Study report on Auxiliary Power
Consumption in TPP
Prepared by Energy Manager / TPS II
M G Morshad , ADGM
STAGE I
(Date 28.09.16)
Date 28.09.16
Generation
(MU)
Average Load
(MW)
% APC APC (MU) APC (MW)
UNIT 1 4.614 192.25 8.46 0.390 16.26
UNIT 2 4.803 200.12 8.12 0.390 16.25
UNIT 3 4.850 202.08 8.54 0.414 17.26
TOTAL 14.267 594.45 8.37 1.195 49.77
Unit Consumption
1.195 MU
49.77 Ave MW
Station consumption
0.204 MU
8.52 Ave MW
Station ( Unit + Station) Consumption
1.399 MU
58.29 Ave MW
Station ( Unit + Station) APC ( %) 9.81%
STAGE II
(Date 28.09.16)
Date :28.09.16
Generation
(MU)
Average Load
(MW)
% APC APC (MU) APC (MW)
UNIT 4 4.710 196.25 7.96 0.375 15.62
UNIT 5 4.722 196.75 8.19 0.387 16.11
UNIT 6 4.729 197.04 7.96 0.376 15.68
UNIT 7 4.456 185.67 8.23 0.367 15.28
TOTAL 18.617 775.71 8.08 1.505 62.70
Unit Consumption
1.505 MU
62.70 Ave MW
Station consumption
0.218 MU
9.09 Ave MW
Station ( Unit + Station) Consumption
1.723 MU
71.79 Ave MW
% APC 9.25%
Typical Generation particulars
TPS II
(Date 28.09.16)
Total (Stage I + II) Generation
32.884 MU
1370.16 Ave MW
Total (Stage I + II)Unit Consumption
2.70 MU
112.47 Ave MW
Total (Stage I + II)Station consumption
0.42 MU
17.61 Ave MW
Total (Station + Unit) Consumption
3.122 MU
130.08 Ave MW
Station % APC 9.49%
Station %APC = [Fed to the bus (Export) – Station Consumption (Import)] / [Total Generation]
Typical Generation particulars
UAC - ST I SAC - ST I UAC - ST II SAC - ST II
AVE MW 49.00 8.50 62.00 9.09
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
MW
Typical - Average MW consumption
UAC – Unit Auxiliary Consumption
SAC – Station Auxiliary Consumption
Stage I Stage II
% UAC 8.38% 8.08%
%SAC 1.43% 1.17%
0.00%
1.00%
2.00%
3.00%
4.00%
5.00%
6.00%
7.00%
8.00%
9.00%
Comparative % UAC & % SAC
UAC & SAC of stage I units are higher than stage II units
HT LOAD CONSUMPTION
DESIGN
OPERATING
UNIT I UNIT II UNIT III
Date 28.09.2016 28.09.2016 28.09.2016
Time ( From - To) 11:30 To 12Hrs 11:30 To 12Hrs 11:30 To 12Hrs
UNIT LOAD 210 MW 203 213 210
KW KV PF FLC Amps KV KW Amps KV KW Amps KV KW
FD A 1400 6.6 0.85 145 45 6.6 435 55 6.6 531 54 6.6 522
FD B 1400 6.6 0.85 145 45 6.6 435 66 6.6 638 55 6.6 531
ID A 1800 6.6 0.81 195 181 6.6 1674 168 6.6 1554 188 6.6 1739
ID B 1800 6.6 0.81 195 175 6.6 1618 168 6.6 1554 184 6.6 1702
BFPA 3500 6.6 0.85 359 262 6.6 2558 0 6.6 0 0 6.6 0
BFP B 3500 6.6 0.85 359 0 6.6 0 274 6.6 2675 269 6.6 2626
BFP C 3500 6.6 0.85 359 262 6.6 2558 279 6.6 2724 288 6.6 2812
CEP A 515 6.6 0.83 54 43 6.6 408 0 6.6 0 0 6.6 0
CEP B 515 6.6 0.83 54 0 6.6 0 44 6.6 417 43 6.6 408
Mill A 710 6.6 0.82 76 0 6.6 0 48 6.6 450 46 6.6 431
Mill B 710 6.6 0.82 76 42 6.6 394 44 6.6 412 44 6.6 412
Mill C 710 6.6 0.82 76 41 6.6 384 44 6.6 412 47 6.6 441
Mill D 710 6.6 0.82 76 47 6.6 441 43 6.6 403 0 6.6 0
Mill E 710 6.6 0.82 76 47 6.6 441 44 6.6 412 44 6.6 412
Mill F 710 6.6 0.82 76 0 6.6 0 0 6.6 0 41 6.6 384
CWP A 1400 6.6 0.75 163 134 6.6 1149 133 6.6 1140 142 6.6 1217
CWP B 1400 6.6 0.75 163 138 6.6 1183 128 6.6 1097 142 6.6 1217
CWP C 1400 6.6 0.75 163 0 6.6 0 0 6.6 0 0 6.6 0
TOTAL MW 20.265 13.68 14.42 14.85
% APC 6.74% 6.77% 7.07%
Consumption MU 0.33 0.35 0.36
Total consumption (MU) 1.03
HT LOAD CONSUMPTION
DESIGN
OPERATING
UNIT - 4 UNIT - 5 UNIT - 6 UNIT-7
Date 28.09.2016 28.09.2016 28.09.2016 28.09.2016
Time ( From - To) 12:00 to 12:30 hrs 12:00 to 12:30 hrs 12:00 to 12:30 hrs 12:00 to 12:30 hrs
UNIT LOAD 210 MW 213 212 214 213
KW KV PF Amps Amps KV KW Amps KV KW Amps KV KW Amps KV KW
FD A 1200 6.6 0.81 130 57 6.5 520 70 6.5 638 54 6.5 492 65 6.5 593
FD B 1200 6.6 0.81 130 58 6.5 529 58 6.5 529 48 6.5 438 64 6.5 584
ID A 1800 6.6 0.8 197 147 6.5 1324 170 6.5 1531 155 6.5 1396 175 6.5 1576
ID B 1800 6.6 0.8 197 150 6.5 1351 160 6.5 1441 145 6.5 1306 170 6.5 1531
BFP A 4000 6.6 0.86 407 298 6.5 2885 300 6.5 2905 298 6.5 2885 263 6.5 2546
BFP B 4000 6.6 0.86 407 300 6.5 2905 0 6.5 0 0 6.5 0 0 6.5 0
BFP C 4000 6.6 0.86 407 0 6.5 0 310 6.5 3001 320 6.5 3098 301 6.5 2914
CEP A 600 6.6 0.78 67 52 6.5 457 0 6.5 0 0 6.5 0 54 6.5 474
CEP B 600 6.6 0.78 67 0 6.5 0 52 6.5 457 55 6.5 483 0 6.5 0
Mill A 600 6.6 0.69 76 0 6.5 0 48 6.5 373 44 6.5 342 50 6.5 388
Mill B 600 6.6 0.69 76 49 6.5 381 48 6.5 373 46 6.5 357 48 6.5 373
