Roxtec CRL Cable Transit Seal - Installation Instructions
1. Installation Instructions
Roxtec CRL 4" and 5"
Installation
Insert the frame into the sleeve
opening.
Lubricate the frame sparsely on
the outside black rubber part with
Roxtec Assembly Gel.
Lubricate the inside faces of the
frame thoroughly, especially into
the corners.
Lubricate all modules for the frame
thoroughly, both the inside and the
outside surfaces.
Achieve a 0.1-1.0 mm gap between
the two halves when held against
the cable/pipe.
Adapt modules which are to hold
cables or pipes by peeling off
layers until you reach the gap seen
in pic. 5b.
Insert the modules in the frame.
Push the front fittings back towards
the centre.
Tighten the nuts.
Max torque is 2 Nm/1.48 lbf·ft.
Loosen the nuts and push the front
fittings to the sides.
The installation is complete.Excess Assembly Gel will protrude
when tightening the seal.
Approx. 10 mm/0.394"
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
2. Roxtec®andMultidiameter®areregisteredtrademarksofRoxtecinSwedenand/orothercountries.
Roxtec International AB
Box 540, 371 23 Karlskrona, SWEDEN
PHONE +46 455 36 67 00, FAX +46 455 820 12
EMAIL info@roxtec.com, www.roxtec.com
DISCLAIMER
”The Roxtec cable entry sealing system (”the Roxtec system”) is a modular-
based system of sealing products consisting of different components. Each
and every one of the components are necessary for the best performance of
the Roxtec system. The Roxtec system has been certified to resist a number
of different hazards. Any such certification, and the ability of the Roxtec system
to resist such hazards, is dependent on all components that are installed as a
part of the Roxtec system. Thus, the certification is not valid and does not apply
unless all components installed as part of the Roxtec system are manufactured
by or under license from Roxtec (“authorized manufacturer”). Roxtec gives no
performance guarantee with respect to the Roxtec system, unless (I) all compo-
nents installed as part of the Roxtec system are manufactured by an authorized
manufacturer and (II) the purchaser is in compliance with (a), and (b), below.
(a) During storage, the Roxtec system or part thereof, shall be kept indoors
in its original packaging at a temperature not exceeding +70°C/+158°F and
not below -40°C/-40°F.
(b) Installation shall be carried out in accordance with Roxtec installation in-
structions in effect from time to time.
The product information provided by Roxtec does not release the purchaser of the
Roxtec system, or part thereof, from the obligation to independently determine
the suitability of the products for the intended process, installation and/or use.
Roxtec gives no guarantee for the Roxtec system or any part thereof and
assumes no liability for any loss or damage whatsoever, whether direct, in-
direct, consequential, loss of profit or otherwise, occurred or caused by the
Roxtec systems or installations containing components not manufactured by
an authorized manufacturer.
Roxtec expressly excludes any implied warranties of merchantability and fitness
for a particular purpose and all other express or implied representations and
warranties provided by statute or common law. User determines suitability of
the Roxtec system for intended use and assumes all risk and liability in con-
nection therewith. In no event shall Roxtec be liable for consequential, punitive,
special, exemplary or incidental damages.”
ASS2009001801ver_1.4/GB/1042/kasve
Pcs Module (mm) For cable diameter (in)
1 CM 66 0+24-54 0+0.945-2.126
Pcs Module (mm) For cable diameter (in)
2 CM 33w66 2x0+10-29 2x0+0.394-1.142
Pcs Module (mm) For cable diameter (in)
3 CM 22w66 3x0+5-16.5 3x0+0.197-0.650
Pcs Module (mm) For cable diameter (in)
1 CM 22w66 3x0+5-16.5 3x0+0.197-0.650
1 CM 11/0
1 CM 33w66 2x0+10-29 2x0+0.394-1.142
Disassembly
Reverse order
For optimum reliability, wait 24 hours or longer after installation before exposing the cables/pipes to strain or pressure.
Cables/pipes shall be routed perpendicularly to the wall.
Note
Roxtec CRL kits
All kits include Roxtec Assembly Gel and installation instructions.
Roxtec CRL 4"/1 Roxtec CRL 5"/1
For 1 cable
Roxtec CRL 4"/4 Roxtec CRL 5"/4
For 4 cables
Roxtec CRL 4"/5 Roxtec CRL 5"/5
For 5 cables
Roxtec CRL 4"/9 Roxtec CRL 5"/9
For 9 cables