and protected outdoor
53
76
76
DK ZE 10
Cable retention
 set with 10 pieces
 for fixing in the bottom part of DK-cable junction boxes
 cable retention with cable clip up to 6.5 mm
KHR 01
Cable retention
for cable diameter 6,5 - 14 mm
 set with 10 x 6 cable rentention rings
 30 pieces for cable diameter 6,5 - 10 mm
 30 pieces for cable diameter 10 - 14 mm
KHR 02
Cable retention
for cable diameter 10 - 16 mm
 set with 10 x 6 cable rentention rings
 30 pieces for cable diameter 10 - 14 mm
 30 pieces for cable diameter 13 - 16 mm
DE MB 10
Assembly bracket
 external brackets 10 units
 material: thermoplastics
 for quick installation of cable junction boxes DE 922. and DN 20..
70
55
10 6ø6
18
10
6
53
DK Cable Junction Boxes
with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
 Degree of protection up to IP 65. In the
case of twisted cables, cable glands
are required in principle to achieve the
degree of protection IP 54.
 Separate clamping units for
aluminium and copper conductors
 Stainless steel cover screws with quick
fastening metric thread.
Reducing cover fixing time.
 Burning behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 °C,
flame-retardant, self-extinguishing
 Labelling system for circuit description.
 Label template on the Internet at
www.hensel-electric.de - in the
’Downloads’ area.
54
DK Cable Junction Boxes
with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
D 9041
Wall
4
2
4 4
1.5-2.5 mm², Cu/Alu 3~
 with terminals
 5-pole per polel 4 x 1.5 mm² sol/f, 4 x 2.5 mm² sol/f, conductors
are inserted into the screw-type terminal, terminal technology,
see annex DK Cable junction boxes
 included cable entry: 4 ESM 25, sealing range Ø 9-17 mm
 In the case of twisted cables, cable glands are required in
principle to achieve the degree of protection IP 54.
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 250 V
current carrying capacity 20 A
tightening torque for terminal 0,5 Nm
98 61
98
K 9061
Wall
10
10
6 5
1.5-4 mm², Cu/Alu 3~
 with terminals
 5-pole per pole 4 x 1.5 mm² sol/f, 4 x 2.5 mm² sol/f, 4 x 4 mm²
sol/f, conductors are inserted into the screw-type terminal,
terminal technology, see annex DK Cable junction boxes
 included cable entry: 3 ESM 32, sealing range Ø 9-23 mm
 In the case of twisted cables, cable glands are required in
principle to achieve the degree of protection IP 54.
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 400 V
current carrying capacity 20 A
tightening torque for terminal 0,6 Nm
139
119
70
55
DK Cable Junction Boxes
with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
K 9351
Wall
13
13
15 15
6-16 mm², Cu/Alu 3~
 with terminals
 5-pole per polel 4 x 6 mm² sol/f, 4 x 10 mm² sol/f, 4 x 16 mm²
sol/s/f, conductors are inserted into the screw-type terminal,
terminal technology, see annex DK Cable junction boxes
 included cable entry: 3 ESM 40, sealing range Ø 17-30 mm
 In the case of twisted cables, cable glands are required in
principle to achieve the degree of protection IP 54.
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 76 A
tightening torque for terminal 3,0 Nm
117260
210
KF 9251
Wall
16
11
8 8
1.5-50 mm², Cu/Alu 3~
 with connecting terminal
 5-pole per pole 2 x 1 x 1.5-50 mm², conductors are inserted into
the screw-type terminal, terminal technology,
see annex DK Cable junction boxes
 included cable entry: 2 EDK 40, sealing range Ø 11-30 mm
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 160 A
tightening torque for terminal 1.5 Nm 1.5-2.5 mm²
5.0 Nm 4-10 mm²
12,0 Nm 16-50 mm²
98
160
200
56
DK Cable Junction Boxes
with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
KF 9501
Wall
12
12
17 17
1.5-50 mm², Cu/Alu 3~
 with connecting terminal
 5-pole per pole 2 x 1 x 1.5-50 mm², conductors are inserted into
the screw-type terminal, terminal technology,
see annex DK Cable junction boxes
 included cable entry: 2 EDK 40, sealing range Ø 11-30 mm
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 160 A
tightening torque for terminal 1.5 Nm 1.5-2.5 mm²
5.0 Nm 4-10 mm²
12,0 Nm 16-50 mm²
310
210 117
K 7051
Wall
20
20
21 21
2.5-50 mm², Cu/Alu 3~
 with terminals
 5-pole per pole 4 x 2.5-50 mm², conductors are inserted into the
screw-type terminal, terminal technology,
see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 750 V
current carrying capacity Cu, 150 A
Alu, 120 A
tightening torque for terminal 10,0 Nm
450
300 170
57
DK Cable Junction Boxes
with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
K 7042
Wall
20
20
21 21
10-95 mm² Cu/Alu 3~
 with terminals
 4-pole per pole 2 x 10-95 mm², conductors can be inserted from
the front into the clamping unit, terminal technology,
see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 160 A
tightening torque for terminal 20,0 Nm
450
300 170
K 7052
Wall
20
20
21 21
10-95 mm² Cu/Alu 3~
 with terminals
 5-pole per pole 2 x 10-95 mm², conductors can be inserted from
the front into the clamping unit, terminal technology,
see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 160 A
tightening torque for terminal 20,0 Nm
450
300 170
58
DK Cable Junction Boxes
with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
K 9951
Wall
20
20
21 21
6-95 mm², Cu/Alu 3~
 with terminals
 5-pole per pole 4 x 6-95 mm², conductors are inserted into the
screw-type terminal, terminal technology,
see annex DK Cable junction boxes
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 490 A
tightening torque for terminal 12.0 Nm 6-25 mm²
22.0 Nm 35-95 mm²
450
300 170
K 1204
Wall
20
20
21 21
16-150 mm², Cu/Alu 3~
 with terminals
 4-pole per pole 2 x 16-150 mm², 4 x 16-70 mm², conductors can
be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 250 A
tightening torque for terminal 20,0 Nm
450
300 170
59
DK Cable Junction Boxes
with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
K 1205
Wall
20
20
21 21
16-150 mm², Cu/Alu 3~
 with terminals
 5-pole per pole 2 x 16-150 mm², 4 x 16-70 mm²,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 250 A
tightening torque for terminal 20,0 Nm
450
300 170
K 2404
Wall
20
18
19 19
25-240 mm², Cu/Alu 3~
 with terminals
 4-pole per pole 2 x 25-185/240 mm², 4 x 25-120 mm²,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 400 A
tightening torque for terminal 40,0 Nm
600
300 170
60
DK Cable Junction Boxes
with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
K 2405
Wall
20
18
19 19
25-240 mm², Cu/Alu 3~
 with terminals
 5-pole per pole 2 x 25-185/240 mm², 4 x 25-120 mm²,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 400 A
tightening torque for terminal 40,0 Nm
600
300 170
K 2401
Wall
20
18
19 19
35-240 mm², Cu/Alu 3~
 with terminals
 5-pole per pole 4 x 35-240 mm², conductors are inserted into the
screw-type terminal, terminal technology,
see annex DK Cable junction boxes
 sealable
 Order cable glands, flanges and other accessories separately as
required
 Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
 for normal environment and protected outdoor
rated insulation voltage AC/DC 690 V
current carrying capacity 850 A
tightening torque for terminal 26.0 Nm 35-120 mm²
55.0 Nm 150-240 mm²
600
300 170
61
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Cable Entry via Metric Knockouts
 Degree of protection IP 66
 Flame retardant, self-extinguishing,
made of high-grade material:
PC-GFS, glass-fibre reinforced
thermoplastics, impact proof
 KF-Cable junction boxes comply with
regulatory restrictions for buildings with
requirements regarding the structural fire
protection!
 halogen-free, silicone-free:
low toxicity, low fume development
 Stainless steel cover screws with quick
fastening metric thread.
Reducing cover fixing time.
 Burning behaviour:
Glow-wire test 960°C
according to IEC 60 695-2-11,
UL Subject 94: V-0
flame-retardant, self-extinguishing
 Degree of protection IP 66 using cable
glands ASS.. (colour black) or cable
glands ASM.. (colour grey), available as
an accessory.
62
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 9025
Wall
3
1
3 3
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
5388
88
KF 9045
Wall
4
2
4 4
1.5-4 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol,
2 x 6 mm² sol
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
98 61
98
KF 9065
Wall
10
10
6 5
2.5-6 mm², Cu 3~
 with terminals
 5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol,
2 x 10 mm² sol
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,5 Nm
139
119
70
KF 9105
Wall
14
10
6 6
4-10 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol,
4 x 10 mm² sol, 2 x 16 mm² s
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
current carrying capacity 63 A
tightening torque for terminal 2,0 Nm
82167
125
63
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 9255
Wall
16
11
8 8
10-25 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 10 mm² sol, 4 x 16 mm² s, 4 x 25 mm² s,
2 x 35 mm² s
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
current carrying capacity 102 A
tightening torque for terminal 3,0 Nm
98
160
200
KF 9355
Wall
15
15
13 13
16-35 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s,
2 x 50 mm² s
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
current carrying capacity 125 A
tightening torque for terminal 12,0 Nm
117
260
210
KF 9505
Wall
12
12
17 17
16-50 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s,
4 x 50 mm² s
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
current carrying capacity 150 A
tightening torque for terminal 12,0 Nm
310
210 117
64
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 9020
Wall
3
1
3 3
 without terminals
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
5388
88
KF 9040
Wall
4
2
4 4
 without terminals
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
98 61
98
KF 9060
Wall
10
10
6 5
 without terminals
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
139
119
70
KF 9100
Wall
14
10
6 6
 without terminals
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
82167
125
KF 9250
Wall
16
11
8 8
 without terminals
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
98
160
200
65
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 9350
Wall
13
13
15 15
 without terminals
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
117260
210
KF 9500
Wall
12
12
17 17
 without terminals
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
310
210 117
66
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 5025
Wall
3
1
3 3
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
5388
88
KF 5045
Wall
4
2
4 4
1.5-4 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol,
2 x 6 mm² sol
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
98 61
98
KF 5065
Wall
10
10
6 5
2.5-6 mm², Cu 3~
 with terminals
 5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol,
2 x 10 mm² sol
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,5 Nm
139
119
70
KF 5105
Wall
14
10
6 6
4-10 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol,
4 x 10 mm² sol, 2 x 16 mm² s
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
current carrying capacity 63 A
tightening torque for terminal 2,0 Nm
82167
125
67
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 5255
Wall
16
11
8 8
10-25 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 10 mm² sol, 4 x 16 mm² s, 4 x 25 mm² s,
2 x 35 mm² s
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
current carrying capacity 102 A
tightening torque for terminal 3,0 Nm
98
160
200
KF 5355
Wall
15
15
13 13
16-35 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s,
2 x 50 mm² s
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
current carrying capacity 125 A
tightening torque for terminal 12,0 Nm
117
260
210
KF 5505
Wall
12
12
17 17
16-50 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s,
4 x 50 mm² s
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
rated insulation voltage AC/DC 690 V
current carrying capacity 150 A
tightening torque for terminal 12,0 Nm
310
210 117
68
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 5020
Wall
3
1
3 3
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
5388
88
KF 5040
Wall
4
2
4 4
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
98 61
98
KF 5060
Wall
10
10
6 5
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
139
119
70
KF 5100
Wall
14
10
6 6
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
82167
125
KF 5250
Wall
16
11
8 8
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
98
160
200
69
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 5350
Wall
13
13
15 15
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
117260
210
KF 5500
Wall
12
12
17 17
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Outdoor - harsh environment and (or) outdoor"
310
210 117
70
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Box Walls without Knockouts
 Cable entries can be drilled individually  Stainless steel cover screws with quick
fastening metric thread.
Reducing cover fixing time.
 Labelling system for circuit description.
 Label template on the Internet at
www.hensel-electric.de - in the
’Downloads’ area.
 Burning behaviour:
Glow-wire test 960 °C
according to IEC 60 695-2-11,
UL Subject 94: V-0
flame-retardant, self-extinguishing
71
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Box Walls without Knockouts
KF 8020
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 20
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 2,3 mm
5388
88
KF 8040
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 20
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 2,3 mm
98 58
98
KF 8060
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 32
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 2,6 mm
139
119
70
KF 8100
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 32
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 2,8 mm
82167
125
72
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Box Walls without Knockouts
KF 8250
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 40
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 3 mm
98
160
200
KF 8350
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 50
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 3 mm
117260
210
KF 8500
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 50
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 3 mm 310
210 117
73
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Box Walls without Knockouts
KF 4020
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 20
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 2,3 mm
5388
88
KF 4040
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 20
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 2,3 mm
98 58
98
KF 4060
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 32
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 2,6 mm
139
119
70
KF 4100
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 32
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 2,8 mm
82167
125
74
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Box Walls without Knockouts
KF 4250
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 40
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 3 mm
98
160
200
KF 4350
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 50
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 3 mm
117260
210
KF 4500
 without terminals
 box walls without knockouts
 wall surface can be drilled individually for cable entry max. M 50
 "Outdoor - harsh environment and (or) outdoor"
wall thickness of the bottom part 3 mm 310
210 117
75
 Stainless steel cover screws with quick
fastening metric thread.
Reducing cover fixing time.