Mill C 600 6.6 0.69 76 43 6.5 334 51 6.5 396 0 6.5 0 49 6.5 381
Mill D 600 6.6 0.69 76 51 6.5 396 0 6.5 0 42 6.5 326 0 6.5 0
Mill E 600 6.6 0.69 76 48 6.5 373 45 6.5 350 46 6.5 357 50 6.5 388
Mill F 600 6.6 0.69 76 48 6.5 373 51 6.5 396 46 6.5 357 53 6.5 412
CWP A 1655 6.6 0.75 193 158 6.5 1334 170 6.5 1435 170 6.5 1435 161 6.5 1359
CWP B 1655 6.6 0.75 193 158 6.5 1334 160 6.5 1351 165 6.5 1393 160 6.5 1351
CWP C 1655 6.6 0.75 193 0 6.5 0 0 6.5 0 0 6.5 0 0 6.5 0
Total
MW
19.71 14.5 15.2 14.7 14.9
% APC 6.81% 7.16% 6.85% 6.98%
Consumption (MU) 0.35 0.36 0.35 0.36
Total consumption (MU) 1.42
Reasons for higher % APC
1.Partial loading of unit
2.Poor Lignite quality
7.80
7.90
8.00
8.10
8.20
8.30
8.40
8.50
8.60
8.70
0.00 50.00 100.00 150.00 200.00 250.00
Break even % UAC - UNIT I
MW % UAC
172.75 8.59
181.31 8.45
193.23 8.30
197.88 8.17
200.58 8.17
202.50 8.02
209.83 7.97
212.79 7.85
For obtaining % UAC less than 8% - Unit 1 has to operated with load higher than 202 MW
7.90
7.95
8.00
8.05
8.10
8.15
8.20
8.25
8.30
8.35
185.00 190.00 195.00 200.00 205.00 210.00 215.00
Break even % UAC – UNIT II
MW %UAC
190.88 8.27
195.86 8.29
207.96 8.07
209.58 8.00
213.01 7.94
For obtaining % UAC less than 8% - Unit 2 has to operated with load higher than 209 MW
8.00
8.10
8.20
8.30
8.40
8.50
8.60
194.00 196.00 198.00 200.00 202.00 204.00 206.00 208.00 210.00 212.00 214.00
Break even % UAC – UNIT III
MW %UAC
196.73 8.57
199.44 8.50
201.59 8.42
205.05 8.37
209.97 8.29
212.20 8.07
For obtaining % UAC less than 8% - Unit 3 has to operated with load higher than 209 MW
7.40
7.60
7.80
8.00
8.20
8.40
8.60
8.80
9.00
0.00 50.00 100.00 150.00 200.00 250.00
Break even %UAC - UNIT 4
MW %UAC
154.74 8.83
178.06 8.53
185.21 8.40
192.06 8.23
199.18 7.96
206.44 7.70
214.76 7.63
For obtaining % UAC less than 8% - Unit 4 has to operated with load higher than 192 MW
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
175.00 180.00 185.00 190.00 195.00 200.00 205.00 210.00 215.00
Break even % UAC- UNIT 5
MW %UAC
180.83 8.70
189.03 8.48
194.77 8.25
203.78 8.15
205.15 7.43
210.59 7.12
For obtaining % UAC less than 8% - Unit 5 has to operated with load higher than 203 MW
7.00
7.20
7.40
7.60
7.80
8.00
8.20
8.40
185.00 190.00 195.00 200.00 205.00 210.00 215.00
Break even % UAC - UNIT 6
MW %UAC
186.41 8.32
193.19 7.93
198.77 7.88
204.61 7.56
213.59 7.17
For obtaining % UAC less than 8% - Unit 6 has to operated with load higher than 186 MW
0
2
4
6
8
10
12
0 50 100 150 200 250
Break even % UAC - UNIT 7
MW %UAC
116.67 10.33
177.45 8.72
184.62 8.32
189.08 8.31
196.95 8.3
201.19 7.99
211.62 7.69
For obtaining % APC less than 8% - Unit 7 has to operated with load higher than 186 MW
UNIT 1 UNIT 2 UNIT 3 UNIT 4 UNIT 5 UNIT 6 UNIT 7
Series1 202 209 212 192 203 186 196
170
175
180
185
190
195
200
205
210
215
UnitLoad(MW) Break even load for obtaining %UAC less than 8%
UNIT 6 UNIT 4 UNIT 7 UNIT 1 UNIT 5 UNIT 2 UNIT 3
% UAC Trend
Highest Unit Auxiliary consumption in Unit -3
Lowest Unit Auxiliary Consumption in Unit - 6
9.6
9.8
10
10.2
10.4
10.6
10.8
0 200 400 600 800 1000 1200 1400
Station % APC
MW APC
780.96 10.71
1048.73 10.39
1239.82 10.21
1308.43 9.74
1318.96 9.68
For obtaining Station % APC less than 10% - Plant to be operated with load
higher than 1240 MW
y = 214.6x2 - 432.4x + 227.0
R² = 0.065
9.15
9.20
9.25
9.30
9.35
9.40
9.45
9.50
0.990 0.995 1.000 1.005 1.010 1.015 1.020 1.025
APC
Poly. (APC)
MW SLC APC
1442 0.993 9.41
1482 0.993 9.28
1447 0.997 9.23
1413 1.002 9.46
1477 1.003 9.20
1466 1.006 9.35
1459 1.006 9.26
1457 1.008 9.26
1434 1.011 9.35
1481 1.011 9.28
1474 1.013 9.33
1473 1.017 9.23
1452 1.020 9.30
1466 1.021 9.28
1441 1.023 9.44
MW SLC APC
Actual % APC
(214.6x2 - 432.4x + 227.0)
Higher % APC due to
lignite quality
1442 0.993 9.41 8.64 0.77
1482 0.993 9.28 8.64 0.64
1447 0.997 9.23 8.61 0.62
1413 1.002 9.46 8.59 0.87
1477 1.003 9.20 8.59 0.61
1466 1.006 9.35 8.58 0.77
1459 1.006 9.26 8.58 0.68
1457 1.008 9.26 8.58 0.68
1434 1.011 9.35 8.58 0.77
1481 1.011 9.28 8.58 0.70
1474 1.013 9.33 8.58 0.75
1473 1.017 9.23 8.59 0.64
1452 1.020 9.30 8.60 0.70
1466 1.021 9.28 8.60 0.68
1441 1.023 9.44 8.61 0.83
Average variation in % APC due to lignite quality 0.71

