HVAC AIR DUCTING CHARTS
1. 1. TRANSFER AIR DUCT
2. GRAVITY RELIEF AIR SHIFTS
MAX FRICTION = 0.03-0.05
in.w.g/100ft
WHEN CFM < 3200
CFM
MAX VELOCITY = 1000
fpm
WHEN
CFM > 3200
CFM
1. LOW PRESSSURE DUCT
2. GENERAL EXHAUST DUCT
3. TOILETS EXHAUST DUCT
MAX FRICTION = 0.1-0.15
in.w.g/100ft
WHEN CFM <6000
CFM
MAX VELOCITY = 1500-1800
fpm
WHEN CFM >6000
CFM
APPLICABLE FOR SUPPLY,RETURN,EXHAUST AND OUT SIDE AIR
HIGH PRESSSURE DUCT
MAX FRICTION= 0.4-0.45
in.w.g/100ft
WHEN CFM < 5000
CFM
MAX VELOCITY = 2500-3500
fpm
WHEN CFM > 5000
CFM
APPLICABLEFOR SUPPLY SYSTEM ONLY
0033 CFM
0033 CFM
6000 CFM
ACID AMMONIA AND SOLVENTS MAINS
MAX FRICTION=0.5-0.6
in.w.g/100ft
MAX VELOCITY =3000
fpm
MIN VELOCITY =1000
fpm
MAIN & RISER = 1500-3000 fpm
BRANCHES & LATERALS = 1000-2000 fpm
MEDIUM PRESSSURE DUCT
MAX FRICTION = 0.2-0.25
in.w.g/100ft
WHEN CFM < 6000
CFM
MAX VELOCITY = 2000-2500
fpm
WHEN CFM > 6000
CFM
APPLICABLEFOR SUPPLY SYSTEM
ONLY
DISH WASHER
EXHAUST DUCT
MAX FRICTION=0.1-
0.15
in.w.g/100ft
MAX VELOCITY
=2200
FPM
MIN VELOCITY 1500
FPM
KITCHEN HOOD EXHAUST DUCT
MAX VELOCITY =2200
FPM
MIN VELOCITY 1500
FPM
ACID , AMMONIA AND SOLVENT STACKS
MAX VELOCITY =4000
CFM
MIN VELOCITY =3000
CFM
700FPM ( EXHAUST OR RELIEF )
MAXIMUM VELOCITY THROUGH FREE AREA
:ASSUMING 50% FREE AREA-MAX.VELOCITY
350 FPM THROUGH GROSS AREA
500FPM ( INTAKE )
MAXIMUM VELOCITY THROUGH FREE AREA
:ASSUMING 50% FREE AREA-MAX.VELOCITY
250 FPM THROUGH GROSS AREA
MIN 250FPM ( SILANE DUCT )
VELOCITY ACROSS THE NECK OF CYLINDER OR
CABINET WINDOW OR ACCESS PORT
MUSTAFA A. ABDULJABBAR
Mustafahmed94@yahoo.com
Mobile 00971 50 499 50 43
OUTSIDE AIR SHIFT
MAX FRICTION = 0.05-
0.1
in.w.g/100ft
WHEN CFM <
1200
CFM
MAX VELOCITY = 1000
fpm
WHEN CFM > 1200
CFM