Armstrong Monitoring Corporation Arenas
Hazards
Toxic Gas(es)
• Ammonia (NH3) refrigerant used to chill and create ice surface
• Carbon Monoxide (CO) from gasoline, propane, or natural gas powered vehicles
• Nitrogen Dioxide (NO2) from diesel powered vehicles
Combustible Gas
• Natural gas (CH4) or Propane (C3H8) used to power Ice Resurfacing machine
2
Armstrong Monitoring Corporation Arenas
• Refrigerant room must have a detector that actuates an alarm and
ventilation at a level no greater than the TLV-TWA
• The alarm shall annunciate visual and audible alarms inside the
machinery room, and at each entrance to the room
• Ability to activate ventilation fans from immediately outside the
mechanical room
• Alarms can only be acknowledged from inside the mechanical room
• Exhaust fans can only be shut off from inside the mechanical room
• Ability to shutdown any combustion processes (boilers, etc.) from
immediately outside the mechanical room
• Ventilation fans shall be on a separate electrical circuit
ASHRAE 15/CSA B52 General Code Requirements
3
Armstrong Monitoring Corporation Arenas
• A sensor for each chiller, specific to the refrigerant
• Electrochemical sensors are most commonly used for ammonia
• A central monitor to power the sensor(s) and provide ventilation and
alarm controls
• Monitor should be installed inside the mechanical room per code
• This facilitates wiring for required fan/control interlocks
• A module inside the mechanical room that can start/stop fans
• Can be a separate module or integrated into the controller (AMC-RAM-4X1)
• An alarm module at each entrance that can start fans
• Includes audible and visual alarms (AMC-RAM-4X2)
What to Use
4
Armstrong Monitoring Corporation Arenas
• A low alarm (typically 25ppm for NH3) should:
• Initiate ventilation
• Initiate audio/visual alarms
• Notify supervised area of a leak
• Shut down any combustion processes in the mechanical room (boilers)
• Instigate refrigerant leak procedures and/or corrective measures
• A high alarm (typically 35ppm for NH3) should:
• Shut down chiller to minimize refrigerant loss
• Initiate evacuation of personnel from the mechanical room
Recommended Sequence of Operation
5
Armstrong Monitoring Corporation Arenas
Single or Dual Channel Monitor
• Accepts up to 2 x 4-20mA Transmitters
• 110 VAC Power
• Rugged Steel Enclosure
• Dual 10A DPDT Alarm Relay
• Dedicated Latching Ventilation Relay
• User Selectable Minimum Run Timer
• Integral 85db Audio Alarm
• CSA Approved
AMC-1AREF
6
Armstrong Monitoring Corporation Arenas
AMC-1400 (4 Channel Analog Monitor)
• Accepts up to 4 x 4-20mA Transmitters
AMC-1800 (8 or 16 Channel Analog Monitor)
• Accepts 8/16 x 4-20mA Transmitters
AMC-1DB1-X-REF (Digital Monitor with BACnet IP/MSTP Interface)
• Accepts multiple 4-20mA Transmitters using Analog Input Modules
• 110 VAC Power
• Dedicated Latching Ventilation Relay
• User Selectable Minimum Run Timer
• Integral 85db Audio Alarm
• CSA/CSA USA Approved
Other Monitor Options
7
Armstrong Monitoring Corporation Arenas
Electrochemical NH3 Sensor/Transmitter
• Linear 4-20mA Output
• 12‐30 VDC, Optional 12‐24 VAC
• ABS Enclosure
• Operating Temperature: ‐20°C to 50°C (‐4°F to 122°F)
• 2 or 3-Wire Installation (twisted pair shielded)
• Operating Humidity: 15‐85% Non‐Condensing
• Optional Relay Contact: SPST 2A @ 30VDC Resistive
AMC-VersaTox
8
Armstrong Monitoring Corporation Arenas
What To Use – Arenas CO & NO2
For Carbon Monoxide & Nitrogen Dioxide analog
sensors we recommend:
• AMC-1228-28s for applications with NO2 only
• AMC-1228-20s for applications with CO only
• AMC-1222 for applications with CO and NO2
For Carbon Monoxide & Nitrogen Dioxide digital
sensors we recommend:
• AMC-400-CO
• AMC-400-NO2
9
Armstrong Monitoring Corporation Arenas
What To Use – Arenas Combustibles
For Propane or Methane detection we typically recommend:
• AMC-CSA-CAT Analog Transmitter
• AMC-DTR-CAT Digital Transmitter
10
Armstrong Monitoring Corporation Arenas
Remote Audio/Visual Alarms
• Available Concentration Display(s)
• 24VDC Power
• Weatherproof FRP Enclosure
• Integral 85db Audio Alarm
• Acknowledge Switch for Audio Alarm
• Configurations for Inside or Outside Mech. Room
• Variants with Fan Start or Fan Start/Stop
AMC-RAM-4
11
Armstrong Monitoring Corporation Arenas
Inside Mechanical Room
Outside Mechanical Room
AMC-RAM-4 Variants
12
Armstrong Monitoring Corporation Arenas

