SlideShare a Scribd company logo
1 of 28
Download to read offline
42.585kWGridTiedPVSystem
ShelliBergh
21511USHwy63N
SturgeonMO65284
660-591-6424;shellibergh@embargmail.com
Missouri Sun Solar, LLC
1926 West Woodland
Springfield, MO 65807
PVGI-1
Designer
D. Hults
Reviewer
B. Arthur
General Information
Grid Tied PV System
Date
2016-03-11
Scale
NTS
System Specifications, Main Components: Roof Mount
Item Manufacturer Model Quantity Size: In Array Area: Sqft Weight: Lbs Array Weight: Lbs Watts: kW
Panel Module Q-Cell Q-Pro.G4 255 167 65.7 x 39.4 x 1.38 3179.68 41.89 6995.63 255
Inverter 1 Fronius Primo 8.2-1 4 16.9 x 24.7 x 8.1 47.29 8200
Inverter 2 Fronius Primo 5.0-1 1 16.9 x 24.7 x 8.1 47.29 5000
Attachment S-5! Protea Bracket with PV Kit 184 0.789 144.39
Generator Generac RG022: 22kW, 60Hz 1 76.8 x 46.1 x 35 905 22000
Transfer
Switch
Generac RTSN200G3: 200A 1 24.1 x 20.2 x 7.1 48
Roof Specifications Array Specifications Site Specifications Average Loads Weight
2" x 4" Truss or 6" Framing 24" O.C. Occupancy: Utility Down: 245 lbs Total Weight: 7140.02 lbs
Corrugated Metal Roof Building Size: 2 Story Uplift: -137 lbs Weight at Attachment: 38.8 lbs
Design Wind Speed: 115 MPH Lateral: 38 lbs Distributed Weight: 2.25 psf
Roof Age: 20 years Exposure Category: B
Expected Life Span: 10+ years Ground Snow Load: 20 PSF
FP
Table of Contents
PVGI-1 General Information
PVAL-2 Array Layout
PVMN-3 Materials & Notes
PVED-4 Electrical Diagram
Attachments
1) Panel Data
2) Panel Warranty
3) Inverter Data
4) Inverter Warranty
5) Monitor Data
6) AC Disconnect Data
7) Transfer Switch Data
8) Generator Data
9) Attachment Data
Scope of Work
1)
Scope includes the
installation of a Photovoltaic
Array in a Roof Mounted
Racking System including
related Hardware and
Electrical Equipment
2)
All Electricity generated is for
consumption on the site
3)
Permit shall include labor of
running of Electrical
Conduit(s), installation of
new Electrical Equipment,
and Electrical Connection to
the Existing Site Transformer
4)
The Project does not include
the installation of Batteries
and Battery Management
Equipment
Boone County Electric
1667002
Jurisdiction: Boone County MO Permit, Inspection
Shelli Bergh
21511 US Hwy 63 N, Sturgeon, MO 65284
660-591-6424; shellibergh@embargmail.com
DC: 42.585 kW
AC: 37.8 kW
Missouri Sun Solar Contact Information:
Primary Contact: Ryan Roller: 417-713-1786: rroller@ussunsolar.com
Design: David Hults: 314-856-2171: dhults@ussunsolar.com
Engineer: Billy Arthur, MO PE: 314-6503263: barthur@ussunsolar.com
Missouri Sun Solar, LLC
260 Old State Rd.
Ellisville, MO 63021
PVAL-2
Designer
D. Hults
Reviewer
B. Arthur
Array Layout
42.585kWGridTiedPVSystem
ShelliBergh
21511USHwy63N
SturgeonMO65284
660-591-6424;shellibergh@embargmail.com
Date
2016-03-11
Scale
NTS
N
Entrance
String Design
Inverter 1: Fronius Primo 8.2-1
2 Strings of 13 Panels
1 String of 11 Panels
Inverter 2: Fronius Primo 5.0-1
1 String of 10 Panels
1 String of 9 Panels
MD G
HOUSE
LAKE
BARN
House Northern Exterior
Existing Utility Meter in Transformer
Transfer Switch: Generac RTSN200G3
Standby Generator: Generac 22kW: RG022
PV AC Disconnect: Square-D 200A: D324NRB
LOCUS Monitor
Interior Northern Wall of House
Main Electrical Panels
2x 200A/240V
27'-2"
30'-8"
129'-8"117'-7"
Trench
4/0 Al Direct BuryCable
in 2 Bundles of 4 Cables
8 Cables Total
Minimum 18" Below Grade
Approximately 450'
Roof of Barn
167 Q-Cell 255W Solar Panels
Module Q-Pro.G4 255
Corrugated Metal Roofing
Protea Bracket and PVKit Attachments
2012 IFC Setbacks
MD GPV AC Disconnect Existing Utility MeterGeneratorTransfer Switch
For the Layout
On the Right
10 Panels
9 Panels
13 Panels
13 Panels
11 Panels
Solar Panel
13
13
11
13
11
13
13
11
13
36" from Ridge and Rake
of Roof per 2012 IFC
Interior Southwest Wall of Barn
Main Service Panel for Barn
200A/240V
L
L
INV1
INV1
INV1
INV1
INV2
Exterior Northwestern Area of Building
In-Ground Tap Box for Electrical Service and Solar
Subpanel
Inverters: Fronius 8.2-1 (x4)
Fronius 5.0-1 (x1)
INV2 LOCUS MonitorSolar Inverter
T
T Existing Transformer
DC
PVED-3
Missouri Sun Solar, LLC
260 Old State Rd.
Ellisville, MO 63021
Designer
D. Hults
Reviewer
B. Arthur
Electrical Diagram
42.585kWGridTiedPVSystem
ShelliBergh
21511USHwy63N
SturgeonMO65284
660-591-6424;shellibergh@embargmail.com
Date
2016-03-11
Scale
NTS
All Equipment Clearly Labeled with Descriptive Signage
Roof
of
Barn
Fused AC Disconnect
Square D D324NRB
200A / 240V
167 Q-Cell Solar Panels
255W
Module Q.Pro-G4 255
M To Utility
Existing
Utility Meter
in Transformer
600A/240V
200A
Type R Fuses
A
Exterior Northern
Side of House
Adjacent to the House Entrance
Bergh Solar Project 42.59 kW: Electrical Diagram
C
C
All Conductors
at this Point
Strings
E
D
Wire Schedule
Tag Wire Type Ground Conduit Length
A USE-2 PV NA NA 650'
B #10 THHN Cu #10 THHN 3/4" EMT 100'
C 3/0 AWG THHN Cu #10 THHN 2" PVC 20'
D
4/0 Direct Bury Cable: 4 Wires for Each:
Solar and Barn Service
CU NA NA 410'
E 4/0 AWG THHN CU #3 THHN 2" PVC 40'
Sub Panel
200A/240V
Inverter 1: Fronius Primo 8.2-1 (x4)
Inverter 2: Fronius Primo 5.0-1 (x1)
45A
LOCUS
Monitor
L-Gate 120
D
To House
Loads
200A Service
to Barn
200A
Solar
45A
45A
45A
20A
L
13
11
13
13
13
11
13
13
11
13
13
11
10
9
C C
E
G
Generac Generator
3-Phase 22kW
Model RG022
Generac Transfer Switch
3-Phase 200A
Model RTSN200G3
To Barn
Loads
In-Ground
Tap-Box
400A
Northwest Wall of Barn
All Conductors
at this Point
B
Boone Electric
Solar Meter
250A*
200A
*BooneCountyRequiresSystemOCPDatMAXAMPx125%
The Generac Generator and Transfer-Switch will be manipulated by the
Manufacturer to change from 3-Phase to Single Phase; they will maintain
the 3-Poles to comply with Boone Electrical Cooperative Requirements
Q.PRO BFR-G4 255-265
1
	 APT test conditions: Cells at -1000 V
against grounded, with conductive me-
tal foil covered module surface, 25 °C,
168 h
2
	 See data sheet on rear for further
information.
POLYCRYSTALLINE SOLAR MODULE
The new Q.PRO BFR-G4 is the result of the continued evolution of our
Q.PRO family. Thanks to improved power yield, excellent reliability, and
high-level operational safety, the new Q.PRO BFR-G4 generates electricity
at a low cost (LCOE) and is suitable for a wide range of applications.
THE IDEAL SOLUTION FOR:
Rooftop arrays on
commercial / industrial
buildings
Ground-mounted
solar power plants
Rooftop arrays on
residential buildings
LOW ELECTRICITY GENERATION COSTS
Higher yield per surface area and lower BOS costs thanks to
higher power classes and an efficiency rate of up to 16.2 %.
INNOVATIVE ALL-WEATHER TECHNOLOGY
Optimal yields, whatever the weather with excellent low-light
and temperature behavior.
ENDURING HIGH PERFORMANCE
Long-term yield security with Anti-PID Technology1
,
Hot-Spot-Protect and Traceable Quality Tra.Q™.
LIGHT-WEIGHT QUALITY FRAME
High-tech aluminum alloy frame, certified for
high snow (5400 Pa) and wind loads (4000 Pa).
MAXIMUM COST REDUCTIONS
Up to 10 % lower logistics costs due to higher module capacity per box.
SAFE ELECTRONICS
Protection against short circuits and thermally induced power losses
due to breathable junction box and welded cables.
A RELIABLE INVESTMENT
Inclusive 12-year product warranty and 25-year
linear performance guarantee2
.
ANTI PID TECHNOLOGY
(APT)
HOT-SPOT PROTECT
(HSP)
TRACEABLE QUALITY
(TRA.Q™)
YIELD SECURITY
151 modules tested
Best polycrystalline
solar module 2013
Q.PRO-G2 235
MOD 278 8 p oton n o/ abo a ory