 Labelling system for circuit description.
 Label template on the Internet at
www.hensel-electric.de - in the
’Downloads’ area.
 Burning behaviour:
Glow-wire test 960 °C
according to IEC 60 695-2-11,
UL Subject 94: V-0
flame-retardant, self-extinguishing
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Approved for United States and Canada (UL/CSA)
Box Walls without Knockouts
 Cable junction boxes with external
brackets made of stainless steel.
 Cable entries can be drilled
individually.
 Approved for United States
and Canada
76
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Approved for United States and Canada (UL/CSA)
Box Walls without Knockouts
KF 7020
 without terminals
 with UL/CSA approval
 box walls without knockouts
 wall surface can be drilled individually for cable entry M 20,
NPT 3/8" and NPT 1/2"
wall thickness of the bottom part 2,3 mm
external brackets 2
5388
88
KF 7040
 without terminals
 with UL/CSA approval
 box walls without knockouts
 wall surface can be drilled individually for cable entry M 20,
NPT 3/8" and NPT 1/2"
wall thickness of the bottom part 2,3 mm
external brackets 2
98 58
98
KF 7060
 without terminals
 with UL/CSA approval
 box walls without knockouts
 wall surface can be drilled individually for cable entry M 20/25/32,
NPT 3/8", NPT 1/2" and NPT 3/4"
wall thickness of the bottom part 2,6 mm
external brackets 2
139
119
70
KF 7100
 without terminals
 with UL/CSA approval
 box walls without knockouts
 wall surface can be drilled individually for cable entry M 20/25/32,
NPT 3/8", NPT 1/2", NPT 3/4" and 1"
wall thickness of the bottom part 2,8 mm
external brackets 2
82167
125
77
DK Cable Junction Boxes
“Weatherproof”, for Outdoor Installation
Approved for United States and Canada (UL/CSA)
Box Walls without Knockouts
KF 7250
 without terminals
 with UL/CSA approval
 box walls without knockouts
 wall surface can be drilled individually for cable entry M 20/25/32,
NPT 3/8", NPT 1/2", NPT 3/4" and 1"
wall thickness of the bottom part 3 mm
external brackets 4
98
160
200
78
DK Cable Junction Boxes
“Waterproof”, for Encapsulating
 Cable junction boxes for encapsulating  In case of re-installation or testing the
sealing compound can be removed
easily
 Stainless steel cover screws with quick
fastening metric thread.
Reducing cover fixing time.
 Scope of application:
Ground level installations
 Scope of application:
Pump shafts
 Scope of application:
Flood areas close to rivers or
unprotected outdoor installations which
are in close proximity to the ground
The ingress of water and formation of
condensation are completely prevented.
The sealing compound can be easily removed
for subsequent installations or inspections.
79
DK Cable Junction Boxes
“Waterproof”, for Encapsulating
Permanent waterproof
connection -
Cable junction boxes
for encapsulating
in accordance with
DIN VDE V 0606-22-100
Time and time again, electricians
come across installation envi-
ronments whereby the ingress
of water into an enclosure must
be safely excluded. Even enclo-
sures which have a high degree
of protection cannot guarantee
this. The IP degree of protection
allows the ingress of non-harmful
quantities of water in the interior
of an enclosure.
Under extreme environmental
conditions, for example, the ac-
cumulation of condensation may
result in damage to the electrical
installation or devices or cause
these to malfunction.
Ventilation measures will often
suffice to prevent harmful con-
densation from forming.
In many cases, however, ventila-
tion is not possible, e.g. because
the cable junction boxes are in-
stalled close to rivers and water
could enter through the vent holes.
Which applications require
waterproof connections?
 Pump shafts
 Ground-level installation ducts
in outdoor areas
 Flood areas close to rivers
 Unprotected outdoor instal-
lations which are in close
proximity to the ground
Why is the IP degree of pro-
tection alone not sufficient?
 All degrees of protection al-
lowed Water ingress
 The accumulation of con-
densation cannot always be
prevented
 Ventilation measures cannot
be applied in all environments
The waterproof connection
Sealing the cable junction boxes
with a fast setting, permanently
elastic sealing compound com-
pletely the ingress of water and the
excludes forming of condensation.
The sealing compound fea-
tures outstanding insula-
tion properties. As the com-
pound is transparent, it is
possible for visual inspections of
the installation to be carried out
at any time. The durable elastic
material is self-sealing, therefore it
is also easy for the electrical con-
nections to be tested after they
have been sealed.
The sealing compound can be
easily removed for repairs, subse-
quent installations or changes to
installations.
Another benefit: the sealed cable
junction boxes also offer reliable
protection against shock and vi-
bration. The sealing compound
does not, however, provide strain
relief as it only adheres to material
and does not stick together. Suit-
able cable entries must also be
used here, e.g. Hensel ASM.
The ingress of water and
formation of condensation
are completely prevented.
The sealing compound
can be easily removed for
subsequent installations or
inspections.
1 2 3
4 5 6
 Scope of application:
Installations which are in close proximity
to the ground or underground
 Scope of application:
Flood areas close to rivers
 Scope of application:
Ground level installations or underground
80
DK Cable Junction Boxes
“Waterproof”, for Encapsulating
KF WP 3025
Wall
3
1
3 3
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 cable junction box for encapsulating
 for ground installation without live loads or in risk of condensation
formation and ingress of liquids
 installation permanently under water up to a depth of 1 meter
possible
 with sealing compound and sealing plug
 in case of re-installation or testing the sealing compound can be
removed easily
 Check the expiry date of the sealing compound!
 enclosure volume 250 ml
Degree of protection For totally encapsulated cable
junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
5388
88
KF WP 3045
Wall
4
2
4 4
1.5-4 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol,
2 x 6 mm² sol
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 cable junction box for encapsulating
 for ground installation without live loads or in risk of condensation
formation and ingress of liquids
 installation permanently under water up to a depth of 1 meter
possible
 with sealing compound and sealing plug
 in case of re-installation or testing the sealing compound can be
removed easily
 Check the expiry date of the sealing compound!
 enclosure volume 350 ml
Degree of protection For totally encapsulated cable
junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
98 61
98
81
DK Cable Junction Boxes
“Waterproof”, for Encapsulating
KF WP 3065
Wall
10
10
6 5
2.5-6 mm², Cu 3~
 with terminals
 5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol,
2 x 10 mm² sol
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 cable junction box for encapsulating
 for ground installation without live loads or in risk of condensation
formation and ingress of liquids
 installation permanently under water up to a depth of 1 meter
possible
 with sealing compound and sealing plug
 in case of re-installation or testing the sealing compound can be
removed easily
 Check the expiry date of the sealing compound!
 enclosure volume 750 ml
Degree of protection For totally encapsulated cable
junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,5 Nm
139
119
70
KF WP 3105
Wall
14
10
6 6
4-10 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol,
4 x 10 mm² sol, 2 x 16 mm² s
 cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
 cable junction box for encapsulating
 for ground installation without live loads or in risk of condensation
formation and ingress of liquids
 installation permanently under water up to a depth of 1 meter
possible
 with sealing compound and sealing plug
 in case of re-installation or testing the sealing compound can be
removed easily
 Check the expiry date of the sealing compound!
 enclosure volume 1200 ml
Degree of protection For totally encapsulated cable
junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
rated insulation voltage AC/DC 690 V
current carrying capacity 63 A
tightening torque for terminal 2,0 Nm
82167
125
82
DK Cable Junction Boxes
“Waterproof”, for Encapsulating
KF WP 2025
Wall
3
1
3 3
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 cable junction box for encapsulating
 for ground installation without live loads or in risk of condensation
formation and ingress of liquids
 installation permanently under water up to a depth of 1 meter
possible
 with sealing compound and sealing plug
 in case of re-installation or testing the sealing compound can be
removed easily
 Check the expiry date of the sealing compound!
 enclosure volume 250 ml
Degree of protection For totally encapsulated cable
junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
5388
88
KF WP 2045
Wall
4
2
4 4
1.5-4 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol,
2 x 6 mm² sol
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 cable junction box for encapsulating
 for ground installation without live loads or in risk of condensation
formation and ingress of liquids
 installation permanently under water up to a depth of 1 meter
possible
 with sealing compound and sealing plug
 in case of re-installation or testing the sealing compound can be
removed easily
 Check the expiry date of the sealing compound!
 enclosure volume 350 ml
Degree of protection For totally encapsulated cable
junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
98 61
98
83
DK Cable Junction Boxes
“Waterproof”, for Encapsulating
KF WP 2065
Wall
10
10
6 5
2.5-6 mm², Cu 3~
 with terminals
 5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol,
2 x 10 mm² sol
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 cable junction box for encapsulating
 for ground installation without live loads or in risk of condensation
formation and ingress of liquids
 installation permanently under water up to a depth of 1 meter
possible
 with sealing compound and sealing plug
 in case of re-installation or testing the sealing compound can be
removed easily
 Check the expiry date of the sealing compound!
 enclosure volume 750 ml
Degree of protection For totally encapsulated cable
junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,5 Nm
139
119
70
KF WP 2105
Wall
14
10
6 6
4-10 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol,
4 x 10 mm² sol, 2 x 16 mm² s
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 cable junction box for encapsulating
 for ground installation without live loads or in risk of condensation
formation and ingress of liquids
 installation permanently under water up to a depth of 1 meter
possible
 with sealing compound and sealing plug
 in case of re-installation or testing the sealing compound can be
removed easily
 Check the expiry date of the sealing compound!
 enclosure volume 1200 ml
Degree of protection For totally encapsulated cable
junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
rated insulation voltage AC/DC 690 V
current carrying capacity 63 A
tightening torque for terminal 2,0 Nm
82167
125
84
DK Cable Junction Boxes
“Waterproof”, for Encapsulating
GH 0250
Set sealing compound, 250 ml
 as spares
 sealing compound for refilling KF WP x025 after changes or repairs
 Check the expiry date of the sealing compound!
GH 0350
Set sealing compound, 350 ml
 as spares
 sealing compound for refilling KF WP x045 after changes or repairs
 Check the expiry date of the sealing compound!
GH 0750
Set sealing compound, 750 ml
 as spares
 sealing compound for refilling KF WP x065 after changes or repairs
 Check the expiry date of the sealing compound!
GH 1200
set sealing compound, 1200 ml
 as spares
 sealing compound for refilling KF WP x105 after changes or repairs
 Check the expiry date of the sealing compound!
85
 Stainless steel cover screws with quick
fastening metric thread.
Reducing cover fixing time.
 Labelling system for circuit description.
 Label template on the Internet at
www.hensel-electric.de - in the
’Downloads’ area.
DK Cable Junction Boxes
for Offshore Applications
Cable Entry via Metric Knockouts
 Degree of protection: IP 66 / IP 67
temporary submersion
 up to 1 meter, max. 15 minutes
 with cable glands ASS.. available as an
accessory
 Cable entries can be drilled individually
 Saltwater-proof
 UV-resistant
 Material:
- halogen free
- impact resistant
- low toxicity
 Burning behaviour: UL Subject 94 = 5V
86
DK Cable Junction Boxes
for Offshore Applications
Cable Entry via Metric Knockouts
KD 5025
Wall
3
1
3 3
1.5-2.5 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
5388
88
KD 5125
Wall
3
1
3 3
1.5-2.5 mm², Cu 3~
with external fixing
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
5388
88
KD 5045
Wall
4
2
4 4
1.5-4 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol,
2 x 6 mm² sol
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,2 Nm
98 6198
87
DK Cable Junction Boxes
for Offshore Applications
Cable Entry via Metric Knockouts
KD 5065
Wall
10
10
6 5
2.5-6 mm², Cu 3~
 with terminals
 5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol,
2 x 10 mm² sol
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
rated insulation voltage AC/DC 690 V
tightening torque for terminal 1,5 Nm
139
119
70
KD 5105
Wall
14
10
6 6
4-10 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol,
4 x 10 mm² sol, 2 x 16 mm² s
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
rated insulation voltage AC/DC 690 V
current carrying capacity 63 A
tightening torque for terminal 2,0 Nm
82167
125
KD 5255
Wall
16
11
8 8
10-25 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 10 mm² sol, 4 x 16 mm² s, 4 x 25 mm² s,
2 x 35 mm² s
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
rated insulation voltage AC/DC 690 V
current carrying capacity 102 A
tightening torque for terminal 3,0 Nm
98
160
200
88
DK Cable Junction Boxes
for Offshore Applications
Cable Entry via Metric Knockouts
KD 5355
Wall
15
15
13 13
16-35 mm², Cu 3~
 with terminals
 5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s,
2 x 50 mm² s
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
rated insulation voltage AC/DC 690 V
current carrying capacity 125 A
tightening torque for terminal 12,0 Nm
117
260
210
89
DK Cable Junction Boxes
for Offshore Applications
Cable Entry via Metric Knockouts
KD 5020
Wall
3
1
3 3
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
5388
88
KD 5120
Wall
3
1
3 3
with external fixing
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
5388
88
KD 5040
Wall
4
2
4 4
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
98 61
98
KD 5060
Wall
10
10
6 5
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
139
119
70
90
DK Cable Junction Boxes
for Offshore Applications
Cable Entry via Metric Knockouts
KD 5100
Wall
14
10
6 6
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
82167
125
KD 5250
Wall
16
11
8 8
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
98
160
200
KD 5350
Wall
13
13
15 15
 without terminals
 cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
 "Offshore applications"
 saltwater-proof
 acid-resistant lid screws made of stainless steel
 burning behaviour 960° C; UL Subject 94: 5 V
117260
210
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67
Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67