More Related Content

What's hot

Unit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdownUnit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdown
Nitin Mahalle
 
Fans in thermal power plants
Fans in thermal power plantsFans in thermal power plants
Fans in thermal power plants
SHIVAJI CHOUDHURY
 
Generator cooling and sealing system 2
Generator cooling and sealing system 2Generator cooling and sealing system 2
Generator cooling and sealing system 2
Mohammad Basid
 

What's hot (20)

THERMAL POWER PLANT EFFICIENCY AND HEAT RATE
THERMAL POWER PLANT EFFICIENCY AND HEAT RATETHERMAL POWER PLANT EFFICIENCY AND HEAT RATE
THERMAL POWER PLANT EFFICIENCY AND HEAT RATE
 
Unit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdownUnit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdown
 
Cogeneration power plant
Cogeneration power plantCogeneration power plant
Cogeneration power plant
 
Unit protection scheme
Unit protection schemeUnit protection scheme
Unit protection scheme
 
Boiler auxillaries in a coal fired power plant
Boiler auxillaries in a coal fired power plantBoiler auxillaries in a coal fired power plant
Boiler auxillaries in a coal fired power plant
 
A technical overview of thermal power plant
A technical overview of thermal power plantA technical overview of thermal power plant
A technical overview of thermal power plant
 
Fans in thermal power plants
Fans in thermal power plantsFans in thermal power plants
Fans in thermal power plants
 
Generator cooling and sealing system 2
Generator cooling and sealing system 2Generator cooling and sealing system 2
Generator cooling and sealing system 2
 
power plant ppt
power plant pptpower plant ppt
power plant ppt
 
210 mw turbine cycle heat rate
210 mw turbine cycle heat rate210 mw turbine cycle heat rate
210 mw turbine cycle heat rate
 
Energy conservation Activites of thermal power plant
Energy conservation Activites of thermal power plantEnergy conservation Activites of thermal power plant
Energy conservation Activites of thermal power plant
 
STUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANT
STUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANTSTUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANT
STUDY OF VARIOUS SYSTEMS IN 500MW THERMAL POWER PLANT
 
210 mw turbine cycle heat rate
210 mw turbine cycle heat rate210 mw turbine cycle heat rate
210 mw turbine cycle heat rate
 
Solar generation for APC
Solar generation for APC Solar generation for APC
Solar generation for APC
 