More Related Content

Similar to Arenas 2021 08 31.pptx

Monicon 4 channel datasheet
Monicon 4 channel datasheetMonicon 4 channel datasheet
Monicon 4 channel datasheet
a1-cbiss
 
4. temperature measurement in the modified claus sulfur reactor - d. ducharm...
4. temperature measurement in the modified claus sulfur reactor  - d. ducharm...4. temperature measurement in the modified claus sulfur reactor  - d. ducharm...
4. temperature measurement in the modified claus sulfur reactor - d. ducharm...
Iman Akbari
 
AODesign&Protection_2015_noNDA
AODesign&Protection_2015_noNDAAODesign&Protection_2015_noNDA
AODesign&Protection_2015_noNDA
Kevin Duke
 
Monicon s500 l ir ndir gas detector
Monicon s500 l ir ndir gas detectorMonicon s500 l ir ndir gas detector
Monicon s500 l ir ndir gas detector
a1-cbiss
 

Similar to Arenas 2021 08 31.pptx (20)

Monicon 4 channel datasheet
Monicon 4 channel datasheetMonicon 4 channel datasheet
Monicon 4 channel datasheet
 
MRU SWG 100 Fixed Biogas Analyzer
MRU SWG 100 Fixed Biogas Analyzer MRU SWG 100 Fixed Biogas Analyzer
MRU SWG 100 Fixed Biogas Analyzer
 
Advanced Control System.ppt
Advanced Control System.pptAdvanced Control System.ppt
Advanced Control System.ppt
 
Advanced Control System.ppt
Advanced Control System.pptAdvanced Control System.ppt
Advanced Control System.ppt
 
Alco general presentation
Alco general presentationAlco general presentation
Alco general presentation
 
DMA Direct Mercury Analyzer
DMA  Direct Mercury AnalyzerDMA  Direct Mercury Analyzer
DMA Direct Mercury Analyzer
 
Vapour pressure-model-1354 atac
Vapour pressure-model-1354 atacVapour pressure-model-1354 atac
Vapour pressure-model-1354 atac
 
Microtrans differential pressure and airflow signal processor
Microtrans differential  pressure and airflow signal processorMicrotrans differential  pressure and airflow signal processor
Microtrans differential pressure and airflow signal processor
 
4. temperature measurement in the modified claus sulfur reactor - d. ducharm...
4. temperature measurement in the modified claus sulfur reactor  - d. ducharm...4. temperature measurement in the modified claus sulfur reactor  - d. ducharm...
4. temperature measurement in the modified claus sulfur reactor - d. ducharm...
 
KEMET EMC Filters
KEMET EMC FiltersKEMET EMC Filters
KEMET EMC Filters
 
C175 16 data sheets epd0105-a
C175 16 data sheets epd0105-aC175 16 data sheets epd0105-a
C175 16 data sheets epd0105-a
 
AODesign&Protection_2015_noNDA
AODesign&Protection_2015_noNDAAODesign&Protection_2015_noNDA
AODesign&Protection_2015_noNDA
 
Fixed installation industrial gas monitors
Fixed installation industrial gas monitorsFixed installation industrial gas monitors
Fixed installation industrial gas monitors
 
In Situ Oxygen Transmitter For Combustion Monitoring
In Situ Oxygen Transmitter For Combustion MonitoringIn Situ Oxygen Transmitter For Combustion Monitoring
In Situ Oxygen Transmitter For Combustion Monitoring
 
1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt
 
Alternative Fuels Workshop & Wisconsin Smart Fleet Recognition Program - Sier...
Alternative Fuels Workshop & Wisconsin Smart Fleet Recognition Program - Sier...Alternative Fuels Workshop & Wisconsin Smart Fleet Recognition Program - Sier...
Alternative Fuels Workshop & Wisconsin Smart Fleet Recognition Program - Sier...
 