More Related Content

What's hot

Ensto Cold Shrink Solutions - Cable Joints & Cable Terminations
Ensto Cold Shrink Solutions - Cable Joints & Cable TerminationsEnsto Cold Shrink Solutions - Cable Joints & Cable Terminations
Ensto Cold Shrink Solutions - Cable Joints & Cable TerminationsThorne & Derrick International
 
24 hour emergency car locksmiths brisbane at hareed
24 hour emergency car locksmiths brisbane at hareed24 hour emergency car locksmiths brisbane at hareed
24 hour emergency car locksmiths brisbane at hareedhareed
 
How to use microcool’s mdt fin technology
How to use microcool’s mdt fin technologyHow to use microcool’s mdt fin technology
How to use microcool’s mdt fin technologyScott Holland
 
Slides standards switchair
Slides standards switchairSlides standards switchair
Slides standards switchairPhil Heft
 
Microcool general liquid cooling presentation 10215
Microcool general liquid cooling presentation  10215Microcool general liquid cooling presentation  10215
Microcool general liquid cooling presentation 10215Scott Holland
 
Microcool General Liquid Cooling Presentation
Microcool General Liquid Cooling Presentation Microcool General Liquid Cooling Presentation
Microcool General Liquid Cooling Presentation Scott Holland
 
Nitrile tube insulation
Nitrile tube insulationNitrile tube insulation
Nitrile tube insulationNESPL
 
Eltherm ELSR-R Heat Trace Cable - Spec Sheet
Eltherm ELSR-R Heat Trace Cable - Spec SheetEltherm ELSR-R Heat Trace Cable - Spec Sheet
Eltherm ELSR-R Heat Trace Cable - Spec SheetThorne & Derrick UK
 
Stainless Steel Enclosures for Hazardous Areas
Stainless Steel Enclosures for Hazardous AreasStainless Steel Enclosures for Hazardous Areas
Stainless Steel Enclosures for Hazardous AreasAbtech Ltd
 
MEDC Manual Call Points & Break Glass Units for Hazardous Areas
MEDC Manual Call Points & Break Glass Units for Hazardous AreasMEDC Manual Call Points & Break Glass Units for Hazardous Areas
MEDC Manual Call Points & Break Glass Units for Hazardous AreasThorne & Derrick International
 
Static/Dynamic Passbox & Air Curtains
Static/Dynamic Passbox  & Air Curtains Static/Dynamic Passbox  & Air Curtains
Static/Dynamic Passbox & Air Curtains PraneshNanda
 
Isopad Flexible Heated Hoses, Gas Analyser Hose, Heavy Oil Transfer Hoses & B...
Isopad Flexible Heated Hoses, Gas Analyser Hose, Heavy Oil Transfer Hoses & B...Isopad Flexible Heated Hoses, Gas Analyser Hose, Heavy Oil Transfer Hoses & B...
Isopad Flexible Heated Hoses, Gas Analyser Hose, Heavy Oil Transfer Hoses & B...Thorne & Derrick UK
 
Laboratory Freezer Brochure
Laboratory Freezer BrochureLaboratory Freezer Brochure
Laboratory Freezer BrochureFPD Group Ltd
 
Walsall E0301 Manual Call Point with Break Glass - Hazardous Area Zone 1 & Zo...
Walsall E0301 Manual Call Point with Break Glass - Hazardous Area Zone 1 & Zo...Walsall E0301 Manual Call Point with Break Glass - Hazardous Area Zone 1 & Zo...
Walsall E0301 Manual Call Point with Break Glass - Hazardous Area Zone 1 & Zo...Thorne & Derrick International
 
8.0 Installation of Ceiling Batts.pdf
8.0 Installation of Ceiling Batts.pdf8.0 Installation of Ceiling Batts.pdf
8.0 Installation of Ceiling Batts.pdfInsulation2
 
Flexicon Flexible Conduit Solutions - Metallic, Non-Metallic & FPA(X) Conduit...
Flexicon Flexible Conduit Solutions - Metallic, Non-Metallic & FPA(X) Conduit...Flexicon Flexible Conduit Solutions - Metallic, Non-Metallic & FPA(X) Conduit...
Flexicon Flexible Conduit Solutions - Metallic, Non-Metallic & FPA(X) Conduit...Thorne & Derrick International
 

What's hot (20)

Ensto Cold Shrink Solutions - Cable Joints & Cable Terminations
Ensto Cold Shrink Solutions - Cable Joints & Cable TerminationsEnsto Cold Shrink Solutions - Cable Joints & Cable Terminations
Ensto Cold Shrink Solutions - Cable Joints & Cable Terminations
 
24 hour emergency car locksmiths brisbane at hareed
24 hour emergency car locksmiths brisbane at hareed24 hour emergency car locksmiths brisbane at hareed
24 hour emergency car locksmiths brisbane at hareed
 
How to use microcool’s mdt fin technology
How to use microcool’s mdt fin technologyHow to use microcool’s mdt fin technology
How to use microcool’s mdt fin technology
 
Przyciski pojemnościowe K30 i K50 z ośwetleniem LED
Przyciski pojemnościowe K30 i K50 z ośwetleniem LEDPrzyciski pojemnościowe K30 i K50 z ośwetleniem LED
Przyciski pojemnościowe K30 i K50 z ośwetleniem LED
 
Slides standards switchair
Slides standards switchairSlides standards switchair
Slides standards switchair
 
Orica_Binder
Orica_BinderOrica_Binder
Orica_Binder
 
Microcool general liquid cooling presentation 10215
Microcool general liquid cooling presentation  10215Microcool general liquid cooling presentation  10215
Microcool general liquid cooling presentation 10215
 
Microcool General Liquid Cooling Presentation
Microcool General Liquid Cooling Presentation Microcool General Liquid Cooling Presentation
Microcool General Liquid Cooling Presentation
 
Nitrile tube insulation
Nitrile tube insulationNitrile tube insulation
Nitrile tube insulation
 
Eltherm ELSR-R Heat Trace Cable - Spec Sheet
Eltherm ELSR-R Heat Trace Cable - Spec SheetEltherm ELSR-R Heat Trace Cable - Spec Sheet
Eltherm ELSR-R Heat Trace Cable - Spec Sheet
 
Stainless Steel Enclosures for Hazardous Areas
Stainless Steel Enclosures for Hazardous AreasStainless Steel Enclosures for Hazardous Areas
Stainless Steel Enclosures for Hazardous Areas
 
MEDC Manual Call Points & Break Glass Units for Hazardous Areas
MEDC Manual Call Points & Break Glass Units for Hazardous AreasMEDC Manual Call Points & Break Glass Units for Hazardous Areas
MEDC Manual Call Points & Break Glass Units for Hazardous Areas
 
Pass Box
Pass Box Pass Box
Pass Box
 
Static/Dynamic Passbox & Air Curtains
Static/Dynamic Passbox  & Air Curtains Static/Dynamic Passbox  & Air Curtains
Static/Dynamic Passbox & Air Curtains
 
Isopad Flexible Heated Hoses, Gas Analyser Hose, Heavy Oil Transfer Hoses & B...
Isopad Flexible Heated Hoses, Gas Analyser Hose, Heavy Oil Transfer Hoses & B...Isopad Flexible Heated Hoses, Gas Analyser Hose, Heavy Oil Transfer Hoses & B...
Isopad Flexible Heated Hoses, Gas Analyser Hose, Heavy Oil Transfer Hoses & B...
 
Laboratory Freezer Brochure
Laboratory Freezer BrochureLaboratory Freezer Brochure
Laboratory Freezer Brochure
 
Walsall E0301 Manual Call Point with Break Glass - Hazardous Area Zone 1 & Zo...
Walsall E0301 Manual Call Point with Break Glass - Hazardous Area Zone 1 & Zo...Walsall E0301 Manual Call Point with Break Glass - Hazardous Area Zone 1 & Zo...
Walsall E0301 Manual Call Point with Break Glass - Hazardous Area Zone 1 & Zo...
 
8.0 Installation of Ceiling Batts.pdf
8.0 Installation of Ceiling Batts.pdf8.0 Installation of Ceiling Batts.pdf
8.0 Installation of Ceiling Batts.pdf
 
Flexicon Flexible Conduit Solutions - Metallic, Non-Metallic & FPA(X) Conduit...
Flexicon Flexible Conduit Solutions - Metallic, Non-Metallic & FPA(X) Conduit...Flexicon Flexible Conduit Solutions - Metallic, Non-Metallic & FPA(X) Conduit...
Flexicon Flexible Conduit Solutions - Metallic, Non-Metallic & FPA(X) Conduit...
 
Hawke CSB 656N Hazardous Area Cable Gland
Hawke CSB 656N Hazardous Area Cable GlandHawke CSB 656N Hazardous Area Cable Gland
Hawke CSB 656N Hazardous Area Cable Gland
 

Similar to Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67

Marechal Distribution Boxes - Marechal Express Boxes, Marechal Express Fire B...
Marechal Distribution Boxes - Marechal Express Boxes, Marechal Express Fire B...Marechal Distribution Boxes - Marechal Express Boxes, Marechal Express Fire B...
Marechal Distribution Boxes - Marechal Express Boxes, Marechal Express Fire B...Thorne & Derrick International
 
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Thorne & Derrick International
 
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...Thorne & Derrick International
 
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HV
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HVNexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HV
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HVThorne & Derrick International
 
ATEX Hazardous Area Explosion Proof Distribution Boxes - Marechal B2X
ATEX Hazardous Area Explosion Proof Distribution Boxes - Marechal B2XATEX Hazardous Area Explosion Proof Distribution Boxes - Marechal B2X
ATEX Hazardous Area Explosion Proof Distribution Boxes - Marechal B2XThorne & Derrick International
 
ICOTEK - Product Catalogue 2016
ICOTEK - Product Catalogue 2016ICOTEK - Product Catalogue 2016
ICOTEK - Product Catalogue 2016Ran Svarth
 
Nexans Cable Terminations - Heat Shrink, Cold Shrink, Slip-On
Nexans Cable Terminations - Heat Shrink, Cold Shrink, Slip-OnNexans Cable Terminations - Heat Shrink, Cold Shrink, Slip-On
Nexans Cable Terminations - Heat Shrink, Cold Shrink, Slip-OnThorne & Derrick International
 
Flexible Cables Solution
Flexible Cables SolutionFlexible Cables Solution
Flexible Cables Solutionprysmianaus
 
Silicon Cables Suppliers in Vadodara | Shreelight Power Pvt. Ltd.
 Silicon Cables Suppliers in Vadodara | Shreelight Power Pvt. Ltd. Silicon Cables Suppliers in Vadodara | Shreelight Power Pvt. Ltd.
Silicon Cables Suppliers in Vadodara | Shreelight Power Pvt. Ltd.ShreeLight Power
 
Sommer cable catalogue section 3
Sommer cable catalogue section 3Sommer cable catalogue section 3
Sommer cable catalogue section 3Aryan Subedi
 
Eltherm ELW-Q Heat Trace Cable - Spec Sheet
Eltherm ELW-Q Heat Trace Cable - Spec SheetEltherm ELW-Q Heat Trace Cable - Spec Sheet
Eltherm ELW-Q Heat Trace Cable - Spec SheetThorne & Derrick UK
 
Master low-voltage saudi cable co.
Master low-voltage saudi cable co.Master low-voltage saudi cable co.
Master low-voltage saudi cable co.Raymund Cortez
 
Rotronic HygroFlex5-EX - HF5-EX Hazardous Area Humidity & Temperature Sensors...
Rotronic HygroFlex5-EX - HF5-EX Hazardous Area Humidity & Temperature Sensors...Rotronic HygroFlex5-EX - HF5-EX Hazardous Area Humidity & Temperature Sensors...
Rotronic HygroFlex5-EX - HF5-EX Hazardous Area Humidity & Temperature Sensors...Thorne & Derrick UK
 

Similar to Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67 (20)

Marechal Distribution Boxes - Marechal Express Boxes, Marechal Express Fire B...
Marechal Distribution Boxes - Marechal Express Boxes, Marechal Express Fire B...Marechal Distribution Boxes - Marechal Express Boxes, Marechal Express Fire B...
Marechal Distribution Boxes - Marechal Express Boxes, Marechal Express Fire B...
 
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
 
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...
Lewden Electrical Palazzoli ATEX Solutions for Explosive Atmospheres - Indust...
 
The Elektro Tipp - Cable Junction Boxes
The Elektro Tipp - Cable Junction BoxesThe Elektro Tipp - Cable Junction Boxes
The Elektro Tipp - Cable Junction Boxes
 
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HV
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HVNexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HV
Nexans Euromold 900 Series Interface F Asymmetrical Cable Connectors HV
 
ATEX Hazardous Area Explosion Proof Distribution Boxes - Marechal B2X
ATEX Hazardous Area Explosion Proof Distribution Boxes - Marechal B2XATEX Hazardous Area Explosion Proof Distribution Boxes - Marechal B2X
ATEX Hazardous Area Explosion Proof Distribution Boxes - Marechal B2X
 
CMP CABLE GLANDS
CMP CABLE GLANDS CMP CABLE GLANDS
CMP CABLE GLANDS
 
ICOTEK - Product Catalogue 2016
ICOTEK - Product Catalogue 2016ICOTEK - Product Catalogue 2016
ICOTEK - Product Catalogue 2016
 
JAREL EXPORT
JAREL EXPORTJAREL EXPORT
JAREL EXPORT
 
Nexans Cable Terminations - Heat Shrink, Cold Shrink, Slip-On
Nexans Cable Terminations - Heat Shrink, Cold Shrink, Slip-OnNexans Cable Terminations - Heat Shrink, Cold Shrink, Slip-On
Nexans Cable Terminations - Heat Shrink, Cold Shrink, Slip-On
 
Connection technology from ifm
Connection technology from ifmConnection technology from ifm
Connection technology from ifm
 
Flexible Cables Solution
Flexible Cables SolutionFlexible Cables Solution
Flexible Cables Solution
 
Silicon Cables Suppliers in Vadodara | Shreelight Power Pvt. Ltd.
 Silicon Cables Suppliers in Vadodara | Shreelight Power Pvt. Ltd. Silicon Cables Suppliers in Vadodara | Shreelight Power Pvt. Ltd.
Silicon Cables Suppliers in Vadodara | Shreelight Power Pvt. Ltd.
 