Quality Tested
ID. 40032587
high re iabi ity
low degradation
frequent
product survei lance
Missouri Sun Solar: Bergh Solar Project 49.585kW 1) Panel Data
MECHANICAL SPECIFICATION
Format 65.7 in × 39.4 in x 1.26 in (including frame)
(1670 mm × 1000 mm × 32 mm)
Weight 41.45 lb (18.8 kg)
Front Cover 0.13 in (3.2 mm) thermally pre-stressed glass with anti-reflection technology
Back Cover Composite film
Frame Black anodized aluminum
Cell 6 × 10 polycrystalline solar cells
Junction box 4.33 in × 4.53 in × 0.9 in (110 mm × 115 mm × 23 mm),
Protection class IP67, with bypass diodes
Cable 4 mm² Solar cable; (+) ≥ 39.37 in (1000 mm), (-) ≥ 39.37 in (1000 mm)
Connector Tyco Solarlok PV4, IP68
DETAIL A 0 630 (16 mm)
0 335 (8 5 mm)
0 965 (24 5 mm)
Junction bo×
Product label
38 58 (980 mm)
65 7 (1670 mm)
4 × Fastening points (DETAIL A)
Cable with
connectors
Frame
5 90 (150
mm)
39 4 (1000 mm)
37 44 (951 mm)
1 26 (32 mm)
8 × Drainage holes
6 × Grounding points ø 0 177 (4 5 mm)
39 37 (1000 mm)
Q CELLS PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE
IRRADIANCE [W/m²]
RELATIVEEFFICIENCY[%]
100 200 300 400 500 600 700 800 900 1000
105
100
95
90
85
80
I rad anc [W/m ]
Reatieefficecy[%]
PROPERTIES FOR SYSTEM DESIGN
Maximum System Voltage VSYS
[V] 1000 (IEC) / 1000 (UL) Safety Class II
Maximum Series Fuse Rating [A DC] 20 Fire Rating C / TYPE 1
Max Load (UL)2
[lbs/ft2
] 75 (3600 Pa) Permitted module temperature
on continuous duty
− 40 °F up to +185 °F
(− 40 °C up to +85 °C)
Load Rating (UL)2
[lbs/ft2
] 55.6 (2666 Pa) 2
see installation manual
QUALIFICATIONS AND CERTIFICATES PACKAGING INFORMATION
Number of Modules per Pallet 32
Number of Pallets per 53' Container 32
Number of Pallets per 40' Container 26
Pallet Dimensions ( L × W × H ) 68.7 in × 45.0 in × 46.0 in
(1745 × 1145 × 1170 mm)
Pallet Weight 1323 lb (651 kg)
NOTE: Installation instructions must be followed. See the installation and operating manual or contact our technical service department for further information on approved installation and use
of this product.
RELATIVEEFFICIENCY
COMPAREDTONOMINALPOWER[%]
100
95
90
85
80
75
155 25200 10
YEARS
97
Q CELLS
Industry standard for tiered warranties*
Industry standard for linear warrant es*
*
Standard terms of guarantee for the 10 PV companies
with the highest production capacity in 2014 (as at: September 2014)
Certified
UL 1703
(254141)
TEMPERATURE COEFFICIENTS
Temperature Coefficient of ISC α [% / K] + 0.04 Temperature Coefficient of VOC β [% / K] − 0.30
Temperature Coefficient of PMPP γ [% / K] − 0.41 Normal Operating Cell Temperature NOCT [°F] 113 ± 5.4 (45 ± 3 °C)
UL 1703; VDE Quality Tested; CE-compliant;
IEC 61215 (Ed.2); IEC 61730 (Ed.1) application class A
Specificationssubjecttotechnicalchanges©HanwhaQ CELLSGmbHQ.PROBFR-G4_2015-04_Rev03_NA
At least 97 % of nominal power during
first year. Thereafter max. 0.6 % degra-
dation per year.
At least 92 % of nominal power after
10 years.
At least 83 % of nominal power after
25 years.
All data within measurement tolerances.
Full warranties in accordance with the
warranty terms of the Q CELLS sales
organisation of your respective country.
The typical change in module efficiency at an irradiance of 200 W/m² in relation
to 1000 W/m² (both at 25 °C and AM 1.5 G spectrum) is -2 % (relative).
Hanwha Q CELLS USA Corp.
300 Spectrum Center Drive, Suite 1250, Irvine, CA 92618, USA | TEL +1 949 748 59 96 | EMAIL q-cells-usa@q-cells.com | WEB www.q-cells.us
ELECTRICAL CHARACTERISTICS
POWER CLASS 255 260 265
MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS, STC1
(POWER TOLERANCE +5 W /- 0 W)
Minimum
Power at MPP2
PMPP [W] 255 260 265
Short Circuit Current* ISC [A] 9.07 9.15 9.23
Open Circuit Voltage* VOC [V] 37.54 37.77 38.01
Current at MPP* IMPP [A] 8.45 8.53 8.62
Voltage at MPP* VMPP [V] 30.18 30.46 30.75
Efficiency2
η [%] ≥ 15.3 ≥ 15.6 ≥ 15.9
MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS, NOC3
Minimum
Power at MPP2
PMPP [W] 188.3 192.0 195.7
Short Circuit Current* ISC [A] 7.31 7.38 7.44
Open Circuit Voltage* VOC [V] 34.95 35.16 35.38
Current at MPP* IMPP [A] 6.61 6.68 6.75
Voltage at MPP* VMPP [V] 28.48 28.75 29.01
1
1000 W/m², 25 °C, spectrum AM 1.5 G	 2
Measurement tolerances STC ± 3 %; NOC ± 5 %	 3
800 W/m², NOCT, spectrum AM 1.5 G	 * typical values, actual values may differ
Missouri Sun Solar: Bergh Solar Project 49.585kW
LIMITED WARRANTY FOR CRYSTALLINE PHOTOVOLTAIC MODULES FROM [HANWHA
Q . C E L L S GMBH]
Dear Customer,
You have made an excellent choice in purchasing quality modules from [Hanwha Q.CELLS GmbH] (“Q CELLS”). The photovoltaic
modules you have purchased have been manufactured with great care and have undergone a final functional test. We also
provide the following limited warranty (“Warranty”):
SCOPE
This Warranty applies exclusively to Q CELLS photovoltaic
modules of the following types (the “Modules”):
• Q.PEAK G2
• Q.PEAK G3
• Q.PEAK BLK G2
• Q.PEAK BLK G3
• Q.PRO G2
• Q.PRO G3
• Q.PRO L
All Modules must be sold and installed within the United States
and bear our manufacturer‘s label to be elig ble for this Warranty.
Warrantor is Hanwha Q.CELLS GmbH, OT Thalheim, Sonnenallee
17-21, 06766 Bitterfeld-Wolfen, Germany.
The applicable Warranty period begins on the date of the initial
purchase of the Modules by the original end customer as set forth
in the applicable invoice (the “Purchase Date”).
12-YEAR PRODUCT WARRANTY
Q CELLS warrants to you that Modules which are installed in
accordance with the applicable installation and operation manual
and other product documentation provided to customers by
Q CELLS for the Modules (collectively, “Product Instructions”) will
not show any defects in materials or workmanship for a period of
twelve years after the applicable Purchase Date. In the event that
a Module has any such defect covered by this warranty (case of
warranty), Q CELLS, at its choice, will either repair the defect or
supply a replacement Module. If Q CELLS is unable to repair the
defect or supply a replacement Module, Q CELLS will have the
right to refund you the prorated value of the purchase price paid by
you to Q CELLS or Q CELLS’ authorized reseller for the affected
Modules (“Purchase Price”), provided that you first return to
Q CELLS the affected Module. The foregoing constitutes your sole
and exclusive remedy for a breach of the warranty set forth in this
paragraph (the “Product Warranty”).
25-YEAR LINEAR PERFORMANCE WARRANTY
In addition, Q CELLS provides you the following performance
warranty (“Performance Warranty”) for Modules which are installed
in accordance with the applicable Product Instructions:
In the first year after the Purchase Date the Modules will produce
a minimum power output of at least 97 % of that specified in the
Module data sheet. From a period beginning on the first
anniversary of the Purchase Date and ending on the twenty-fifth
anniversary of the Purchase Date, the Modules will have a yearly
maximum decrease of power output (degradation) of not more
than 0.6 % of the power output specified in the Module data sheet
within the framework of the power tolerance, i.e. the Module will
have a minimum power output of at least 83 % of the power output
specified in the Module data sheet at the end of the twenty-five
year period.
All power output measurements will be performed under the STC
Standard Test Conditions used by Q CELLS on the Purchase
Date. The STC Standard Test Conditions are customary
standardized basic conditions for the measurement of the power of
solar modules. The currently valid STC Standard Test Conditions
are defined in the IEC standards EN 61215 and 60904-3.
In the event of a breach of this Performance Warranty, Q CELLS
will, at its choice, repair the defect, replace the affected Module,
supply additional modules sufficient to make up for the power
output reduction, refund you the full Purchase Price of the affected
Module provided that you first return to Q CELLS the affected
Module, or refund you a percentage of the Purchase Price of the
affected Module equal to the percentage reduction in minimum
power output compared to the minimum power output warranted
under this Performance Warranty. The foregoing constitutes your
sole and exclusive remedy for a breach of this Performance
Warranty.
EXCLUSIONS FROM THE PRODUCT AND PERFORMANCE
WARRANTY
Irrespective of contributory root causes, this Warranty does not
cover the following cases:
• Handling, storage, installation, configuration, testing, or use not
in accordance with the Product Instructions (e.g., static,
installation of mutually incompatible modules, inadequate
system design, and incompatible inverter);
• Repair, servicing or maintenance work not in accordance with
the Product Instructions or failure to perform maintenance as
required by the Product Instructions.
• Usage in an environment outside the parameters specified in
the Product Instructions, including without limitation high snow
load outside such parameters;
• Usage for purposes or in circumstances not conforming to the
product specifications (as set out in the module data sheet
applicable to the modules in any given case) and not complying
with the installation and operating instructions;
• Damage caused by environmental sources, such as but not
limited to pollution of any kind as well as fire, explosion, smoke
or charring;
• Damage caused by acts of nature or God, including without
limitation lightning, hail, frost, snow, or storms;
• Damage caused by abuse, negligence, neglect, or accident,
including without limitation acts of violence and vandalism
• Damages to the photovoltaic system in which the Modules are
installed, or damages caused by factors such as voltage
fluctuations, power peaks, excess voltage, power failure etc.;
• Scratches, marks, mechanical wear, rust, mold, degradation,
dis-coloration and other changes which occur after the delivery
of the Modules but which do not result in any adverse effect on
the mechanical stability of the Module or a reduction of
performance which exceeds the levels set out in the
Performance Warranty; and
• Issues not reproduc ble by Q CELLS.
The following cases are also excluded from the Warranty:
• The Q CELLS Modules are modified or altered or used in
processes involving other products without obtaining prior
written consent from Q CELLS.
• The serial number or product label has been removed,
changed, deleted or made unrecognizable or if it is no longer
clearly distinguishable for other reasons beyond Q CELLS’
control and therefore it is not possible to conclusively identify
the Modules.
Use on mobile carriers such as motor vehicles or ships. As part of
the warranty there is no claim to compensation for the
2) Panel Warranty DataMissouri Sun Solar: Bergh Solar Project 49.585kW
LIMITED WARRANTY FOR CRYSTALLINE PHOTOVOLTAIC MODULES FROM [HANWHA
Q . C E L L S GMBH]
reimbursement of costs for dismantling, installation or
replacement, loss of yield or other indirect damages.
CLAIMS UNDER WARRANTY/NOTIFICATION OF DEFECTS
You must check the Modules for visible defects upon delivery. If
you discover any defects, you must report these immediately to
Q CELLS.
You must report any Warranty claim to Q CELLS during the
applicable Warranty period and no later than thirty (30) days after
discovering the breach of Warranty.
Please contact us first in writing or electronically. Contact
information, the required data and the procedure of the complaint
process are described in document Q CELLS’ RMA process
(Return Merchandise Authorization). You must follow the RMA
process to be eligible for Warranty service.
If you have any questions please contact your seller or Q CELLS
at the following e-mail address: service@q-cells.com.
We ask for our customers’ understanding that Q CELLS cannot
accept any unauthorized return shipments of Modules and will not
take delivery of such items.
PERFORMANCE OF THE WARRANTY SERVICES
In all cases, Q CELLS shall have the choice in accordance with
this Warranty as to how Warranty claims are settled. Q CELLS
may use the services of a third party service partner for this
purpose.
• Q CELLS shall pay the costs of a technical inspection of the
affected Module in case of a Warranty claim. If there is no
breach of Warranty as reasonably determined by Q CELLS, you
will pay these costs
• Q CELLS shall only accept liability under the performance
warranty if the performance parameters measured by Q CELLS
in the STCs (Standard Test Conditions) are not achieved.
• The returned Modules shall remain your property unless
Q CELLS chooses to replace such Modules, in which case
ownership of the replaced Modules passes to Q CELLS.
• Any repaired or replaced Modules shall be covered by the
Warranty for the remaining portion of the original Warranty
period as applicable.
• If Q CELLS supplies replacement or additional modules under
this Warranty and the original Module type is no longer
available, Q CELLS will have the right to provide replacement or
additional modules of a similar or equivalent type from the
product range available at the time of the claim as long as they
are suitable for the intended purpose.
• In the event of glass breakage, Q CELLS reserves the right to
perform a static calculation to verify the substructure was
designed in accordance with the Product Instructions.
• Q CELLS will have no liability in connection with this Warranty
for any costs or expenses of dismantling or installing Modules or
replacement modules.
DISCLAIMER
EXCEPT AS EXPRESSLY SET FORTH IN THE PRODUCT
WARRANTY AND THE PERFORMANCE WARRANTY, Q CELLS
HEREBY DISCLAIMS ALL WARRANTIES, WHETHER
EXPRESS, IMPLIED, OR STATUTORY, REGARDING THE
MODULES, INCLUDING WITHOUT LIMITATION ANY
WARRANTIES OF MERCHANTABILITY, FITNESS FOR A
PARTICULAR PURPOSE, TITLE, NON-INFRINGEMENT OF
THIRD-PARTY RIGHTS, AND SYSTEM INTEGRATION.
LIMITATION OF LIABILITY
Q CELLS WILL NOT BE LIABLE FOR ANY CONSEQUENTIAL,
EXEMPLARY, SPECIAL, INDIRECT, OR INCIDENTAL
DAMAGES, INCLUDING ANY DAMAGES FOR LOST PROFITS
OR LOSS OF YIELD, ARISING FROM OR RELATING TO THIS
WARRANTY OR THE MODULES, EVEN IF Q CELLS KNEW OR
SHOULD HAVE KNOWN OF THE POSSIBILITY OF SUCH
DAMAGES. Q CELLS’ TOTAL CUMULATIVE LIABILITY
ARISING FROM OR RELATED TO THIS WARRANTY AND THE
MODULES, WHETHER IN CONTRACT OR TORT OR
OTHERWISE, WILL NOT EXCEED THE PRODUCT PRICE FOR
THE MODULE(S) AT ISSUE. THE FOREGOING LIMITATIONS
OF LIABILITY ARE INDEPENDENT OF EXCLUSIVE REMEDIES
FOR BREACH OF THIS WARRANTY. Q CELLS DISCLAIMS
ALL LIABILITY OF ANY KIND OF Q CELLS’ SUPPLIERS UNDER
THIS AGREEMENT.
SOME STATES DO NOT ALLOW THE EXCLUSION OF IMPLIED
WARRANTIES OR THE EXCLUSION OR LIMITATION OF
INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE
ABOVE LIMITATIONS OR EXCLUSIONS MAY NOT APPLY TO
YOU. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS,
AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY
FROM STATE TO STATE. THE DISCLAIMERS, EXCLUSIONS,
AND LIMITATIONS OF LIABILITY UNDER THIS WARRANTY
WILL NOT APPLY TO THE EXTENT PROHIBITED BY
APPLICABLE LAW.
ASSIGNMENT OF WARRANTY FOR PV MODULES
This Warranty for PV Modules in its entirety, extends only to the
original purchaser, and is transferrable in its entirety to any other
person to whom title to the PV Modules has been transferred
provided that a) a prior written notice of such transfer has been
received by Q CELLS, and b) the PV Modules remain installed in
their original installation location.
GOVERNING LAW
These Warranty terms and conditions shall be exclusively
governed by the laws of the State of California, without giving
effect to any conflict of laws principles that would require the
application of the laws of another State laws principles that would
require the application of the laws of another State.
Missouri Sun Solar: Bergh Solar Project 49.585kW
/ Perfect Welding / Solar Energy / Perfect Charging
/ With power categories ranging from 3.8 kW to 15.0 kW, the transformerless Fronius Primo is the ideal compact
single-phase inverter for residential applications. The sleek design is equipped with the SnapINverter hinge mounting
system which allows for lightweight, secure and convenient installation and service. The Fronius Primo has several
integrated features that set it apart from competitors including dual powerpoint trackers, high system voltage, a wide
input voltage range, Wi-Fi* and SunSpec Modbus interface for seamless monitoring and datalogging, Arc Fault Circuit
Interruption (AFCI), and Fronius’ online and mobile platform Fronius Solar.web. The Fronius Primo is designed to
adjust to future standards, offering a complete solution to code restrictions and technical innovations of tomorrow. It
also works seamlessly with the Fronius Rapid Shutdown Box for a reliable NEC 2014 solution.
TECHNICAL DATA FRONIUS PRIMO
/ The future of residential solar is here - Introducing the new Fronius Primo.
/ SuperFlex
Design
/ Wi-Fi®*
interface
/ Smart Grid
Ready
/ Arc Fault Circuit
Interruption
/ SnapINverter
mounting system
/ PC board
replacement process
FRONIUS PRIMO
GENERAL DATA FRONIUS PRIMO 3.8 - 8.2 FRONIUS PRIMO 10.0-15.0
Dimensions (width x height x depth) 16.9 x 24.7 x 8.1 in. 20.1 x 28.5 x 8.9 in.
Weight 47.29 lb. 82.5 lbs.
Degree of protection NEMA 4X
Night time consumption < 1 W
Inverter topology Transformerless
Cooling Variable speed fan
Installation Indoor and outdoor installation
Ambient operating temperature range -40 - 131°F (-40 - 55°C) -40 - 140°F (-40 - 60°C)
Permitted humidity 0 - 100 %
DC connection terminals
4x DC+ and 4x DC- screw terminals for copper (solid / stranded /
fine stranded) or aluminum (solid / stranded)
4x DC+1, 2x DC+2 and 6x DC- screw terminals for copper (solid /
stranded / fine stranded) or aluminum (solid / stranded)
AC connection terminals Screw terminals 12 - 6 AWG
Revenue Grade Metering Optional (ANSI C12.1 accuracy)
Certificates and compliance with standards
UL 1741-2010, UL1998 (for functions: AFCI and isolation
monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE
C62.41, FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01
(September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1
-2013
UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation
monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE
C62.41, FCC Part 15 A & B, NEC Article 690-2014, C22. 2 No.
107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL
M-07 Issue 1 -2013
PROTECTIVE DEVICES STANDARD WITH ALL PRIMO MODELS
AFCI & 2014 NEC Ready Yes
Ground Fault Protection with Isolation Monitor
Interrupter
Yes
DC disconnect Yes
DC reverse polarity protection Yes
N
W
S
E
INTERFACES STANDARD WITH ALL PRIMO MODELS
Wi-Fi*/Ethernet/Serial Wireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU
6 inputs or 4 digital inputs/outputs External relay controls
USB (A socket) Datalogging and/or updating via USB
2x RS422 (RJ45 socket) Fronius Solar Net, interface protocol
Datalogger and Webserver Included
*The term Wi-Fi® is a registered trademark of the Wi-Fi Alliance.
3) Inverter DataMissouri Sun Solar: Bergh Solar Project 49.585kW
Rev. 11.3.15 USA
/ Perfect Welding / Solar Energy / Perfect Charging
v05 May 2015 EN
Further information about all Fronius products and our global sales partners and representatives can be found at www.fronius.com
WE HAVE THREE DIVISIONS AND ONE PASSION: SHIFTING THE LIMITS OF POSSIBILITY.
/ Whether welding technology, photovoltaics or battery charging technology − our goal is clearly defined: to be the innovation leader. With around
3,300 employees worldwide, we shift the limits of what’s possible - our record of over 900 granted patents is testimony to this. While others progress
step by step, we innovate in leaps and bounds. Just as we’ve always done. The responsible use of our resources forms the basis of our corporate policy.
Fronius USA LLC
6797 Fronius Drive
Portage, IN 46368
USA
pv-support-usa@fronius.com
www.fronius-usa.com
TECHNICAL DATA FRONIUS PRIMO
INPUT DATA PRIMO 3.8-1 PRIMO 5.0-1 PRIMO 6.0-1 PRIMO 7.6-1 PRIMO 8.2-1
Recommended PV power (kWp) 3.0 - 6.0 kW 4.0 - 7.8 kW 4.8 - 9.3 kW 6.1 - 11.7 kW 6.6 - 12.7 kW
Max. usable input current (MPPT 1/MPPT 2) 18 A / 18 A 18 A / 18 A 18 A / 18 A 18 A / 18 A 18 A / 18 A
Total max. DC current 36 A
Max. array short circuit current (1.25 Imax) (MPPT 1/
MPPT 2)
22.5 A / 22.5 A
Operating voltage range 80 V - 600 V
Max. input voltage 600 V
Nominal input voltage 410 V 420 V 420 V 420 V 420 V
Admissable conductor size DC AWG 14 - AWG 6
MPP Voltage Range 200 - 480 V 240 - 480 V 240 - 480 V 250 - 480 V 270 - 480 V
Number of MPPT 2
OUTPUT DATA PRIMO 3.8-1 PRIMO 5.0-1 PRIMO 6.0-1 PRIMO 7.6-1 PRIMO 8.2-1
Max. output power 240 V 3800 W 5000 W 6000 W 7600 W 8200 W
208 V 3800 W 5000 W 6000 W 7600 W 7900 W
Max. continuous output current 240 V 15.8 A 20.8 A 25.0 A 31.7 A 34.2 A
208 V 18.3 A 24.0 A 28.8 A 36.5 A 38.0 A
Recommended OCPD/AC breaker size 240 V 20 A 30 A 35 A 40 A 45 A
208 V 25 A 30 A 40 A 50 A 50 A
Max. Efficiency 96.7 % 96.9 % 96.9 % 96.9 % 97.0 %
CEC Efficiency 240 V 95.0 % 95.5 % 96.0 % 96.0 % 96.5 %
Admissable conductor size AC AWG 14 - AWG 6
Grid connection 208 / 240 V
Frequency 60 Hz
Total harmonic distortion < 5.0 %
Power factor (cos φac,r) 0.85-1 ind./cap
INPUT DATA PRIMO 10.0-1 PRIMO 11.4-1 PRIMO 12.5-1 PRIMO 15.0-1
Recommended PV power (kWp) 8.0 - 12.0 kW 9.1 - 13.7 kW 10.0 - 15.0 kW 12.0 - 18.0 kW
Max. usable input current (MPPT 1/MPPT 2) 33.0 A / 18.0 A
Total max. DC current 51 A
Max. array short circuit current (1.25 Imax) (MPPT 1/MPPT 2) 41.3 A / 22.5 A
Operating voltage range 80 V - 600 V
Max. input voltage 600 V
Nominal input voltage 415 V 420 V 425 V 440 V
Admissable conductor size DC
AWG 14 - AWG 6 copper direct, AWG 6 aluminum direct (AWG 10 copper or AWG 8 aluminium for overcurrent protective devices
up to 60A, from 61 to 100A minimum AWG 8 for copper or AWG 6 aluminium has to be used), AWG 4 - AWG 2 copper or alu-
minum with optional input combiner
MPP Voltage Range 220 - 480 V 240 - 480 V 260 - 480 V 320 - 480 V
Integrated DC string fuse holders 4- and 4+ for MPPT 1 / no fusing requried on MPPT 2
Number of MPPT 2
OUTPUT DATA PRIMO 10.0-1 PRIMO 11.4-1 PRIMO 12.5-1 PRIMO 15.0-1
Max. output power 240 V 9995 W 11400 W 12500 W 15000 W
208 V 9995 W 11400 W 12500 W 13750 W
Max. continuous output current 240 V 41.6 A 47.5 A 52.1 A 62.5 A
208 V 48.1 A 54.8 A 60.1 A 66.1 A
Recommended OCPD/AC breaker size 240 V 60 A 60 A 70 A 80 A
208 V 70 A 70 A 80 A 90 A
Max. Efficiency 96.7 %
CEC Efficiency 96.0 % 96.5 %
Admissable conductor size AC
AWG 10 - AWG 2 copper (solid / stranded / fine stranded)(AWG 10 copper or AWG 8 aluminium for overcurrent protective devices
up to 60A, from 61 to 100A minimum AWG 8 for copper or AWG 6 aluminium has to be used) , AWG 6 - AWG 2 copper(solid /
stranded) MultiContactWiringable with AWG 12
Grid connection 208 / 240 V
Frequency 60 Hz
Total harmonic distortion < 2.5 %
Power factor (cos φac,r) 0-1 ind./cap.
Missouri Sun Solar: Bergh Solar Project 49.585kW
SE_ToW_EN_US_0415 1/2
FRONIUS LIMITED WARRANTY
TERMS AND CONDITIONS
valid from: 10/15/2015
These limited warranty terms and conditions apply to original
installation of Fronius inverters in the United States of
America. The warranty agreement is concluded between
Fronius and the warranty holder (owner of the installed
system).
Content of the warranty:
Fronius Warranty Plus/Warranty Extension Plus
The Fronius Warranty Plus/Warranty Extension Plus covers
the costs of materials, servicing and transport under the
terms and conditions indicated below.
Fronius Warranty/Warranty Extension
The Fronius Warranty/Warranty Extension covers the costs
of materials under the terms and conditions indicated below.
Duration of warranty:
In each case the warranty period begins the day that the
products leave the Fronius factory.
Fronius string inverters (wall-mounted devices)
Fronius string inverters are supplied with a 10-year Fronius
Warranty Plus.
Fronius central inverters (free-standing devices)
Fronius central inverters are supplied with a 5-year Fronius
Warranty Plus.
Fronius Rapid Shut-down Box (RSB)
Fronius Rapid Shut-down boxes are supplied with a 5-year
Fronius Warranty Plus.
Warranty services:
If a fault should occur during the Fronius warranty period and
the fault is covered by the limited warranty terms and
conditions, Fronius reserves the right to
 make the corresponding spare parts available,
 make an equivalent replacement device available,
 repair this fault at its premises or on the customer's
premises,
 or have these services carried out by a suitably-trained
Fronius Service Partner.
Materials
"Materials" means that, during the warranty period, Fronius
will bear the cost of materials (spare part or replacement
device excluding labour costs) associated with the warranty
service.
Servicing
The warranty covers the labour costs associated with the
materials, provided that these are incurred by Fronius itself
or a Fronius Service Partner (service fee).
Other incidental costs (such as travel costs, installation costs,
if these exceed the Fronius service fee, customs duties, etc.)
are not covered by the warranties.
Transport
National transport costs are covered by the Fronius Warranty
Plus and Fronius Warranty Extension Plus, provided that
these are incurred in accordance with the standard claim
procedures with the Fronius Service Provider. Fronius will
not bear the costs of any unjustified or express deliveries.
General provisions
Devices or components are to be returned in the original or
equivalent packaging. Fronius retains ownership of
replacement devices and components inside or outside of
the warranty/warranty exclusion until the faulty parts/devices
have been received. In all cases ownership of the faulty
device/parts is transferred to Fronius when the replacement
device is received. If the faulty device/parts is/are not
returned to Fronius within 60 days, they will be charged to
the installer at the current replacement prices.
Fronius Warranty Extension/Warranty Extension Plus
An extended warranty can be purchased up to 30 months
after dispatch by Fronius. Fronius may reject orders received
later. The extended warranties only apply to Fronius
inverters unambiguously identified by their serial number.
It is possible to extend the warranty to 10, 15 or 20 years
from dispatch by Fronius.
Considerations when making a warranty claim
First contact an installer, who will then contact Fronius if
necessary.
The Fronius warranty procedure must be strictly adhered to
in the event of a warranty claim. This is the only way of
ensuring that the warranty services remain free of charge for
the warranty holder.
The purchase invoice, serial number of the device and start-
up report (the date on which the device was
provided/commissioned and report from the power supply
company), as well as proof of payment of the warranty
extension fee, are required for warranty claims. The
purchase price must have been paid to Fronius in full in order
for the warranty service to be provided.
When devices or components are replaced, the remaining
warranty period is transferred to the replacement device or
4) Inverter Warranty Data
Missouri Sun Solar: Bergh Solar Project 49.585kW
SE_ToW_EN_US_0415 2/2
replacement component. This is automatically registered at
Fronius. A new certificate is not issued.
If servicing is carried out on site, the client must guarantee
unrestricted access to the Fronius inverters. If necessary, the
warranty holder must make the equipment required by the
applicable health and safety regulations available free of
charge.
Scope and validity of the warranty
The Fronius warranties apply only to Fronius products that
have been identified unambiguously by their serial number.
These must be appropriately certified for the country of
installation. The other components of the photovoltaic
system as well as the system add-ons, system monitoring
and data communication components, any accessories, and
pre-production devices are excluded from the warranty.
These components fall under the corresponding provisions
of the applicable General Delivery and Payment Conditions
of Fronius.
Exclusions from the Fronius warranties
Failure to observe the operating instructions, installation
instructions or maintenance procedures.
 Improper installation
 Improper commissioning
 Improper transportation
 Improper or incorrect operation
 Inadequate ventilation of the device
 Any work performed on the device by companies or
persons that have not been authorised by Fronius
 Failure to observe safety rules and installation standards
 Force majeure (storm, lightning, overvoltage, fire, etc.)
Damage to the Fronius inverter caused by other components
in the photovoltaic system or damage that does not impair
the function of the Fronius inverter ("cosmetic flaws") is also
excluded from the warranty.
The warranty does not cover travel and accommodation
expenses as well as on-site assembly and installation costs,
if these exceed the service reimbursement paid to the
installer by Fronius depending on the service and agreement.
Changes to the existing PV system, in-house installation and
similar or the time involved and the costs incurred are not
covered by the warranty.
Due to technological progress, the equivalent replacement
or new device provided may not be compatible with the
system monitoring or other components installed on site (e.g.
Fronius DATCOM). The warranty does not cover the
expenses and costs incurred as a result of upgrading system
monitors or other components of the PV system.
A claim for compensation cannot be made for energy that
has not been fed into the grid or energy that has not been
consumed in-house, etc.
Fuses and other wearing parts are excluded from the
warranty.
Other legal information
SELLER DISCLAIMS ALL IMPLIED WARRANTIES AND
SIMILAR OBLIGATIONS (OTHER THAN THAT THE
GOODS WILL BE NEW AND GOOD TITLE) INCLUDING
BUT NOT LIMITED TO THOSE OF FITNESS FOR A
PARTICULAR PURPOSE, AND MERCHANTABILITY,
WHETHER OTHERWISE ARISING BY LAW, CUSTOM,
USAGE, TRADE PRACTICE, COURSE OF DEALING, OR
COURSE OF PERFORMANCE. There are no warranties
which extend beyond those express warranties contained in
the Agreement. Buyer affirms that it has not relied upon
Seller’s skill nor judgment to select or furnish the Goods for
any particular purpose beyond the specific express
warranties in the Agreement. Seller does not warrant the
Goods will comply with the requirements of any safety or
environmental code or regulation of any federal, state,
municipality or other jurisdiction beyond the specific express
warranties in the Agreement. Seller does not warrant that
the Goods will operate with any accessories or within any
system not sold under the Agreement and Seller’s warranty
is limited to the operation of the Goods in a stand-alone
