CE 5312 ADVANCED CONCRETE
DESIGN SPRING 2015
GROUP 4
Prof : Dr. Mohammad Razavi
Task
 Design Two Story Residential Building located in Charleston,
South Carolina.
Plan of the Residential Building.
 Material Properties:
Concrete: 𝑓ʹ 𝑐 = 5.5 𝑘𝑠𝑖 Steel: 𝑓𝑦 = 60 𝑘𝑠𝑖
Groups Location A B C D E F First
Story
Second
Story
1 Charlotte, NC 60 20 12 20 40 36 20 12
2 Austin, TX 65 18 10 18 45 36 19 13
3 Chicago, IL 55 22 12 22 40 50 20 14
4 Charleston, SC 50 25 10 25 35 48 18 13
5 Seattle, WA 60 25 12 25 50 52 16 15
6 Denver, CO 65 22 10 22 50 42 17 14
Scope
 The following are required to be designed:
 Two way slab system
 Beam design; edge beam torsional design
 Design of columns with magnified moments
 Design of corbel
 Design of shear wall
Ultimate Design Wind Speeds
Load Combinations
 1.6(D.L)+1(L.L)+1(Ey)
 0.9(D.L)+1(Ey)
 1.2(D.L)+1.6(L.L)
 1.4(D.L)
Where
D.L=Dead Load
L.L=Live Load
Ey =EarthQuake Load
W =Wind load
Load Considerations
 We took into consideration :
 Dead Load - 150 psf
 Live load - 40 psf
 Wind Load - 30psf
 Rain Load - 20 psf
General layout
Deformed building structure
Design of the structure
Slab Panel
 Slab panel (C-D 4-5)
Moment for load combination Dcon4
Shear for load combination Dcon4
Tortion for load combination Dcon4
SLAB DESIGN
Assumed thickness -- 6in
 Slab panel -- 12.5ft x 10ft
 One way shear -- Vu=1.272k < ᶲVc=6.6k O.K
 Two way shear -- Vu=30.94k < ᶲVc=58.64 O.K
 qu -- 0.2 ksf
 Mos -- 31.64k-ft
 Mol -- 41.328k-ft
Slab Design
 Long span C.S reinforcement – 10 #4bars (1.96in^2)
 Long span M.S reinforcement – 12 #4bars(2.36in^2)
 Short span C.S reinforcement - 10 #4bars(1.96in^2)
 Shorts span M.S reinforcement – 8# 4bars(1.57in^2)
Tortional Beam Design
 Beam cross section = 16in x 18in
 Vu = 3.425k
 ᶲVc = 28.4k (shear reinforcement no needed)
 Tu = 85.46k.in
 Tth= 67.8 k.in
 Top rebars = #6 3bars (1.32in^2)
 Mid rebars = #6 3bars
 Bot rebars = #6 3bars
Column Design
 Column size = 12in x 12in
 Ultimate factored load = 54.43 kip
 Lu = 13ft
 Mtop = 0.0065 k-ft
 Mbot = 0.0343 k-ft
 Magnified moment = 4.35 k-ft
 Required Ast = 1.465in^2
 Rebars used = 4 #9 bars
Design Of Shear Wall
 Length of the wall = 16ft
 Height of 2nd story = 13ft
 Height of the 1st story = 18ft
 Thickness of the wall =10in
 Total fatored load on 2nd floor = 88.66 k
 Total fatored load on 1st floor = 258.505 k
 Wind load on 2nd floor = 1.298 k
 Wind load on 2nd floor = 0.298 k
Shear wall Design
 Moment (Mu) = 45.602 k-ft
 Ultimate factored moment = 72.963 k-ft
 Check for moment O.k
 Vu =2.553k
 ᶲVc =424.54k
References
 ASCE-07, “Minimum Design Loads for
Buildings and Other Structures”.
 International Building code 2012.
 James K. Wight & James G. Macgregor,
(2009), “Reinforced concrete Mechanics &
 Design” Sixth edition, Pearson & Prentice
Hall.
 Class handouts and examples.
 Wikipedia.

More Related Content

Similar to PRESENTATION (1)

Design project of blood bank building
Design project of blood bank buildingDesign project of blood bank building
Design project of blood bank buildingmuthudeva
 
Albany Turnpike over CSXT Railroad Superstucture Replacement, East Chatham, N...
Albany Turnpike over CSXT Railroad Superstucture Replacement, East Chatham, N...Albany Turnpike over CSXT Railroad Superstucture Replacement, East Chatham, N...
Albany Turnpike over CSXT Railroad Superstucture Replacement, East Chatham, N...dgonano
 
PRESENTATION.pptxA EXPERIMENTAL STUDY ON PARTIAL REPLACEMENT OF FINE AGGREGA...
PRESENTATION.pptxA EXPERIMENTAL STUDY ON PARTIAL REPLACEMENT OF FINE  AGGREGA...PRESENTATION.pptxA EXPERIMENTAL STUDY ON PARTIAL REPLACEMENT OF FINE  AGGREGA...
PRESENTATION.pptxA EXPERIMENTAL STUDY ON PARTIAL REPLACEMENT OF FINE AGGREGA...pakkurathikailashpav
 