Hensel company profile catalogue
Hensel company profile catalogueHensel company profile catalogue
Hensel company profile catalogue
 
Sommer cable catalogue section 3
Sommer cable catalogue section 3Sommer cable catalogue section 3
Sommer cable catalogue section 3
 
Eltherm ELW-Q Heat Trace Cable - Spec Sheet
Eltherm ELW-Q Heat Trace Cable - Spec SheetEltherm ELW-Q Heat Trace Cable - Spec Sheet
Eltherm ELW-Q Heat Trace Cable - Spec Sheet
 
Master low-voltage saudi cable co.
Master low-voltage saudi cable co.Master low-voltage saudi cable co.
Master low-voltage saudi cable co.
 
421-cable glands
421-cable glands421-cable glands
421-cable glands
 
The Elektro Tipp - DK Cable Junction Boxes
The Elektro Tipp - DK Cable Junction BoxesThe Elektro Tipp - DK Cable Junction Boxes
The Elektro Tipp - DK Cable Junction Boxes
 
Rotronic HygroFlex5-EX - HF5-EX Hazardous Area Humidity & Temperature Sensors...
Rotronic HygroFlex5-EX - HF5-EX Hazardous Area Humidity & Temperature Sensors...Rotronic HygroFlex5-EX - HF5-EX Hazardous Area Humidity & Temperature Sensors...
Rotronic HygroFlex5-EX - HF5-EX Hazardous Area Humidity & Temperature Sensors...
 

More from Thorne & Derrick International

Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Thorne & Derrick International
 
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptTHORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptThorne & Derrick International
 
The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018Thorne & Derrick International
 
3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick InternationalThorne & Derrick International
 
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-AThorne & Derrick International
 
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...Thorne & Derrick International
 
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Thorne & Derrick International
 
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RowePepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RoweThorne & Derrick International
 
Ultrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandUltrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandThorne & Derrick International
 
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DSIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DThorne & Derrick International
 
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...Thorne & Derrick International
 
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetFiloform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetThorne & Derrick International
 

More from Thorne & Derrick International (20)

Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...
 
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptTHORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
 
The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018
 
3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International
 
CATU Electrical Safety Catalogue
CATU Electrical Safety CatalogueCATU Electrical Safety Catalogue
CATU Electrical Safety Catalogue
 
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
 
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
 
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
 
Roxtec Cable Transit - B Frame Dimensional Drawing
Roxtec Cable Transit - B Frame Dimensional DrawingRoxtec Cable Transit - B Frame Dimensional Drawing
Roxtec Cable Transit - B Frame Dimensional Drawing
 
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RowePepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
 
T&D Experts In Equipment For Explosive Atmospheres
T&D Experts In Equipment For Explosive AtmospheresT&D Experts In Equipment For Explosive Atmospheres
T&D Experts In Equipment For Explosive Atmospheres
 
Ultrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandUltrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification Demand
 
Emtelle Fibre Optic Cables - Product Catalogue 2016
Emtelle Fibre Optic Cables - Product Catalogue 2016Emtelle Fibre Optic Cables - Product Catalogue 2016
Emtelle Fibre Optic Cables - Product Catalogue 2016
 
Thorne & Derrick Process Heating Brochure 2016
Thorne & Derrick Process Heating Brochure 2016Thorne & Derrick Process Heating Brochure 2016
Thorne & Derrick Process Heating Brochure 2016
 
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DSIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
 
Ripley Utility Tool Cable Preparation Tools
Ripley Utility Tool Cable Preparation ToolsRipley Utility Tool Cable Preparation Tools
Ripley Utility Tool Cable Preparation Tools
 
RIDGID micro CD100 Combustible Gas Detector
RIDGID micro CD100 Combustible Gas DetectorRIDGID micro CD100 Combustible Gas Detector
RIDGID micro CD100 Combustible Gas Detector
 
Itron Fact Sheet
Itron Fact SheetItron Fact Sheet
Itron Fact Sheet
 
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
 
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetFiloform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
 

Recently uploaded

Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j
 
Slack Application Development 101 Slides
Slack Application Development 101 SlidesSlack Application Development 101 Slides
Slack Application Development 101 Slidespraypatel2
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Patryk Bandurski
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsMark Billinghurst
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhisoniya singh
 
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersEnhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersThousandEyes
 
Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machinePadma Pradeep
 
How to Remove Document Management Hurdles with X-Docs?
How to Remove Document Management Hurdles with X-Docs?How to Remove Document Management Hurdles with X-Docs?
How to Remove Document Management Hurdles with X-Docs?XfilesPro
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Alan Dix
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticscarlostorres15106
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsMemoori
 
Maximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxMaximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxOnBoard
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreternaman860154
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 
SIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge GraphSIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge GraphNeo4j
 
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 3652toLead Limited
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationMichael W. Hawkins
 

Recently uploaded (20)

Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
 
Slack Application Development 101 Slides
Slack Application Development 101 SlidesSlack Application Development 101 Slides
Slack Application Development 101 Slides
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR Systems
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
 
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersEnhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
 
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptxE-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
 
Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machine
 
How to Remove Document Management Hurdles with X-Docs?
How to Remove Document Management Hurdles with X-Docs?How to Remove Document Management Hurdles with X-Docs?
How to Remove Document Management Hurdles with X-Docs?
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial Buildings
 
Maximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxMaximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptx
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreter
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 
SIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge GraphSIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge Graph
 
The transition to renewables in India.pdf
The transition to renewables in India.pdfThe transition to renewables in India.pdf
The transition to renewables in India.pdf
 