mode. Some countries, states, or provinces do not allow the
exclusion or limitation of implied warranties or the limitation
of incidental or consequential damages for certain products
supplied to consumers, or the limitation of liability for
personal injury, so such limitations and exclusions may be
limited in their application to an end user and others. When
the implied warranties are not allowed to be excluded in their
entirety, they will be limited to the duration of the applicable
written warranty. The warranty gives specific legal rights
which may vary depending on local law.
Other legal warranty or liability claims against Fronius remain
unaffected by this warranty.
In the event of such claims, please contact the vendor of your
device.
Our General Delivery and Payment Conditions under "Legal
information" on our website (www.fronius.com) also apply.
Previously valid warranty conditions are replaced by these
conditions. Fronius reserves the right to make changes to
the warranty process at any time.
Current and detailed information about warranty terms and
conditions can be found on our website at
www.fronius.com/solar/warranty
Missouri Sun Solar: Bergh Solar Project 49.585kW
LGate 120
RESIDENTIAL SOLAR MONITORING SOLUTION
Product Datasheet
The LGate 120 is a single-phase electronic watt-hour meter
for remote monitoring of solar photovoltaic systems. It
features a smart communications module to automatically
transmit meter data over cellular or Ethernet networks
allowing system owners and operators to easily manage
distributed solar assets.
The LGate 120 combines a revenue-grade, solid-state power meter with an advanced communications gateway.
These components work in conjunction to remotely monitor the performance of residential solar energy installation
regardless of panel or inverter type. The LGate 120 is a one-piece completely under glass meter which installs
easily using a standard socket base. Performance data is uploaded in near real-time to the Locus Energy SolarOS
monitoring platform which provides a suite of tools and analytics for asset managers.
DATA COLLECTION
AC energy data is collected by the meter and passed to the communications module. Additional system
performance data can be collected directly from meteorological sensors and supported inverters via RS-485 or
Zigbee connections. All data is stored in non-volatile memory and then automatically uploaded to the SolarOS and
SolarNOC platforms.
NETWORK CONNECTIVITY
The communications gateway inside the LGate 120 supports plug and play connectivity through a cellular or Ethernet
network connection. Once the unit is installed and powered on, it will immediately begin transmitting data without
any configuration. For maximum reliability, the communications gateway will automatically route uploads between the
wireless and wired connections if either of the networks are unavailable.
FEATURES
• ANSI C12.20 power meter
• RS-485 and Zigbee inputs
• GSM cellular or Ethernet connectivity
• Over the air firmware updates
• Easy, low cost installation
• Doesn’t require entrance into the building
• Plug and play activation
• LCD display
Missouri Sun Solar: Bergh Solar Project 49.585kW 5) Monitor Data
DATALOGGER
Processor	 ARM9 embedded CPU
OS			 Custom version of Linux 2.6, OTA firmware updates
Memory	 128 MB RAM
Display	 LCD screen
SPECIFICATIONS
COMMUNICATIONS
LAN		 RJ45 10/100 Ethernet, full half duplex, auto polarity
Cellular	 3G GSM
Networking	 DHCP or static
PHYSICAL
Enclosure	 NEMA 3R Type
Weight	 8 oz
Dimensions	 6.95” x 6.5” x 7.3”
Environment	 -20 to 60C, all-weather
Warranty	 5 year limited warranty
DIAGRAM – TYPICAL CONFIGURATION
DIMENSIONS
I/O
RS485 2 wire and 4 wire
Modbus
Zigbee
Shielded CAT5
LEGEND
6.95 in
6.31 in
5.46 in
6.00 in
7.30 in
SOCKET METER
COMPLIANCE
ANSI 12.20 class 0.2%
FCC Part 15B
PTCRB
AT&T Carrier Compliance
PV ARRAY
ELECTRICAL
SERVICE
INVERTER(S)
INTERNET
LGATE 120
METER BASE METER MODULE
LOCUS ENERGY
COMM MODULE
POWER
Accuracy		 ANSI 12.20 (Class 0.2%)
Voltage Inputs		 120 - 480 VAC
Max. Current Input		 200 A
Service Type		 Single phase , 60 Hz
Socket Type		 2S
Missouri Sun Solar: Bergh Solar Project 49.585kW
Product Data Sheet D324NRB
Safety Switch , 200A, Fusible, Cartridge (Class H,
K or R), 3-Pole
List Price $1,461.00 USD
Availability Stock Item: This item is normally stocked in our distribution facility.
Terminal Type Lugs
Type of Duty General Duty
Maximum Voltage Rating 240VAC
Wire Size #2 to 300 AWG/kcmil(Al) - #4 to 300 AWG/kcmil(Cu)
Depth 8.25 Inches
Height 29.25 Inches
Width 17.25 Inches
Action Single Throw
Ampere Rating 200A
Approvals UL Listed File: E2875
Enclosure Rating NEMA 3R
Enclosure Type Rainproof and Sleet/Ice proof (Indoor/Outdoor)
Enclosure Material Galvannealed Steel
Factory Installed Neutral Yes
Fuse Type Cartridge (Class H, K or R)
Disconnect Type Fusible
Short Circuit Current Rating 100kA (max. depending on fuse type)
Mounting Type Surface
Number of Poles 3-Pole
Technical Characteristics
Category 00106 - Safety Switch, General Duty, 30 - 200 Amp, NEMA3R
Discount Schedule DE1A
GTIN 00785901461524
Package Quantity 1
Weight 45.33 lbs.
Availability Code Stock Item: This item is normally stocked in our distr bution facility.
Returnability Y
Country of Origin US
Shipping and Ordering
As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this document.
Generated: 06/30/2010 15:08:04
© 2010 Schneider Electric. All rights reserved. 1
6) Disconnect DataMissouri Sun Solar: Bergh Solar Project 49.585kW
1 of 11
¡	INNOVATIVE DESIGN  PROTOTYPE TESTING are key components of
GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it
doesn’t stop there. Total commitment to component testing, reliability
testing, environmental testing, destruction and life testing, plus testing
to applicable CSA, NEMA, EGSA, and other standards, allows you to
choose GENERAC POWER SYSTEMS with the confidence that these
systems will provide superior performance.
¡	 TEST CRITERIA:
	 3	PROTOTYPE TESTED	 3	NEMA MG1-22 EVALUATION
	 3	SYSTEM TORSIONAL TESTED	 3	MOTOR STARTING ABILITY
¡	SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
This state-of-the-art power maximizing regulation system is standard on
all Generac models. It provides optimized FAST RESPONSE to changing
load conditions and MAXIMUM MOTOR STARTING CAPABILITY by
electronically torque-matching the surge loads to the engine. Digital
voltage regulation at ±1%.
¡	SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer
network provides parts and service know-how for the entire unit, from the
engine to the smallest electronic component.
¡	GENERAC TRANSFER SWITCHES. Long life and reliability are
synonymous with GENERAC POWER SYSTEMS. One reason for this
confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility.
INCLUDES:
• Two Line LCD Multilingual Digital
Evolution™ Controller (English/Spanish/
French/Portuguese) with external
viewing window for easy indication of
generator status and breaker position.
• True Power™ Electrical Technology
• Isochronous Electronic Governor
• Sound Attenuated Enclosure
• Closed Coolant Recovery System
• Smart Battery Charger
• UV/Ozone Resistant Hoses
• ±1% Voltage Regulation
• Natural Gas or LP Operation
• 5 Year Limited Warranty
• UL 2200 Listed
Standby Power Rating
Model RG022 (Aluminum - Gray) - 22 kW 60 Hz
Model RG027 (Aluminum - Gray) - 27 kW 60 Hz
Model RG032 (Aluminum - Gray) - 32 kW 60 Hz
Model RG038 (Aluminum - Gray) - 38 kW 60 Hz
Model RG048 (Aluminum - Gray) - 48 kW 60 Hz
FEATURES
ISO9001:
2008
PROTECTOR® QS SERIES
Standby Generators
Liquid-Cooled Gaseous Engine
Protector®QSSeries
Protector®
QS
Series
Meets EPA Emission Regulations
22  27 kW are CA/MA emissions compliant
48 kW meets CA/MA emissions requirements with optional catalyst
32  38 kW not for sale in CA/MA
®
*Built in the USA using domestic
and foreign parts
Missouri Sun Solar: Bergh Solar Project 49.585kW 7) Generator Data
2 of 11
22 • 27 • 32 • 38 • 48 kW	 application  engineering data
GENERATOR SPECIFICATIONS
Type Synchronous
Rotor Insulation Class
H (22  27 kW) or
F (32, 38  48 kW)
Stator Insulation Class H
Telephone Interference Factor (TIF) 50
Alternator Output Leads 1-Phase 4 wire
Alternator Output Leads 3-Phase 6 wire
Bearings Sealed Ball
Coupling Flexible Disc
Excitation System Direct
VOLTAGE REGULATION
Type Electronic
Sensing Single Phase
Regulation ± 1%
GOVERNOR SPECIFICATIONS
Type Electronic
Frequency Regulation Isochronous
Steady State Regulation ± 0.25%
ELECTRICAL SYSTEM
Battery Charge Alternator 12 Volt 30 Amp
Static Battery Charger 2.5 Amp
Recommended Battery (battery not included)
Group 26 (22, 27, 32  38 kW)
or Group 24F (48 kW), 525CCA
System Voltage 12 Volts
GENERATOR FEATURES
Revolving field heavy duty generator
Directly connected to the engine
Operating temperature rise 120 °C above a 40 °C ambient
Class H insulation is NEMA rated
Class F insulation is NEMA rated
All models fully prototyped tested
ENCLOSURE FEATURES
Aluminum weather
protective enclosure
Ensures protection against mother nature.
Electrostatically applied textured epoxy paint for added
durability.
Enclosed critical grade
muffler
Quiet, critical grade muffler is mounted inside the unit
to prevent injuries.
Small, compact, attractive Makes for an easy, eye appealing installation.
SAE Sound attenuated enclosure ensures quiet operation.
ENGINE SPECIFICATIONS: 22, 27, 32  38 kW
Make Generac
Model In-line
Cylinders 4
Displacement (Liters) 2.4
Bore (in/mm) 3.41/86.5
Stroke (in/mm) 3.94/100
Compression Ratio 9.5:1
Intake Air System
Naturally Aspirated (22  27 kW) or
Turbocharged/Aftercooled
(32  38 kW)
Lifter Type Hydraulic
ENGINE SPECIFICATIONS: 48 kW
Make Generac
Model V-Type
Cylinders 8
Displacement (Liters) 5.4
Bore (in/mm) 3.55/90.2
Stroke (in/mm) 4.17/105.9
Compression Ratio 9:1
Intake Air System Naturally Aspirated
Lifter Type Hydraulic
ENGINE LUBRICATION SYSTEM
Oil Pump Type Gear
Oil Filter Type Full flow spin-on cartridge
Crankcase Capacity (qt/l)
4/3.8 (22, 27, 32  38 kW) or
6/5.7 (48 kW)
ENGINE COOLING SYSTEM
Type Closed
Water Pump Belt driven
Fan Speed (rpm)
1980 - 22  27 kW
1500 - 32  38 kW
1954 - 48 kW
Fan Diameter (in/mm)
18.1/459.7 (22  27 kW) or
22/558.8 (32, 38  48 kW)
Fan Mode
Pusher (22  27 kW) or
Puller (32, 38  48 kW)
FUEL SYSTEM
Fuel Type Natural gas, propane vapor
Carburetor Down Draft
Secondary Fuel Regulator Standard
Fuel Shut Off Solenoid Standard
Operating Fuel Pressure 5-14 water column/9-26 mm HG
(All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271)
Protector®QSSeries
®
3 of 11
22 • 27 • 32 • 38 • 48 kW	 operating data
GENERATOR OUTPUT VOLTAGE/kW - 60 Hz
kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both)
RG022
120/240 V, 1Ø, 1.0 pf 22 92 22 92 100
120/208 V, 3Ø, 0.8 pf 22 76 22 76 80
120/240 V, 3Ø, 0.8 pf 22 66 22 66 80
RG027
120/240 V, 1Ø, 1.0 pf 27 113 25 104 125
120/208 V, 3Ø, 0.8 pf 27 94 25 87 100
120/240 V, 3Ø, 0.8 pf 27 81 25 75 90
RG032
120/240 V, 1Ø, 1.0 pf 32 133 32 133 150
120/208 V, 3Ø, 0.8 pf 32 111 32 111 125
120/240 V, 3Ø, 0.8 pf 32 96 32 96 100
277/480 V, 3Ø, 0.8 pf 32 48 32 48 60
RG038
120/240 V, 1Ø, 1.0 pf 38 158 38 158 175
120/208 V, 3Ø, 0.8 pf 38 132 38 132 150
120/240 V, 3Ø, 0.8 pf 38 114 38 114 125
277/480 V, 3Ø, 0.8 pf 38 57 38 57 60
RG048
120/240 V, 1Ø, 1.0 pf 48 200 48 200 200
120/208 V, 3Ø, 0.8 pf 48 167 48 167 175
120/240 V, 3Ø, 0.8 pf 48 144 48 144 150
277/480 V, 3Ø, 0.8 pf 48 72 48 72 80
SURGE CAPACITY IN AMPS
Voltage Dip @  .4 pf
15% 30%
RG022
120/240 V, 1Ø 55 135
120/208 V, 3Ø 40 92
120/240 V, 3Ø 35 80
RG027
120/240 V, 1Ø 62 170
120/208 V, 3Ø 70 120
120/240 V, 3Ø 61 103
RG032
120/240 V, 1Ø 75 180
120/208 V, 3Ø 87 210
120/240 V, 3Ø 75 182
277/480 V, 3Ø 36 87
RG038
120/240 V, 1Ø 75 180
120/208 V, 3Ø 87 210
120/240 V, 3Ø 75 182
277/480 V, 3Ø 36 87
RG048
120/240 V, 1Ø 85 195
120/208 V, 3Ø 90 218
120/240 V, 3Ø 78 189
277/480 V, 3Ø 36 87
ENGINE FUEL CONSUMPTION
Natural Gas Propane
(ft³/hr) (m³/hr) (gal/hr) (l/hr) (ft³/hr)
RG022
Exercise cycle 42 1.2 0.44 1.7 16
25% of rated load 100 2.8 1.1 4.2 40
50% of rated load 190 5.4 2.1 7.8 75
75% of rated load 255 7.2 2.8 10.5 101
100% of rated load 316 9 3.4 13 125
RG027
Exercise cycle 42 1.2 0.44 1.7 16
25% of rated load 108 3.1 1.2 4.5 43
50% of rated load 197 5.6 2.1 8.1 78
75% of rated load 287 8.2 3.1 11.8 114
100% of rated load 359 10.2 3.9 14.8 143
RG032
Exercise cycle 79 2.2 0.8 3.2 30
25% of rated load 144 4.1 1.7 6.3 60
50% of rated load 226 6.4 2.7 10.3 97
75% of rated load 298 6.4 3.7 13.9 132
100% of rated load 375 10.6 4.6 17.5 166
RG038
Exercise cycle 83 2.3 0.9 3.2 31
25% of rated load 162 4.6 1.7 6.6 62
50% of rated load 255 7.2 2.9 10.8 103
75% of rated load 345 9.8 4 15 142
100% of rated load 437 12.4 5.2 19 185
RG048
Exercise cycle 95 2.7 1 3.9 38
25% of rated load 204 5.8 2.16 8.5 82
50% of rated load 392 11.1 4.14 15.7 151
75% of rated load 547 15.5 5.8 22.8 220
100% of rated load 756 21.5 7.96 31.3 302
Protector®QSSeries
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Note: Fuel pipe must be sized for full load.
For Btu content, multiply ft³/hr x 2520 (LP) or ft³/hr x 1000 (NG)
For megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG)
Refer to Emissions Data Sheets for maximum fuel flow for EPA and
SCAQMD permitting purposes.
®
4 of 11
22 • 27 • 32 • 38 • 48 kW	 operating data
Protector®QSSeries
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration............................................................................................................3% for every 10 °C above 25 °C or 1.65% for every 10 °F above 77 °F
Altitude Deration (22, 27  48 kW)......................................................................................1% for every 100 m above 183 m or 3% for every 1000 ft above 600 ft
Altitude Deration (32  38 kW) ........................................................................................ 1% for every 100 m above 915 m or 3% for every 1000 ft above 3000 ft
CONTROLLER FEATURES
2-Line Plain Text LCD Display.........................................................................................................................................Simple user interface for ease of operation.
Mode Switch: 	Auto ...............................................................................................................................................Automatic Start on Utility failure. 7 day exerciser
	Off............................................................................................................................Stops unit. Power is removed. Control and charger still operate.
	Manual.......................................................................................... Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Programmable start delay between 10-30 seconds.............................................................................................................................................................Standard
Engine Start Sequence......................................................................................................................Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration)
Engine Warm-up......................................................................................................................................................................................................................5 sec
Engine Cool-Down...................................................................................................................................................................................................................1 min
Starter Lock-out.................................................................................................................................Starter cannot re-engage until 5 sec after engine has stopped.
Smart Battery Charger.........................................................................................................................................................................................................Standard
Automatic Voltage Regulation with Over and Under Voltage Protection.................................................................................................................................Standard
Automatic Low Oil Pressure Shutdown................................................................................................................................................................................Standard
Overspeed Shutdown...............................................................................................................................................................................................Standard, 72 Hz
High Temperature Shutdown................................................................................................................................................................................................Standard
Overcrank Protection...........................................................................................................................................................................................................Standard
Safety Fused.......................................................................................................................................................................................................................Standard
Failure to Transfer Protection...............................................................................................................................................................................................Standard
Low Battery Protection.........................................................................................................................................................................................................Standard
50 Event Run Log................................................................................................................................................................................................................Standard
Future Set Capable Exerciser...............................................................................................................................................................................................Standard
Incorrect Wiring Protection..................................................................................................................................................................................................Standard
Internal Fault Protection......................................................................................................................................................................................................Standard
Common External Fault Capability.......................................................................................................................................................................................Standard
Governor Failure Protection.................................................................................................................................................................................................Standard
ENGINE COOLING
22 kW 27 kW 32  38 kW 48 kW
Air flow (inlet air including alternator and combustion air in cfm/cmm) 2400/68 2400/68 2200/62.3 4350/123.2
System coolant capacity (gal/liters) 2.5/9.5 2.5/9.5 2.5/9.5 3/11.4
Heat rejection to coolant (BTU per hr/MJ per hr) 99,000/104.5 105,000/110.8 145,000/153 186,000/196.2
Maximum operation air temperature on radiator (°C/°F) 60/150
Maximum ambient temperature (°C/°F) 50/140
COMBUSTION REQUIREMENTS
Flow at rated power (cfm/cmm) 68/1.9 68/1.9 106/3 163/4.6
SOUND EMISSIONS
Sound output in dB(A) at 23 ft (7 m) with generator in exercise mode* 61 61 58 63
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load* 70 70 64 68
*Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters.
EXHAUST
Exhaust flow at rated output (cfm/cmm) 165/4.7 180/5.1 300/8.5 414/11.7
Exhaust temperature at muffler outlet (°C/°F) 482/900 538/1000 579/1075 552/1025
ENGINE PARAMETERS
Rated Synchronous rpm 1800
®
5 of 11
22 • 27 • 32 • 38 • 48 kW	 available accessories
Protector®QSSeries
Model # Product Description
006463-3 Mobile Link™
Generac's Mobile Link allows you to check the status of your generator from
anywhere that you have access to an Internet connection from a PC or with
any smart device. You will even be notified when a change in the generator’s
status occurs via e-mail or text message. Note: Harness Adapter Kit required.
Available in the U.S. only.
006478-0 Harness Adapter Kit
The Harness Adapter Kit is required to make liquid-cooled units compatible with
Mobile Link™.
005630-1 - 22, 27, 32  38 kW
005632-1 - 48 kW
Cold Weather Kit
If the temperature regularly falls below 32 °F (0 °C), install a cold weather kit
to maintain optimal battery temperature. Kit consists of battery warmer with
thermostat built into the wrap.
005616-0 - 22, 27, 32  38 kW
006204-0 - 48 kW
Extreme Cold
Weather Kit
Recommended where the temperature regularly falls below 32 °F (0 °C) for
extended periods of time. For liquid cooled units only.
005651-0 Base Plug Kit Add base plugs to the base of the generator to keep out debris.
005704-0 Paint Kit
If the generator enclosure is scratched or damaged, it is important to touch-up
the paint to protect from future corrosion. The paint kit includes the necessary
paint to properly maintain or touch-up a generator enclosure.
005656-0 - 22  27 kW
005984-0 - 32  38 kW
006205-0 - 48 kW
Scheduled
Maintenance Kit
The Liquid-Cooled Scheduled Maintenance Kits offer all the hardware necessary
to perform complete maintenance on Generac liquid-cooled generators.
006664-0
Local Wireless
Monitor
Completely wireless and battery powered, Generac's wireless remote monitor
provides you with instant status information without ever leaving the house.
006665-0
Wireless Remote
Extension Harness
Recommended for use with the Wireless Remote on units up to 60 kW, required
for use on units 70 kW or greater.
006873-0
Smart Management
Module (50 Amps)
Smart Management Modules are used in conjunction with the Automatic
Transfer Switch to increase its power management capabilities. It provides
additional power management flexibility not found in any other power
management system.
006510-0 E-Stop
E-stop allows for immediate fuel shutoff and generator shutdown in the event of
an emergency.
®
1 of 2
Non-Service Rated
Automatic Transfer Switches
100-400Amps
®
100-400 Amps
100 - 400 Amps, Three Phase
DESCRIPTION
All non-service rated switches are available in 120/208 3ø, 120/240 3ø, and 277/480 3ø. All switches are open transition.
STANDARD FEATURES
All non-service rated transfer switches are housed in a steel NEMA/UL Type 3R enclosure, with electrostatically applied and baked
powder paint. The Heavy Duty Generac Contactor is a UL recognized device, designed for years of service. The controller at the
generator handles all the timing, sensing, exercising functions, and transfer commands.
8 Transfer Switch Data
Missouri Sun Solar: Bergh Solar Project 49.585kW
2 of 2
Functions
Dimensions
®
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2015 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0186650SBY-L Printed in U.S.A. 09/23/15
100-400 Amps 	 Non-Service Rated Transfer Switches
®
Model RTSN100G3 RTSN100J3 RTSN100K3 RTSN200G3 RTSN200J3 RTSN200K3 RTSN400G3 RTSN400J3 RTSN400K3
Amps 100 200 400
Voltage 120/208 3Ø 120/240 3Ø 277/480 3Ø 120/208 3Ø 120/240 3Ø 277/480 3Ø 120/208 3Ø 120/240 3Ø 277/480 3Ø
Load Transition Type
(Automatic)
Open Transition
Enclosure Type NEMA 3R
Withstand Rating (Amps) 14,000 14,000 14,000 25,000 25,000 25,000 35,000 35,000 35,000
Lug Range 2/0 - #6 400 MCM - #4 600 MCM - #4 or 1/0 - 250 MCM
• Electrically operated, mechanically-held contacts for fast, positive
connections.
• Rated for all classes of load, 100% equipment rated, both inductive and
resistive.
• 160 millisecond transfer time.
• Single coil design.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMA 3R (indoor/outdoor rated) steel enclosure is standard.
• Limited Five Year Warranty.
H2
DEPTH
H1
W2
W1
Specifications
Features
Model
Height (in./mm) Width (in./mm) Depth
(in./mm)
Weight
(lbs./kilos)H1 H2 W1 W2
RTSN100G3 19.3/490.2 24.1/612.1 16.9/429.3 20.2/513.1 7.1/180.3 65/29.48
RTSN100J3 19.3/490.2 24.1/612.1 16.9/429.3 20.2/513.1 7.1/180.3 57/25.85
RTSN100K3 31.3/795 36.1/916.9 19.2/487.7 24/609.6 10/254 135/61.24
RTSN200G3 19.3/490.2 24.1/612.1 16.9/429.3 20.2/513.1 7.1/180.3 48/21.77
RTSN200J3 19.3/490.2 24.1/612.1 16.9/429.3 20.2/513.1 7.1/180.3 65/29.48
RTSN200K3 43/1092.2 48.1/1221.7 25/635 30.1/764.5 13.1/332.7 105/47.63
RTSN400G3 31.3/795 36.1/916.9 19.2/487.7 24/609.6 10/254 160/72.57
RTSN400J3 31.3/795 36.1/916.9 19.2/487.7 24/609.6 10/254 133/60.33
RTSN400K3 43/1092.2 48.1/1221.7 25/635 30.1/764.5 13.1/332.7 133/60.33
100-400Amps
All timing and sensing functions originate in the generator controller
	 Utility voltage drop-out.......................................................................................................................................................................................................................60%
	 Timer to generator start.......................................................................................................................................10 second factory set, adjustable between 10-30 seconds
	 Engine warm up delay..................................................................................................................................................................................................................5 seconds
	 Standby voltage sensor...................................................................................................................................................................................................60% for 5 seconds
	 Utility voltage pickup..........................................................................................................................................................................................................................80%
	 Re-transfer time delay................................................................................................................................................................................................................15 seconds
	 Engine cool-down timer.............................................................................................................................................................................................................60 seconds
	Exerciser ............................................................................................................................................................................................................. 12 minutes every 7 days*
	 *Function of the controller
	 The transfer switch can be operated manually without power applied.
Missouri Sun Solar: Bergh Solar Project 49.585kW
9) Attachment Data
Missouri Sun Solar: Bergh Solar Project 49.585kW
Missouri Sun Solar: Bergh Solar Project 49.585kW
Missouri Sun Solar: Bergh Solar Project 49.585kW
Therightwaytoattachalmostanythingtometalroofs!
S-5-PVKitandEdgeGrab™
888-825-3432|www.S-5.com|
S-5-PV Kit and EdgeGrab™
The concept of combining photovoltaic arrays with standing seam metal roofing is growing—and
for good reasons. A standing seam metal roof has a life expectancy consistent with that of framed
PV modules. A 30-year power source on a 40-year roof, along with zero-penetration technology,
creates the most sustainable roof system available with alternative power generation, all without
compromising the roof manufacturer's warranty!
The new S-5-PV Kit boasts an important breakthrough in PV mounting technology. It is one of
the first solar module mounting solutions in the industry to be listed to the new UL subject 2703,
a standard that covers both bonding and mounting. Furthermore, the S-5!® Mounting Disk has
gained an ETL Listing to UL 1703.*
The S-5-PV Kit features a groundbreaking new stainless steel mounting disk with twelve nodes
designed to ensure the module-to-module conductivity of anodized aluminum module frames.
This means it automatically provides a ground path in the module frame. No lugs or wire required
except to connect one string of modules to another and to ground the system. This connection
detail represents installed electrical cost savings of $6-$12 per unit. In most cases, the savings in
time and materials is sufficient to pay for the entire S-5-PV Kit and clamp setup.
Missouri Sun Solar: Bergh Solar Project 49.585kW
Distributed byS-5!® Warning! Please use this product responsibly!
Products are protected by multiple U.S. and foreign patents. Visit the website at www.S-5.com for
complete information on patents and trademarks. For maximum holding strength, setscrews should
be tensioned and re-tensioned as the seam material compresses. Clamp setscrew tension should be
verified using a calibrated torque wrench between 160 and 180 inch pounds when used on 22ga steel,
and between 130 and 150 inch pounds for all other metals and thinner gauges of steel. Consult the S-5!
website at www.S-5.com for published data regarding holding strength.
Copyright2015,MetalRoofInnovations,Ltd.S-5!productsarepatentprotected.
S-5!aggressivelyprotectsitspatents,trademarks,andcopyrights.Version052115.
The S-5-PV Kit is a revolutionary new solution to attach solar PV panels
to standing seam metal roofs!
R
S-5-PV Kit
(UL and ETL Listed)
EdgeGrab™
(Not UL or ETL Listed)
R
0.47
(12.00 mm)
1.50
(38.00 mm)
Wire Zip Tie Slots
Module Placement Bevel Guide
Friction Reducing
Coated Stainless Steel
Universal PV Stud w/
M8 Integral Hex Nut
3.00
(76.00 mm)
ETL Listed
Mounting Disc
Stud
Height
2.67
(68.00 mm)
†
Hold Min/Max
1.18-1.89
(30.00-48.00 mm)
0.06
(1.50 mm)
0.48
(12.19 mm)
1.50
(38.10 mm)
0.84
(21.34 mm)
2.00
(50.80 mm)
1.00
(25.00 mm)
0.71
(18.00 mm)
0.87
(22.00 mm)
Wire
Management
Hooks
1 2 3
The S-5-PV Kit is furnished with the hardware shown at
right, excluding the attachment clamp, which is supplied
separately. (When ProteaBracket™ is used in conjunction with
the S-5-PV Kit, an additional nut is required during installation
to secure the universal PV stud and mounting disk to
ProteaBracket's slotted L-flange.) The S-5-PV Kit is compatible
with most common metal roofing materials, including brass.
The S-5!® EdgeGrab™ and S-5-PV Kit together accommodate
PV frame thicknesses 30–48 mm (if EdgeGrab's serrated
L-flange is positioned below the stud's hex nut) and 34–51
mm (if EdgeGrab's serrated L-flange is positioned above the
stud's hex nut).†

