CHAPTER 6
DESIGN OF
REINFORCED
CONCRETE SLAB (TWO-
WAY SLAB)
Introduction
In two-way slab, the reinforcement is designedon both directions.
The condition occurs when the slab is supported on all four edge and the ratio of
longer span to shorter span less than 2.
one-way slab two-way slab
Introduction
The failure mode of the simply supported two-way slab is shown in the figure where
the bending moment and shear force of the slab depends on the ratio of Ly/Lx, the
continuity of the slab andtype of support (simplysupported or continuous)
Type of Slab
If the slab consist of a single panel and the sides of the slab are not resisted from
lifting, than this type of slab is consideredto be simple supported.
This is usually occurs when slab is supported by steel beam of the slab and beam is
not monolithically constructed as shown in the figure.
Calculating Moment Mx and My
Moment of simplysupported beam
Msx = αsx nlx²
Msy = αsy nlx²
Slab Thickness
Slab Thickness
Example (two-way slab)
Design a reinforced concrete slab for a room measuring 7.5 m x 4.0 m. The slab carries
a variable action of 2.5 kN/m² and permanent action due to finishes of 1.2 kN/m²
(excluded self-weight). the characteristic materials strength are Fck = 25 N/mm² and
Fyk = 500 N/mm². The slab is inside the building and subjected to 1.5 hour fire resistance
and 50 years of design life. The slab can be consider as simply supported on all four
edgewith corners free to lift. Designthe slab.
7.5m
4.0m
Example (two-way slab)
1. Specification
Permanent action Gk = 1.20 kN/m² (Excludeds-w)
Variable action, QK = 2.50 kN/m²
Strength of concrete = 25 N/mm²
Strength of steel = 500 N/mm²
Fire resistance = 1.5 hours
Exposure Classes = XC1
Assume:
Øbar = 10mm
Example (two-way slab)
2. Slab thickness
Minimum thicknessfor fire resistance= 100 mm (Table5.8EN1992.1.2)
Estimatedthickness consideringdeflection control, h = Lx/20
h = 4000/20 mm
use h = 200 mm
Example (two-way slab)
3. Assessdurability requirement, fire andbond
Min. coverwithregardto bond, Cmin,b - 10 mm (table 4.2)
Min. cover withregardto durability,Cmin,dur - 10 mm (table 4.4N)
Min. Requirementaxis distancefor R60 fire - a= 20mm (table 5.8 EN1992.1.2)
Min. cover withregardto fire,Cmin, - a – Øbar/2
- 20mm- 10mm/2= 15 mm
Allowable in designfor deviation,∆Cdev - 10 mm (BS EN 1992-1-1- 4.4.1.3)
Nominal Cover,Cnom - Cmin(a)+ ∆Cdev= 20mm + 10 mm = 30 mm
use Cnom = 30 mm
Example (two-way slab)
4. Assessaction on slab
Slab self-weight 0.200 x25 = 5.00 kN/m²
Permanent loading (excludingself-weight) = 1.20 kN/m²
Permanent action, GK = 6.20 kN/m²
Variable action, Qk = 2.50 kN/m²
Designaction = 1.35 Gk+ 1.50 Qk
= 1.35(6.20)+ 1.50(2.50)
= 12.12 kN/m²
Consider 1m width = 12.12 x 1m = 12.12 kN/m
Example (two-way slab)
5. Critical moment and shear forces
Ly/Lx= 7500/4000 = 1.88 < 2.00 – two-way slab
12.12 kN/m
4.00 m
Shear force, VEd = WL/2
VEd = 12.12(4)/2
VEd = 24.24kN
Bendingmoment,
Short span, Msx = αsxnlx²
Msx = 0.116x12.12x4²= 22.49kNm/m
Longspan,Msy = αsy nlx²
Msy = 0.033x12.12x4²= 6.40 kNm/m
Example (two-way slab)
6. Designof main reinforcement
Effective depth, dx = h – Cnom – Øbar/2 = 200 – 30 – (10/2) = 165 mm
Effective depth, dy = h – Cnom – 1.5Øbar = 200 – 30 – (1.5x10) = 155 mm
Example (two-way slab)
6. Designof main reinforcement
ShortSpan:
Mbal = 0.167 fck bd²
Mbal = 0.167(25)(1000)(165²)
Mbal = 114kNm > M = 22.49kNm
As = M As = 22.49x10^6
0.87 fykZ 0.87(500)(0.95x165)
Asreq = 329mm²/m
Provide H10-225(Asprov = 349 mm²/m)
compression reinforcement is not required
use z = 0.95d
Example (two-way slab)
6. Designof main reinforcement
LongSpan:
Mbal = 0.167 fck bd²
Mbal = 0.167(25)(1000)(155²)
Mbal = 100kNm > M = 6.40kNm
As = M As = 6.40 x 10^6
0.87 fykZ 0.87(500)(0.95x155)
Asreq = 100 mm²/m
Provide H10-300 (Asprov = 262 mm²/m)
compression reinforcement is not required
use z = 0.95d
Example (two-way slab)
6. Designof main reinforcement
Calculate minimum and maximum
Asmin = 0.0015 bd
Asmin = 0.0015(1000)(165)
= 248 mm²/m
Asmax = 0.04 Ac
Asmax = 0.04 (1000x200)
= 8000 mm²/m
Bar Reinforced Concrete (BRC)
THANK YOU

chapter6designofconcreteslab-28two-wayslab-29.pptx

  • 1.