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 

Hensel DK Cable Junction Boxes - 1.5mm² up to 240 mm² IP 54-67

  • 1. 15 DK Cable Junction Boxes DK Cable Junction Boxes - 1.5 up to 240 mm² - Degree of protection IP 54-67 - Cable Junction Boxes are VDE tested in accordance with IEC 60670-22 i Assembling videos
  • 2. 16 DK Cable Junction Boxes Content Criteria for selecting 18 - 19 Box walls 20 Box walls without knockouts from 1.5 up to 50 mm2 IP 65 box walls without knockouts, can be drilled individually for customized requirements - without terminals 33 - 34 - without terminals, for electrical equipment up to 63 A 35 - 36 - Accessories 37 - 39 With or without terminals from 1.5 up to 240 mm2 IP 65/IP 55 cable entry via metric knockouts - with terminals for copper conductors 24 - 29 - without terminals 30 - 31 With FIXCONNECT® plug-in technology for copper conductors from 1.5 up to 16 mm2 IP 65/IP 55 cable entry via metric knockouts 22 For aluminium- (Alu) and copper (Cu) conductors from 1.5 up to 240 mm2 IP 65/55 cable entry via metric knockouts - with terminal blocks for aluminium- (Alu) and copper (Cu) conductors 54 - 60 Cable entry via elastic membranes and integrated M20 thread up to 4 mm2 IP 55 - without terminals 41 - with terminals for copper conductors 41 Cable entry via cable, cable trunking and conduits from 1.5 up to 4 mm2 IP 54 - with terminals for copper conductors 43 - without terminals, Accessories 44 Cable entry via elastic membranes from 1.5 up to 4 mm2 IP 55 - with terminals for copper conductors, grey RAL 7035 46 - without terminals, grey RAL 7035 47 - with terminals for copper conductors, white RAL 9016 48 - without terminals, white RAL 9016, Accessories 49 Cable entry via elastic membranes from the rear and by box walls and lid from 1.5 up to 2.5 mm2 IP 55 for the clip-on attachment - with terminals for copper conductors, grey RAL 7035 51 - without terminals, grey RAL 7035 51 - with terminals for copper conductors, white RAL 9016 52 - without terminals, white RAL 9016 52 "Weatherproof" - for outdoor installation - harsh environment and/or outdoor from 1.5 up to 50 mm2 IP 66 cable/conduit entry via metric knockouts - with / without terminals, colours grey RAL 7032, black RAL 9011 62 - 69 box walls without knockouts - without terminals, colours grey RAL 7032, black RAL 901 71 - 74
  • 3. 17 DK Cable Junction Boxes Content Additional information and planning tools (e.g. CAD parts libraries) can be found on the Internet at www.hensel-electric.in "Waterproof" - for outdoor installation - harsh environment and/or outdoor from 1,5 up to 10 mm2 cable entry via metric knockouts - for encapsulating, colours grey RAL 7032, black RAL 9011 NEW 80 - 84 Tested for intrinsic fire resistance from 0.5 up to 16 mm2 IP 65 / IP 66 - material: duroplast, cable entry via included grommets, IP 65 94 - 95, 101 - material: sheet steel, powder-coated, cable entry via mounted grommets, IP 66 96 - 100, 101 For special applications from 1.5 up to 25 mm2 IP 55 / IP 65 cable entry via metric knockouts - for security lighting circuits, with red lid 103 - for equipotential bonding conductors 104 With main line branch terminals from 25 up to 35 mm2 IP 55 / IP 65 cable/conduit entry via metric knockouts - with terminal blocks for copper conductors 25 mm² and 35 mm² 106 - 107 With terminal blocks for aluminium- (Alu) and copper conductors (Cu) from 1.5 up to 4 mm2 IP 65 cable/conduit entry via metric knockouts - Terminal boxes with terminal blocks 109 - 111 Accessories 113 - 121 "Weatherproof" - for outdoor installation - harsh environment and/or outdoor from 1.5 up to 50 mm2 IP 66 / IP 65 with UL/CSA approval, (Nema 4X) box walls without knockouts, can be drilled individually - without terminals 76 - 77 For offshore / heavy duty applications from 1.5 up to 35 mm2 IP 66 / IP 67 cable entry via metric knockouts - with / without terminals 86 - 90 box walls without knockouts - without terminals 91 - 92 Technical Details 123 - 134
  • 4. 18 DK Cable Junction Boxes Criteria for Selecting Applications Functions Branching and connecting of copper conduc- tors Branching and connecting of aluminium and copper conduc- tors  In rooms with dry climate  In damp and wet environments  Protected outdoors (refer to technical details)  On flameable parts of buildings  In buildings with mainly inflammable materials  In areas with a high risk of fire Pages 22-52 Pages 54-60  Cable trunking installation Pages 43-44  Intrinsic fire resistance Pages 94-101  "Waterproof" for encapsulating Pages 80-84  “Weatherproof”, for outdoor installation (harsh environment and/or outdoor)  Improved behaviour in cases of fire “flame-resistant” and “halogen-free” Pages 62-74  Offshore applications Pages 86-92  Security lighting circuits Page 103  Equipotential bonding Page 104  UL Approval Page 76-77  DNV Approval  Germanisch Lloyd  Russian Maritime Register of Shipping Pages 62-92 PA
  • 5. 19 DK Cable Junction Boxes Criteria for Selecting Connecting solid conductors and stranded conduc- tors Combining multi- ple control wires to one control cable 2 circuits in one box Main line branch terminals Without terminals Box walls without knockouts Page 54-55 Pages 109-111 Pages 109-111 Pages 43-44 DP 9220, DP 9221, DP 9222 Page 106-107 Pages 30-36, Page 41 DN 2000, DN 2030, Page 44, 47 Page 48 DE 9321, Page 49, Page 51 DE 9220, Page 52 DE 9221, Pages 64-65, 68-69, 71-74, 76-77, 89-92 Page 103 D 9220, D 9240 Pages 33-36 all Boxes, Pages 71-74, 76-77 Page 91-92 Pages 43-44 DP 9220, DP 9221, DP 9222 Page 44 Pages 64-65 Pages 68-69 Pages 71-74 Pages 71-74 Pages 89-92 Page 91-92 Page 76-77 Pages 64-65, 68-69 Pages 71-74, 89-92 Pages 71-74, 89-92
  • 6. 20 Assignment of box walls: The assignment of box walls is effected via wall symbols that are assigned to each product. The individual figures 2 give an indication, which wall is concerned. Wand 4 6 5 5 Wall 18 4 x M 25 3 x M 40/50 Wall 19 8 x M 32 4 x M 40/50 Wall 20 2 x M 20 10 x M 25 1 x M 32/40 Wall 21 1 x M 20 4 x M 25 1 x M 32/40 3 x M 40/50 Wall 22 1 x Elastic membranes Wall 23 2 x Elastic membranes Wall 24 3 x Elastic membranes Wall 1 1 x M 20 Wall 2 1 x M 20/25 Wand 3 2 x M 20 Wall 4 2 x M 20/25 Wall 5 1 x M 20/25 1 x M 25/32 Wall 6 2 x M 25/32 Wall 7 2 x M 32 Wall 8 2 x M 32/40 Wall 9 2 x M 40 Wall 10 2 x M 20/25 1 x M 25/32 Wall 11 2 x M 20/25 1 x M 32/40 Wall 12 1 x M 20/25 1 x M 25/32 1 x M 40/50 Wall 13 1 x M 20/25 2 x M 40/50 Wall 14 3 x M 25/32 Wall 15 2 x M 25/32 1 x M 40/50 Wall 16 3 x M 32/40 Wall 17 4 x M 25/32 1 x M 40/50 Wall 25 1 x Removable- system Wall 26 2 x Removable- system Wall 27 3 x Removable- system Wall 28 4 x Removable- system DK Cable junction boxes Box Walls All box walls are listed in the fold-out of the coverpages. Wall 29 1 x M 63 Wall 30 2 x M 50 Wall 31 4 x up to Ø 16 mm 1 x up to Ø 35 mm
  • 7. 21 DK Cable Junction Boxes with Terminals in Plug-in Technology Cable Entry via Metric Knockouts  Plenty of space for the wiring: Wiring facilities both below the DIN rails and between the terminals.  Different conductor types - rigid (r) and flexible (f) without treatment of conduc- tors - can be connected in one terminal.  Conductors can be directly connected and disconnected with installed terminal.  Stainless steel cover screws with quick fastening metric thread. Reducing cover fixing time.  Burning behaviour: Glow wire test according to IEC 60 695-2-11: 750 °C, flame-retardant, self-extinguishing  Labelling system for circuit description  Label template on the Internet at www.hensel-electric.de - in the ’Downloads’ area.
  • 8. 22 DK Cable Junction Boxes with Terminals in Plug-in Technology Cable Entry via Metric Knockouts KC 9045 Wall 10 10 6 5 1.5-4 mm², Cu 3~  FIXCONNECT® plug-in terminal technology  5-pole per pole 4 x 1 x 1,5-4 mm² sol/f, terminal technology, see annex DK Cable junction boxes  included cable entry: 4 ESM 25, sealing range Ø 9-17 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 32 A 139 119 70 KC 9255 Wall 16 11 8 8 2.5-10 mm², Cu 3~  FIXCONNECT® plug-in terminal technology  5-pole per pole 4 x 1 x 2.5-10 mm² r/f  included cable entry: 3 ESM 32, sealing range Ø 9-23 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 50 A 98 160 200 KC 9355 Wall 13 13 15 15 2.5-16 mm², Cu 3~  FIXCONNECT® plug-in terminal technology  5-pole per pole 4 x 1 x 2.5-16 mm² r/f  included cable entry: 3 ESM 40, sealing range Ø 17-30 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 76 A 117260 210
  • 9. 23 DK Cable Junction Boxes Cable Entry via Metric Knockouts  Variable terminal mounting positions (5 positions) and new terminal technology  Included accessories as listed: grommets ESM = IP 55  Hensel cable junction boxes can in general also be used in poor environmental conditions by using IP 65 cable glands AKM/ASM.  Stainless steel cover screws with quick fastening metric thread. Reducing cover fixing time.  Burning behaviour: Glow wire test according to IEC 60 695-2-11: 750 °C / 960 °C, flame-retardant, self-extinguishing  Labelling system for circuit description  Label template on the Internet at www.hensel-electric.de - in the ’Downloads’ area.
  • 10. 24 DK Cable Junction Boxes Cable Entry via Metric Knockouts D 9025 Wall 3 1 3 3 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  included cable entry: 4 ESM 20, sealing range Ø 6-13 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 5388 88 D 9125 Wall 3 1 3 3 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  included cable entry: 4 ESM 20, sealing range Ø 6-13 mm  with external fixing  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 5388 88 D 9045 Wall 4 2 4 4 1.5-4 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol, 2 x 6 mm² sol  included cable entry: 4 ESM 25, sealing range Ø 9-17 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 98 61 98 D 9145 Wall 3 1 3 3 1.5-4 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol, 2 x 6 mm² sol  included cable entry: 4 ESM 20, sealing range Ø 6-13 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 98 61 98
  • 11. 25 DK Cable Junction Boxes Cable Entry via Metric Knockouts K 9065 Wall 10 10 6 5 2.5-6 mm², Cu 3~  with terminals  5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol, 2 x 10 mm² sol  included cable entry: 3 ESM 32, sealing range Ø 9-23 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,5 Nm 139 119 70 K 9105 Wall 14 10 6 6 4-10 mm², Cu 3~  with terminals  5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol, 4 x 10 mm² sol, 2 x 16 mm² s  included cable entry: 3 ESM 32, sealing range Ø 9-23 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 63 A tightening torque for terminal 2,0 Nm 82167 125 K 9255 Wall 16 11 8 8 10-25 mm², Cu 3~  with terminals  5-pole per pole 6 x 10 mm² sol, 4 x 16 mm² s, 4 x 25 mm² s, 2 x 35 mm² s  included cable entry: 3 ESM 40, sealing range Ø 17-30 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 102 A tightening torque for terminal 3,0 Nm 98 160 200 K 9502 Wall 12 12 17 17 10-35 mm², Cu 3~  with terminals  5-pole per pole 4 x 10 mm² sol, 4 x 16 mm² s, 4 x 25 mm² s, 2 x 35 mm² s  included cable entry: 3 ESM 40, sealing range Ø 17-30 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 102 A tightening torque for terminal 3,0 Nm 310 210 117
  • 12. 26 DK Cable Junction Boxes Cable Entry via Metric Knockouts K 9504 Wall 12 12 17 17 16-50 mm², Cu 3~  with terminals  4-pole per polel 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s, 4 x 50 mm² s  cable entry via knockouts, order AKM/ASM separately (refer to index cable entry systems)  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 150 A tightening torque for terminal 12,0 Nm 310 210 117 K 9505 Wall 12 12 17 17 16-50 mm², Cu 3~  with terminals  5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s, 4 x 50 mm² s  cable entry via knockouts, order AKM/ASM separately (refer to index cable entry systems)  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 150 A tightening torque for terminal 12,0 Nm 310 210 117 K 7055 Wall 20 20 21 21 16-50 mm², Cu 3~  with terminals  5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s, 4 x 50 mm² s  sealable  Order cable glands, flanges and other accessories separately as required  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 150 A tightening torque for terminal 12,0 Nm 450 300 170 K 9355 Wall 15 15 13 13 16-35 mm², Cu 3~  with terminals  5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s, 2 x 50 mm² s  included cable entry: 3 ESM 40, sealing range Ø 17-30 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 125 A tightening torque for terminal 12,0 Nm 117 260 210
  • 13. 27 DK Cable Junction Boxes Cable Entry via Metric Knockouts K 7004 Wall 20 20 21 21 16-70 mm², Cu 3~  with terminals  4-pole per pole 4 x 16-70 mm² s  sealable  Order cable glands, flanges and other accessories separately as required  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 216 A tightening torque for terminal 10,0 Nm 450 300 170 K 7005 Wall 20 20 21 21 16-70 mm², Cu 3~  with terminals  5-pole per polel 4 x 16-70 mm² s  sealable  Order cable glands, flanges and other accessories separately as required  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 216 A tightening torque for terminal 10,0 Nm 450 300 170 K 1204 Wall 20 20 21 21 16-150 mm², Cu/Alu 3~  with terminals  4-pole per pole 2 x 16-150 mm², 4 x 16-70 mm², conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 250 A tightening torque for terminal 20,0 Nm 450 300 170
  • 14. 28 DK Cable Junction Boxes Cable Entry via Metric Knockouts K 1205 Wall 20 20 21 21 16-150 mm², Cu/Alu 3~  with terminals  5-pole per pole 2 x 16-150 mm², 4 x 16-70 mm², conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 250 A tightening torque for terminal 20,0 Nm 450 300 170 K 2404 Wall 20 18 19 19 25-240 mm², Cu/Alu 3~  with terminals  4-pole per pole 2 x 25-185/240 mm², 4 x 25-120 mm², conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 400 A tightening torque for terminal 40,0 Nm 600 300 170
  • 15. 29 DK Cable Junction Boxes Cable Entry via Metric Knockouts K 2405 Wall 20 18 19 19 25-240 mm², Cu/Alu 3~  with terminals  5-pole per pole 2 x 25-185/240 mm², 4 x 25-120 mm², conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 400 A tightening torque for terminal 40,0 Nm 600 300 170
  • 16. 30 DK Cable Junction Boxes Cable Entry via Metric Knockouts D 9020 Wall 3 1 3 3  without terminals  included cable entry: 4 ESM 20, sealing range Ø 6-13 mm  for normal environment and protected outdoor 5388 88 D 9120 Wall 3 1 3 3  without terminals  with external fixing  included cable entry: 4 ESM 20, sealing range Ø 6-13 mm  for normal environment and protected outdoor 5388 88 D 9140 Wall 3 1 3 3  without terminals  included cable entry: 4 ESM 20, sealing range Ø 6-13 mm  for normal environment and protected outdoor 98 58 98 D 9040 Wall 4 2 4 4  without terminals  included cable entry: 4 ESM 25, sealing range Ø 9-17 mm  for normal environment and protected outdoor 98 61 98 K 9060 Wall 10 10 6 5  without terminals  included cable entry: 3 ESM 32, sealing range Ø 9-23 mm  for normal environment and protected outdoor 139 119 70 K 9100 Wall 14 10 6 6  without terminals  included cable entry: 3 ESM 32, sealing range Ø 9-23 mm  for normal environment and protected outdoor 82167 125
  • 17. 31 DK Cable Junction Boxes Cable Entry via Metric Knockouts K 9250 Wall 16 11 8 8  without terminals  included cable entry: 3 ESM 40, sealing range Ø 17-30 mm  for normal environment and protected outdoor 98 160 200 K 9350 Wall 13 13 15 15  without terminals  included cable entry: 3 ESM 40, sealing range Ø 17-30 mm  for normal environment and protected outdoor 117260 210 K 9500 Wall 12 12 17 17  without terminals  cable entry via knockouts, order AKM/ASM separately (refer to index cable entry systems)  for normal environment and protected outdoor 310 210 117
  • 18. 32 DK Cable Junction Boxes Box Walls without Knockouts Cable entries can be drilled individually.  Labelling system for circuit description  Label template on the Internet at www.hensel-electric.de - in the ’Downloads’ area.  Burning behaviour: Glow wire test according to IEC 60 695-2-11: 750 °C, flame-retardant, self-extinguishing  Stainless steel cover screws with quick fastening metric thread. Reducing cover fixing time.
