1. Technical Specification SCM500GA
Gas Generator Set
We have the ability to produce Gas
generators from 30kW to 550kW with
the Cummins engine. It has so many
features such as widely adoption of
gas, high average effective pressure,
low heat load of gas engine, lower
heat, lower material use, good
emission, good starting performance,
good speed control, high reliability and
so on.
Technical Specification Data
Genset Model SCM500GA
Prime Rating (kW) 388
Genset
Standby Power (kW) 427
Heat Consumption (MJ/kWh) 11
Engine Manufacture CUMMINS
Engine Model KTA38--GA
Bore× Stock (mm) 159×159
Cylinder numbers 12
Rated Speed (r/min) 1500/1800
12-hour Power (kW) 414
Engine Intaking Method Turbocharged Inter-cooled
Reference Gas Consumption (m3/h) 125
Reference Air Consumption (m3/h) 1516
Coolant Heat (kW) 329.8
Coolant Flux (kg/s) 13.1
Fan-air Flux (m3/h) 22.7
Exhaust Flux (m3/h) 4857
Starting Method Electrical Starting
Alternator Siemens, Marathon etc
Alternator Model HCI5C
Rated Power (kW) 400
Frequency (HZ) 50/60
Rated Voltage (V) 400/230
Alternator
Rated Current (A) 722
Power Factor (cosφ) 0.8
Excitation Method Brushless
V-regulator Method Automatic
Phase/Connection 3 Phase 4 Wire, Y-connection
Net Weight (kg) 8478
Spec
Dimension (L×W×H mm) 4525×1900×2310