  • 2.
    Introduction In two-way slab,the reinforcement is designedon both directions. The condition occurs when the slab is supported on all four edge and the ratio of longer span to shorter span less than 2. one-way slab two-way slab
  • 3.
    Introduction The failure modeof the simply supported two-way slab is shown in the figure where the bending moment and shear force of the slab depends on the ratio of Ly/Lx, the continuity of the slab andtype of support (simplysupported or continuous)
  • 4.
    Type of Slab Ifthe slab consist of a single panel and the sides of the slab are not resisted from lifting, than this type of slab is consideredto be simple supported. This is usually occurs when slab is supported by steel beam of the slab and beam is not monolithically constructed as shown in the figure.
  • 5.
    Calculating Moment Mxand My Moment of simplysupported beam Msx = αsx nlx² Msy = αsy nlx²
  • 6.
  • 7.
  • 8.
    Example (two-way slab) Designa reinforced concrete slab for a room measuring 7.5 m x 4.0 m. The slab carries a variable action of 2.5 kN/m² and permanent action due to finishes of 1.2 kN/m² (excluded self-weight). the characteristic materials strength are Fck = 25 N/mm² and Fyk = 500 N/mm². The slab is inside the building and subjected to 1.5 hour fire resistance and 50 years of design life. The slab can be consider as simply supported on all four edgewith corners free to lift. Designthe slab. 7.5m 4.0m
  • 9.
    Example (two-way slab) 1.Specification Permanent action Gk = 1.20 kN/m² (Excludeds-w) Variable action, QK = 2.50 kN/m² Strength of concrete = 25 N/mm² Strength of steel = 500 N/mm² Fire resistance = 1.5 hours Exposure Classes = XC1 Assume: Øbar = 10mm
  • 10.
    Example (two-way slab) 2.Slab thickness Minimum thicknessfor fire resistance= 100 mm (Table5.8EN1992.1.2) Estimatedthickness consideringdeflection control, h = Lx/20 h = 4000/20 mm use h = 200 mm
  • 11.
    Example (two-way slab) 3.Assessdurability requirement, fire andbond Min. coverwithregardto bond, Cmin,b - 10 mm (table 4.2) Min. cover withregardto durability,Cmin,dur - 10 mm (table 4.4N) Min. Requirementaxis distancefor R60 fire - a= 20mm (table 5.8 EN1992.1.2) Min. cover withregardto fire,Cmin, - a – Øbar/2 - 20mm- 10mm/2= 15 mm Allowable in designfor deviation,∆Cdev - 10 mm (BS EN 1992-1-1- 4.4.1.3) Nominal Cover,Cnom - Cmin(a)+ ∆Cdev= 20mm + 10 mm = 30 mm use Cnom = 30 mm
  • 12.
    Example (two-way slab) 4.Assessaction on slab Slab self-weight 0.200 x25 = 5.00 kN/m² Permanent loading (excludingself-weight) = 1.20 kN/m² Permanent action, GK = 6.20 kN/m² Variable action, Qk = 2.50 kN/m² Designaction = 1.35 Gk+ 1.50 Qk = 1.35(6.20)+ 1.50(2.50) = 12.12 kN/m² Consider 1m width = 12.12 x 1m = 12.12 kN/m
  • 13.
    Example (two-way slab) 5.Critical moment and shear forces Ly/Lx= 7500/4000 = 1.88 < 2.00 – two-way slab 12.12 kN/m 4.00 m Shear force, VEd = WL/2 VEd = 12.12(4)/2 VEd = 24.24kN Bendingmoment, Short span, Msx = αsxnlx² Msx = 0.116x12.12x4²= 22.49kNm/m Longspan,Msy = αsy nlx² Msy = 0.033x12.12x4²= 6.40 kNm/m
  • 14.
    Example (two-way slab) 6.Designof main reinforcement Effective depth, dx = h – Cnom – Øbar/2 = 200 – 30 – (10/2) = 165 mm Effective depth, dy = h – Cnom – 1.5Øbar = 200 – 30 – (1.5x10) = 155 mm
  • 15.
    Example (two-way slab) 6.Designof main reinforcement ShortSpan: Mbal = 0.167 fck bd² Mbal = 0.167(25)(1000)(165²) Mbal = 114kNm > M = 22.49kNm As = M As = 22.49x10^6 0.87 fykZ 0.87(500)(0.95x165) Asreq = 329mm²/m Provide H10-225(Asprov = 349 mm²/m) compression reinforcement is not required use z = 0.95d
  • 16.
    Example (two-way slab) 6.Designof main reinforcement LongSpan: Mbal = 0.167 fck bd² Mbal = 0.167(25)(1000)(155²) Mbal = 100kNm > M = 6.40kNm As = M As = 6.40 x 10^6 0.87 fykZ 0.87(500)(0.95x155) Asreq = 100 mm²/m Provide H10-300 (Asprov = 262 mm²/m) compression reinforcement is not required use z = 0.95d
  • 17.
    Example (two-way slab) 6.Designof main reinforcement Calculate minimum and maximum Asmin = 0.0015 bd Asmin = 0.0015(1000)(165) = 248 mm²/m Asmax = 0.04 Ac Asmax = 0.04 (1000x200) = 8000 mm²/m
  • 18.
  • 19.