  • 19. 33 DK Cable Junction Boxes Box Walls without Knockouts D 8020  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 20  for normal environment and protected outdoor wall thickness of the bottom part 2,3 mm 5388 88 D 8120  without terminals  with external fixing  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 20  for normal environment and protected outdoor wall thickness of the bottom part 2,3 mm 5388 88 D 8040  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 20  for normal environment and protected outdoor wall thickness of the bottom part 2,3 mm 98 58 98 K 8060  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 32  for normal environment and protected outdoor wall thickness of the bottom part 2,6 mm 139 119 70 K 8100  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 32  for normal environment and protected outdoor wall thickness of the bottom part 2,8 mm 82167 125
  • 20. 34 DK Cable Junction Boxes Box Walls without Knockouts K 8250  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 40  for normal environment and protected outdoor wall thickness of the bottom part 3 mm 98 160 200 K 8350  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 50  for normal environment and protected outdoor wall thickness of the bottom part 3 mm 117260 210 K 8500  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 50  for normal environment and protected outdoor wall thickness of the bottom part 3 mm 310 210 117
  • 21. 35 DK Cable Junction Boxes Box Walls without Knockouts K 0100  with transparent lid  lid fasteners for tool operation  box walls without knockouts  please order DIN rails or mounting plates additionally  for normal environment and protected outdoor rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm 300 170 150 K 0200  with transparent lid  lid fasteners for tool operation  box walls without knockouts  please order DIN rails or mounting plates additionally  for normal environment and protected outdoor rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm 300 170 300 K 0300  with transparent lid  lid fasteners for tool operation  box walls without knockouts  please order DIN rails or mounting plates additionally  for normal environment and protected outdoor rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm 300 170 450 K 0400  with transparent lid  lid fasteners for tool operation  box walls without knockouts  please order DIN rails or mounting plates additionally  for normal environment and protected outdoor rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm 600 300 170
  • 22. 36 DK Cable Junction Boxes Box Walls without Knockouts K 0101  with opaque lid  lid fasteners for tool operation  box walls without knockouts  please order DIN rails or mounting plates additionally  for normal environment and protected outdoor rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm 300 170 150 K 0201  with opaque lid  lid fasteners for tool operation  box walls without knockouts  please order DIN rails or mounting plates additionally  for normal environment and protected outdoor rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm 300 170 300 K 0301  with opaque lid  lid fasteners for tool operation  box walls without knockouts  please order DIN rails or mounting plates additionally  for normal environment and protected outdoor rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm 300 170 450 K 0401  with opaque lid  lid fasteners for tool operation  box walls without knockouts  please order DIN rails or mounting plates additionally  for normal environment and protected outdoor rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm 600 300 170
  • 23. 37 DK Cable Junction Boxes Empty Boxes Accessories for Cable Junction Boxes K0x0x Mi TS 15 DIN rail length 134 mm  in accordance with DIN EN 60 715  for Mi Empty box size 1  for equipment or terminals with clip-on mounting  with fixing screws 35 15 134 Mi TS 30 DIN rail length 284 mm  in accordance with DIN EN 60 715  for Mi empty box sizes 1 to 8  for equipment or terminals with clip-on mounting  with fixing screws 35 15 284 Mi TS 45 DIN rail length 434 mm  in accordance with DIN EN 60 715  for Mi empty box size 3  for equipment or terminals with clip-on mounting  with fixing screws 35 15 434 Mi TS 60 DIN rail length 584 mm  in accordance with DIN EN 60 715  for Mi empty box sizes 4 and 8  for equipment or terminals with clip-on mounting  with fixing screws 35 15 584 Mi MP 1 Mounting plate W 259 x H 115 mm  material thickness 4 mm  for Mi-Empty boxes sizes 1, 2, 3, 4  with fixing screws 259 115 Mi MP 2 Mounting plate W 265 x H 265 mm  material thickness 4 mm  for Mi-Empty boxes sizes 2 to 8  with fixing screws 265 265
  • 24. 38 DK Cable Junction Boxes Empty Boxes Accessories for Cable Junction Boxes K0x0x Mi MP 3 Mounting plate W 265 x H 415 mm  material thickness 4 mm  for Mi-Empty boxes sizes 3, 4  with fixing screws 415 265 Mi MP 4 Mounting plate W 265 x H 565 mm  material thickness 4 mm  for Mi-Empty boxes sizes 4, 8  with fixing screws 565 265 Mi PL 2 Sealing cap  2 sealing caps for converting the lid fasteners Mi SR 4 Conversion set for manual operation on tool operation  4 fastening covers Mi SN 4 Conversion set for converting lid fasteners from tool to manual operation  4 manual actuators
  • 25. 39 DK Cable Junction Boxes Empty Boxes Accessories for Cable Junction Boxes K0x0x Mi DV 01 Locking device insertion  only in connection with Mi PL 2, Mi SR 4 or Mi SN 4 Mi ZS 11 Lid lock with locking device I  Is being used instead of fasteners for hand or tool operation in order to prevent unauthorised opening of the lids  consisting of: cylinder lock, keys, locking device insertion, dust cover Mi ZS 12 Lid lock with locking device II  Is being used instead of fasteners for hand or tool operation in order to prevent unauthorised opening of the lids  consisting of: cylinder lock, keys, locking device insertion, dust cover Mi DR 04 Lid fastener for tool operation triangle 8 mm  is used instead of fasteners for hand- or tool operation, in order to make unauthorized opening of lids more difficult  4 locking devices with triangle 8 mm and key DS 1 Triangular key 8 mm Mi AL 40 4 stainless steel external brackets  for external fixing of enclosures
  • 26. 40 DK Cable Junction Boxes Cable Entry via Elastic Membranes and Integrated M 20 Thread  IP 55 with cable entry via elastic membranes.  IP 65 with ADM 20 cable gland without locknut. The gland is secured by an integrated M 20 thread.  Captive cover screws with quick-release lock.  Burning behaviour: Glow wire test according to IEC 60 695-2-11: 750 °C, flame-retardant, self-extinguishing
  • 27. 41 DK Cable Junction boxes Cable Entry via Elastic Membranes and Integrated M 20 Thread DN 2035 Wall 3 3 3 3 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  cable entry via elastic membranes and integrated M 20 thread  8 elastic membranes, closed, sealing range Ø 3-12 mm  included cable entry: 3 ADM 20, sealing range Ø 6,5-13,5 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 5185 85 DN 2005 Wall 3 3 3 3 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  cable entry via elastic membranes and integrated M 20 thread  8 elastic membranes, closed, sealing range Ø 3-12 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 5185 85 DN 2030 Wall 3 3 3 3  without terminals  cable entry via elastic membranes and integrated M 20 thread  8 elastic membranes, closed, sealing range Ø 3-12 mm  included cable entry: 3 ADM 20, sealing range Ø 6,5-13,5 mm 5185 85 DN 2000 Wall 3 3 3 3  without terminals  cable entry via elastic membranes and integrated M 20 thread  8 elastic membranes, closed, sealing range Ø 3-12 mm  for normal environment and protected outdoor 518585 ADM 20 ISO thread M 20 x 1.5  sealing range Ø 6,5-13,5 mm  with strain relief  for indoor - normal environment and (or) protected outdoor installation  ambient temperature - 25° to + 35° C  glow wire test IEC 60 695-2-11: 750° C tightening torque 2,0 Nm
  • 28. 42 DK Cable Junction Boxes Cable Entry via Knockouts for Cable Trunking and Conduit Installation  Simply cut out cable trunking wall to the required width.  The cables can be inserted from the front! No threading of cables neccessary!  Supplied accessory grommets DPS 02 = IP 54  The clean installation solution for cable trunking!  Removable trunking adapters for connection of cable trunkings to junction boxes.  Stainless steel cover screws with quick fastening metric thread. Reducing cover fixing time.  Burning behaviour: Glow wire test according to IEC 60 695-2-11: 750 °C, flame-retardant, self-extinguishing  Labelling system for circuit description  Label template on the Internet at www.hensel-electric.de - in the ’Downloads’ area.
  • 29. 43 DK Cable Junction Boxes Cable Entry via Knockouts for Cable Trunking and Conduit Installation DP 9025 Wall 26 25 26 26 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  for cable trunking and conduit installation  included cable entry: 4 DPS 02, sealing range Ø 10-13,5 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 5088 88 DP 9221 Wall 28 27 27 27 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  for cable trunking and conduit installation  included cable entry: 7 DPS 02, sealing range Ø 10-13,5 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 50139 119 DP 9222 Wall 28 27 27 27 1.5-2.5 mm², Cu 3~  with 2 terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  for cable trunking and conduit installation  included cable entry: 7 DPS 02, sealing range Ø 10-13,5 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 50139 119 DPC 9225 Wall 28 27 27 27 1.5-2.5 mm², Cu 3~  FIXCONNECT® plug-in terminal technology  5-pole per pole 4 x 1 x 1.5-2.5 mm² sol/f, terminal technology, see annex DK Cable junction boxes  for cable trunking and conduit installation  included cable entry: 4 DPS 02, sealing range Ø 10-13,5 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 32 A 50139 119
  • 30. 44 DK Cable Junction Boxes Cable Entry via Knockouts for Cable Trunking and Conduit Installation DP 9020 Wall 26 25 26 26  without terminals  for cable trunking and conduit installation  included cable entry: 4 DPS 02, sealing range Ø 10-13,5 mm  for normal environment and protected outdoor 5088 88 DP 9220 Wall 28 27 27 27  without terminals  for cable trunking and conduit installation  included cable entry: 7 DPS 02, sealing range Ø 10-13,5 mm  for normal environment and protected outdoor 50139 119 DPS 02 Removable grommet  degree of protection: IP 54 sealing range Ø 10-13.5 mm  for retrofitting  for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225 ERA 20 Removable conduit adapter  degree of protection: IP 54 sealing range Ø 10-13.5 mm  for wiring conduits M 20  for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225 EKA 20 Removable trunking adapter  degree of protection: IP 54 sealing range Ø 10-13.5 mm  for mini trunking up to 20 x 20 mm  for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225
  • 31. 45 DK Cable Junction Boxes Cable Entry via Elastic Membranes  No punching tool required - insert the conductor and it‘s done  Degree of protection IP 55  Grommet supplied for sealing membra- nes in case of modifications.  Box wall with 3 cable entries  Stainless steel cover screws with quick fastening metric thread. Reducing cover fixing time.  Burning behaviour: Glow wire test according to IEC 60 695-2-11: 750 °C, flame-retardant, self-extinguishing  Labelling system for circuit description  Label template on the Internet at www.hensel-electric.de - in the ’Downloads’ area.
  • 32. 46 DK Cable Junction Boxes Cable Entry via Elastic Membranes DE 9325 Wall 24 24 23 23 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  10 elastic membranes, closed cable entries, sealing range Ø 6.5-16 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 4788 88 DE 9345 Wall 24 24 23 23 1.5-4 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol, 2 x 6 mm² sol  10 elastic membranes, closed cable entries, sealing range Ø 6.5-18 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 98 98 52 DE 9335 Wall 24 24 23 23 1.5-4 mm², Cu 3~  terminals with wire protection  5-pole per pole 4 x 1.5 mm² sol/s/f, 4 x 2.5 mm² sol/s/f, 2 x 4 mm² sol/s/f  10 elastic membranes, closed cable entries, sealing range Ø 6.5-16 mm  with cable retention (2 pc.) for cable tie up to 6.5 mm width  for normal environment and protected outdoor rated insulation voltage AC/DC 500 V rated current 32 A tightening torque for terminal 0,8 Nm Dismantling length 6 mm 4788 88
  • 33. 47 DK Cable Junction Boxes Cable Entry via Elastic Membranes DE 9320 Wall 24 24 23 23  without terminals  10 elastic membranes, closed cable entries, sealing range Ø 6.5-16 mm  for normal environment and protected outdoor 4788 88 DE 9340 Wall 24 24 23 23  without terminals  10 elastic membranes, closed cable entries, sealing range Ø 6.5-18 mm  for normal environment and protected outdoor 98 98 52 DE 9330 Wall 24 24 23 23  without terminals  10 elastic membranes, closed cable entries, sealing range Ø 6.5-16 mm  with cable retention (2 pc.) for cable tie up to 6.5 mm width  for normal environment and protected outdoor 4788 88 DE 9350 Wall 24 24 23 23  without terminals  10 elastic membranes, closed cable entries, sealing range Ø 6.5-18 mm  with cable retention (2 pc.) for cable tie up to 6.5 mm width  for normal environment and protected outdoor 98 98 52
  • 34. 48 DK Cable Junction Boxes Cable Entry via Elastic Membranes DE 9326 Wall 24 24 23 23 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  10 elastic membranes, closed cable entries, sealing range Ø 6.5-16 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 4788 88 DE 9346 Wall 24 24 23 23 1.5-4 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol, 2 x 6 mm² sol  10 elastic membranes, closed cable entries, sealing range Ø 6.5-18 mm  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 98 98 52 DE 9336 Wall 24 24 23 23 1.5-2.5 mm², Cu 3~  terminals with wire protection  5-pole per pole 4 x 1.5 mm² sol/s/f, 4 x 2.5 mm² sol/s/f, 2 x 4 mm² sol/s/f  10 elastic membranes, closed cable entries, sealing range Ø 6.5-16 mm  with cable retention (2 pc.) for cable tie up to 6.5 mm width  for normal environment and protected outdoor rated insulation voltage AC/DC 500 V rated current 32 A tightening torque for terminal 0,8 Nm Dismantling length 11 mm 4788 88 DE 9321 Wall 24 24 23 23  without terminals  10 elastic membranes, closed cable entries, sealing range Ø 6.5-16 mm  for normal environment and protected outdoor 4788 88
  • 35. 49 DK Cable Junction Boxes Cable Entry via Elastic Membranes DE 9341 Wall 24 24 23 23  without terminals  10 elastic membranes, closed cable entries, sealing range Ø 6.5-18 mm  for normal environment and protected outdoor 98 98 52 DE 9331 Wall 24 24 23 23  without terminals  10 elastic membranes, closed cable entries, sealing range Ø 6.5-16 mm  with cable retention (2 pc.) for cable tie up to 6.5 mm width  for normal environment and protected outdoor 4788 88 DE 9351 Wall 24 24 23 23  without terminals  10 elastic membranes, closed cable entries, sealing range Ø 6.5-18 mm  with cable retention (2 pc.) for cable tie up to 6.5 mm width  for normal environment and protected outdoor 98 98 52 KHR 01 Cable retention for cable diameter 6,5 - 14 mm  set with 10 x 6 cable rentention rings  30 pieces for cable diameter 6,5 - 10 mm  30 pieces for cable diameter 10 - 14 mm KHR 02 Cable retention for cable diameter 10 - 16 mm  set with 10 x 6 cable rentention rings  30 pieces for cable diameter 10 - 14 mm  30 pieces for cable diameter 13 - 16 mm DK ZE 10 Cable retention  set with 10 pieces  for fixing in the bottom part of DK-cable junction boxes  cable retention with cable clip up to 6.5 mm
  • 36. 50 DK Cable Junction Boxes Cable Entry via Elastic Membranes in Bottom and Box Walls  Cable entry from the rear via elastic membranes in the bottom  Lid for clip-on attachment. Reducing cover fixing time  Flexible elastic membranes - no cable glands required. Push through and tight!  Cable entry via elastic membranes in box walls  Burning behaviour: Glow wire test according to IEC 60 695-2-11: 750 °C, flame-retardant, self-extinguishing
  • 37. 51 DK Cable Junction Boxes Cable Entry via Elastic Membranes in Bottom and Box Walls DE 9225 Wall 23 23 24 24 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  box walls with 10 elastic membranes, closed, sealing range Ø 3-14 mm, bottom with 2 elastic membranes, closed  lid with clip-on attachment  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 53 76 76 DE 9220 Wall 23 23 24 24  without terminals  box walls with 10 elastic membranes, closed, sealing range Ø 3-14 mm, bottom with 2 elastic membranes, closed  lid with clip-on attachment  with cable retention (2 pc.) for cable tie up to 6.5 mm width  for normal environment and protected outdoor 53 76 76 DK ZE 10 Cable retention  set with 10 pieces  for fixing in the bottom part of DK-cable junction boxes  cable retention with cable clip up to 6.5 mm KHR 01 Cable retention for cable diameter 6,5 - 14 mm  set with 10 x 6 cable rentention rings  30 pieces for cable diameter 6,5 - 10 mm  30 pieces for cable diameter 10 - 14 mm KHR 02 Cable retention for cable diameter 10 - 16 mm  set with 10 x 6 cable rentention rings  30 pieces for cable diameter 10 - 14 mm  30 pieces for cable diameter 13 - 16 mm DE MB 10 Assembly bracket  external brackets 10 units  material: thermoplastics  for quick installation of cable junction boxes DE 922. and DN 20.. 70 55 10 6ø6 18 10 6
