This document discusses busbar protection and differential protection of busbars. It begins by introducing busbars and explaining why they require protection. Differential protection is identified as the best method since the ends of the busbar are physically close. The document then discusses several key aspects of differential protection for busbars including:
- Correct selection of CT ratios to avoid spill currents during normal operation
- Issues caused by CT saturation during external faults that can lead to maloperation
- Minimum internal fault levels that can be detected
- Use of high impedance schemes and stabilizing resistances to improve stability
- Calculation of stability ratios for schemes
- Use of supervisory relays to detect issues like open CT circuits
Need of FACTS devices, classification of FACTS devices, operating principle of SVC, V-I characteristic of SVC, advantage of slope in V-I characteristic, SVC applications for transient and voltage stability improvement, mitigation of SSR, advantages of TCSC, different mode of operation of TCSC, different modeling concepts of TCSC, Operating principle of STATCOM,TCSC, SVC and their applications for power system performance improvement, Power flow solution with SVC, TCSC.
Saudi Arabia stands as a titan in the global energy landscape, renowned for its abundant oil and gas resources. It's the largest exporter of petroleum and holds some of the world's most significant reserves. Let's delve into the top 10 oil and gas projects shaping Saudi Arabia's energy future in 2024.
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxR&R Consult
CFD analysis is incredibly effective at solving mysteries and improving the performance of complex systems!
Here's a great example: At a large natural gas-fired power plant, where they use waste heat to generate steam and energy, they were puzzled that their boiler wasn't producing as much steam as expected.
R&R and Tetra Engineering Group Inc. were asked to solve the issue with reduced steam production.
An inspection had shown that a significant amount of hot flue gas was bypassing the boiler tubes, where the heat was supposed to be transferred.
R&R Consult conducted a CFD analysis, which revealed that 6.3% of the flue gas was bypassing the boiler tubes without transferring heat. The analysis also showed that the flue gas was instead being directed along the sides of the boiler and between the modules that were supposed to capture the heat. This was the cause of the reduced performance.
Based on our results, Tetra Engineering installed covering plates to reduce the bypass flow. This improved the boiler's performance and increased electricity production.
It is always satisfying when we can help solve complex challenges like this. Do your systems also need a check-up or optimization? Give us a call!
Work done in cooperation with James Malloy and David Moelling from Tetra Engineering.
More examples of our work https://www.r-r-consult.dk/en/cases-en/
Need of FACTS devices, classification of FACTS devices, operating principle of SVC, V-I characteristic of SVC, advantage of slope in V-I characteristic, SVC applications for transient and voltage stability improvement, mitigation of SSR, advantages of TCSC, different mode of operation of TCSC, different modeling concepts of TCSC, Operating principle of STATCOM,TCSC, SVC and their applications for power system performance improvement, Power flow solution with SVC, TCSC.
Saudi Arabia stands as a titan in the global energy landscape, renowned for its abundant oil and gas resources. It's the largest exporter of petroleum and holds some of the world's most significant reserves. Let's delve into the top 10 oil and gas projects shaping Saudi Arabia's energy future in 2024.
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxR&R Consult
CFD analysis is incredibly effective at solving mysteries and improving the performance of complex systems!
Here's a great example: At a large natural gas-fired power plant, where they use waste heat to generate steam and energy, they were puzzled that their boiler wasn't producing as much steam as expected.
R&R and Tetra Engineering Group Inc. were asked to solve the issue with reduced steam production.
An inspection had shown that a significant amount of hot flue gas was bypassing the boiler tubes, where the heat was supposed to be transferred.
R&R Consult conducted a CFD analysis, which revealed that 6.3% of the flue gas was bypassing the boiler tubes without transferring heat. The analysis also showed that the flue gas was instead being directed along the sides of the boiler and between the modules that were supposed to capture the heat. This was the cause of the reduced performance.
Based on our results, Tetra Engineering installed covering plates to reduce the bypass flow. This improved the boiler's performance and increased electricity production.
It is always satisfying when we can help solve complex challenges like this. Do your systems also need a check-up or optimization? Give us a call!
Work done in cooperation with James Malloy and David Moelling from Tetra Engineering.
More examples of our work https://www.r-r-consult.dk/en/cases-en/
Overview of the fundamental roles in Hydropower generation and the components involved in wider Electrical Engineering.