Thermal power plant
Thermal power plantThermal power plant
Thermal power plant
 
Heat balance diagram
Heat balance diagramHeat balance diagram
Heat balance diagram
 
vdocument.in_660-mw-turbine.ppt
vdocument.in_660-mw-turbine.pptvdocument.in_660-mw-turbine.ppt
vdocument.in_660-mw-turbine.ppt
 
Bowl mill in thermal power plant
Bowl mill in thermal power plantBowl mill in thermal power plant
Bowl mill in thermal power plant
 
Thermal Power Plant Simulator Hands-on Malfunctions
Thermal Power Plant Simulator Hands-on MalfunctionsThermal Power Plant Simulator Hands-on Malfunctions
Thermal Power Plant Simulator Hands-on Malfunctions
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergencies
 

Similar to APC in thermal power plant

8b80ade8 7b96-4114-9e36-76dcf21dc74d-150219134514-conversion-gate02 (1) (1) (...
8b80ade8 7b96-4114-9e36-76dcf21dc74d-150219134514-conversion-gate02 (1) (1) (...8b80ade8 7b96-4114-9e36-76dcf21dc74d-150219134514-conversion-gate02 (1) (1) (...
8b80ade8 7b96-4114-9e36-76dcf21dc74d-150219134514-conversion-gate02 (1) (1) (...
Shubham Garg
 
Review Week_12_Customer_PulauPanggung (PT.BAS).pptx
Review Week_12_Customer_PulauPanggung (PT.BAS).pptxReview Week_12_Customer_PulauPanggung (PT.BAS).pptx
Review Week_12_Customer_PulauPanggung (PT.BAS).pptx
noelmanroe1
 
Costo referencial de posecion y operacion
Costo referencial de posecion y operacionCosto referencial de posecion y operacion
Costo referencial de posecion y operacion
Deyvis Ubaldo
 
Complete catalogue
Complete catalogueComplete catalogue
Complete catalogue
Cathy Hsu
 
Applimotion uth motor_kits_datasheet
Applimotion uth motor_kits_datasheetApplimotion uth motor_kits_datasheet
Applimotion uth motor_kits_datasheet
Electromate
 
City council 8 6-13 ai 32 vv ground water group presentation
City council 8 6-13 ai 32 vv ground water group presentationCity council 8 6-13 ai 32 vv ground water group presentation
City council 8 6-13 ai 32 vv ground water group presentation
City of San Angelo Texas
 

Similar to APC in thermal power plant (20)

Bảng giá mitsubishi 2020
Bảng giá mitsubishi 2020Bảng giá mitsubishi 2020
Bảng giá mitsubishi 2020
 
8b80ade8 7b96-4114-9e36-76dcf21dc74d-150219134514-conversion-gate02 (1) (1) (...
8b80ade8 7b96-4114-9e36-76dcf21dc74d-150219134514-conversion-gate02 (1) (1) (...8b80ade8 7b96-4114-9e36-76dcf21dc74d-150219134514-conversion-gate02 (1) (1) (...
8b80ade8 7b96-4114-9e36-76dcf21dc74d-150219134514-conversion-gate02 (1) (1) (...
 
Weg vector-duty-motor-tenv
Weg vector-duty-motor-tenvWeg vector-duty-motor-tenv
Weg vector-duty-motor-tenv
 
Review W 26 & Plan Week 27 2022_MUM.pptx
Review W 26 & Plan Week 27 2022_MUM.pptxReview W 26 & Plan Week 27 2022_MUM.pptx
Review W 26 & Plan Week 27 2022_MUM.pptx
 
Kollmorgen pma series_catalog
Kollmorgen  pma  series_catalogKollmorgen  pma  series_catalog
Kollmorgen pma series_catalog
 
Review Week_12_Customer_PulauPanggung (PT.BAS).pptx
Review Week_12_Customer_PulauPanggung (PT.BAS).pptxReview Week_12_Customer_PulauPanggung (PT.BAS).pptx
Review Week_12_Customer_PulauPanggung (PT.BAS).pptx
 
Costo referencial de posecion y operacion
Costo referencial de posecion y operacionCosto referencial de posecion y operacion
Costo referencial de posecion y operacion
 
Complete catalogue
Complete catalogueComplete catalogue
Complete catalogue
 
ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...
ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...
ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...
 
upblast roof fan
upblast roof fanupblast roof fan
upblast roof fan
 
ABB POLIM-I..N High Voltage Surge Arresters AC up to 72 kV - AC Surge Arreste...
ABB POLIM-I..N High Voltage Surge Arresters AC up to 72 kV - AC Surge Arreste...ABB POLIM-I..N High Voltage Surge Arresters AC up to 72 kV - AC Surge Arreste...
ABB POLIM-I..N High Voltage Surge Arresters AC up to 72 kV - AC Surge Arreste...
 
ABB MWK High Voltage Surge Arresters AC 4kV - 44kV - AC Surge Arresters & Pr...
ABB MWK High Voltage Surge Arresters AC 4kV - 44kV -  AC Surge Arresters & Pr...ABB MWK High Voltage Surge Arresters AC 4kV - 44kV -  AC Surge Arresters & Pr...
ABB MWK High Voltage Surge Arresters AC 4kV - 44kV - AC Surge Arresters & Pr...
 