The embossed panel guide makes the module placement easier.
The mounting disk is multi-directional and rails are not required.
Four strategically placed under-disk hooks assist in wire
management. The PV grab ears that hold the solar panel in
place are broader to allow for ease of installation and precise
module engagement.
Accommodating module thicknesses between 30 and 51
mm, the S-5-PV Kit fits the majority of solar panels on the
market. Using the S-5! mini clamps, it fits most standing
seam metal roofs. When paired with other S-5! products, the
S-5-PV Kit and EdgeGrab will work on most exposed-fastened
and corrugated metal roofs. The standard grab is designed
to fit field conditions (two adjacent panels), while the new
EdgeGrab is designed specifically for end conditions.
Wind dynamics are complex; thus, each system should
be reviewed by a qualified licensed professional who
understands wind effects on metal roof design and
construction prior to purchase and installation. For more
detailed information including specifications, installation
instructions, and CAD drawings, visit www.S-5.com or your
S-5-PV Kit distributor.
The S-5-PV Kit continues to be
the easiest, most cost-effective
way to install solar panels directly
to standing seam metal roofs,
remaining the most popular
choice worldwide.
Please note: All measurements are rounded to the second
decimal place.
* Patents pending. Certain components featured in
illustration may not be UL listed.
Due to the variety of attachment needs, S-5-PV Kits are
sold separately from S-5! mini clamps. The S-5-PV Kit
fits only S-5! mini clamps, NOT standard clamps.
Listed to UL subject 2703.
ETL Listed to UL 1703.*
Please Note:
Dimensions of both the
Universal PV Stud and
the Mounting Disk are
identical between these
two illustrations.
Please note: The
assembly option in the
diagram to the right
illustrates he serrated
L-flange positioned below
the stud's hex nut.
S-5! clamp not included.
S-5! clamp not included.
Missouri Sun Solar: Bergh Solar Project 49.585kW
Missouri Sun Solar: Bergh Solar Project 49.585kW