This paper presents the design and construction of hydroelectric dams from the hydrologist’s survey of the valley before construction, all aspects and involved disciplines, fluid dynamics, structural engineering, generation and mains frequency regulation to the very transmission of power through the network in the United Kingdom.
Author: Robbie Edward Sayers
Collaborators and co editors: Charlie Sims and Connor Healey.
(C) 2024 Robbie E. Sayers
Explore the innovative world of trenchless pipe repair with our comprehensive guide, "The Benefits and Techniques of Trenchless Pipe Repair." This document delves into the modern methods of repairing underground pipes without the need for extensive excavation, highlighting the numerous advantages and the latest techniques used in the industry.
Learn about the cost savings, reduced environmental impact, and minimal disruption associated with trenchless technology. Discover detailed explanations of popular techniques such as pipe bursting, cured-in-place pipe (CIPP) lining, and directional drilling. Understand how these methods can be applied to various types of infrastructure, from residential plumbing to large-scale municipal systems.
Ideal for homeowners, contractors, engineers, and anyone interested in modern plumbing solutions, this guide provides valuable insights into why trenchless pipe repair is becoming the preferred choice for pipe rehabilitation. Stay informed about the latest advancements and best practices in the field.
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...Amil Baba Dawood bangali
Contact with Dawood Bhai Just call on +92322-6382012 and we'll help you. We'll solve all your problems within 12 to 24 hours and with 101% guarantee and with astrology systematic. If you want to take any personal or professional advice then also you can call us on +92322-6382012 , ONLINE LOVE PROBLEM & Other all types of Daily Life Problem's.Then CALL or WHATSAPP us on +92322-6382012 and Get all these problems solutions here by Amil Baba DAWOOD BANGALI
#vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore#blackmagicformarriage #aamilbaba #kalajadu #kalailam #taweez #wazifaexpert #jadumantar #vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore #blackmagicforlove #blackmagicformarriage #aamilbaba #kalajadu #kalailam #taweez #wazifaexpert #jadumantar #vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore #Amilbabainuk #amilbabainspain #amilbabaindubai #Amilbabainnorway #amilbabainkrachi #amilbabainlahore #amilbabaingujranwalan #amilbabainislamabad
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)MdTanvirMahtab2
This presentation is about the working procedure of Shahjalal Fertilizer Company Limited (SFCL). A Govt. owned Company of Bangladesh Chemical Industries Corporation under Ministry of Industries.
2. 5.1 Introduction
• The word bus is derived from the Latin
word omnibus which means common for
all.
• Busbars are the nerve-centres of the power
system where various circuits are
connected together.
• These are the nodes of the electrical circuit.
• Under the normal power flow condition the
sum of incoming currents is equal to the
sum of outgoing currents, i.e
3. • Thus, there is a large concentration of short-circuit capacity at the busbars.
A fault on the busbar, though rare, causes enormous damage.
• When protective relays operate,to isolate the busbar from the system,
there is a large disruption to- the loads.
• The causes of faults experienced on busbars are:
weakening of insulation because of
Ageing
corrosion beccause of salty water
breakdown of insulation because of over-voltages
foreign objects, and so on.
• For example, rodents, lizards and snakes are known to have caused busbar
faults in remote unmanned substations.
4. • Because of the low probability of busbar faults, for many years, it was
considered unnecessary to provide explicit protection to busbars.
• It should be noted that busbars fall in the overlap between protective
zones on either side, so they do get back-up protection.
• Hence, Protection engineers hesitated from providing exclusive
busbar protection.
• However, as the system voltage went on increasing and short-circuit
capacities went on building up, it was no longer advisable to leave
busbars unprotected on a primary basis.
5. • What form of protection is best suited for busbars? A little reflection
will convince the reader that differential protection will suit this
situation best because the ends (terminals) of the system are
physically near to each other.
• Thus, by installing CTs on the two sides, we can simply compare the
current entering the busbar with that leaving it.
• Any discrepancy between the two will immediately signal an internal
fault.
6. 5.2 Differential Protection of Busbars
5-2.1 Selection of CT Ratios in Case of
Busbar Protection: Wrong Method
• The currents shown are for normal load flow.
• The CT ratios on the basis of maximum primary load
current seen by each CT.