IE4Brochure Crompton Greaves
IE4Brochure Crompton GreavesIE4Brochure Crompton Greaves
IE4Brochure Crompton Greaves
 
Applimotion uth motor_kits_datasheet
Applimotion uth motor_kits_datasheetApplimotion uth motor_kits_datasheet
Applimotion uth motor_kits_datasheet
 
China shoto slide show
China shoto slide showChina shoto slide show
China shoto slide show
 
Motor Technical Brochure for ABB LT Motors LT
Motor Technical Brochure for ABB LT Motors LTMotor Technical Brochure for ABB LT Motors LT
Motor Technical Brochure for ABB LT Motors LT
 
Presentación energía linea industrial
Presentación energía linea industrialPresentación energía linea industrial
Presentación energía linea industrial
 
City council 8 6-13 ai 32 vv ground water group presentation
City council 8 6-13 ai 32 vv ground water group presentationCity council 8 6-13 ai 32 vv ground water group presentation
City council 8 6-13 ai 32 vv ground water group presentation
 
Samsung Twin rotary compressor R-410A / R-22
Samsung Twin rotary compressor R-410A / R-22Samsung Twin rotary compressor R-410A / R-22
Samsung Twin rotary compressor R-410A / R-22
 
MRM APRIL 2023.pptx
MRM APRIL 2023.pptxMRM APRIL 2023.pptx
MRM APRIL 2023.pptx
 

More from Molla Morshad

More from Molla Morshad (20)

Circulating water treatment project
Circulating water treatment projectCirculating water treatment project
Circulating water treatment project
 
Condition Monitoring of electrical machine
Condition Monitoring of electrical machine Condition Monitoring of electrical machine
Condition Monitoring of electrical machine
 
Condition Monitoring of electrical machine
Condition Monitoring of electrical machine Condition Monitoring of electrical machine
Condition Monitoring of electrical machine
 
Design turbo generator
Design turbo generatorDesign turbo generator
Design turbo generator
 
Turbo generator
Turbo generator Turbo generator
Turbo generator
 
electrical system
electrical system electrical system
electrical system
 
insulation monitoring in electrical machine
insulation monitoring in electrical machine insulation monitoring in electrical machine
insulation monitoring in electrical machine
 
smart grid
smart grid smart grid
smart grid
 
southern grid
southern grid southern grid
southern grid
 
Motor Bearings
Motor Bearings Motor Bearings
Motor Bearings
 
Electrical Motor
Electrical Motor Electrical Motor
Electrical Motor
 
Transformer oil analysis
Transformer oil analysisTransformer oil analysis
Transformer oil analysis
 
Transformer maintenance
Transformer maintenance Transformer maintenance
Transformer maintenance
 
ESP Rectifier transformer
ESP Rectifier transformerESP Rectifier transformer
ESP Rectifier transformer
 
Transformer Maintenance
Transformer Maintenance Transformer Maintenance
Transformer Maintenance
 
Resource
ResourceResource
Resource
 
Islamic prayer namaz
Islamic prayer namazIslamic prayer namaz
Islamic prayer namaz
 
Swachh bharat
Swachh bharatSwachh bharat
Swachh bharat
 
Basic concept of inventory management
Basic concept of inventory management Basic concept of inventory management
Basic concept of inventory management
 
Reactors
ReactorsReactors
Reactors
 

Recently uploaded

Teachers record management system project report..pdf
Teachers record management system project report..pdfTeachers record management system project report..pdf
Teachers record management system project report..pdf
Kamal Acharya
 

Recently uploaded (20)

"United Nations Park" Site Visit Report.
"United Nations Park" Site  Visit Report."United Nations Park" Site  Visit Report.
"United Nations Park" Site Visit Report.
 
Software Engineering - Modelling Concepts + Class Modelling + Building the An...
Software Engineering - Modelling Concepts + Class Modelling + Building the An...Software Engineering - Modelling Concepts + Class Modelling + Building the An...
Software Engineering - Modelling Concepts + Class Modelling + Building the An...
 
Introduction to Machine Learning Unit-4 Notes for II-II Mechanical Engineering
Introduction to Machine Learning Unit-4 Notes for II-II Mechanical EngineeringIntroduction to Machine Learning Unit-4 Notes for II-II Mechanical Engineering
Introduction to Machine Learning Unit-4 Notes for II-II Mechanical Engineering
 
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdfInvolute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
 
Electrical shop management system project report.pdf
Electrical shop management system project report.pdfElectrical shop management system project report.pdf
Electrical shop management system project report.pdf
 
Artificial Intelligence Bayesian Reasoning
Artificial Intelligence Bayesian ReasoningArtificial Intelligence Bayesian Reasoning
Artificial Intelligence Bayesian Reasoning
 
KIT-601 Lecture Notes-UNIT-5.pdf Frame Works and Visualization
KIT-601 Lecture Notes-UNIT-5.pdf Frame Works and VisualizationKIT-601 Lecture Notes-UNIT-5.pdf Frame Works and Visualization
KIT-601 Lecture Notes-UNIT-5.pdf Frame Works and Visualization
 
Attraction and Repulsion type Moving Iron Instruments.pptx
Attraction and Repulsion type Moving Iron Instruments.pptxAttraction and Repulsion type Moving Iron Instruments.pptx
Attraction and Repulsion type Moving Iron Instruments.pptx
 
ANSI(ST)-III_Manufacturing-I_05052020.pdf
ANSI(ST)-III_Manufacturing-I_05052020.pdfANSI(ST)-III_Manufacturing-I_05052020.pdf
ANSI(ST)-III_Manufacturing-I_05052020.pdf
 