IDP PROJECT column.pptxvjfhhfudyytststrrsrsr
IDP PROJECT column.pptxvjfhhfudyytststrrsrsrIDP PROJECT column.pptxvjfhhfudyytststrrsrsr
IDP PROJECT column.pptxvjfhhfudyytststrrsrsrct571999
 
Design & Development of Rotating Work-piece Holding Mechanism for EDM Process
Design & Development of Rotating Work-piece Holding Mechanism for EDM ProcessDesign & Development of Rotating Work-piece Holding Mechanism for EDM Process
Design & Development of Rotating Work-piece Holding Mechanism for EDM ProcessSahil Dev
 
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERINGDESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERINGLiyaWilson4
 
Post graduate exam in hydraulic 2018.docx
Post graduate exam in hydraulic   2018.docxPost graduate exam in hydraulic   2018.docx
Post graduate exam in hydraulic 2018.docxDr. Ezzat Elsayed Gomaa
 
Design and Analysis of RC beam
Design and Analysis of RC beamDesign and Analysis of RC beam
Design and Analysis of RC beamMohammad Anis
 
Design and Analysis of RC beam
Design and Analysis of RC beamDesign and Analysis of RC beam
Design and Analysis of RC beamMohammad Anis
 
CM - Jauregui - Sapienza University of Rome (60 min, part i, members modified)
CM - Jauregui - Sapienza University of Rome (60 min, part i, members modified)CM - Jauregui - Sapienza University of Rome (60 min, part i, members modified)
CM - Jauregui - Sapienza University of Rome (60 min, part i, members modified)Franco Bontempi Org Didattica
 
Multi storey building design of 7 storey commercial building
Multi storey building design of 7 storey commercial buildingMulti storey building design of 7 storey commercial building
Multi storey building design of 7 storey commercial buildingRazes Dhakal
 
multistorey building design by sap and autocad
multistorey building design by sap and autocadmultistorey building design by sap and autocad
multistorey building design by sap and autocadRazes Dhakal
 

Similar to PRESENTATION (1) (20)

DCE.DOCX
DCE.DOCXDCE.DOCX
DCE.DOCX
 
Design project of blood bank building
Design project of blood bank buildingDesign project of blood bank building
Design project of blood bank building
 
Albany Turnpike over CSXT Railroad Superstucture Replacement, East Chatham, N...
Albany Turnpike over CSXT Railroad Superstucture Replacement, East Chatham, N...Albany Turnpike over CSXT Railroad Superstucture Replacement, East Chatham, N...
Albany Turnpike over CSXT Railroad Superstucture Replacement, East Chatham, N...
 
RCC BMD
RCC BMDRCC BMD
RCC BMD
 
CFST columns
CFST columnsCFST columns
CFST columns
 
PRESENTATION.pptxA EXPERIMENTAL STUDY ON PARTIAL REPLACEMENT OF FINE AGGREGA...
PRESENTATION.pptxA EXPERIMENTAL STUDY ON PARTIAL REPLACEMENT OF FINE  AGGREGA...PRESENTATION.pptxA EXPERIMENTAL STUDY ON PARTIAL REPLACEMENT OF FINE  AGGREGA...
PRESENTATION.pptxA EXPERIMENTAL STUDY ON PARTIAL REPLACEMENT OF FINE AGGREGA...
 
IDP PROJECT column.pptxvjfhhfudyytststrrsrsr
IDP PROJECT column.pptxvjfhhfudyytststrrsrsrIDP PROJECT column.pptxvjfhhfudyytststrrsrsr
IDP PROJECT column.pptxvjfhhfudyytststrrsrsr
 
Design & Development of Rotating Work-piece Holding Mechanism for EDM Process
Design & Development of Rotating Work-piece Holding Mechanism for EDM ProcessDesign & Development of Rotating Work-piece Holding Mechanism for EDM Process
Design & Development of Rotating Work-piece Holding Mechanism for EDM Process
 
unit-3.ppt
unit-3.pptunit-3.ppt
unit-3.ppt
 
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERINGDESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
 
Post graduate exam in hydraulic 2018.docx
Post graduate exam in hydraulic   2018.docxPost graduate exam in hydraulic   2018.docx
Post graduate exam in hydraulic 2018.docx
 
mid-defnse-1.pptx
mid-defnse-1.pptxmid-defnse-1.pptx
mid-defnse-1.pptx
 
Rvec pkg 3
Rvec pkg 3Rvec pkg 3
Rvec pkg 3
 
Design and Analysis of RC beam
Design and Analysis of RC beamDesign and Analysis of RC beam
Design and Analysis of RC beam
 
Design and Analysis of RC beam
Design and Analysis of RC beamDesign and Analysis of RC beam
Design and Analysis of RC beam
 