• Thus, the CTs on the incoming feeder will have CT ratios
of 1000/1 A and 2000/1 A, respectively. The CT on the
outgoing feeder will have a CT ratio of 3000/1 A.
• However, with this choice of CT ratios, it can be seen
from the diagram that there is a spill current even during
the healthy condition.
• Thus, the method of selecting CT ratio on the basis of
maximum primary current seen by the feeder is not
correct.
7. 5.2.2 Selection of CT Ratios in Case of Busbar Protection: Correct
Method
• the CT ratios of all the CTs are equal and are based on
the primary current of that feeder which carries the
maximum current.
• Thus, all the CT ratios are 3000/1 A. Therefore, as
can be seen from the figure, there is no spill current
through the OC relay connected in the spill path and
the scheme remains stable.
8. 5.3 External and Internal Fault
• In the preceding discussion, we have assumed that the CTs are ideal.
When the CT primary current, or the burden on it, is within its design
limits, the CT can indeed be assumed to be more or less ideal.
• However, as the primary current exceeds the design value or the CT
burden (output of CT in VA) becomes excessive, the CT no longer
behaves in an ideal fashion.
• Then on-ideal behaviour of the CT has very serious implications for
the protective schemes.
9. • Figure 5.4 shows currents during an external
fault beyond CTc. It can be seen that
• CTc, the CT on the faulted feeder, has to carry
the sum of all currents fed into the fault by
various feeders.
• Therefore, CTc sees a substantially larger
primary current than either CTA or CTB.
• In all likelihood, CTc will therefore become
saturated.
• We can, therefore, no longer assume that CTc
will faithfully transform the fault current.
• For the sake of illustration, we have assumed
that the secondary current of CTc is only 4 A
instead of 10 A.
• It can be seen that this results into a spill
current of 6 A, causing the scheme to
maloperate, i.e. lose stability on external
fault.
10. • In the worst case scenario, CTA and CTB continue to transform
faithfully as per their nameplate CT ratio but CTc, which carries the
total fault current, gets completely saturated.
• This clearly indicates the occurrence of an imbalance in transformed
secondary currents, resulting in substantial spill current.
• This situation most likely will cause the scheme to operate.
• Operation of a differential scheme under external faults is, therefore,
clearly a case of maloperation
11. • Interestingly, as the fault shifts by a
small distance to the left and
becomes an internal fault, still
drawing the same current, the
situation dramatically changes as far
as CTc is concerned.
• This is depicted in Figure 5.5, wherein
it can be seen that CTc now does not
carry any fault current (assuming a
single-end-fed system with source on
left-hand side).
• Since CTA and CTB are not carrying
excessive primary currents, they
transform the current without too
much error.
• There is thus a spill current in the
spill path and the scheme operates as
expected.
The maloperation of the busbar differential scheme on external faults is caused due to non-ideal
behaviour of a CT carrying excessive primary current.
12. 5.4 Actual Behaviour of a Protective CT
• At low values of primary current 𝐼𝑝and therefore 𝑰𝒔, voltage 𝑬𝒔 to be induced by the secondary
winding, which is approximately equal to (𝒁𝒃𝒖𝒓𝒅𝒆𝒏𝑰𝒔) , is quite low. The working flux in the CT,
which is equal to (𝑬𝒔/4.44 fN) is also very low.
• The magnetizing current requirement is, therefore, correspondingly low. Thus, the secondary
current 𝑰𝒔 is substantially equal to𝑰𝒑/N.
• If the primary current increases, initially, the secondary current also increases proportionately.
This causes the secondary induced voltage to increase as well.
• Increased secondary voltage can only be met with an increase in the working flux of the CT.
• AS the flux increases, the transformer needs to draw a higher magnetizing current.
• However, because of the nonlinear nature of the B-H curve for the CT, as the knee of the
excitation characteristics is passed, any further increase in flux demand causes a
disproportionately large increase in the magnetizing current requirement of the CT.
• It may also be noted that 𝐼0, is no longer sinusoidal and its waveform has a prominent peak
13.
14. • As the primary current goes on increasing, a
stage comes when the magnetizing current
requirement is so large that almost all the
transformed current is taken up by the CT for
the sole purpose of magnetization, with the
result that there is hardly any current available
for the burden.
• When this occurs, we say that the CT is
completely saturated.