More Related Content

What's hot

Intelligent system for production, storage and management of Multi-MW Solar P...
Intelligent system for production, storage and management of Multi-MW Solar P...Intelligent system for production, storage and management of Multi-MW Solar P...
Intelligent system for production, storage and management of Multi-MW Solar P...Antonio Moreno-Munoz
 
Crown micro corporate profile energy &amp; solar products ( l )
Crown micro corporate profile   energy &amp; solar products ( l ) Crown micro corporate profile   energy &amp; solar products ( l )
Crown micro corporate profile energy &amp; solar products ( l ) Syed Khursheed Abbas
 
Nidec asi electric power solutions for ship to shore connection
Nidec asi electric power solutions for ship to shore connectionNidec asi electric power solutions for ship to shore connection
Nidec asi electric power solutions for ship to shore connectionNidec Corporation
 
Solar Cold Storage Solution
Solar Cold Storage SolutionSolar Cold Storage Solution
Solar Cold Storage SolutionStatcon Energiaa
 
Amerisolar Intelligence Sunshine Box(iSBox)
Amerisolar Intelligence Sunshine Box(iSBox)Amerisolar Intelligence Sunshine Box(iSBox)
Amerisolar Intelligence Sunshine Box(iSBox)Alan Wang
 
Umbarger, Angela 17.68kW Planset Final
Umbarger, Angela 17.68kW Planset FinalUmbarger, Angela 17.68kW Planset Final
Umbarger, Angela 17.68kW Planset FinalDavid Hults
 
Inertia dynamics controls_d2101_11_specsheet
Inertia dynamics controls_d2101_11_specsheetInertia dynamics controls_d2101_11_specsheet
Inertia dynamics controls_d2101_11_specsheetElectromate
 
Cost Components in a MW Scale Solar Power Project
Cost Components in a MW Scale Solar Power ProjectCost Components in a MW Scale Solar Power Project
Cost Components in a MW Scale Solar Power ProjectSrini Chopakatla, PE, PMP
 
Elektro Tipp July 2011
Elektro Tipp July 2011Elektro Tipp July 2011
Elektro Tipp July 2011Rajesh Rajan
 
KEHUA Tech INDIA - Corporate Presentation
KEHUA Tech INDIA - Corporate Presentation KEHUA Tech INDIA - Corporate Presentation
KEHUA Tech INDIA - Corporate Presentation Tahnoon Elahi
 
Project Proposal on 10 MW Solar PV Power Plant
Project Proposal on 10 MW Solar PV Power PlantProject Proposal on 10 MW Solar PV Power Plant
Project Proposal on 10 MW Solar PV Power PlantVignesh Sekar
 
Inertia dynamics controls_d2100_10_specsheet
Inertia dynamics controls_d2100_10_specsheetInertia dynamics controls_d2100_10_specsheet
Inertia dynamics controls_d2100_10_specsheetElectromate
 

What's hot (19)

EJOT Solar Brochure
EJOT Solar BrochureEJOT Solar Brochure
EJOT Solar Brochure
 
Quotation 10 kw_ongrid_rajkot_std
Quotation 10 kw_ongrid_rajkot_stdQuotation 10 kw_ongrid_rajkot_std
Quotation 10 kw_ongrid_rajkot_std
 
Quotation 10 kw_std_offgrid_nareshji
Quotation 10 kw_std_offgrid_nareshjiQuotation 10 kw_std_offgrid_nareshji
Quotation 10 kw_std_offgrid_nareshji
 
Quotation 50 kva_std_ongrid
Quotation 50 kva_std_ongridQuotation 50 kva_std_ongrid
Quotation 50 kva_std_ongrid
 
Intelligent system for production, storage and management of Multi-MW Solar P...
Intelligent system for production, storage and management of Multi-MW Solar P...Intelligent system for production, storage and management of Multi-MW Solar P...
Intelligent system for production, storage and management of Multi-MW Solar P...
 