Theory for How to calculation capacitor bank
Theory for How to calculation capacitor bankTheory for How to calculation capacitor bank
Theory for How to calculation capacitor bank
 
BURGER ORDERING SYSYTEM PROJECT REPORT..pdf
BURGER ORDERING SYSYTEM PROJECT REPORT..pdfBURGER ORDERING SYSYTEM PROJECT REPORT..pdf
BURGER ORDERING SYSYTEM PROJECT REPORT..pdf
 
RESORT MANAGEMENT AND RESERVATION SYSTEM PROJECT REPORT.pdf
RESORT MANAGEMENT AND RESERVATION SYSTEM PROJECT REPORT.pdfRESORT MANAGEMENT AND RESERVATION SYSTEM PROJECT REPORT.pdf
RESORT MANAGEMENT AND RESERVATION SYSTEM PROJECT REPORT.pdf
 
Intelligent Agents, A discovery on How A Rational Agent Acts
Intelligent Agents, A discovery on How A Rational Agent ActsIntelligent Agents, A discovery on How A Rational Agent Acts
Intelligent Agents, A discovery on How A Rational Agent Acts
 
Arduino based vehicle speed tracker project
Arduino based vehicle speed tracker projectArduino based vehicle speed tracker project
Arduino based vehicle speed tracker project
 
solid state electronics ktu module 5 slides
solid state electronics ktu module 5 slidessolid state electronics ktu module 5 slides
solid state electronics ktu module 5 slides
 
Object Oriented Programming OOP Lab Manual.docx
Object Oriented Programming OOP Lab Manual.docxObject Oriented Programming OOP Lab Manual.docx
Object Oriented Programming OOP Lab Manual.docx
 
Natalia Rutkowska - BIM School Course in Kraków
Natalia Rutkowska - BIM School Course in KrakówNatalia Rutkowska - BIM School Course in Kraków
Natalia Rutkowska - BIM School Course in Kraków
 
Lect_Z_Transform_Main_digital_image_processing.pptx
Lect_Z_Transform_Main_digital_image_processing.pptxLect_Z_Transform_Main_digital_image_processing.pptx
Lect_Z_Transform_Main_digital_image_processing.pptx
 
Teachers record management system project report..pdf
Teachers record management system project report..pdfTeachers record management system project report..pdf
Teachers record management system project report..pdf
 
Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1
 

APC in thermal power plant

  • 1. Study report on Auxiliary Power Consumption in TPP Prepared by Energy Manager / TPS II M G Morshad , ADGM
  • 2. STAGE I (Date 28.09.16) Date 28.09.16 Generation (MU) Average Load (MW) % APC APC (MU) APC (MW) UNIT 1 4.614 192.25 8.46 0.390 16.26 UNIT 2 4.803 200.12 8.12 0.390 16.25 UNIT 3 4.850 202.08 8.54 0.414 17.26 TOTAL 14.267 594.45 8.37 1.195 49.77 Unit Consumption 1.195 MU 49.77 Ave MW Station consumption 0.204 MU 8.52 Ave MW Station ( Unit + Station) Consumption 1.399 MU 58.29 Ave MW Station ( Unit + Station) APC ( %) 9.81% STAGE II (Date 28.09.16) Date :28.09.16 Generation (MU) Average Load (MW) % APC APC (MU) APC (MW) UNIT 4 4.710 196.25 7.96 0.375 15.62 UNIT 5 4.722 196.75 8.19 0.387 16.11 UNIT 6 4.729 197.04 7.96 0.376 15.68 UNIT 7 4.456 185.67 8.23 0.367 15.28 TOTAL 18.617 775.71 8.08 1.505 62.70 Unit Consumption 1.505 MU 62.70 Ave MW Station consumption 0.218 MU 9.09 Ave MW Station ( Unit + Station) Consumption 1.723 MU 71.79 Ave MW % APC 9.25% Typical Generation particulars
  • 3.
  • 4.
  • 5. TPS II (Date 28.09.16) Total (Stage I + II) Generation 32.884 MU 1370.16 Ave MW Total (Stage I + II)Unit Consumption 2.70 MU 112.47 Ave MW Total (Stage I + II)Station consumption 0.42 MU 17.61 Ave MW Total (Station + Unit) Consumption 3.122 MU 130.08 Ave MW Station % APC 9.49% Station %APC = [Fed to the bus (Export) – Station Consumption (Import)] / [Total Generation] Typical Generation particulars
  • 6. UAC - ST I SAC - ST I UAC - ST II SAC - ST II AVE MW 49.00 8.50 62.00 9.09 0.00 10.00 20.00 30.00 40.00 50.00 60.00 70.00 MW Typical - Average MW consumption UAC – Unit Auxiliary Consumption SAC – Station Auxiliary Consumption
  • 7. Stage I Stage II % UAC 8.38% 8.08% %SAC 1.43% 1.17% 0.00% 1.00% 2.00% 3.00% 4.00% 5.00% 6.00% 7.00% 8.00% 9.00% Comparative % UAC & % SAC UAC & SAC of stage I units are higher than stage II units
  • 8. HT LOAD CONSUMPTION DESIGN OPERATING UNIT I UNIT II UNIT III Date 28.09.2016 28.09.2016 28.09.2016 Time ( From - To) 11:30 To 12Hrs 11:30 To 12Hrs 11:30 To 12Hrs UNIT LOAD 210 MW 203 213 210 KW KV PF FLC Amps KV KW Amps KV KW Amps KV KW FD A 1400 6.6 0.85 145 45 6.6 435 55 6.6 531 54 6.6 522 FD B 1400 6.6 0.85 145 45 6.6 435 66 6.6 638 55 6.6 531 ID A 1800 6.6 0.81 195 181 6.6 1674 168 6.6 1554 188 6.6 1739 ID B 1800 6.6 0.81 195 175 6.6 1618 168 6.6 1554 184 6.6 1702 BFPA 3500 6.6 0.85 359 262 6.6 2558 0 6.6 0 0 6.6 0 BFP B 3500 6.6 0.85 359 0 6.6 0 274 6.6 2675 269 6.6 2626 BFP C 3500 6.6 0.85 359 262 6.6 2558 279 6.6 2724 288 6.6 2812 CEP A 515 6.6 0.83 54 43 6.6 408 0 6.6 0 0 6.6 0 CEP B 515 6.6 0.83 54 0 6.6 0 44 6.6 417 43 6.6 408 Mill A 710 6.6 0.82 76 0 6.6 0 48 6.6 450 46 6.6 431 Mill B 710 6.6 0.82 76 42 6.6 394 44 6.6 412 44 6.6 412 Mill C 710 6.6 0.82 76 41 6.6 384 44 6.6 412 47 6.6 441 Mill D 710 6.6 0.82 76 47 6.6 441 43 6.6 403 0 6.6 0 Mill E 710 6.6 0.82 76 47 6.6 441 44 6.6 412 44 6.6 412 Mill F 710 6.6 0.82 76 0 6.6 0 0 6.6 0 41 6.6 384 CWP A 1400 6.6 0.75 163 134 6.6 1149 133 6.6 1140 142 6.6 1217 CWP B 1400 6.6 0.75 163 138 6.6 1183 128 6.6 1097 142 6.6 1217 CWP C 1400 6.6 0.75 163 0 6.6 0 0 6.6 0 0 6.6 0 TOTAL MW 20.265 13.68 14.42 14.85 % APC 6.74% 6.77% 7.07% Consumption MU 0.33 0.35 0.36 Total consumption (MU) 1.03
  • 9. HT LOAD CONSUMPTION DESIGN OPERATING UNIT - 4 UNIT - 5 UNIT - 6 UNIT-7 Date 28.09.2016 28.09.2016 28.09.2016 28.09.2016 Time ( From - To) 12:00 to 12:30 hrs 12:00 to 12:30 hrs 12:00 to 12:30 hrs 12:00 to 12:30 hrs UNIT LOAD 210 MW 213 212 214 213 KW KV PF Amps Amps KV KW Amps KV KW Amps KV KW Amps KV KW FD A 1200 6.6 0.81 130 57 6.5 520 70 6.5 638 54 6.5 492 65 6.5 593 FD B 1200 6.6 0.81 130 58 6.5 529 58 6.5 529 48 6.5 438 64 6.5 584 ID A 1800 6.6 0.8 197 147 6.5 1324 170 6.5 1531 155 6.5 1396 175 6.5 1576 ID B 1800 6.6 0.8 197 150 6.5 1351 160 6.5 1441 145 6.5 1306 170 6.5 1531 BFP A 4000 6.6 0.86 407 298 6.5 2885 300 6.5 2905 298 6.5 2885 263 6.5 2546 BFP B 4000 6.6 0.86 407 300 6.5 2905 0 6.5 0 0 6.5 0 0 6.5 0 BFP C 4000 6.6 0.86 407 0 6.5 0 310 6.5 3001 320 6.5 3098 301 6.5 2914 CEP A 600 6.6 0.78 67 52 6.5 457 0 6.5 0 0 6.5 0 54 6.5 474 CEP B 600 6.6 0.78 67 0 6.5 0 52 6.5 457 55 6.5 483 0 6.5 0 Mill A 600 6.6 0.69 76 0 6.5 0 48 6.5 373 44 6.5 342 50 6.5 388 Mill B 600 6.6 0.69 76 49 6.5 381 48 6.5 373 46 6.5 357 48 6.5 373 Mill C 600 6.6 0.69 76 43 6.5 334 51 6.5 396 0 6.5 0 49 6.5 381 Mill D 600 6.6 0.69 76 51 6.5 396 0 6.5 0 42 6.5 326 0 6.5 0 Mill E 600 6.6 0.69 76 48 6.5 373 45 6.5 350 46 6.5 357 50 6.5 388 Mill F 600 6.6 0.69 76 48 6.5 373 51 6.5 396 46 6.5 357 53 6.5 412 CWP A 1655 6.6 0.75 193 158 6.5 1334 170 6.5 1435 170 6.5 1435 161 6.5 1359 CWP B 1655 6.6 0.75 193 158 6.5 1334 160 6.5 1351 165 6.5 1393 160 6.5 1351 CWP C 1655 6.6 0.75 193 0 6.5 0 0 6.5 0 0 6.5 0 0 6.5 0 Total MW 19.71 14.5 15.2 14.7 14.9 % APC 6.81% 7.16% 6.85% 6.98% Consumption (MU) 0.35 0.36 0.35 0.36 Total consumption (MU) 1.42