• The secondary induced voltage and burden
current waveforms of a CT, operating in
saturation, are highly distorted. They, in fact,
consist only of sharp pulses near the zero-
crossings of the primary current.
• Where it can be seen that in order to reach the
peak of the sinusoidal flux waveform, the CT is
driven deep into saturation.
• Due to flatness of the excitation curve in this
region, a very large amount of exciting current is
demanded by the CT The waveform of the
exciting current becomes distorted and is, in
fact, very peaky in nature.
15. 5.5 Circuit Model of Saturated CT
• It can be seen that the magnetizing
branch is replaced with a short circuit to
signify the fact that the magnetizing
branch is taking up all the secondary
current and none is available to the
burden.
• Thus, the circuit model consists of a
current source of value (𝐼𝑝/𝑁) feeding
into a short circuit through 𝑅𝑝
′
and 𝑋𝑝
′
• The connections to the outside world
are available through 𝑅𝑠 and 𝑋𝑠.
16. 5.6 External Fault with One CT Saturated:
Need for High Impedance Busbar Protection
• Consider the external fault of 30,000 A, on the busbar shown in Figure 5.4.
• Assuming that CTc gets completely saturated while CTA and CTB continue
to operate normally, Figure 5.10 shows the equivalent circuit as seen from
the CT secondaries. Note that for simplicity, all leakage reactances have
been neglected.
• It can be seen from Figure 5.10 that currents [(𝐼𝐴/N) - 𝐼0𝐴] and [(𝐼𝐵/N) - 𝐼0𝐵]
sum up and the resultant current has two parallel paths available.
• One path is through the over-current relay and the other is through (𝑹𝒔 +
𝑹𝑳) via the short representing the saturated CT magnetizing branch. Thus,
the part of fault current will flow through the over-current relay, causing it
to trip, even though the fault is external. Hence, the OC relay needs to be
restrained from tripping on external faults (with one CT completeiy
saturated).
17. We can easily accomplish this by connecting a
high resistance (known as the stabilizing
resistance) in series with the OC relay.
The stabilizing resistance should be of such a
value that under the worst case of maximum
external fault and full saturation of one CT, the
current through the OC relay is less than its
pick-up value.
Such schemes are known as high impedance
busbar differential schemes.
18. The Value of the Stabilizing Resistance
• let the pick-up value of the OC relay be 𝐼𝑝𝑢 and the value of the resistance associated with the
saturated CT be (𝑅𝑠 + 𝑅𝐿).
• The impedance of the secondary circuit of the saturated CT be represented by 𝑍𝑠 = (𝑅𝑠 + 𝑅𝐿).
• The procedure is as follows: First consider that the 0C relay is not connected and find out the
voltage that will be developed across it, let it be 𝑉𝑠𝑒𝑡.
• Now, the stabilizing resistance should be of such a value that with the relay connected, the
current through the relay should be less than the pick-up value of the relay.
• Therefore, we have the following relationship:
• Voltage across the over current relay in series with the stabilizing resistor
• In order that under this condition, the current through the relay be less than or equal to its pick-
up value 𝐼𝑝𝑢,we have
19.
20. 5.7 Minimum Internal Fault That Can Be Detected
by the High Impedance Busbar Differential Scheme
• The equivalent CT secondary circuit during internal fault is shown in Figure 5 .11.
It is assumed that none of the CTs is saturated. The high impedance scheme has a
pick-up of 𝑰𝒑𝒖 ,a stabilizing resistance of 𝑹𝒔𝒕𝒂𝒃 and, therefore, needs a minimum
voltage of 𝑽𝒔𝒆𝒕 to be developed across the series combination of the stabilizing
resistance and the OC relay
• Thus, the minimum fault current on the CT secondary side, that can develop the
required voltage 𝑽𝒔𝒆𝒕will be given by
21.
22. • Figure 5.11 shows that during internal fault, all the CT secondaries
feed into the spill path.