Fronius Symo Hybrid 3.0-5.0 Package
Fronius Symo Hybrid 3.0-5.0 PackageFronius Symo Hybrid 3.0-5.0 Package
Fronius Symo Hybrid 3.0-5.0 Package
 
Crown micro corporate profile energy &amp; solar products ( l )
Crown micro corporate profile   energy &amp; solar products ( l ) Crown micro corporate profile   energy &amp; solar products ( l )
Crown micro corporate profile energy &amp; solar products ( l )
 
Nidec asi silcovert tn
Nidec asi silcovert tnNidec asi silcovert tn
Nidec asi silcovert tn
 
Webinar Training 041609
Webinar Training 041609Webinar Training 041609
Webinar Training 041609
 
Nidec asi electric power solutions for ship to shore connection
Nidec asi electric power solutions for ship to shore connectionNidec asi electric power solutions for ship to shore connection
Nidec asi electric power solutions for ship to shore connection
 
Solar Cold Storage Solution
Solar Cold Storage SolutionSolar Cold Storage Solution
Solar Cold Storage Solution
 
Amerisolar Intelligence Sunshine Box(iSBox)
Amerisolar Intelligence Sunshine Box(iSBox)Amerisolar Intelligence Sunshine Box(iSBox)
Amerisolar Intelligence Sunshine Box(iSBox)
 
Umbarger, Angela 17.68kW Planset Final
Umbarger, Angela 17.68kW Planset FinalUmbarger, Angela 17.68kW Planset Final
Umbarger, Angela 17.68kW Planset Final
 
Inertia dynamics controls_d2101_11_specsheet
Inertia dynamics controls_d2101_11_specsheetInertia dynamics controls_d2101_11_specsheet
Inertia dynamics controls_d2101_11_specsheet
 
Cost Components in a MW Scale Solar Power Project
Cost Components in a MW Scale Solar Power ProjectCost Components in a MW Scale Solar Power Project
Cost Components in a MW Scale Solar Power Project
 
Elektro Tipp July 2011
Elektro Tipp July 2011Elektro Tipp July 2011
Elektro Tipp July 2011
 
KEHUA Tech INDIA - Corporate Presentation
KEHUA Tech INDIA - Corporate Presentation KEHUA Tech INDIA - Corporate Presentation
KEHUA Tech INDIA - Corporate Presentation
 
Project Proposal on 10 MW Solar PV Power Plant
Project Proposal on 10 MW Solar PV Power PlantProject Proposal on 10 MW Solar PV Power Plant
Project Proposal on 10 MW Solar PV Power Plant
 
Inertia dynamics controls_d2100_10_specsheet
Inertia dynamics controls_d2100_10_specsheetInertia dynamics controls_d2100_10_specsheet
Inertia dynamics controls_d2100_10_specsheet
 

Viewers also liked

Listing Presentation
Listing PresentationListing Presentation
Listing PresentationMatt Broyles
 
Not-So-Secret Secrets To Real Estate Agent Perpetual Success
Not-So-Secret Secrets To Real Estate Agent Perpetual SuccessNot-So-Secret Secrets To Real Estate Agent Perpetual Success
Not-So-Secret Secrets To Real Estate Agent Perpetual SuccessKen Brand
 
Social Reputation Management for Restaurants
Social ReputationManagement forRestaurantsSocial ReputationManagement forRestaurants
Social Reputation Management for RestaurantsCharlie Shin
 
Caracteristicas de los modulos fotovoltaicos
Caracteristicas de los modulos fotovoltaicosCaracteristicas de los modulos fotovoltaicos
Caracteristicas de los modulos fotovoltaicosKarolayn Farfan Cruz
 

Viewers also liked (6)

Www.homeseeker.com
Www.homeseeker.comWww.homeseeker.com
Www.homeseeker.com
 
Listing Presentation
Listing PresentationListing Presentation
Listing Presentation
 
Not-So-Secret Secrets To Real Estate Agent Perpetual Success
Not-So-Secret Secrets To Real Estate Agent Perpetual SuccessNot-So-Secret Secrets To Real Estate Agent Perpetual Success
Not-So-Secret Secrets To Real Estate Agent Perpetual Success
 
Social Reputation Management for Restaurants
Social ReputationManagement forRestaurantsSocial ReputationManagement forRestaurants
Social Reputation Management for Restaurants
 
Introduction to Amazon DynamoDB
Introduction to Amazon DynamoDBIntroduction to Amazon DynamoDB
Introduction to Amazon DynamoDB
 
Caracteristicas de los modulos fotovoltaicos
Caracteristicas de los modulos fotovoltaicosCaracteristicas de los modulos fotovoltaicos
Caracteristicas de los modulos fotovoltaicos
 

Similar to 42kW Missouri Solar Panel System Layout

Canadian solar datasheet-hi-ku_cs3w-p_en-2
Canadian solar datasheet-hi-ku_cs3w-p_en-2Canadian solar datasheet-hi-ku_cs3w-p_en-2
Canadian solar datasheet-hi-ku_cs3w-p_en-2Fabiola Sosa-Rodríguez
 
Canadian solar datasheet-hi-ku_cs3w-ms_v5.59_en
Canadian solar datasheet-hi-ku_cs3w-ms_v5.59_enCanadian solar datasheet-hi-ku_cs3w-ms_v5.59_en
Canadian solar datasheet-hi-ku_cs3w-ms_v5.59_enNaveed Ahmed
 
Ornate Solar x Canadian Solar HiKu Series | High Efficiency Solar Panels
Ornate Solar x Canadian Solar HiKu Series | High Efficiency Solar PanelsOrnate Solar x Canadian Solar HiKu Series | High Efficiency Solar Panels
Ornate Solar x Canadian Solar HiKu Series | High Efficiency Solar PanelsOrnate Solar
 
Canadian solar HiKU CS3W-440
Canadian solar HiKU CS3W-440Canadian solar HiKU CS3W-440
Canadian solar HiKU CS3W-440Naveed Ahmed
 
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdf
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdfBaladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdf
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdfAbdulkadirHassanMoha
 
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unitSolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unitOptimus Energy Philippines
 
1500V String Inverter Utility PV System Solution 2021.pdf
1500V String Inverter Utility PV System Solution 2021.pdf1500V String Inverter Utility PV System Solution 2021.pdf
1500V String Inverter Utility PV System Solution 2021.pdfgoangagoanga99
 
SM210D-210watt
SM210D-210wattSM210D-210watt
SM210D-210wattIan Harvey
 
4983 br001 -en-p
4983 br001 -en-p4983 br001 -en-p
4983 br001 -en-pnguyensun
 
Hanwha q cells_data_sheet_qpeak_duo_l-g5.2_380-395_2018-03_rev05_na (1)
Hanwha q cells_data_sheet_qpeak_duo_l-g5.2_380-395_2018-03_rev05_na (1)Hanwha q cells_data_sheet_qpeak_duo_l-g5.2_380-395_2018-03_rev05_na (1)
Hanwha q cells_data_sheet_qpeak_duo_l-g5.2_380-395_2018-03_rev05_na (1)Nav Ahmed
 
72 cells polycrystalline 320 340 wp - saatvik green energy
72 cells polycrystalline 320 340 wp - saatvik green energy72 cells polycrystalline 320 340 wp - saatvik green energy
72 cells polycrystalline 320 340 wp - saatvik green energySaatvik Green Energy
 
72 Cell Modules and 60 cell modules (multi-crystalline)
72 Cell Modules and 60 cell modules (multi-crystalline)72 Cell Modules and 60 cell modules (multi-crystalline)
72 Cell Modules and 60 cell modules (multi-crystalline)Emmvee India
 
Solar rooftop projects primotech
Solar rooftop projects primotechSolar rooftop projects primotech
Solar rooftop projects primotechvimalranaprimotech
 

Similar to 42kW Missouri Solar Panel System Layout (20)

Canadian solar datasheet-hi-ku_cs3w-p_en-2
Canadian solar datasheet-hi-ku_cs3w-p_en-2Canadian solar datasheet-hi-ku_cs3w-p_en-2
Canadian solar datasheet-hi-ku_cs3w-p_en-2
 
Canadian solar datasheet-hi-ku_cs3w-ms_v5.59_en
Canadian solar datasheet-hi-ku_cs3w-ms_v5.59_enCanadian solar datasheet-hi-ku_cs3w-ms_v5.59_en
Canadian solar datasheet-hi-ku_cs3w-ms_v5.59_en
 
Canadian 290w panel Kuk
Canadian 290w panel KukCanadian 290w panel Kuk
Canadian 290w panel Kuk
 
Ornate Solar x Canadian Solar HiKu Series | High Efficiency Solar Panels
Ornate Solar x Canadian Solar HiKu Series | High Efficiency Solar PanelsOrnate Solar x Canadian Solar HiKu Series | High Efficiency Solar Panels
Ornate Solar x Canadian Solar HiKu Series | High Efficiency Solar Panels
 
Canadian solar HiKU CS3W-440
Canadian solar HiKU CS3W-440Canadian solar HiKU CS3W-440
Canadian solar HiKU CS3W-440
 
Q Plus
Q PlusQ Plus
Q Plus
 
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdf
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdfBaladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdf
Baladweyne-Irrigation-System__13m_3,690cbm_46,800Wp.pdf
 
Solar Barge
Solar BargeSolar Barge
Solar Barge
 
Canadian Solar 265w Poly Modules
Canadian Solar 265w Poly Modules Canadian Solar 265w Poly Modules
Canadian Solar 265w Poly Modules
 
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unitSolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
 
1500V String Inverter Utility PV System Solution 2021.pdf
1500V String Inverter Utility PV System Solution 2021.pdf1500V String Inverter Utility PV System Solution 2021.pdf
1500V String Inverter Utility PV System Solution 2021.pdf
 
shagufta-final review
shagufta-final reviewshagufta-final review
shagufta-final review
 
SM210D-210watt
SM210D-210wattSM210D-210watt
SM210D-210watt
 
4983 br001 -en-p
4983 br001 -en-p4983 br001 -en-p
4983 br001 -en-p
 
Hanwha q cells_data_sheet_qpeak_duo_l-g5.2_380-395_2018-03_rev05_na (1)
Hanwha q cells_data_sheet_qpeak_duo_l-g5.2_380-395_2018-03_rev05_na (1)Hanwha q cells_data_sheet_qpeak_duo_l-g5.2_380-395_2018-03_rev05_na (1)
Hanwha q cells_data_sheet_qpeak_duo_l-g5.2_380-395_2018-03_rev05_na (1)
 
72 cells polycrystalline 320 340 wp - saatvik green energy
72 cells polycrystalline 320 340 wp - saatvik green energy72 cells polycrystalline 320 340 wp - saatvik green energy
72 cells polycrystalline 320 340 wp - saatvik green energy
 
72 Cell Modules and 60 cell modules (multi-crystalline)
72 Cell Modules and 60 cell modules (multi-crystalline)72 Cell Modules and 60 cell modules (multi-crystalline)
72 Cell Modules and 60 cell modules (multi-crystalline)
 
Canadian 285w poly
Canadian 285w polyCanadian 285w poly
Canadian 285w poly
 
Canadian 355w Poly Dual Cell panel
Canadian 355w Poly Dual Cell panelCanadian 355w Poly Dual Cell panel
Canadian 355w Poly Dual Cell panel
 
Solar rooftop projects primotech
Solar rooftop projects primotechSolar rooftop projects primotech
Solar rooftop projects primotech
 