Macnaught MX Series of Oval Gear Flow Meters
Macnaught MX Series of Oval Gear Flow MetersMacnaught MX Series of Oval Gear Flow Meters
Macnaught MX Series of Oval Gear Flow Meters
 
Safety Requirement for Rigs.pptx
Safety Requirement for Rigs.pptxSafety Requirement for Rigs.pptx
Safety Requirement for Rigs.pptx
 
Orto Alresa series_Digtor_22_C_ENG.pdf
Orto Alresa series_Digtor_22_C_ENG.pdfOrto Alresa series_Digtor_22_C_ENG.pdf
Orto Alresa series_Digtor_22_C_ENG.pdf
 
Monicon s500 l ir ndir gas detector
Monicon s500 l ir ndir gas detectorMonicon s500 l ir ndir gas detector
Monicon s500 l ir ndir gas detector
 

Recently uploaded

一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
kywwoyk
 
一比一原版UVM毕业证佛蒙特大学毕业证成绩单如何办理
一比一原版UVM毕业证佛蒙特大学毕业证成绩单如何办理一比一原版UVM毕业证佛蒙特大学毕业证成绩单如何办理
一比一原版UVM毕业证佛蒙特大学毕业证成绩单如何办理
kywwoyk
 
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
eemet
 
NO1 Uk Amil Baba In Lahore Kala Jadu In Lahore Best Amil In Lahore Amil In La...
NO1 Uk Amil Baba In Lahore Kala Jadu In Lahore Best Amil In Lahore Amil In La...NO1 Uk Amil Baba In Lahore Kala Jadu In Lahore Best Amil In Lahore Amil In La...
NO1 Uk Amil Baba In Lahore Kala Jadu In Lahore Best Amil In Lahore Amil In La...
Amil baba
 

Recently uploaded (6)

F5 LTM TROUBLESHOOTING Guide latest.pptx
F5 LTM TROUBLESHOOTING Guide latest.pptxF5 LTM TROUBLESHOOTING Guide latest.pptx
F5 LTM TROUBLESHOOTING Guide latest.pptx
 
Memory compiler tutorial – TSMC 40nm technology
Memory compiler tutorial – TSMC 40nm technologyMemory compiler tutorial – TSMC 40nm technology
Memory compiler tutorial – TSMC 40nm technology
 
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
 
一比一原版UVM毕业证佛蒙特大学毕业证成绩单如何办理
一比一原版UVM毕业证佛蒙特大学毕业证成绩单如何办理一比一原版UVM毕业证佛蒙特大学毕业证成绩单如何办理
一比一原版UVM毕业证佛蒙特大学毕业证成绩单如何办理
 
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
一比一原版SDSU毕业证圣地亚哥州立大学毕业证成绩单如何办理
 
NO1 Uk Amil Baba In Lahore Kala Jadu In Lahore Best Amil In Lahore Amil In La...
NO1 Uk Amil Baba In Lahore Kala Jadu In Lahore Best Amil In Lahore Amil In La...NO1 Uk Amil Baba In Lahore Kala Jadu In Lahore Best Amil In Lahore Amil In La...
NO1 Uk Amil Baba In Lahore Kala Jadu In Lahore Best Amil In Lahore Amil In La...
 