  • 38. 52 DK Cable Junction Boxes Cable Entry via Elastic Membranes in Bottom and Box Walls DE 9226 Wall 23 23 24 24 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  box walls with 10 elastic membranes, closed, sealing range Ø 3-14 mm, bottom with 2 elastic membranes, closed  lid with clip-on attachment  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 53 76 76 DE 9221 Wall 23 23 24 24  without terminals  box walls with 10 elastic membranes, closed, sealing range Ø 3-14 mm, bottom with 2 elastic membranes, closed  lid with clip-on attachment  with cable retention (2 pc.) for cable tie up to 6.5 mm width  for normal environment and protected outdoor 53 76 76 DK ZE 10 Cable retention  set with 10 pieces  for fixing in the bottom part of DK-cable junction boxes  cable retention with cable clip up to 6.5 mm KHR 01 Cable retention for cable diameter 6,5 - 14 mm  set with 10 x 6 cable rentention rings  30 pieces for cable diameter 6,5 - 10 mm  30 pieces for cable diameter 10 - 14 mm KHR 02 Cable retention for cable diameter 10 - 16 mm  set with 10 x 6 cable rentention rings  30 pieces for cable diameter 10 - 14 mm  30 pieces for cable diameter 13 - 16 mm DE MB 10 Assembly bracket  external brackets 10 units  material: thermoplastics  for quick installation of cable junction boxes DE 922. and DN 20.. 70 55 10 6ø6 18 10 6
  • 39. 53 DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts  Degree of protection up to IP 65. In the case of twisted cables, cable glands are required in principle to achieve the degree of protection IP 54.  Separate clamping units for aluminium and copper conductors  Stainless steel cover screws with quick fastening metric thread. Reducing cover fixing time.  Burning behaviour: Glow wire test according to IEC 60 695-2-11: 750 °C, flame-retardant, self-extinguishing  Labelling system for circuit description.  Label template on the Internet at www.hensel-electric.de - in the ’Downloads’ area.
  • 40. 54 DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts D 9041 Wall 4 2 4 4 1.5-2.5 mm², Cu/Alu 3~  with terminals  5-pole per polel 4 x 1.5 mm² sol/f, 4 x 2.5 mm² sol/f, conductors are inserted into the screw-type terminal, terminal technology, see annex DK Cable junction boxes  included cable entry: 4 ESM 25, sealing range Ø 9-17 mm  In the case of twisted cables, cable glands are required in principle to achieve the degree of protection IP 54.  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 250 V current carrying capacity 20 A tightening torque for terminal 0,5 Nm 98 61 98 K 9061 Wall 10 10 6 5 1.5-4 mm², Cu/Alu 3~  with terminals  5-pole per pole 4 x 1.5 mm² sol/f, 4 x 2.5 mm² sol/f, 4 x 4 mm² sol/f, conductors are inserted into the screw-type terminal, terminal technology, see annex DK Cable junction boxes  included cable entry: 3 ESM 32, sealing range Ø 9-23 mm  In the case of twisted cables, cable glands are required in principle to achieve the degree of protection IP 54.  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 400 V current carrying capacity 20 A tightening torque for terminal 0,6 Nm 139 119 70
  • 41. 55 DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts K 9351 Wall 13 13 15 15 6-16 mm², Cu/Alu 3~  with terminals  5-pole per polel 4 x 6 mm² sol/f, 4 x 10 mm² sol/f, 4 x 16 mm² sol/s/f, conductors are inserted into the screw-type terminal, terminal technology, see annex DK Cable junction boxes  included cable entry: 3 ESM 40, sealing range Ø 17-30 mm  In the case of twisted cables, cable glands are required in principle to achieve the degree of protection IP 54.  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 76 A tightening torque for terminal 3,0 Nm 117260 210 KF 9251 Wall 16 11 8 8 1.5-50 mm², Cu/Alu 3~  with connecting terminal  5-pole per pole 2 x 1 x 1.5-50 mm², conductors are inserted into the screw-type terminal, terminal technology, see annex DK Cable junction boxes  included cable entry: 2 EDK 40, sealing range Ø 11-30 mm  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 160 A tightening torque for terminal 1.5 Nm 1.5-2.5 mm² 5.0 Nm 4-10 mm² 12,0 Nm 16-50 mm² 98 160 200
  • 42. 56 DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts KF 9501 Wall 12 12 17 17 1.5-50 mm², Cu/Alu 3~  with connecting terminal  5-pole per pole 2 x 1 x 1.5-50 mm², conductors are inserted into the screw-type terminal, terminal technology, see annex DK Cable junction boxes  included cable entry: 2 EDK 40, sealing range Ø 11-30 mm  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 160 A tightening torque for terminal 1.5 Nm 1.5-2.5 mm² 5.0 Nm 4-10 mm² 12,0 Nm 16-50 mm² 310 210 117 K 7051 Wall 20 20 21 21 2.5-50 mm², Cu/Alu 3~  with terminals  5-pole per pole 4 x 2.5-50 mm², conductors are inserted into the screw-type terminal, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 750 V current carrying capacity Cu, 150 A Alu, 120 A tightening torque for terminal 10,0 Nm 450 300 170
  • 43. 57 DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts K 7042 Wall 20 20 21 21 10-95 mm² Cu/Alu 3~  with terminals  4-pole per pole 2 x 10-95 mm², conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 160 A tightening torque for terminal 20,0 Nm 450 300 170 K 7052 Wall 20 20 21 21 10-95 mm² Cu/Alu 3~  with terminals  5-pole per pole 2 x 10-95 mm², conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 160 A tightening torque for terminal 20,0 Nm 450 300 170
  • 44. 58 DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts K 9951 Wall 20 20 21 21 6-95 mm², Cu/Alu 3~  with terminals  5-pole per pole 4 x 6-95 mm², conductors are inserted into the screw-type terminal, terminal technology, see annex DK Cable junction boxes  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 490 A tightening torque for terminal 12.0 Nm 6-25 mm² 22.0 Nm 35-95 mm² 450 300 170 K 1204 Wall 20 20 21 21 16-150 mm², Cu/Alu 3~  with terminals  4-pole per pole 2 x 16-150 mm², 4 x 16-70 mm², conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 250 A tightening torque for terminal 20,0 Nm 450 300 170
  • 45. 59 DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts K 1205 Wall 20 20 21 21 16-150 mm², Cu/Alu 3~  with terminals  5-pole per pole 2 x 16-150 mm², 4 x 16-70 mm², conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 250 A tightening torque for terminal 20,0 Nm 450 300 170 K 2404 Wall 20 18 19 19 25-240 mm², Cu/Alu 3~  with terminals  4-pole per pole 2 x 25-185/240 mm², 4 x 25-120 mm², conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 400 A tightening torque for terminal 40,0 Nm 600 300 170
  • 46. 60 DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts K 2405 Wall 20 18 19 19 25-240 mm², Cu/Alu 3~  with terminals  5-pole per pole 2 x 25-185/240 mm², 4 x 25-120 mm², conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 400 A tightening torque for terminal 40,0 Nm 600 300 170 K 2401 Wall 20 18 19 19 35-240 mm², Cu/Alu 3~  with terminals  5-pole per pole 4 x 35-240 mm², conductors are inserted into the screw-type terminal, terminal technology, see annex DK Cable junction boxes  sealable  Order cable glands, flanges and other accessories separately as required  Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.  for normal environment and protected outdoor rated insulation voltage AC/DC 690 V current carrying capacity 850 A tightening torque for terminal 26.0 Nm 35-120 mm² 55.0 Nm 150-240 mm² 600 300 170
  • 47. 61 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Cable Entry via Metric Knockouts  Degree of protection IP 66  Flame retardant, self-extinguishing, made of high-grade material: PC-GFS, glass-fibre reinforced thermoplastics, impact proof  KF-Cable junction boxes comply with regulatory restrictions for buildings with requirements regarding the structural fire protection!  halogen-free, silicone-free: low toxicity, low fume development  Stainless steel cover screws with quick fastening metric thread. Reducing cover fixing time.  Burning behaviour: Glow-wire test 960°C according to IEC 60 695-2-11, UL Subject 94: V-0 flame-retardant, self-extinguishing  Degree of protection IP 66 using cable glands ASS.. (colour black) or cable glands ASM.. (colour grey), available as an accessory.
  • 48. 62 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Cable Entry via Metric Knockouts KF 9025 Wall 3 1 3 3 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 5388 88 KF 9045 Wall 4 2 4 4 1.5-4 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol, 2 x 6 mm² sol  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 98 61 98 KF 9065 Wall 10 10 6 5 2.5-6 mm², Cu 3~  with terminals  5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol, 2 x 10 mm² sol  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V tightening torque for terminal 1,5 Nm 139 119 70 KF 9105 Wall 14 10 6 6 4-10 mm², Cu 3~  with terminals  5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol, 4 x 10 mm² sol, 2 x 16 mm² s  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V current carrying capacity 63 A tightening torque for terminal 2,0 Nm 82167 125
  • 49. 63 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Cable Entry via Metric Knockouts KF 9255 Wall 16 11 8 8 10-25 mm², Cu 3~  with terminals  5-pole per pole 6 x 10 mm² sol, 4 x 16 mm² s, 4 x 25 mm² s, 2 x 35 mm² s  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V current carrying capacity 102 A tightening torque for terminal 3,0 Nm 98 160 200 KF 9355 Wall 15 15 13 13 16-35 mm², Cu 3~  with terminals  5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s, 2 x 50 mm² s  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V current carrying capacity 125 A tightening torque for terminal 12,0 Nm 117 260 210 KF 9505 Wall 12 12 17 17 16-50 mm², Cu 3~  with terminals  5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s, 4 x 50 mm² s  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V current carrying capacity 150 A tightening torque for terminal 12,0 Nm 310 210 117
  • 50. 64 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Cable Entry via Metric Knockouts KF 9020 Wall 3 1 3 3  without terminals  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 5388 88 KF 9040 Wall 4 2 4 4  without terminals  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 98 61 98 KF 9060 Wall 10 10 6 5  without terminals  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 139 119 70 KF 9100 Wall 14 10 6 6  without terminals  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 82167 125 KF 9250 Wall 16 11 8 8  without terminals  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 98 160 200
  • 51. 65 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Cable Entry via Metric Knockouts KF 9350 Wall 13 13 15 15  without terminals  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 117260 210 KF 9500 Wall 12 12 17 17  without terminals  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 310 210 117
  • 52. 66 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Cable Entry via Metric Knockouts KF 5025 Wall 3 1 3 3 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 5388 88 KF 5045 Wall 4 2 4 4 1.5-4 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol, 2 x 6 mm² sol  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 98 61 98 KF 5065 Wall 10 10 6 5 2.5-6 mm², Cu 3~  with terminals  5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol, 2 x 10 mm² sol  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V tightening torque for terminal 1,5 Nm 139 119 70 KF 5105 Wall 14 10 6 6 4-10 mm², Cu 3~  with terminals  5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol, 4 x 10 mm² sol, 2 x 16 mm² s  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V current carrying capacity 63 A tightening torque for terminal 2,0 Nm 82167 125
  • 53. 67 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Cable Entry via Metric Knockouts KF 5255 Wall 16 11 8 8 10-25 mm², Cu 3~  with terminals  5-pole per pole 6 x 10 mm² sol, 4 x 16 mm² s, 4 x 25 mm² s, 2 x 35 mm² s  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V current carrying capacity 102 A tightening torque for terminal 3,0 Nm 98 160 200 KF 5355 Wall 15 15 13 13 16-35 mm², Cu 3~  with terminals  5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s, 2 x 50 mm² s  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V current carrying capacity 125 A tightening torque for terminal 12,0 Nm 117 260 210 KF 5505 Wall 12 12 17 17 16-50 mm², Cu 3~  with terminals  5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s, 4 x 50 mm² s  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" rated insulation voltage AC/DC 690 V current carrying capacity 150 A tightening torque for terminal 12,0 Nm 310 210 117
  • 54. 68 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Cable Entry via Metric Knockouts KF 5020 Wall 3 1 3 3  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 5388 88 KF 5040 Wall 4 2 4 4  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 98 61 98 KF 5060 Wall 10 10 6 5  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 139 119 70 KF 5100 Wall 14 10 6 6  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 82167 125 KF 5250 Wall 16 11 8 8  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 98 160 200
  • 55. 69 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Cable Entry via Metric Knockouts KF 5350 Wall 13 13 15 15  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 117260 210 KF 5500 Wall 12 12 17 17  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Outdoor - harsh environment and (or) outdoor" 310 210 117
  • 56. 70 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Box Walls without Knockouts  Cable entries can be drilled individually  Stainless steel cover screws with quick fastening metric thread. Reducing cover fixing time.  Labelling system for circuit description.  Label template on the Internet at www.hensel-electric.de - in the ’Downloads’ area.  Burning behaviour: Glow-wire test 960 °C according to IEC 60 695-2-11, UL Subject 94: V-0 flame-retardant, self-extinguishing
  • 57. 71 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Box Walls without Knockouts KF 8020  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 20  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 2,3 mm 5388 88 KF 8040  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 20  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 2,3 mm 98 58 98 KF 8060  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 32  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 2,6 mm 139 119 70 KF 8100  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 32  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 2,8 mm 82167 125
  • 58. 72 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Box Walls without Knockouts KF 8250  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 40  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 3 mm 98 160 200 KF 8350  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 50  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 3 mm 117260 210 KF 8500  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 50  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 3 mm 310 210 117
  • 59. 73 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Box Walls without Knockouts KF 4020  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 20  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 2,3 mm 5388 88 KF 4040  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 20  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 2,3 mm 98 58 98 KF 4060  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 32  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 2,6 mm 139 119 70 KF 4100  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 32  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 2,8 mm 82167 125
  • 60. 74 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Box Walls without Knockouts KF 4250  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 40  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 3 mm 98 160 200 KF 4350  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 50  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 3 mm 117260 210 KF 4500  without terminals  box walls without knockouts  wall surface can be drilled individually for cable entry max. M 50  "Outdoor - harsh environment and (or) outdoor" wall thickness of the bottom part 3 mm 310 210 117