42kW Missouri Solar Panel System Layout

  • 1. 42.585kWGridTiedPVSystem ShelliBergh 21511USHwy63N SturgeonMO65284 660-591-6424;shellibergh@embargmail.com Missouri Sun Solar, LLC 1926 West Woodland Springfield, MO 65807 PVGI-1 Designer D. Hults Reviewer B. Arthur General Information Grid Tied PV System Date 2016-03-11 Scale NTS System Specifications, Main Components: Roof Mount Item Manufacturer Model Quantity Size: In Array Area: Sqft Weight: Lbs Array Weight: Lbs Watts: kW Panel Module Q-Cell Q-Pro.G4 255 167 65.7 x 39.4 x 1.38 3179.68 41.89 6995.63 255 Inverter 1 Fronius Primo 8.2-1 4 16.9 x 24.7 x 8.1 47.29 8200 Inverter 2 Fronius Primo 5.0-1 1 16.9 x 24.7 x 8.1 47.29 5000 Attachment S-5! Protea Bracket with PV Kit 184 0.789 144.39 Generator Generac RG022: 22kW, 60Hz 1 76.8 x 46.1 x 35 905 22000 Transfer Switch Generac RTSN200G3: 200A 1 24.1 x 20.2 x 7.1 48 Roof Specifications Array Specifications Site Specifications Average Loads Weight 2" x 4" Truss or 6" Framing 24" O.C. Occupancy: Utility Down: 245 lbs Total Weight: 7140.02 lbs Corrugated Metal Roof Building Size: 2 Story Uplift: -137 lbs Weight at Attachment: 38.8 lbs Design Wind Speed: 115 MPH Lateral: 38 lbs Distributed Weight: 2.25 psf Roof Age: 20 years Exposure Category: B Expected Life Span: 10+ years Ground Snow Load: 20 PSF FP Table of Contents PVGI-1 General Information PVAL-2 Array Layout PVMN-3 Materials & Notes PVED-4 Electrical Diagram Attachments 1) Panel Data 2) Panel Warranty 3) Inverter Data 4) Inverter Warranty 5) Monitor Data 6) AC Disconnect Data 7) Transfer Switch Data 8) Generator Data 9) Attachment Data Scope of Work 1) Scope includes the installation of a Photovoltaic Array in a Roof Mounted Racking System including related Hardware and Electrical Equipment 2) All Electricity generated is for consumption on the site 3) Permit shall include labor of running of Electrical Conduit(s), installation of new Electrical Equipment, and Electrical Connection to the Existing Site Transformer 4) The Project does not include the installation of Batteries and Battery Management Equipment Boone County Electric 1667002 Jurisdiction: Boone County MO Permit, Inspection Shelli Bergh 21511 US Hwy 63 N, Sturgeon, MO 65284 660-591-6424; shellibergh@embargmail.com DC: 42.585 kW AC: 37.8 kW Missouri Sun Solar Contact Information: Primary Contact: Ryan Roller: 417-713-1786: rroller@ussunsolar.com Design: David Hults: 314-856-2171: dhults@ussunsolar.com Engineer: Billy Arthur, MO PE: 314-6503263: barthur@ussunsolar.com
  • 2. Missouri Sun Solar, LLC 260 Old State Rd. Ellisville, MO 63021 PVAL-2 Designer D. Hults Reviewer B. Arthur Array Layout 42.585kWGridTiedPVSystem ShelliBergh 21511USHwy63N SturgeonMO65284 660-591-6424;shellibergh@embargmail.com Date 2016-03-11 Scale NTS N Entrance String Design Inverter 1: Fronius Primo 8.2-1 2 Strings of 13 Panels 1 String of 11 Panels Inverter 2: Fronius Primo 5.0-1 1 String of 10 Panels 1 String of 9 Panels MD G HOUSE LAKE BARN House Northern Exterior Existing Utility Meter in Transformer Transfer Switch: Generac RTSN200G3 Standby Generator: Generac 22kW: RG022 PV AC Disconnect: Square-D 200A: D324NRB LOCUS Monitor Interior Northern Wall of House Main Electrical Panels 2x 200A/240V 27'-2" 30'-8" 129'-8"117'-7" Trench 4/0 Al Direct BuryCable in 2 Bundles of 4 Cables 8 Cables Total Minimum 18" Below Grade Approximately 450' Roof of Barn 167 Q-Cell 255W Solar Panels Module Q-Pro.G4 255 Corrugated Metal Roofing Protea Bracket and PVKit Attachments 2012 IFC Setbacks MD GPV AC Disconnect Existing Utility MeterGeneratorTransfer Switch For the Layout On the Right 10 Panels 9 Panels 13 Panels 13 Panels 11 Panels Solar Panel 13 13 11 13 11 13 13 11 13 36" from Ridge and Rake of Roof per 2012 IFC Interior Southwest Wall of Barn Main Service Panel for Barn 200A/240V L L INV1 INV1 INV1 INV1 INV2 Exterior Northwestern Area of Building In-Ground Tap Box for Electrical Service and Solar Subpanel Inverters: Fronius 8.2-1 (x4) Fronius 5.0-1 (x1) INV2 LOCUS MonitorSolar Inverter T T Existing Transformer
  • 3.
  • 4. DC PVED-3 Missouri Sun Solar, LLC 260 Old State Rd. Ellisville, MO 63021 Designer D. Hults Reviewer B. Arthur Electrical Diagram 42.585kWGridTiedPVSystem ShelliBergh 21511USHwy63N SturgeonMO65284 660-591-6424;shellibergh@embargmail.com Date 2016-03-11 Scale NTS All Equipment Clearly Labeled with Descriptive Signage Roof of Barn Fused AC Disconnect Square D D324NRB 200A / 240V 167 Q-Cell Solar Panels 255W Module Q.Pro-G4 255 M To Utility Existing Utility Meter in Transformer 600A/240V 200A Type R Fuses A Exterior Northern Side of House Adjacent to the House Entrance Bergh Solar Project 42.59 kW: Electrical Diagram C C All Conductors at this Point Strings E D Wire Schedule Tag Wire Type Ground Conduit Length A USE-2 PV NA NA 650' B #10 THHN Cu #10 THHN 3/4" EMT 100' C 3/0 AWG THHN Cu #10 THHN 2" PVC 20' D 4/0 Direct Bury Cable: 4 Wires for Each: Solar and Barn Service CU NA NA 410' E 4/0 AWG THHN CU #3 THHN 2" PVC 40' Sub Panel 200A/240V Inverter 1: Fronius Primo 8.2-1 (x4) Inverter 2: Fronius Primo 5.0-1 (x1) 45A LOCUS Monitor L-Gate 120 D To House Loads 200A Service to Barn 200A Solar 45A 45A 45A 20A L 13 11 13 13 13 11 13 13 11 13 13 11 10 9 C C E G Generac Generator 3-Phase 22kW Model RG022 Generac Transfer Switch 3-Phase 200A Model RTSN200G3 To Barn Loads In-Ground Tap-Box 400A Northwest Wall of Barn All Conductors at this Point B Boone Electric Solar Meter 250A* 200A *BooneCountyRequiresSystemOCPDatMAXAMPx125% The Generac Generator and Transfer-Switch will be manipulated by the Manufacturer to change from 3-Phase to Single Phase; they will maintain the 3-Poles to comply with Boone Electrical Cooperative Requirements
  • 5. Q.PRO BFR-G4 255-265 1 APT test conditions: Cells at -1000 V against grounded, with conductive me- tal foil covered module surface, 25 °C, 168 h 2 See data sheet on rear for further information. POLYCRYSTALLINE SOLAR MODULE The new Q.PRO BFR-G4 is the result of the continued evolution of our Q.PRO family. Thanks to improved power yield, excellent reliability, and high-level operational safety, the new Q.PRO BFR-G4 generates electricity at a low cost (LCOE) and is suitable for a wide range of applications. THE IDEAL SOLUTION FOR: Rooftop arrays on commercial / industrial buildings Ground-mounted solar power plants Rooftop arrays on residential buildings LOW ELECTRICITY GENERATION COSTS Higher yield per surface area and lower BOS costs thanks to higher power classes and an efficiency rate of up to 16.2 %. INNOVATIVE ALL-WEATHER TECHNOLOGY Optimal yields, whatever the weather with excellent low-light and temperature behavior. ENDURING HIGH PERFORMANCE Long-term yield security with Anti-PID Technology1 , Hot-Spot-Protect and Traceable Quality Tra.Q™. LIGHT-WEIGHT QUALITY FRAME High-tech aluminum alloy frame, certified for high snow (5400 Pa) and wind loads (4000 Pa). MAXIMUM COST REDUCTIONS Up to 10 % lower logistics costs due to higher module capacity per box. SAFE ELECTRONICS Protection against short circuits and thermally induced power losses due to breathable junction box and welded cables. A RELIABLE INVESTMENT Inclusive 12-year product warranty and 25-year linear performance guarantee2 . ANTI PID TECHNOLOGY (APT) HOT-SPOT PROTECT (HSP) TRACEABLE QUALITY (TRA.Q™) YIELD SECURITY 151 modules tested Best polycrystalline solar module 2013 Q.PRO-G2 235 MOD 278 8 p oton n o/ abo a ory    Quality Tested ID. 40032587 high re iabi ity low degradation frequent product survei lance Missouri Sun Solar: Bergh Solar Project 49.585kW 1) Panel Data
  • 6. MECHANICAL SPECIFICATION Format 65.7 in × 39.4 in x 1.26 in (including frame) (1670 mm × 1000 mm × 32 mm) Weight 41.45 lb (18.8 kg) Front Cover 0.13 in (3.2 mm) thermally pre-stressed glass with anti-reflection technology Back Cover Composite film Frame Black anodized aluminum Cell 6 × 10 polycrystalline solar cells Junction box 4.33 in × 4.53 in × 0.9 in (110 mm × 115 mm × 23 mm), Protection class IP67, with bypass diodes Cable 4 mm² Solar cable; (+) ≥ 39.37 in (1000 mm), (-) ≥ 39.37 in (1000 mm) Connector Tyco Solarlok PV4, IP68 DETAIL A 0 630 (16 mm) 0 335 (8 5 mm) 0 965 (24 5 mm) Junction bo× Product label 38 58 (980 mm) 65 7 (1670 mm) 4 × Fastening points (DETAIL A) Cable with connectors Frame 5 90 (150 mm) 39 4 (1000 mm) 37 44 (951 mm) 1 26 (32 mm) 8 × Drainage holes 6 × Grounding points ø 0 177 (4 5 mm) 39 37 (1000 mm) Q CELLS PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE IRRADIANCE [W/m²] RELATIVEEFFICIENCY[%] 100 200 300 400 500 600 700 800 900 1000 105 100 95 90 85 80 I rad anc [W/m ] Reatieefficecy[%] PROPERTIES FOR SYSTEM DESIGN Maximum System Voltage VSYS [V] 1000 (IEC) / 1000 (UL) Safety Class II Maximum Series Fuse Rating [A DC] 20 Fire Rating C / TYPE 1 Max Load (UL)2 [lbs/ft2 ] 75 (3600 Pa) Permitted module temperature on continuous duty − 40 °F up to +185 °F (− 40 °C up to +85 °C) Load Rating (UL)2 [lbs/ft2 ] 55.6 (2666 Pa) 2 see installation manual QUALIFICATIONS AND CERTIFICATES PACKAGING INFORMATION Number of Modules per Pallet 32 Number of Pallets per 53' Container 32 Number of Pallets per 40' Container 26 Pallet Dimensions ( L × W × H ) 68.7 in × 45.0 in × 46.0 in (1745 × 1145 × 1170 mm) Pallet Weight 1323 lb (651 kg) NOTE: Installation instructions must be followed. See the installation and operating manual or contact our technical service department for further information on approved installation and use of this product. RELATIVEEFFICIENCY COMPAREDTONOMINALPOWER[%] 100 95 90 85 80 75 155 25200 10 YEARS 97 Q CELLS Industry standard for tiered warranties* Industry standard for linear warrant es* * Standard terms of guarantee for the 10 PV companies with the highest production capacity in 2014 (as at: September 2014) Certified UL 1703 (254141) TEMPERATURE COEFFICIENTS Temperature Coefficient of ISC α [% / K] + 0.04 Temperature Coefficient of VOC β [% / K] − 0.30 Temperature Coefficient of PMPP γ [% / K] − 0.41 Normal Operating Cell Temperature NOCT [°F] 113 ± 5.4 (45 ± 3 °C) UL 1703; VDE Quality Tested; CE-compliant; IEC 61215 (Ed.2); IEC 61730 (Ed.1) application class A Specificationssubjecttotechnicalchanges©HanwhaQ CELLSGmbHQ.PROBFR-G4_2015-04_Rev03_NA At least 97 % of nominal power during first year. Thereafter max. 0.6 % degra- dation per year. At least 92 % of nominal power after 10 years. At least 83 % of nominal power after 25 years. All data within measurement tolerances. Full warranties in accordance with the warranty terms of the Q CELLS sales organisation of your respective country. The typical change in module efficiency at an irradiance of 200 W/m² in relation to 1000 W/m² (both at 25 °C and AM 1.5 G spectrum) is -2 % (relative). Hanwha Q CELLS USA Corp. 300 Spectrum Center Drive, Suite 1250, Irvine, CA 92618, USA | TEL +1 949 748 59 96 | EMAIL q-cells-usa@q-cells.com | WEB www.q-cells.us ELECTRICAL CHARACTERISTICS POWER CLASS 255 260 265 MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS, STC1 (POWER TOLERANCE +5 W /- 0 W) Minimum Power at MPP2 PMPP [W] 255 260 265 Short Circuit Current* ISC [A] 9.07 9.15 9.23 Open Circuit Voltage* VOC [V] 37.54 37.77 38.01 Current at MPP* IMPP [A] 8.45 8.53 8.62 Voltage at MPP* VMPP [V] 30.18 30.46 30.75 Efficiency2 η [%] ≥ 15.3 ≥ 15.6 ≥ 15.9 MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS, NOC3 Minimum Power at MPP2 PMPP [W] 188.3 192.0 195.7 Short Circuit Current* ISC [A] 7.31 7.38 7.44 Open Circuit Voltage* VOC [V] 34.95 35.16 35.38 Current at MPP* IMPP [A] 6.61 6.68 6.75 Voltage at MPP* VMPP [V] 28.48 28.75 29.01 1 1000 W/m², 25 °C, spectrum AM 1.5 G 2 Measurement tolerances STC ± 3 %; NOC ± 5 % 3 800 W/m², NOCT, spectrum AM 1.5 G * typical values, actual values may differ Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 7. LIMITED WARRANTY FOR CRYSTALLINE PHOTOVOLTAIC MODULES FROM [HANWHA Q . C E L L S GMBH] Dear Customer, You have made an excellent choice in purchasing quality modules from [Hanwha Q.CELLS GmbH] (“Q CELLS”). The photovoltaic modules you have purchased have been manufactured with great care and have undergone a final functional test. We also provide the following limited warranty (“Warranty”): SCOPE This Warranty applies exclusively to Q CELLS photovoltaic modules of the following types (the “Modules”): • Q.PEAK G2 • Q.PEAK G3 • Q.PEAK BLK G2 • Q.PEAK BLK G3 • Q.PRO G2 • Q.PRO G3 • Q.PRO L All Modules must be sold and installed within the United States and bear our manufacturer‘s label to be elig ble for this Warranty. Warrantor is Hanwha Q.CELLS GmbH, OT Thalheim, Sonnenallee 17-21, 06766 Bitterfeld-Wolfen, Germany. The applicable Warranty period begins on the date of the initial purchase of the Modules by the original end customer as set forth in the applicable invoice (the “Purchase Date”). 12-YEAR PRODUCT WARRANTY Q CELLS warrants to you that Modules which are installed in accordance with the applicable installation and operation manual and other product documentation provided to customers by Q CELLS for the Modules (collectively, “Product Instructions”) will not show any defects in materials or workmanship for a period of twelve years after the applicable Purchase Date. In the event that a Module has any such defect covered by this warranty (case of warranty), Q CELLS, at its choice, will either repair the defect or supply a replacement Module. If Q CELLS is unable to repair the defect or supply a replacement Module, Q CELLS will have the right to refund you the prorated value of the purchase price paid by you to Q CELLS or Q CELLS’ authorized reseller for the affected Modules (“Purchase Price”), provided that you first return to Q CELLS the affected Module. The foregoing constitutes your sole and exclusive remedy for a breach of the warranty set forth in this paragraph (the “Product Warranty”). 25-YEAR LINEAR PERFORMANCE WARRANTY In addition, Q CELLS provides you the following performance warranty (“Performance Warranty”) for Modules which are installed in accordance with the applicable Product Instructions: In the first year after the Purchase Date the Modules will produce a minimum power output of at least 97 % of that specified in the Module data sheet. From a period beginning on the first anniversary of the Purchase Date and ending on the twenty-fifth anniversary of the Purchase Date, the Modules will have a yearly maximum decrease of power output (degradation) of not more than 0.6 % of the power output specified in the Module data sheet within the framework of the power tolerance, i.e. the Module will have a minimum power output of at least 83 % of the power output specified in the Module data sheet at the end of the twenty-five year period. All power output measurements will be performed under the STC Standard Test Conditions used by Q CELLS on the Purchase Date. The STC Standard Test Conditions are customary standardized basic conditions for the measurement of the power of solar modules. The currently valid STC Standard Test Conditions are defined in the IEC standards EN 61215 and 60904-3. In the event of a breach of this Performance Warranty, Q CELLS will, at its choice, repair the defect, replace the affected Module, supply additional modules sufficient to make up for the power output reduction, refund you the full Purchase Price of the affected Module provided that you first return to Q CELLS the affected Module, or refund you a percentage of the Purchase Price of the affected Module equal to the percentage reduction in minimum power output compared to the minimum power output warranted under this Performance Warranty. The foregoing constitutes your sole and exclusive remedy for a breach of this Performance Warranty. EXCLUSIONS FROM THE PRODUCT AND PERFORMANCE WARRANTY Irrespective of contributory root causes, this Warranty does not cover the following cases: • Handling, storage, installation, configuration, testing, or use not in accordance with the Product Instructions (e.g., static, installation of mutually incompatible modules, inadequate system design, and incompatible inverter); • Repair, servicing or maintenance work not in accordance with the Product Instructions or failure to perform maintenance as required by the Product Instructions. • Usage in an environment outside the parameters specified in the Product Instructions, including without limitation high snow load outside such parameters; • Usage for purposes or in circumstances not conforming to the product specifications (as set out in the module data sheet applicable to the modules in any given case) and not complying with the installation and operating instructions; • Damage caused by environmental sources, such as but not limited to pollution of any kind as well as fire, explosion, smoke or charring; • Damage caused by acts of nature or God, including without limitation lightning, hail, frost, snow, or storms; • Damage caused by abuse, negligence, neglect, or accident, including without limitation acts of violence and vandalism • Damages to the photovoltaic system in which the Modules are installed, or damages caused by factors such as voltage fluctuations, power peaks, excess voltage, power failure etc.; • Scratches, marks, mechanical wear, rust, mold, degradation, dis-coloration and other changes which occur after the delivery of the Modules but which do not result in any adverse effect on the mechanical stability of the Module or a reduction of performance which exceeds the levels set out in the Performance Warranty; and • Issues not reproduc ble by Q CELLS. The following cases are also excluded from the Warranty: • The Q CELLS Modules are modified or altered or used in processes involving other products without obtaining prior written consent from Q CELLS. • The serial number or product label has been removed, changed, deleted or made unrecognizable or if it is no longer clearly distinguishable for other reasons beyond Q CELLS’ control and therefore it is not possible to conclusively identify the Modules. Use on mobile carriers such as motor vehicles or ships. As part of the warranty there is no claim to compensation for the 2) Panel Warranty DataMissouri Sun Solar: Bergh Solar Project 49.585kW
  • 8. LIMITED WARRANTY FOR CRYSTALLINE PHOTOVOLTAIC MODULES FROM [HANWHA Q . C E L L S GMBH] reimbursement of costs for dismantling, installation or replacement, loss of yield or other indirect damages. CLAIMS UNDER WARRANTY/NOTIFICATION OF DEFECTS You must check the Modules for visible defects upon delivery. If you discover any defects, you must report these immediately to Q CELLS. You must report any Warranty claim to Q CELLS during the applicable Warranty period and no later than thirty (30) days after discovering the breach of Warranty. Please contact us first in writing or electronically. Contact information, the required data and the procedure of the complaint process are described in document Q CELLS’ RMA process (Return Merchandise Authorization). You must follow the RMA process to be eligible for Warranty service. If you have any questions please contact your seller or Q CELLS at the following e-mail address: service@q-cells.com. We ask for our customers’ understanding that Q CELLS cannot accept any unauthorized return shipments of Modules and will not take delivery of such items. PERFORMANCE OF THE WARRANTY SERVICES In all cases, Q CELLS shall have the choice in accordance with this Warranty as to how Warranty claims are settled. Q CELLS may use the services of a third party service partner for this purpose. • Q CELLS shall pay the costs of a technical inspection of the affected Module in case of a Warranty claim. If there is no breach of Warranty as reasonably determined by Q CELLS, you will pay these costs • Q CELLS shall only accept liability under the performance warranty if the performance parameters measured by Q CELLS in the STCs (Standard Test Conditions) are not achieved. • The returned Modules shall remain your property unless Q CELLS chooses to replace such Modules, in which case ownership of the replaced Modules passes to Q CELLS. • Any repaired or replaced Modules shall be covered by the Warranty for the remaining portion of the original Warranty period as applicable. • If Q CELLS supplies replacement or additional modules under this Warranty and the original Module type is no longer available, Q CELLS will have the right to provide replacement or additional modules of a similar or equivalent type from the product range available at the time of the claim as long as they are suitable for the intended purpose. • In the event of glass breakage, Q CELLS reserves the right to perform a static calculation to verify the substructure was designed in accordance with the Product Instructions. • Q CELLS will have no liability in connection with this Warranty for any costs or expenses of dismantling or installing Modules or replacement modules. DISCLAIMER EXCEPT AS EXPRESSLY SET FORTH IN THE PRODUCT WARRANTY AND THE PERFORMANCE WARRANTY, Q CELLS HEREBY DISCLAIMS ALL WARRANTIES, WHETHER EXPRESS, IMPLIED, OR STATUTORY, REGARDING THE MODULES, INCLUDING WITHOUT LIMITATION ANY WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, TITLE, NON-INFRINGEMENT OF THIRD-PARTY RIGHTS, AND SYSTEM INTEGRATION. LIMITATION OF LIABILITY Q CELLS WILL NOT BE LIABLE FOR ANY CONSEQUENTIAL, EXEMPLARY, SPECIAL, INDIRECT, OR INCIDENTAL DAMAGES, INCLUDING ANY DAMAGES FOR LOST PROFITS OR LOSS OF YIELD, ARISING FROM OR RELATING TO THIS WARRANTY OR THE MODULES, EVEN IF Q CELLS KNEW OR SHOULD HAVE KNOWN OF THE POSSIBILITY OF SUCH DAMAGES. Q CELLS’ TOTAL CUMULATIVE LIABILITY ARISING FROM OR RELATED TO THIS WARRANTY AND THE MODULES, WHETHER IN CONTRACT OR TORT OR OTHERWISE, WILL NOT EXCEED THE PRODUCT PRICE FOR THE MODULE(S) AT ISSUE. THE FOREGOING LIMITATIONS OF LIABILITY ARE INDEPENDENT OF EXCLUSIVE REMEDIES FOR BREACH OF THIS WARRANTY. Q CELLS DISCLAIMS ALL LIABILITY OF ANY KIND OF Q CELLS’ SUPPLIERS UNDER THIS AGREEMENT. SOME STATES DO NOT ALLOW THE EXCLUSION OF IMPLIED WARRANTIES OR THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS OR EXCLUSIONS MAY NOT APPLY TO YOU. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE. THE DISCLAIMERS, EXCLUSIONS, AND LIMITATIONS OF LIABILITY UNDER THIS WARRANTY WILL NOT APPLY TO THE EXTENT PROHIBITED BY APPLICABLE LAW. ASSIGNMENT OF WARRANTY FOR PV MODULES This Warranty for PV Modules in its entirety, extends only to the original purchaser, and is transferrable in its entirety to any other person to whom title to the PV Modules has been transferred provided that a) a prior written notice of such transfer has been received by Q CELLS, and b) the PV Modules remain installed in their original installation location. GOVERNING LAW These Warranty terms and conditions shall be exclusively governed by the laws of the State of California, without giving effect to any conflict of laws principles that would require the application of the laws of another State laws principles that would require the application of the laws of another State. Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 9. / Perfect Welding / Solar Energy / Perfect Charging / With power categories ranging from 3.8 kW to 15.0 kW, the transformerless Fronius Primo is the ideal compact single-phase inverter for residential applications. The sleek design is equipped with the SnapINverter hinge mounting system which allows for lightweight, secure and convenient installation and service. The Fronius Primo has several integrated features that set it apart from competitors including dual powerpoint trackers, high system voltage, a wide input voltage range, Wi-Fi* and SunSpec Modbus interface for seamless monitoring and datalogging, Arc Fault Circuit Interruption (AFCI), and Fronius’ online and mobile platform Fronius Solar.web. The Fronius Primo is designed to adjust to future standards, offering a complete solution to code restrictions and technical innovations of tomorrow. It also works seamlessly with the Fronius Rapid Shutdown Box for a reliable NEC 2014 solution. TECHNICAL DATA FRONIUS PRIMO / The future of residential solar is here - Introducing the new Fronius Primo. / SuperFlex Design / Wi-Fi®* interface / Smart Grid Ready / Arc Fault Circuit Interruption / SnapINverter mounting system / PC board replacement process FRONIUS PRIMO GENERAL DATA FRONIUS PRIMO 3.8 - 8.2 FRONIUS PRIMO 10.0-15.0 Dimensions (width x height x depth) 16.9 x 24.7 x 8.1 in. 20.1 x 28.5 x 8.9 in. Weight 47.29 lb. 82.5 lbs. Degree of protection NEMA 4X Night time consumption < 1 W Inverter topology Transformerless Cooling Variable speed fan Installation Indoor and outdoor installation Ambient operating temperature range -40 - 131°F (-40 - 55°C) -40 - 140°F (-40 - 60°C) Permitted humidity 0 - 100 % DC connection terminals 4x DC+ and 4x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded) 4x DC+1, 2x DC+2 and 6x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded) AC connection terminals Screw terminals 12 - 6 AWG Revenue Grade Metering Optional (ANSI C12.1 accuracy) Certificates and compliance with standards UL 1741-2010, UL1998 (for functions: AFCI and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC Article 690, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013 UL 1741-2015, UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC Article 690-2014, C22. 2 No. 107.1-01 (September 2001) , UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013 PROTECTIVE DEVICES STANDARD WITH ALL PRIMO MODELS AFCI & 2014 NEC Ready Yes Ground Fault Protection with Isolation Monitor Interrupter Yes DC disconnect Yes DC reverse polarity protection Yes N W S E INTERFACES STANDARD WITH ALL PRIMO MODELS Wi-Fi*/Ethernet/Serial Wireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU 6 inputs or 4 digital inputs/outputs External relay controls USB (A socket) Datalogging and/or updating via USB 2x RS422 (RJ45 socket) Fronius Solar Net, interface protocol Datalogger and Webserver Included *The term Wi-Fi® is a registered trademark of the Wi-Fi Alliance. 3) Inverter DataMissouri Sun Solar: Bergh Solar Project 49.585kW
  • 10. Rev. 11.3.15 USA / Perfect Welding / Solar Energy / Perfect Charging v05 May 2015 EN Further information about all Fronius products and our global sales partners and representatives can be found at www.fronius.com WE HAVE THREE DIVISIONS AND ONE PASSION: SHIFTING THE LIMITS OF POSSIBILITY. / Whether welding technology, photovoltaics or battery charging technology − our goal is clearly defined: to be the innovation leader. With around 3,300 employees worldwide, we shift the limits of what’s possible - our record of over 900 granted patents is testimony to this. While others progress step by step, we innovate in leaps and bounds. Just as we’ve always done. The responsible use of our resources forms the basis of our corporate policy. Fronius USA LLC 6797 Fronius Drive Portage, IN 46368 USA pv-support-usa@fronius.com www.fronius-usa.com TECHNICAL DATA FRONIUS PRIMO INPUT DATA PRIMO 3.8-1 PRIMO 5.0-1 PRIMO 6.0-1 PRIMO 7.6-1 PRIMO 8.2-1 Recommended PV power (kWp) 3.0 - 6.0 kW 4.0 - 7.8 kW 4.8 - 9.3 kW 6.1 - 11.7 kW 6.6 - 12.7 kW Max. usable input current (MPPT 1/MPPT 2) 18 A / 18 A 18 A / 18 A 18 A / 18 A 18 A / 18 A 18 A / 18 A Total max. DC current 36 A Max. array short circuit current (1.25 Imax) (MPPT 1/ MPPT 2) 22.5 A / 22.5 A Operating voltage range 80 V - 600 V Max. input voltage 600 V Nominal input voltage 410 V 420 V 420 V 420 V 420 V Admissable conductor size DC AWG 14 - AWG 6 MPP Voltage Range 200 - 480 V 240 - 480 V 240 - 480 V 250 - 480 V 270 - 480 V Number of MPPT 2 OUTPUT DATA PRIMO 3.8-1 PRIMO 5.0-1 PRIMO 6.0-1 PRIMO 7.6-1 PRIMO 8.2-1 Max. output power 240 V 3800 W 5000 W 6000 W 7600 W 8200 W 208 V 3800 W 5000 W 6000 W 7600 W 7900 W Max. continuous output current 240 V 15.8 A 20.8 A 25.0 A 31.7 A 34.2 A 208 V 18.3 A 24.0 A 28.8 A 36.5 A 38.0 A Recommended OCPD/AC breaker size 240 V 20 A 30 A 35 A 40 A 45 A 208 V 25 A 30 A 40 A 50 A 50 A Max. Efficiency 96.7 % 96.9 % 96.9 % 96.9 % 97.0 % CEC Efficiency 240 V 95.0 % 95.5 % 96.0 % 96.0 % 96.5 % Admissable conductor size AC AWG 14 - AWG 6 Grid connection 208 / 240 V Frequency 60 Hz Total harmonic distortion < 5.0 % Power factor (cos φac,r) 0.85-1 ind./cap INPUT DATA PRIMO 10.0-1 PRIMO 11.4-1 PRIMO 12.5-1 PRIMO 15.0-1 Recommended PV power (kWp) 8.0 - 12.0 kW 9.1 - 13.7 kW 10.0 - 15.0 kW 12.0 - 18.0 kW Max. usable input current (MPPT 1/MPPT 2) 33.0 A / 18.0 A Total max. DC current 51 A Max. array short circuit current (1.25 Imax) (MPPT 1/MPPT 2) 41.3 A / 22.5 A Operating voltage range 80 V - 600 V Max. input voltage 600 V Nominal input voltage 415 V 420 V 425 V 440 V Admissable conductor size DC AWG 14 - AWG 6 copper direct, AWG 6 aluminum direct (AWG 10 copper or AWG 8 aluminium for overcurrent protective devices up to 60A, from 61 to 100A minimum AWG 8 for copper or AWG 6 aluminium has to be used), AWG 4 - AWG 2 copper or alu- minum with optional input combiner MPP Voltage Range 220 - 480 V 240 - 480 V 260 - 480 V 320 - 480 V Integrated DC string fuse holders 4- and 4+ for MPPT 1 / no fusing requried on MPPT 2 Number of MPPT 2 OUTPUT DATA PRIMO 10.0-1 PRIMO 11.4-1 PRIMO 12.5-1 PRIMO 15.0-1 Max. output power 240 V 9995 W 11400 W 12500 W 15000 W 208 V 9995 W 11400 W 12500 W 13750 W Max. continuous output current 240 V 41.6 A 47.5 A 52.1 A 62.5 A 208 V 48.1 A 54.8 A 60.1 A 66.1 A Recommended OCPD/AC breaker size 240 V 60 A 60 A 70 A 80 A 208 V 70 A 70 A 80 A 90 A Max. Efficiency 96.7 % CEC Efficiency 96.0 % 96.5 % Admissable conductor size AC AWG 10 - AWG 2 copper (solid / stranded / fine stranded)(AWG 10 copper or AWG 8 aluminium for overcurrent protective devices up to 60A, from 61 to 100A minimum AWG 8 for copper or AWG 6 aluminium has to be used) , AWG 6 - AWG 2 copper(solid / stranded) MultiContactWiringable with AWG 12 Grid connection 208 / 240 V Frequency 60 Hz Total harmonic distortion < 2.5 % Power factor (cos φac,r) 0-1 ind./cap. Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 11. SE_ToW_EN_US_0415 1/2 FRONIUS LIMITED WARRANTY TERMS AND CONDITIONS valid from: 10/15/2015 These limited warranty terms and conditions apply to original installation of Fronius inverters in the United States of America. The warranty agreement is concluded between Fronius and the warranty holder (owner of the installed system). Content of the warranty: Fronius Warranty Plus/Warranty Extension Plus The Fronius Warranty Plus/Warranty Extension Plus covers the costs of materials, servicing and transport under the terms and conditions indicated below. Fronius Warranty/Warranty Extension The Fronius Warranty/Warranty Extension covers the costs of materials under the terms and conditions indicated below. Duration of warranty: In each case the warranty period begins the day that the products leave the Fronius factory. Fronius string inverters (wall-mounted devices) Fronius string inverters are supplied with a 10-year Fronius Warranty Plus. Fronius central inverters (free-standing devices) Fronius central inverters are supplied with a 5-year Fronius Warranty Plus. Fronius Rapid Shut-down Box (RSB) Fronius Rapid Shut-down boxes are supplied with a 5-year Fronius Warranty Plus. Warranty services: If a fault should occur during the Fronius warranty period and the fault is covered by the limited warranty terms and conditions, Fronius reserves the right to  make the corresponding spare parts available,  make an equivalent replacement device available,  repair this fault at its premises or on the customer's premises,  or have these services carried out by a suitably-trained Fronius Service Partner. Materials "Materials" means that, during the warranty period, Fronius will bear the cost of materials (spare part or replacement device excluding labour costs) associated with the warranty service. Servicing The warranty covers the labour costs associated with the materials, provided that these are incurred by Fronius itself or a Fronius Service Partner (service fee). Other incidental costs (such as travel costs, installation costs, if these exceed the Fronius service fee, customs duties, etc.) are not covered by the warranties. Transport National transport costs are covered by the Fronius Warranty Plus and Fronius Warranty Extension Plus, provided that these are incurred in accordance with the standard claim procedures with the Fronius Service Provider. Fronius will not bear the costs of any unjustified or express deliveries. General provisions Devices or components are to be returned in the original or equivalent packaging. Fronius retains ownership of replacement devices and components inside or outside of the warranty/warranty exclusion until the faulty parts/devices have been received. In all cases ownership of the faulty device/parts is transferred to Fronius when the replacement device is received. If the faulty device/parts is/are not returned to Fronius within 60 days, they will be charged to the installer at the current replacement prices. Fronius Warranty Extension/Warranty Extension Plus An extended warranty can be purchased up to 30 months after dispatch by Fronius. Fronius may reject orders received later. The extended warranties only apply to Fronius inverters unambiguously identified by their serial number. It is possible to extend the warranty to 10, 15 or 20 years from dispatch by Fronius. Considerations when making a warranty claim First contact an installer, who will then contact Fronius if necessary. The Fronius warranty procedure must be strictly adhered to in the event of a warranty claim. This is the only way of ensuring that the warranty services remain free of charge for the warranty holder. The purchase invoice, serial number of the device and start- up report (the date on which the device was provided/commissioned and report from the power supply company), as well as proof of payment of the warranty extension fee, are required for warranty claims. The purchase price must have been paid to Fronius in full in order for the warranty service to be provided. When devices or components are replaced, the remaining warranty period is transferred to the replacement device or 4) Inverter Warranty Data Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 12. SE_ToW_EN_US_0415 2/2 replacement component. This is automatically registered at Fronius. A new certificate is not issued. If servicing is carried out on site, the client must guarantee unrestricted access to the Fronius inverters. If necessary, the warranty holder must make the equipment required by the applicable health and safety regulations available free of charge. Scope and validity of the warranty The Fronius warranties apply only to Fronius products that have been identified unambiguously by their serial number. These must be appropriately certified for the country of installation. The other components of the photovoltaic system as well as the system add-ons, system monitoring and data communication components, any accessories, and pre-production devices are excluded from the warranty. These components fall under the corresponding provisions of the applicable General Delivery and Payment Conditions of Fronius. Exclusions from the Fronius warranties Failure to observe the operating instructions, installation instructions or maintenance procedures.  