CM - Jauregui - Sapienza University of Rome (60 min, part i, members modified)
CM - Jauregui - Sapienza University of Rome (60 min, part i, members modified)CM - Jauregui - Sapienza University of Rome (60 min, part i, members modified)
CM - Jauregui - Sapienza University of Rome (60 min, part i, members modified)
 
Multi storey building design of 7 storey commercial building
Multi storey building design of 7 storey commercial buildingMulti storey building design of 7 storey commercial building
Multi storey building design of 7 storey commercial building
 
multistorey building design by sap and autocad
multistorey building design by sap and autocadmultistorey building design by sap and autocad
multistorey building design by sap and autocad
 
Steel book
Steel bookSteel book
Steel book
 
Steel book
Steel bookSteel book
Steel book
 

PRESENTATION (1)

  • 1. Ashraf Khan Bhanu Sri Routhu Haroon Rasheed Ahmed Luqman Sheeraz Mohammed Manoj Kandel Muqtadar Shareef Mohammed Punith Yadav Saeed Janbaz CE 5312 ADVANCED CONCRETE DESIGN SPRING 2015 GROUP 4 Prof : Dr. Mohammad Razavi
  • 2. Task  Design Two Story Residential Building located in Charleston, South Carolina. Plan of the Residential Building.
  • 3.  Material Properties: Concrete: 𝑓ʹ 𝑐 = 5.5 𝑘𝑠𝑖 Steel: 𝑓𝑦 = 60 𝑘𝑠𝑖 Groups Location A B C D E F First Story Second Story 1 Charlotte, NC 60 20 12 20 40 36 20 12 2 Austin, TX 65 18 10 18 45 36 19 13 3 Chicago, IL 55 22 12 22 40 50 20 14 4 Charleston, SC 50 25 10 25 35 48 18 13 5 Seattle, WA 60 25 12 25 50 52 16 15 6 Denver, CO 65 22 10 22 50 42 17 14
  • 4. Scope  The following are required to be designed:  Two way slab system  Beam design; edge beam torsional design  Design of columns with magnified moments  Design of corbel  Design of shear wall
  • 6. Load Combinations  1.6(D.L)+1(L.L)+1(Ey)  0.9(D.L)+1(Ey)  1.2(D.L)+1.6(L.L)  1.4(D.L) Where D.L=Dead Load L.L=Live Load Ey =EarthQuake Load W =Wind load
  • 7. Load Considerations  We took into consideration :  Dead Load - 150 psf  Live load - 40 psf  Wind Load - 30psf  Rain Load - 20 psf
  • 10. Design of the structure
  • 11. Slab Panel  Slab panel (C-D 4-5)
  • 12. Moment for load combination Dcon4
  • 13. Shear for load combination Dcon4
  • 14. Tortion for load combination Dcon4
  • 15. SLAB DESIGN Assumed thickness -- 6in  Slab panel -- 12.5ft x 10ft  One way shear -- Vu=1.272k < ᶲVc=6.6k O.K  Two way shear -- Vu=30.94k < ᶲVc=58.64 O.K  qu -- 0.2 ksf  Mos -- 31.64k-ft  Mol -- 41.328k-ft
  • 16. Slab Design  Long span C.S reinforcement – 10 #4bars (1.96in^2)  Long span M.S reinforcement – 12 #4bars(2.36in^2)  Short span C.S reinforcement - 10 #4bars(1.96in^2)  Shorts span M.S reinforcement – 8# 4bars(1.57in^2)
  • 17. Tortional Beam Design  Beam cross section = 16in x 18in  Vu = 3.425k  ᶲVc = 28.4k (shear reinforcement no needed)  Tu = 85.46k.in  Tth= 67.8 k.in  Top rebars = #6 3bars (1.32in^2)  Mid rebars = #6 3bars  Bot rebars = #6 3bars
  • 18. Column Design  Column size = 12in x 12in  Ultimate factored load = 54.43 kip  Lu = 13ft  Mtop = 0.0065 k-ft  Mbot = 0.0343 k-ft  Magnified moment = 4.35 k-ft  Required Ast = 1.465in^2  Rebars used = 4 #9 bars
  • 19. Design Of Shear Wall  Length of the wall = 16ft  Height of 2nd story = 13ft  Height of the 1st story = 18ft  Thickness of the wall =10in  Total fatored load on 2nd floor = 88.66 k  Total fatored load on 1st floor = 258.505 k  Wind load on 2nd floor = 1.298 k  Wind load on 2nd floor = 0.298 k
  • 20. Shear wall Design  Moment (Mu) = 45.602 k-ft  Ultimate factored moment = 72.963 k-ft  Check for moment O.k  Vu =2.553k  ᶲVc =424.54k
  • 21. References  ASCE-07, “Minimum Design Loads for Buildings and Other Structures”.  International Building code 2012.  James K. Wight & James G. Macgregor, (2009), “Reinforced concrete Mechanics &  Design” Sixth edition, Pearson & Prentice Hall.  Class handouts and examples.  Wikipedia.