  • 61. 75  Stainless steel cover screws with quick fastening metric thread. Reducing cover fixing time.  Labelling system for circuit description.  Label template on the Internet at www.hensel-electric.de - in the ’Downloads’ area.  Burning behaviour: Glow-wire test 960 °C according to IEC 60 695-2-11, UL Subject 94: V-0 flame-retardant, self-extinguishing DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Approved for United States and Canada (UL/CSA) Box Walls without Knockouts  Cable junction boxes with external brackets made of stainless steel.  Cable entries can be drilled individually.  Approved for United States and Canada
  • 62. 76 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Approved for United States and Canada (UL/CSA) Box Walls without Knockouts KF 7020  without terminals  with UL/CSA approval  box walls without knockouts  wall surface can be drilled individually for cable entry M 20, NPT 3/8" and NPT 1/2" wall thickness of the bottom part 2,3 mm external brackets 2 5388 88 KF 7040  without terminals  with UL/CSA approval  box walls without knockouts  wall surface can be drilled individually for cable entry M 20, NPT 3/8" and NPT 1/2" wall thickness of the bottom part 2,3 mm external brackets 2 98 58 98 KF 7060  without terminals  with UL/CSA approval  box walls without knockouts  wall surface can be drilled individually for cable entry M 20/25/32, NPT 3/8", NPT 1/2" and NPT 3/4" wall thickness of the bottom part 2,6 mm external brackets 2 139 119 70 KF 7100  without terminals  with UL/CSA approval  box walls without knockouts  wall surface can be drilled individually for cable entry M 20/25/32, NPT 3/8", NPT 1/2", NPT 3/4" and 1" wall thickness of the bottom part 2,8 mm external brackets 2 82167 125
  • 63. 77 DK Cable Junction Boxes “Weatherproof”, for Outdoor Installation Approved for United States and Canada (UL/CSA) Box Walls without Knockouts KF 7250  without terminals  with UL/CSA approval  box walls without knockouts  wall surface can be drilled individually for cable entry M 20/25/32, NPT 3/8", NPT 1/2", NPT 3/4" and 1" wall thickness of the bottom part 3 mm external brackets 4 98 160 200
  • 64. 78 DK Cable Junction Boxes “Waterproof”, for Encapsulating  Cable junction boxes for encapsulating  In case of re-installation or testing the sealing compound can be removed easily  Stainless steel cover screws with quick fastening metric thread. Reducing cover fixing time.  Scope of application: Ground level installations  Scope of application: Pump shafts  Scope of application: Flood areas close to rivers or unprotected outdoor installations which are in close proximity to the ground The ingress of water and formation of condensation are completely prevented. The sealing compound can be easily removed for subsequent installations or inspections.
  • 65. 79 DK Cable Junction Boxes “Waterproof”, for Encapsulating Permanent waterproof connection - Cable junction boxes for encapsulating in accordance with DIN VDE V 0606-22-100 Time and time again, electricians come across installation envi- ronments whereby the ingress of water into an enclosure must be safely excluded. Even enclo- sures which have a high degree of protection cannot guarantee this. The IP degree of protection allows the ingress of non-harmful quantities of water in the interior of an enclosure. Under extreme environmental conditions, for example, the ac- cumulation of condensation may result in damage to the electrical installation or devices or cause these to malfunction. Ventilation measures will often suffice to prevent harmful con- densation from forming. In many cases, however, ventila- tion is not possible, e.g. because the cable junction boxes are in- stalled close to rivers and water could enter through the vent holes. Which applications require waterproof connections?  Pump shafts  Ground-level installation ducts in outdoor areas  Flood areas close to rivers  Unprotected outdoor instal- lations which are in close proximity to the ground Why is the IP degree of pro- tection alone not sufficient?  All degrees of protection al- lowed Water ingress  The accumulation of con- densation cannot always be prevented  Ventilation measures cannot be applied in all environments The waterproof connection Sealing the cable junction boxes with a fast setting, permanently elastic sealing compound com- pletely the ingress of water and the excludes forming of condensation. The sealing compound fea- tures outstanding insula- tion properties. As the com- pound is transparent, it is possible for visual inspections of the installation to be carried out at any time. The durable elastic material is self-sealing, therefore it is also easy for the electrical con- nections to be tested after they have been sealed. The sealing compound can be easily removed for repairs, subse- quent installations or changes to installations. Another benefit: the sealed cable junction boxes also offer reliable protection against shock and vi- bration. The sealing compound does not, however, provide strain relief as it only adheres to material and does not stick together. Suit- able cable entries must also be used here, e.g. Hensel ASM. The ingress of water and formation of condensation are completely prevented. The sealing compound can be easily removed for subsequent installations or inspections. 1 2 3 4 5 6  Scope of application: Installations which are in close proximity to the ground or underground  Scope of application: Flood areas close to rivers  Scope of application: Ground level installations or underground
  • 66. 80 DK Cable Junction Boxes “Waterproof”, for Encapsulating KF WP 3025 Wall 3 1 3 3 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  cable junction box for encapsulating  for ground installation without live loads or in risk of condensation formation and ingress of liquids  installation permanently under water up to a depth of 1 meter possible  with sealing compound and sealing plug  in case of re-installation or testing the sealing compound can be removed easily  Check the expiry date of the sealing compound!  enclosure volume 250 ml Degree of protection For totally encapsulated cable junction boxes the degree of protection of enclosures according to DIN EN 60529 is not applicable. rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 5388 88 KF WP 3045 Wall 4 2 4 4 1.5-4 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol, 2 x 6 mm² sol  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  cable junction box for encapsulating  for ground installation without live loads or in risk of condensation formation and ingress of liquids  installation permanently under water up to a depth of 1 meter possible  with sealing compound and sealing plug  in case of re-installation or testing the sealing compound can be removed easily  Check the expiry date of the sealing compound!  enclosure volume 350 ml Degree of protection For totally encapsulated cable junction boxes the degree of protection of enclosures according to DIN EN 60529 is not applicable. rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 98 61 98
  • 67. 81 DK Cable Junction Boxes “Waterproof”, for Encapsulating KF WP 3065 Wall 10 10 6 5 2.5-6 mm², Cu 3~  with terminals  5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol, 2 x 10 mm² sol  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  cable junction box for encapsulating  for ground installation without live loads or in risk of condensation formation and ingress of liquids  installation permanently under water up to a depth of 1 meter possible  with sealing compound and sealing plug  in case of re-installation or testing the sealing compound can be removed easily  Check the expiry date of the sealing compound!  enclosure volume 750 ml Degree of protection For totally encapsulated cable junction boxes the degree of protection of enclosures according to DIN EN 60529 is not applicable. rated insulation voltage AC/DC 690 V tightening torque for terminal 1,5 Nm 139 119 70 KF WP 3105 Wall 14 10 6 6 4-10 mm², Cu 3~  with terminals  5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol, 4 x 10 mm² sol, 2 x 16 mm² s  cable entry via knockouts, order ASM separately (refer to index cable entry systems)  cable junction box for encapsulating  for ground installation without live loads or in risk of condensation formation and ingress of liquids  installation permanently under water up to a depth of 1 meter possible  with sealing compound and sealing plug  in case of re-installation or testing the sealing compound can be removed easily  Check the expiry date of the sealing compound!  enclosure volume 1200 ml Degree of protection For totally encapsulated cable junction boxes the degree of protection of enclosures according to DIN EN 60529 is not applicable. rated insulation voltage AC/DC 690 V current carrying capacity 63 A tightening torque for terminal 2,0 Nm 82167 125
  • 68. 82 DK Cable Junction Boxes “Waterproof”, for Encapsulating KF WP 2025 Wall 3 1 3 3 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  cable junction box for encapsulating  for ground installation without live loads or in risk of condensation formation and ingress of liquids  installation permanently under water up to a depth of 1 meter possible  with sealing compound and sealing plug  in case of re-installation or testing the sealing compound can be removed easily  Check the expiry date of the sealing compound!  enclosure volume 250 ml Degree of protection For totally encapsulated cable junction boxes the degree of protection of enclosures according to DIN EN 60529 is not applicable. rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 5388 88 KF WP 2045 Wall 4 2 4 4 1.5-4 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol, 2 x 6 mm² sol  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  cable junction box for encapsulating  for ground installation without live loads or in risk of condensation formation and ingress of liquids  installation permanently under water up to a depth of 1 meter possible  with sealing compound and sealing plug  in case of re-installation or testing the sealing compound can be removed easily  Check the expiry date of the sealing compound!  enclosure volume 350 ml Degree of protection For totally encapsulated cable junction boxes the degree of protection of enclosures according to DIN EN 60529 is not applicable. rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 98 61 98
  • 69. 83 DK Cable Junction Boxes “Waterproof”, for Encapsulating KF WP 2065 Wall 10 10 6 5 2.5-6 mm², Cu 3~  with terminals  5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol, 2 x 10 mm² sol  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  cable junction box for encapsulating  for ground installation without live loads or in risk of condensation formation and ingress of liquids  installation permanently under water up to a depth of 1 meter possible  with sealing compound and sealing plug  in case of re-installation or testing the sealing compound can be removed easily  Check the expiry date of the sealing compound!  enclosure volume 750 ml Degree of protection For totally encapsulated cable junction boxes the degree of protection of enclosures according to DIN EN 60529 is not applicable. rated insulation voltage AC/DC 690 V tightening torque for terminal 1,5 Nm 139 119 70 KF WP 2105 Wall 14 10 6 6 4-10 mm², Cu 3~  with terminals  5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol, 4 x 10 mm² sol, 2 x 16 mm² s  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  cable junction box for encapsulating  for ground installation without live loads or in risk of condensation formation and ingress of liquids  installation permanently under water up to a depth of 1 meter possible  with sealing compound and sealing plug  in case of re-installation or testing the sealing compound can be removed easily  Check the expiry date of the sealing compound!  enclosure volume 1200 ml Degree of protection For totally encapsulated cable junction boxes the degree of protection of enclosures according to DIN EN 60529 is not applicable. rated insulation voltage AC/DC 690 V current carrying capacity 63 A tightening torque for terminal 2,0 Nm 82167 125
  • 70. 84 DK Cable Junction Boxes “Waterproof”, for Encapsulating GH 0250 Set sealing compound, 250 ml  as spares  sealing compound for refilling KF WP x025 after changes or repairs  Check the expiry date of the sealing compound! GH 0350 Set sealing compound, 350 ml  as spares  sealing compound for refilling KF WP x045 after changes or repairs  Check the expiry date of the sealing compound! GH 0750 Set sealing compound, 750 ml  as spares  sealing compound for refilling KF WP x065 after changes or repairs  Check the expiry date of the sealing compound! GH 1200 set sealing compound, 1200 ml  as spares  sealing compound for refilling KF WP x105 after changes or repairs  Check the expiry date of the sealing compound!
  • 71. 85  Stainless steel cover screws with quick fastening metric thread. Reducing cover fixing time.  Labelling system for circuit description.  Label template on the Internet at www.hensel-electric.de - in the ’Downloads’ area. DK Cable Junction Boxes for Offshore Applications Cable Entry via Metric Knockouts  Degree of protection: IP 66 / IP 67 temporary submersion  up to 1 meter, max. 15 minutes  with cable glands ASS.. available as an accessory  Cable entries can be drilled individually  Saltwater-proof  UV-resistant  Material: - halogen free - impact resistant - low toxicity  Burning behaviour: UL Subject 94 = 5V
  • 72. 86 DK Cable Junction Boxes for Offshore Applications Cable Entry via Metric Knockouts KD 5025 Wall 3 1 3 3 1.5-2.5 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 5388 88 KD 5125 Wall 3 1 3 3 1.5-2.5 mm², Cu 3~ with external fixing  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 5388 88 KD 5045 Wall 4 2 4 4 1.5-4 mm², Cu 3~  with terminals  5-pole per pole 6 x 1.5 mm² sol, 4 x 2.5 mm² sol, 3 x 4 mm² sol, 2 x 6 mm² sol  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm 98 6198
  • 73. 87 DK Cable Junction Boxes for Offshore Applications Cable Entry via Metric Knockouts KD 5065 Wall 10 10 6 5 2.5-6 mm², Cu 3~  with terminals  5-pole per pole 4 x 2.5 mm² sol, 4 x 4 mm² sol, 3 x 6 mm² sol, 2 x 10 mm² sol  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V rated insulation voltage AC/DC 690 V tightening torque for terminal 1,5 Nm 139 119 70 KD 5105 Wall 14 10 6 6 4-10 mm², Cu 3~  with terminals  5-pole per pole 6 x 2.5 mm² sol, 4 x 4 mm² sol, 4 x 6 mm² sol, 4 x 10 mm² sol, 2 x 16 mm² s  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V rated insulation voltage AC/DC 690 V current carrying capacity 63 A tightening torque for terminal 2,0 Nm 82167 125 KD 5255 Wall 16 11 8 8 10-25 mm², Cu 3~  with terminals  5-pole per pole 6 x 10 mm² sol, 4 x 16 mm² s, 4 x 25 mm² s, 2 x 35 mm² s  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V rated insulation voltage AC/DC 690 V current carrying capacity 102 A tightening torque for terminal 3,0 Nm 98 160 200
  • 74. 88 DK Cable Junction Boxes for Offshore Applications Cable Entry via Metric Knockouts KD 5355 Wall 15 15 13 13 16-35 mm², Cu 3~  with terminals  5-pole per pole 6 x 16 mm² s, 4 x 25 mm² s, 4 x 35 mm² s, 2 x 50 mm² s  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V rated insulation voltage AC/DC 690 V current carrying capacity 125 A tightening torque for terminal 12,0 Nm 117 260 210
  • 75. 89 DK Cable Junction Boxes for Offshore Applications Cable Entry via Metric Knockouts KD 5020 Wall 3 1 3 3  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V 5388 88 KD 5120 Wall 3 1 3 3 with external fixing  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V 5388 88 KD 5040 Wall 4 2 4 4  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V 98 61 98 KD 5060 Wall 10 10 6 5  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V 139 119 70
  • 76. 90 DK Cable Junction Boxes for Offshore Applications Cable Entry via Metric Knockouts KD 5100 Wall 14 10 6 6  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V 82167 125 KD 5250 Wall 16 11 8 8  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V 98 160 200 KD 5350 Wall 13 13 15 15  without terminals  cable entry via knockouts, order ASS separately (refer to index cable entry systems)  "Offshore applications"  saltwater-proof  acid-resistant lid screws made of stainless steel  burning behaviour 960° C; UL Subject 94: 5 V 117260 210