Arenas 2021 08 31.pptx

  • 2. Hazards Toxic Gas(es) • Ammonia (NH3) refrigerant used to chill and create ice surface • Carbon Monoxide (CO) from gasoline, propane, or natural gas powered vehicles • Nitrogen Dioxide (NO2) from diesel powered vehicles Combustible Gas • Natural gas (CH4) or Propane (C3H8) used to power Ice Resurfacing machine 2 Armstrong Monitoring Corporation Arenas
  • 3. • Refrigerant room must have a detector that actuates an alarm and ventilation at a level no greater than the TLV-TWA • The alarm shall annunciate visual and audible alarms inside the machinery room, and at each entrance to the room • Ability to activate ventilation fans from immediately outside the mechanical room • Alarms can only be acknowledged from inside the mechanical room • Exhaust fans can only be shut off from inside the mechanical room • Ability to shutdown any combustion processes (boilers, etc.) from immediately outside the mechanical room • Ventilation fans shall be on a separate electrical circuit ASHRAE 15/CSA B52 General Code Requirements 3 Armstrong Monitoring Corporation Arenas
  • 4. • A sensor for each chiller, specific to the refrigerant • Electrochemical sensors are most commonly used for ammonia • A central monitor to power the sensor(s) and provide ventilation and alarm controls • Monitor should be installed inside the mechanical room per code • This facilitates wiring for required fan/control interlocks • A module inside the mechanical room that can start/stop fans • Can be a separate module or integrated into the controller (AMC-RAM-4X1) • An alarm module at each entrance that can start fans • Includes audible and visual alarms (AMC-RAM-4X2) What to Use 4 Armstrong Monitoring Corporation Arenas
  • 5. • A low alarm (typically 25ppm for NH3) should: • Initiate ventilation • Initiate audio/visual alarms • Notify supervised area of a leak • Shut down any combustion processes in the mechanical room (boilers) • Instigate refrigerant leak procedures and/or corrective measures • A high alarm (typically 35ppm for NH3) should: • Shut down chiller to minimize refrigerant loss • Initiate evacuation of personnel from the mechanical room Recommended Sequence of Operation 5 Armstrong Monitoring Corporation Arenas
  • 6. Single or Dual Channel Monitor • Accepts up to 2 x 4-20mA Transmitters • 110 VAC Power • Rugged Steel Enclosure • Dual 10A DPDT Alarm Relay • Dedicated Latching Ventilation Relay • User Selectable Minimum Run Timer • Integral 85db Audio Alarm • CSA Approved AMC-1AREF 6 Armstrong Monitoring Corporation Arenas
  • 7. AMC-1400 (4 Channel Analog Monitor) • Accepts up to 4 x 4-20mA Transmitters AMC-1800 (8 or 16 Channel Analog Monitor) • Accepts 8/16 x 4-20mA Transmitters AMC-1DB1-X-REF (Digital Monitor with BACnet IP/MSTP Interface) • Accepts multiple 4-20mA Transmitters using Analog Input Modules • 110 VAC Power • Dedicated Latching Ventilation Relay • User Selectable Minimum Run Timer • Integral 85db Audio Alarm • CSA/CSA USA Approved Other Monitor Options 7 Armstrong Monitoring Corporation Arenas
  • 8. Electrochemical NH3 Sensor/Transmitter • Linear 4-20mA Output • 12‐30 VDC, Optional 12‐24 VAC • ABS Enclosure • Operating Temperature: ‐20°C to 50°C (‐4°F to 122°F) • 2 or 3-Wire Installation (twisted pair shielded) • Operating Humidity: 15‐85% Non‐Condensing • Optional Relay Contact: SPST 2A @ 30VDC Resistive AMC-VersaTox 8 Armstrong Monitoring Corporation Arenas
  • 9. What To Use – Arenas CO & NO2 For Carbon Monoxide & Nitrogen Dioxide analog sensors we recommend: • AMC-1228-28s for applications with NO2 only • AMC-1228-20s for applications with CO only • AMC-1222 for applications with CO and NO2 For Carbon Monoxide & Nitrogen Dioxide digital sensors we recommend: • AMC-400-CO • AMC-400-NO2 9 Armstrong Monitoring Corporation Arenas
  • 10. What To Use – Arenas Combustibles For Propane or Methane detection we typically recommend: • AMC-CSA-CAT Analog Transmitter • AMC-DTR-CAT Digital Transmitter 10 Armstrong Monitoring Corporation Arenas
  • 11. Remote Audio/Visual Alarms • Available Concentration Display(s) • 24VDC Power • Weatherproof FRP Enclosure • Integral 85db Audio Alarm • Acknowledge Switch for Audio Alarm • Configurations for Inside or Outside Mech. Room • Variants with Fan Start or Fan Start/Stop AMC-RAM-4 11 Armstrong Monitoring Corporation Arenas
  • 12. Inside Mechanical Room Outside Mechanical Room AMC-RAM-4 Variants 12 Armstrong Monitoring Corporation Arenas