  • 10. Reasons for higher % APC 1.Partial loading of unit 2.Poor Lignite quality
  • 11. 7.80 7.90 8.00 8.10 8.20 8.30 8.40 8.50 8.60 8.70 0.00 50.00 100.00 150.00 200.00 250.00 Break even % UAC - UNIT I MW % UAC 172.75 8.59 181.31 8.45 193.23 8.30 197.88 8.17 200.58 8.17 202.50 8.02 209.83 7.97 212.79 7.85 For obtaining % UAC less than 8% - Unit 1 has to operated with load higher than 202 MW
  • 12. 7.90 7.95 8.00 8.05 8.10 8.15 8.20 8.25 8.30 8.35 185.00 190.00 195.00 200.00 205.00 210.00 215.00 Break even % UAC – UNIT II MW %UAC 190.88 8.27 195.86 8.29 207.96 8.07 209.58 8.00 213.01 7.94 For obtaining % UAC less than 8% - Unit 2 has to operated with load higher than 209 MW
  • 13. 8.00 8.10 8.20 8.30 8.40 8.50 8.60 194.00 196.00 198.00 200.00 202.00 204.00 206.00 208.00 210.00 212.00 214.00 Break even % UAC – UNIT III MW %UAC 196.73 8.57 199.44 8.50 201.59 8.42 205.05 8.37 209.97 8.29 212.20 8.07 For obtaining % UAC less than 8% - Unit 3 has to operated with load higher than 209 MW
  • 14. 7.40 7.60 7.80 8.00 8.20 8.40 8.60 8.80 9.00 0.00 50.00 100.00 150.00 200.00 250.00 Break even %UAC - UNIT 4 MW %UAC 154.74 8.83 178.06 8.53 185.21 8.40 192.06 8.23 199.18 7.96 206.44 7.70 214.76 7.63 For obtaining % UAC less than 8% - Unit 4 has to operated with load higher than 192 MW
  • 15. 0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00 175.00 180.00 185.00 190.00 195.00 200.00 205.00 210.00 215.00 Break even % UAC- UNIT 5 MW %UAC 180.83 8.70 189.03 8.48 194.77 8.25 203.78 8.15 205.15 7.43 210.59 7.12 For obtaining % UAC less than 8% - Unit 5 has to operated with load higher than 203 MW
  • 16. 7.00 7.20 7.40 7.60 7.80 8.00 8.20 8.40 185.00 190.00 195.00 200.00 205.00 210.00 215.00 Break even % UAC - UNIT 6 MW %UAC 186.41 8.32 193.19 7.93 198.77 7.88 204.61 7.56 213.59 7.17 For obtaining % UAC less than 8% - Unit 6 has to operated with load higher than 186 MW
  • 17. 0 2 4 6 8 10 12 0 50 100 150 200 250 Break even % UAC - UNIT 7 MW %UAC 116.67 10.33 177.45 8.72 184.62 8.32 189.08 8.31 196.95 8.3 201.19 7.99 211.62 7.69 For obtaining % APC less than 8% - Unit 7 has to operated with load higher than 186 MW
  • 18. UNIT 1 UNIT 2 UNIT 3 UNIT 4 UNIT 5 UNIT 6 UNIT 7 Series1 202 209 212 192 203 186 196 170 175 180 185 190 195 200 205 210 215 UnitLoad(MW) Break even load for obtaining %UAC less than 8%
  • 19. UNIT 6 UNIT 4 UNIT 7 UNIT 1 UNIT 5 UNIT 2 UNIT 3 % UAC Trend Highest Unit Auxiliary consumption in Unit -3 Lowest Unit Auxiliary Consumption in Unit - 6
  • 20. 9.6 9.8 10 10.2 10.4 10.6 10.8 0 200 400 600 800 1000 1200 1400 Station % APC MW APC 780.96 10.71 1048.73 10.39 1239.82 10.21 1308.43 9.74 1318.96 9.68 For obtaining Station % APC less than 10% - Plant to be operated with load higher than 1240 MW
  • 21. y = 214.6x2 - 432.4x + 227.0 R² = 0.065 9.15 9.20 9.25 9.30 9.35 9.40 9.45 9.50 0.990 0.995 1.000 1.005 1.010 1.015 1.020 1.025 APC Poly. (APC) MW SLC APC 1442 0.993 9.41 1482 0.993 9.28 1447 0.997 9.23 1413 1.002 9.46 1477 1.003 9.20 1466 1.006 9.35 1459 1.006 9.26 1457 1.008 9.26 1434 1.011 9.35 1481 1.011 9.28 1474 1.013 9.33 1473 1.017 9.23 1452 1.020 9.30 1466 1.021 9.28 1441 1.023 9.44
  • 22. MW SLC APC Actual % APC (214.6x2 - 432.4x + 227.0) Higher % APC due to lignite quality 1442 0.993 9.41 8.64 0.77 1482 0.993 9.28 8.64 0.64 1447 0.997 9.23 8.61 0.62 1413 1.002 9.46 8.59 0.87 1477 1.003 9.20 8.59 0.61 1466 1.006 9.35 8.58 0.77 1459 1.006 9.26 8.58 0.68 1457 1.008 9.26 8.58 0.68 1434 1.011 9.35 8.58 0.77 1481 1.011 9.28 8.58 0.70 1474 1.013 9.33 8.58 0.75 1473 1.017 9.23 8.59 0.64 1452 1.020 9.30 8.60 0.70 1466 1.021 9.28 8.60 0.68 1441 1.023 9.44 8.61 0.83 Average variation in % APC due to lignite quality 0.71