• Therefore, the current for a minimum internal fault in the high
impedance spill path will be
𝐼𝑓,𝑚𝑖𝑛,𝑠𝑒𝑐 = 𝐼𝑝𝑢 =
𝐼𝐴
𝑁
− 𝐼0𝐴 +
𝐼𝐵
𝑁
− 𝐼0𝐵 +
𝐼𝐶
𝑁
− 𝐼0𝐶
=
𝐼𝐴
𝑁
+
𝐼𝐵
𝑁
+
𝐼𝐶
𝑁
- 𝐼0𝐴 + 𝐼0𝐵 + 𝐼0𝐶
=
𝐼𝐴+𝐼𝐵+𝐼𝐶
𝑁
- 𝐼0𝐴 + 𝐼0𝐵 + 𝐼0𝐶
=
𝐼𝑓,𝑖𝑛𝑡,𝑚𝑖𝑛,𝑝𝑟𝑖
𝑁
− 3𝐼0
23. • Assuming 𝐼0𝐴 = 𝐼0𝐵 = 𝐼0𝐶=𝐼0, (i.e. all the CT magnetizing currents to
be equal) and multiplying both sides by N, we get
𝑁𝐼𝑝𝑢=𝐼𝑓,𝑖𝑛𝑡,𝑚𝑖𝑛,𝑝𝑟𝑖 − 3𝑁𝐼0
or
𝐼𝑓,𝑖𝑛𝑡,𝑚𝑖𝑛,𝑝𝑟𝑖=N 𝐼𝑝𝑢 + 3𝐼0 (with 3 feeders terminating on the bus)
• For the general case of n feeders terminating on the busbar, the
minimum internal fault current that can be detected by the high
impedance busbar differential scheme will be given by
𝑰𝒇,𝒊𝒏𝒕𝒆𝒓𝒏𝒂𝒍,𝒎𝒊𝒏𝒊𝒎𝒖𝒎,𝒑𝒓𝒊𝒎𝒂𝒓𝒚=N 𝑰𝒑𝒖 + 𝟑𝑰𝟎
24. 5.8 Stability Ratio of High Impedance Busbar
Differential Scheme
• The stability ratio S of the high impedance busbar differential scheme
is defined as the ratio of maximum external fault current for which
the scheme remains stable to the minimum internal fault current for
which it operates.
𝑺 =
𝑰𝒇,𝒆𝒙𝒕𝒆𝒓𝒏𝒂𝒍,𝒎𝒂𝒙𝒊𝒎𝒖𝒎
𝑰𝒇,𝒊𝒏𝒕𝒓𝒏𝒂𝒍,𝒎𝒊𝒏𝒊𝒎𝒖𝒎
• The stability ratio is a dimensionless quantity. The higher the value of
stability ratio S, the better is the quality of differential protection.
Stability ratios of a few tens are common in EHV busbar differential
schemes.
25. 5.9 Supervisory Relay
• In the busbar differential scheme, it may, at times, happen that a particular CT
secondary gets open circuited.
• At other times there may be a break in the pilot wire coming from a particular CT
secondary winding.
• Thus, even though there may be no internal fault on the busbar, an imbalance is
created on the secondary side, causing a spill current which is equal to the
current that was being contributed by the particular CT before its secondary got
open circuited.
• Such types of events are, no doubt, dangerous.
• The current contribution of an individual CT would be much less than the pick-up
value of the OC relay and the scheme will remain insensitive to such CT open-
circuit faults.
• All the same, we need to develop a mechanism to detect such faults so as to raise
an alarm to alert the operating personnel
26. • The highest spill current, in case of loss of one CT secondary current,
will be caused in case of the CT which carries the maximum load
current, 𝐼𝐿,𝑚𝑎𝑥.
• Figure 5.12 shows the normal load being supplied by the feeders.
There is a break in the pilot wire coming from secondary of CTc.
• This will cause a spill current equal to the current that was being
contributed by CTc before the break occurred, as shown in Figure
5.12. Thus, the spill current = Ic/N. This spill current will develop a
voltage across the series combination of the stabilizing resistance and
OC relay, which can be sensed by a sensitive over-voltage relay known
as supervisory relay.
27. The supervisory relay is set to pick-up at:
𝑉supervisory =
𝐼𝐿,𝑚𝑎𝑥
𝑁
𝑅𝑠𝑡𝑎𝑏𝑖𝑙𝑖𝑧𝑖𝑛𝑔 + 𝑅𝑜𝑐,𝑟𝑒𝑙𝑎𝑦
The above discussion neglects the magnetizing
currents of the CTs.
The setting of the supervisory relay 𝑉supervisory
will be much less than the setting of the high
impedance differential relay 𝑉set.