Improper installation  Improper commissioning  Improper transportation  Improper or incorrect operation  Inadequate ventilation of the device  Any work performed on the device by companies or persons that have not been authorised by Fronius  Failure to observe safety rules and installation standards  Force majeure (storm, lightning, overvoltage, fire, etc.) Damage to the Fronius inverter caused by other components in the photovoltaic system or damage that does not impair the function of the Fronius inverter ("cosmetic flaws") is also excluded from the warranty. The warranty does not cover travel and accommodation expenses as well as on-site assembly and installation costs, if these exceed the service reimbursement paid to the installer by Fronius depending on the service and agreement. Changes to the existing PV system, in-house installation and similar or the time involved and the costs incurred are not covered by the warranty. Due to technological progress, the equivalent replacement or new device provided may not be compatible with the system monitoring or other components installed on site (e.g. Fronius DATCOM). The warranty does not cover the expenses and costs incurred as a result of upgrading system monitors or other components of the PV system. A claim for compensation cannot be made for energy that has not been fed into the grid or energy that has not been consumed in-house, etc. Fuses and other wearing parts are excluded from the warranty. Other legal information SELLER DISCLAIMS ALL IMPLIED WARRANTIES AND SIMILAR OBLIGATIONS (OTHER THAN THAT THE GOODS WILL BE NEW AND GOOD TITLE) INCLUDING BUT NOT LIMITED TO THOSE OF FITNESS FOR A PARTICULAR PURPOSE, AND MERCHANTABILITY, WHETHER OTHERWISE ARISING BY LAW, CUSTOM, USAGE, TRADE PRACTICE, COURSE OF DEALING, OR COURSE OF PERFORMANCE. There are no warranties which extend beyond those express warranties contained in the Agreement. Buyer affirms that it has not relied upon Seller’s skill nor judgment to select or furnish the Goods for any particular purpose beyond the specific express warranties in the Agreement. Seller does not warrant the Goods will comply with the requirements of any safety or environmental code or regulation of any federal, state, municipality or other jurisdiction beyond the specific express warranties in the Agreement. Seller does not warrant that the Goods will operate with any accessories or within any system not sold under the Agreement and Seller’s warranty is limited to the operation of the Goods in a stand-alone mode. Some countries, states, or provinces do not allow the exclusion or limitation of implied warranties or the limitation of incidental or consequential damages for certain products supplied to consumers, or the limitation of liability for personal injury, so such limitations and exclusions may be limited in their application to an end user and others. When the implied warranties are not allowed to be excluded in their entirety, they will be limited to the duration of the applicable written warranty. The warranty gives specific legal rights which may vary depending on local law. Other legal warranty or liability claims against Fronius remain unaffected by this warranty. In the event of such claims, please contact the vendor of your device. Our General Delivery and Payment Conditions under "Legal information" on our website (www.fronius.com) also apply. Previously valid warranty conditions are replaced by these conditions. Fronius reserves the right to make changes to the warranty process at any time. Current and detailed information about warranty terms and conditions can be found on our website at www.fronius.com/solar/warranty Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 13. LGate 120 RESIDENTIAL SOLAR MONITORING SOLUTION Product Datasheet The LGate 120 is a single-phase electronic watt-hour meter for remote monitoring of solar photovoltaic systems. It features a smart communications module to automatically transmit meter data over cellular or Ethernet networks allowing system owners and operators to easily manage distributed solar assets. The LGate 120 combines a revenue-grade, solid-state power meter with an advanced communications gateway. These components work in conjunction to remotely monitor the performance of residential solar energy installation regardless of panel or inverter type. The LGate 120 is a one-piece completely under glass meter which installs easily using a standard socket base. Performance data is uploaded in near real-time to the Locus Energy SolarOS monitoring platform which provides a suite of tools and analytics for asset managers. DATA COLLECTION AC energy data is collected by the meter and passed to the communications module. Additional system performance data can be collected directly from meteorological sensors and supported inverters via RS-485 or Zigbee connections. All data is stored in non-volatile memory and then automatically uploaded to the SolarOS and SolarNOC platforms. NETWORK CONNECTIVITY The communications gateway inside the LGate 120 supports plug and play connectivity through a cellular or Ethernet network connection. Once the unit is installed and powered on, it will immediately begin transmitting data without any configuration. For maximum reliability, the communications gateway will automatically route uploads between the wireless and wired connections if either of the networks are unavailable. FEATURES • ANSI C12.20 power meter • RS-485 and Zigbee inputs • GSM cellular or Ethernet connectivity • Over the air firmware updates • Easy, low cost installation • Doesn’t require entrance into the building • Plug and play activation • LCD display Missouri Sun Solar: Bergh Solar Project 49.585kW 5) Monitor Data
  • 14. DATALOGGER Processor ARM9 embedded CPU OS Custom version of Linux 2.6, OTA firmware updates Memory 128 MB RAM Display LCD screen SPECIFICATIONS COMMUNICATIONS LAN RJ45 10/100 Ethernet, full half duplex, auto polarity Cellular 3G GSM Networking DHCP or static PHYSICAL Enclosure NEMA 3R Type Weight 8 oz Dimensions 6.95” x 6.5” x 7.3” Environment -20 to 60C, all-weather Warranty 5 year limited warranty DIAGRAM – TYPICAL CONFIGURATION DIMENSIONS I/O RS485 2 wire and 4 wire Modbus Zigbee Shielded CAT5 LEGEND 6.95 in 6.31 in 5.46 in 6.00 in 7.30 in SOCKET METER COMPLIANCE ANSI 12.20 class 0.2% FCC Part 15B PTCRB AT&T Carrier Compliance PV ARRAY ELECTRICAL SERVICE INVERTER(S) INTERNET LGATE 120 METER BASE METER MODULE LOCUS ENERGY COMM MODULE POWER Accuracy ANSI 12.20 (Class 0.2%) Voltage Inputs 120 - 480 VAC Max. Current Input 200 A Service Type Single phase , 60 Hz Socket Type 2S Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 15. Product Data Sheet D324NRB Safety Switch , 200A, Fusible, Cartridge (Class H, K or R), 3-Pole List Price $1,461.00 USD Availability Stock Item: This item is normally stocked in our distribution facility. Terminal Type Lugs Type of Duty General Duty Maximum Voltage Rating 240VAC Wire Size #2 to 300 AWG/kcmil(Al) - #4 to 300 AWG/kcmil(Cu) Depth 8.25 Inches Height 29.25 Inches Width 17.25 Inches Action Single Throw Ampere Rating 200A Approvals UL Listed File: E2875 Enclosure Rating NEMA 3R Enclosure Type Rainproof and Sleet/Ice proof (Indoor/Outdoor) Enclosure Material Galvannealed Steel Factory Installed Neutral Yes Fuse Type Cartridge (Class H, K or R) Disconnect Type Fusible Short Circuit Current Rating 100kA (max. depending on fuse type) Mounting Type Surface Number of Poles 3-Pole Technical Characteristics Category 00106 - Safety Switch, General Duty, 30 - 200 Amp, NEMA3R Discount Schedule DE1A GTIN 00785901461524 Package Quantity 1 Weight 45.33 lbs. Availability Code Stock Item: This item is normally stocked in our distr bution facility. Returnability Y Country of Origin US Shipping and Ordering As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this document. Generated: 06/30/2010 15:08:04 © 2010 Schneider Electric. All rights reserved. 1 6) Disconnect DataMissouri Sun Solar: Bergh Solar Project 49.585kW
  • 16. 1 of 11 ¡ INNOVATIVE DESIGN PROTOTYPE TESTING are key components of GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance. ¡ TEST CRITERIA: 3 PROTOTYPE TESTED 3 NEMA MG1-22 EVALUATION 3 SYSTEM TORSIONAL TESTED 3 MOTOR STARTING ABILITY ¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION. This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. Digital voltage regulation at ±1%. ¡ SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component. ¡ GENERAC TRANSFER SWITCHES. Long life and reliability are synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems and controls for total system compatibility. INCLUDES: • Two Line LCD Multilingual Digital Evolution™ Controller (English/Spanish/ French/Portuguese) with external viewing window for easy indication of generator status and breaker position. • True Power™ Electrical Technology • Isochronous Electronic Governor • Sound Attenuated Enclosure • Closed Coolant Recovery System • Smart Battery Charger • UV/Ozone Resistant Hoses • ±1% Voltage Regulation • Natural Gas or LP Operation • 5 Year Limited Warranty • UL 2200 Listed Standby Power Rating Model RG022 (Aluminum - Gray) - 22 kW 60 Hz Model RG027 (Aluminum - Gray) - 27 kW 60 Hz Model RG032 (Aluminum - Gray) - 32 kW 60 Hz Model RG038 (Aluminum - Gray) - 38 kW 60 Hz Model RG048 (Aluminum - Gray) - 48 kW 60 Hz FEATURES ISO9001: 2008 PROTECTOR® QS SERIES Standby Generators Liquid-Cooled Gaseous Engine Protector®QSSeries Protector® QS Series Meets EPA Emission Regulations 22 27 kW are CA/MA emissions compliant 48 kW meets CA/MA emissions requirements with optional catalyst 32 38 kW not for sale in CA/MA ® *Built in the USA using domestic and foreign parts Missouri Sun Solar: Bergh Solar Project 49.585kW 7) Generator Data
  • 17. 2 of 11 22 • 27 • 32 • 38 • 48 kW application engineering data GENERATOR SPECIFICATIONS Type Synchronous Rotor Insulation Class H (22 27 kW) or F (32, 38 48 kW) Stator Insulation Class H Telephone Interference Factor (TIF) 50 Alternator Output Leads 1-Phase 4 wire Alternator Output Leads 3-Phase 6 wire Bearings Sealed Ball Coupling Flexible Disc Excitation System Direct VOLTAGE REGULATION Type Electronic Sensing Single Phase Regulation ± 1% GOVERNOR SPECIFICATIONS Type Electronic Frequency Regulation Isochronous Steady State Regulation ± 0.25% ELECTRICAL SYSTEM Battery Charge Alternator 12 Volt 30 Amp Static Battery Charger 2.5 Amp Recommended Battery (battery not included) Group 26 (22, 27, 32 38 kW) or Group 24F (48 kW), 525CCA System Voltage 12 Volts GENERATOR FEATURES Revolving field heavy duty generator Directly connected to the engine Operating temperature rise 120 °C above a 40 °C ambient Class H insulation is NEMA rated Class F insulation is NEMA rated All models fully prototyped tested ENCLOSURE FEATURES Aluminum weather protective enclosure Ensures protection against mother nature. Electrostatically applied textured epoxy paint for added durability. Enclosed critical grade muffler Quiet, critical grade muffler is mounted inside the unit to prevent injuries. Small, compact, attractive Makes for an easy, eye appealing installation. SAE Sound attenuated enclosure ensures quiet operation. ENGINE SPECIFICATIONS: 22, 27, 32 38 kW Make Generac Model In-line Cylinders 4 Displacement (Liters) 2.4 Bore (in/mm) 3.41/86.5 Stroke (in/mm) 3.94/100 Compression Ratio 9.5:1 Intake Air System Naturally Aspirated (22 27 kW) or Turbocharged/Aftercooled (32 38 kW) Lifter Type Hydraulic ENGINE SPECIFICATIONS: 48 kW Make Generac Model V-Type Cylinders 8 Displacement (Liters) 5.4 Bore (in/mm) 3.55/90.2 Stroke (in/mm) 4.17/105.9 Compression Ratio 9:1 Intake Air System Naturally Aspirated Lifter Type Hydraulic ENGINE LUBRICATION SYSTEM Oil Pump Type Gear Oil Filter Type Full flow spin-on cartridge Crankcase Capacity (qt/l) 4/3.8 (22, 27, 32 38 kW) or 6/5.7 (48 kW) ENGINE COOLING SYSTEM Type Closed Water Pump Belt driven Fan Speed (rpm) 1980 - 22 27 kW 1500 - 32 38 kW 1954 - 48 kW Fan Diameter (in/mm) 18.1/459.7 (22 27 kW) or 22/558.8 (32, 38 48 kW) Fan Mode Pusher (22 27 kW) or Puller (32, 38 48 kW) FUEL SYSTEM Fuel Type Natural gas, propane vapor Carburetor Down Draft Secondary Fuel Regulator Standard Fuel Shut Off Solenoid Standard Operating Fuel Pressure 5-14 water column/9-26 mm HG (All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271) Protector®QSSeries ®
  • 18. 3 of 11 22 • 27 • 32 • 38 • 48 kW operating data GENERATOR OUTPUT VOLTAGE/kW - 60 Hz kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both) RG022 120/240 V, 1Ø, 1.0 pf 22 92 22 92 100 120/208 V, 3Ø, 0.8 pf 22 76 22 76 80 120/240 V, 3Ø, 0.8 pf 22 66 22 66 80 RG027 120/240 V, 1Ø, 1.0 pf 27 113 25 104 125 120/208 V, 3Ø, 0.8 pf 27 94 25 87 100 120/240 V, 3Ø, 0.8 pf 27 81 25 75 90 RG032 120/240 V, 1Ø, 1.0 pf 32 133 32 133 150 120/208 V, 3Ø, 0.8 pf 32 111 32 111 125 120/240 V, 3Ø, 0.8 pf 32 96 32 96 100 277/480 V, 3Ø, 0.8 pf 32 48 32 48 60 RG038 120/240 V, 1Ø, 1.0 pf 38 158 38 158 175 120/208 V, 3Ø, 0.8 pf 38 132 38 132 150 120/240 V, 3Ø, 0.8 pf 38 114 38 114 125 277/480 V, 3Ø, 0.8 pf 38 57 38 57 60 RG048 120/240 V, 1Ø, 1.0 pf 48 200 48 200 200 120/208 V, 3Ø, 0.8 pf 48 167 48 167 175 120/240 V, 3Ø, 0.8 pf 48 144 48 144 150 277/480 V, 3Ø, 0.8 pf 48 72 48 72 80 SURGE CAPACITY IN AMPS Voltage Dip @ .4 pf 15% 30% RG022 120/240 V, 1Ø 55 135 120/208 V, 3Ø 40 92 120/240 V, 3Ø 35 80 RG027 120/240 V, 1Ø 62 170 120/208 V, 3Ø 70 120 120/240 V, 3Ø 61 103 RG032 120/240 V, 1Ø 75 180 120/208 V, 3Ø 87 210 120/240 V, 3Ø 75 182 277/480 V, 3Ø 36 87 RG038 120/240 V, 1Ø 75 180 120/208 V, 3Ø 87 210 120/240 V, 3Ø 75 182 277/480 V, 3Ø 36 87 RG048 120/240 V, 1Ø 85 195 120/208 V, 3Ø 90 218 120/240 V, 3Ø 78 189 277/480 V, 3Ø 36 87 ENGINE FUEL CONSUMPTION Natural Gas Propane (ft³/hr) (m³/hr) (gal/hr) (l/hr) (ft³/hr) RG022 Exercise cycle 42 1.2 0.44 1.7 16 25% of rated load 100 2.8 1.1 4.2 40 50% of rated load 190 5.4 2.1 7.8 75 75% of rated load 255 7.2 2.8 10.5 101 100% of rated load 316 9 3.4 13 125 RG027 Exercise cycle 42 1.2 0.44 1.7 16 25% of rated load 108 3.1 1.2 4.5 43 50% of rated load 197 5.6 2.1 8.1 78 75% of rated load 287 8.2 3.1 11.8 114 100% of rated load 359 10.2 3.9 14.8 143 RG032 Exercise cycle 79 2.2 0.8 3.2 30 25% of rated load 144 4.1 1.7 6.3 60 50% of rated load 226 6.4 2.7 10.3 97 75% of rated load 298 6.4 3.7 13.9 132 100% of rated load 375 10.6 4.6 17.5 166 RG038 Exercise cycle 83 2.3 0.9 3.2 31 25% of rated load 162 4.6 1.7 6.6 62 50% of rated load 255 7.2 2.9 10.8 103 75% of rated load 345 9.8 4 15 142 100% of rated load 437 12.4 5.2 19 185 RG048 Exercise cycle 95 2.7 1 3.9 38 25% of rated load 204 5.8 2.16 8.5 82 50% of rated load 392 11.1 4.14 15.7 151 75% of rated load 547 15.5 5.8 22.8 220 100% of rated load 756 21.5 7.96 31.3 302 Protector®QSSeries STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. Note: Fuel pipe must be sized for full load. For Btu content, multiply ft³/hr x 2520 (LP) or ft³/hr x 1000 (NG) For megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG) Refer to Emissions Data Sheets for maximum fuel flow for EPA and SCAQMD permitting purposes. ®
  • 19. 4 of 11 22 • 27 • 32 • 38 • 48 kW operating data Protector®QSSeries POWER ADJUSTMENT FOR AMBIENT CONDITIONS Temperature Deration............................................................................................................3% for every 10 °C above 25 °C or 1.65% for every 10 °F above 77 °F Altitude Deration (22, 27 48 kW)......................................................................................1% for every 100 m above 183 m or 3% for every 1000 ft above 600 ft Altitude Deration (32 38 kW) ........................................................................................ 1% for every 100 m above 915 m or 3% for every 1000 ft above 3000 ft CONTROLLER FEATURES 2-Line Plain Text LCD Display.........................................................................................................................................Simple user interface for ease of operation. Mode Switch: Auto ...............................................................................................................................................Automatic Start on Utility failure. 7 day exerciser Off............................................................................................................................Stops unit. Power is removed. Control and charger still operate. Manual.......................................................................................... Start with starter control, unit stays on. If utility fails, transfer to load takes place. Programmable start delay between 10-30 seconds.............................................................................................................................................................Standard Engine Start Sequence......................................................................................................................Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration) Engine Warm-up......................................................................................................................................................................................................................5 sec Engine Cool-Down...................................................................................................................................................................................................................1 min Starter Lock-out.................................................................................................................................Starter cannot re-engage until 5 sec after engine has stopped. Smart Battery Charger.........................................................................................................................................................................................................Standard Automatic Voltage Regulation with Over and Under Voltage Protection.................................................................................................................................Standard Automatic Low Oil Pressure Shutdown................................................................................................................................................................................Standard Overspeed Shutdown...............................................................................................................................................................................................Standard, 72 Hz High Temperature Shutdown................................................................................................................................................................................................Standard Overcrank Protection...........................................................................................................................................................................................................Standard Safety Fused.......................................................................................................................................................................................................................Standard Failure to Transfer Protection...............................................................................................................................................................................................Standard Low Battery Protection.........................................................................................................................................................................................................Standard 50 Event Run Log................................................................................................................................................................................................................Standard Future Set Capable Exerciser...............................................................................................................................................................................................Standard Incorrect Wiring Protection..................................................................................................................................................................................................Standard Internal Fault Protection......................................................................................................................................................................................................Standard Common External Fault Capability.......................................................................................................................................................................................Standard Governor Failure Protection.................................................................................................................................................................................................Standard ENGINE COOLING 22 kW 27 kW 32 38 kW 48 kW Air flow (inlet air including alternator and combustion air in cfm/cmm) 2400/68 2400/68 2200/62.3 4350/123.2 System coolant capacity (gal/liters) 2.5/9.5 2.5/9.5 2.5/9.5 3/11.4 Heat rejection to coolant (BTU per hr/MJ per hr) 99,000/104.5 105,000/110.8 145,000/153 186,000/196.2 Maximum operation air temperature on radiator (°C/°F) 60/150 Maximum ambient temperature (°C/°F) 50/140 COMBUSTION REQUIREMENTS Flow at rated power (cfm/cmm) 68/1.9 68/1.9 106/3 163/4.6 SOUND EMISSIONS Sound output in dB(A) at 23 ft (7 m) with generator in exercise mode* 61 61 58 63 Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load* 70 70 64 68 *Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters. EXHAUST Exhaust flow at rated output (cfm/cmm) 165/4.7 180/5.1 300/8.5 414/11.7 Exhaust temperature at muffler outlet (°C/°F) 482/900 538/1000 579/1075 552/1025 ENGINE PARAMETERS Rated Synchronous rpm 1800 ®
  • 20. 5 of 11 22 • 27 • 32 • 38 • 48 kW available accessories Protector®QSSeries Model # Product Description 006463-3 Mobile Link™ Generac's Mobile Link allows you to check the status of your generator from anywhere that you have access to an Internet connection from a PC or with any smart device. You will even be notified when a change in the generator’s status occurs via e-mail or text message. Note: Harness Adapter Kit required. Available in the U.S. only. 006478-0 Harness Adapter Kit The Harness Adapter Kit is required to make liquid-cooled units compatible with Mobile Link™. 005630-1 - 22, 27, 32 38 kW 005632-1 - 48 kW Cold Weather Kit If the temperature regularly falls below 32 °F (0 °C), install a cold weather kit to maintain optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap. 005616-0 - 22, 27, 32 38 kW 006204-0 - 48 kW Extreme Cold Weather Kit Recommended where the temperature regularly falls below 32 °F (0 °C) for extended periods of time. For liquid cooled units only. 005651-0 Base Plug Kit Add base plugs to the base of the generator to keep out debris. 005704-0 Paint Kit If the generator enclosure is scratched or damaged, it is important to touch-up the paint to protect from future corrosion. The paint kit includes the necessary paint to properly maintain or touch-up a generator enclosure. 005656-0 - 22 27 kW 005984-0 - 32 38 kW 006205-0 - 48 kW Scheduled Maintenance Kit The Liquid-Cooled Scheduled Maintenance Kits offer all the hardware necessary to perform complete maintenance on Generac liquid-cooled generators. 006664-0 Local Wireless Monitor Completely wireless and battery powered, Generac's wireless remote monitor provides you with instant status information without ever leaving the house. 006665-0 Wireless Remote Extension Harness Recommended for use with the Wireless Remote on units up to 60 kW, required for use on units 70 kW or greater. 006873-0 Smart Management Module (50 Amps) Smart Management Modules are used in conjunction with the Automatic Transfer Switch to increase its power management capabilities. It provides additional power management flexibility not found in any other power management system. 006510-0 E-Stop E-stop allows for immediate fuel shutoff and generator shutdown in the event of an emergency. ®
  • 21. 1 of 2 Non-Service Rated Automatic Transfer Switches 100-400Amps ® 100-400 Amps 100 - 400 Amps, Three Phase DESCRIPTION All non-service rated switches are available in 120/208 3ø, 120/240 3ø, and 277/480 3ø. All switches are open transition. STANDARD FEATURES All non-service rated transfer switches are housed in a steel NEMA/UL Type 3R enclosure, with electrostatically applied and baked powder paint. The Heavy Duty Generac Contactor is a UL recognized device, designed for years of service. The controller at the generator handles all the timing, sensing, exercising functions, and transfer commands. 8 Transfer Switch Data Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 22. 2 of 2 Functions Dimensions ® Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com ©2015 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0186650SBY-L Printed in U.S.A. 09/23/15 100-400 Amps Non-Service Rated Transfer Switches ® Model RTSN100G3 RTSN100J3 RTSN100K3 RTSN200G3 RTSN200J3 RTSN200K3 RTSN400G3 RTSN400J3 RTSN400K3 Amps 100 200 400 Voltage 120/208 3Ø 120/240 3Ø 277/480 3Ø 120/208 3Ø 120/240 3Ø 277/480 3Ø 120/208 3Ø 120/240 3Ø 277/480 3Ø Load Transition Type (Automatic) Open Transition Enclosure Type NEMA 3R Withstand Rating (Amps) 14,000 14,000 14,000 25,000 25,000 25,000 35,000 35,000 35,000 Lug Range 2/0 - #6 400 MCM - #4 600 MCM - #4 or 1/0 - 250 MCM • Electrically operated, mechanically-held contacts for fast, positive connections. • Rated for all classes of load, 100% equipment rated, both inductive and resistive. • 160 millisecond transfer time. • Single coil design. • Main contacts are silver plated or silver alloy to resist welding and sticking. • NEMA 3R (indoor/outdoor rated) steel enclosure is standard. • Limited Five Year Warranty. H2 DEPTH H1 W2 W1 Specifications Features Model Height (in./mm) Width (in./mm) Depth (in./mm) Weight (lbs./kilos)H1 H2 W1 W2 RTSN100G3 19.3/490.2 24.1/612.1 16.9/429.3 20.2/513.1 7.1/180.3 65/29.48 RTSN100J3 19.3/490.2 24.1/612.1 16.9/429.3 20.2/513.1 7.1/180.3 57/25.85 RTSN100K3 31.3/795 36.1/916.9 19.2/487.7 24/609.6 10/254 135/61.24 RTSN200G3 19.3/490.2 24.1/612.1 16.9/429.3 20.2/513.1 7.1/180.3 48/21.77 RTSN200J3 19.3/490.2 24.1/612.1 16.9/429.3 20.2/513.1 7.1/180.3 65/29.48 RTSN200K3 43/1092.2 48.1/1221.7 25/635 30.1/764.5 13.1/332.7 105/47.63 RTSN400G3 31.3/795 36.1/916.9 19.2/487.7 24/609.6 10/254 160/72.57 RTSN400J3 31.3/795 36.1/916.9 19.2/487.7 24/609.6 10/254 133/60.33 RTSN400K3 43/1092.2 48.1/1221.7 25/635 30.1/764.5 13.1/332.7 133/60.33 100-400Amps All timing and sensing functions originate in the generator controller Utility voltage drop-out.......................................................................................................................................................................................................................60% Timer to generator start.......................................................................................................................................10 second factory set, adjustable between 10-30 seconds Engine warm up delay..................................................................................................................................................................................................................5 seconds Standby voltage sensor...................................................................................................................................................................................................60% for 5 seconds Utility voltage pickup..........................................................................................................................................................................................................................80% Re-transfer time delay................................................................................................................................................................................................................15 seconds Engine cool-down timer.............................................................................................................................................................................................................60 seconds Exerciser ............................................................................................................................................................................................................. 12 minutes every 7 days* *Function of the controller The transfer switch can be operated manually without power applied. Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 23. 9) Attachment Data Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 24. Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 25. Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 26. Therightwaytoattachalmostanythingtometalroofs! S-5-PVKitandEdgeGrab™ 888-825-3432|www.S-5.com| S-5-PV Kit and EdgeGrab™ The concept of combining photovoltaic arrays with standing seam metal roofing is growing—and for good reasons. A standing seam metal roof has a life expectancy consistent with that of framed PV modules. A 30-year power source on a 40-year roof, along with zero-penetration technology, creates the most sustainable roof system available with alternative power generation, all without compromising the roof manufacturer's warranty! The new S-5-PV Kit boasts an important breakthrough in PV mounting technology. It is one of the first solar module mounting solutions in the industry to be listed to the new UL subject 2703, a standard that covers both bonding and mounting. Furthermore, the S-5!® Mounting Disk has gained an ETL Listing to UL 1703.* The S-5-PV Kit features a groundbreaking new stainless steel mounting disk with twelve nodes designed to ensure the module-to-module conductivity of anodized aluminum module frames. This means it automatically provides a ground path in the module frame. No lugs or wire required except to connect one string of modules to another and to ground the system. This connection detail represents installed electrical cost savings of $6-$12 per unit. In most cases, the savings in time and materials is sufficient to pay for the entire S-5-PV Kit and clamp setup. Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 27. Distributed byS-5!® Warning! Please use this product responsibly! Products are protected by multiple U.S. and foreign patents. Visit the website at www.S-5.com for complete information on patents and trademarks. For maximum holding strength, setscrews should be tensioned and re-tensioned as the seam material compresses. Clamp setscrew tension should be verified using a calibrated torque wrench between 160 and 180 inch pounds when used on 22ga steel, and between 130 and 150 inch pounds for all other metals and thinner gauges of steel. Consult the S-5! website at www.S-5.com for published data regarding holding strength. Copyright2015,MetalRoofInnovations,Ltd.S-5!productsarepatentprotected. S-5!aggressivelyprotectsitspatents,trademarks,andcopyrights.Version052115. The S-5-PV Kit is a revolutionary new solution to attach solar PV panels to standing seam metal roofs! R S-5-PV Kit (UL and ETL Listed) EdgeGrab™ (Not UL or ETL Listed) R 0.47 (12.00 mm) 1.50 (38.00 mm) Wire Zip Tie Slots Module Placement Bevel Guide Friction Reducing Coated Stainless Steel Universal PV Stud w/ M8 Integral Hex Nut 3.00 (76.00 mm) ETL Listed Mounting Disc Stud Height 2.67 (68.00 mm) † Hold Min/Max 1.18-1.89 (30.00-48.00 mm) 0.06 (1.50 mm) 0.48 (12.19 mm) 1.50 (38.10 mm) 0.84 (21.34 mm) 2.00 (50.80 mm) 1.00 (25.00 mm) 0.71 (18.00 mm) 0.87 (22.00 mm) Wire Management Hooks 1 2 3 The S-5-PV Kit is furnished with the hardware shown at right, excluding the attachment clamp, which is supplied separately. (When ProteaBracket™ is used in conjunction with the S-5-PV Kit, an additional nut is required during installation to secure the universal PV stud and mounting disk to ProteaBracket's slotted L-flange.) The S-5-PV Kit is compatible with most common metal roofing materials, including brass. The S-5!® EdgeGrab™ and S-5-PV Kit together accommodate PV frame thicknesses 30–48 mm (if EdgeGrab's serrated L-flange is positioned below the stud's hex nut) and 34–51 mm (if EdgeGrab's serrated L-flange is positioned above the stud's hex nut).† The embossed panel guide makes the module placement easier. The mounting disk is multi-directional and rails are not required. Four strategically placed under-disk hooks assist in wire management. The PV grab ears that hold the solar panel in place are broader to allow for ease of installation and precise module engagement. Accommodating module thicknesses between 30 and 51 mm, the S-5-PV Kit fits the majority of solar panels on the market. Using the S-5! mini clamps, it fits most standing seam metal roofs. When paired with other S-5! products, the S-5-PV Kit and EdgeGrab will work on most exposed-fastened and corrugated metal roofs. The standard grab is designed to fit field conditions (two adjacent panels), while the new EdgeGrab is designed specifically for end conditions. Wind dynamics are complex; thus, each system should be reviewed by a qualified licensed professional who understands wind effects on metal roof design and construction prior to purchase and installation. For more detailed information including specifications, installation instructions, and CAD drawings, visit www.S-5.com or your S-5-PV Kit distributor. The S-5-PV Kit continues to be the easiest, most cost-effective way to install solar panels directly to standing seam metal roofs, remaining the most popular choice worldwide. Please note: All measurements are rounded to the second decimal place. * Patents pending. Certain components featured in illustration may not be UL listed. Due to the variety of attachment needs, S-5-PV Kits are sold separately from S-5! mini clamps. The S-5-PV Kit fits only S-5! mini clamps, NOT standard clamps. Listed to UL subject 2703. ETL Listed to UL 1703.* Please Note: Dimensions of both the Universal PV Stud and the Mounting Disk are identical between these two illustrations. Please note: The assembly option in the diagram to the right illustrates he serrated L-flange positioned below the stud's hex nut. S-5! clamp not included. S-5! clamp not included. Missouri Sun Solar: Bergh Solar Project 49.585kW
  • 28. Missouri Sun Solar: Bergh Solar Project 49.585kW