Fan	
  Testing	
  at	
  Malabar	
  Odor	
  Control	
  Site,	
  Sydney	
  
	
  
	
  
Roy	
  Singh	
  
	
  
7th
	
  February,	
  2011	
  
	
  
Page 2 of 2
INTRODUCTION
The purpose of this report is to capture the knowledge, skills and lessons learnt when fan
tests were done to determine its performance at the Sydney Water Odour Control Site in
Malabar, Sydney. Often the data provided by the manufactures regarding the
performance can be misleading. This could be due to the way the test was done by the
supplier or the data provided was obsolete. Tests were required to be carried out to
determine the base line before and after the refurbishment and also to determine if the
current fan or a pump can be used when subjected to elevated duty points.
There are situations where the test rig set up in house is not possible due to the size of the
system. A good example is the Malabar Odour Control Project in Sydney. The fan
assemblies were just too large for a temporary test rig to be set up, however, tests were
carried out with the fans in its installed arrangement and the testing method applied,
provided results which were comparable with the factory data and decisions could be
made with high level of confidence.
It is also important to understand the balancing theory of rotating discs so that the balance
class of the impeller of a blower or a pump can be determined correctly. For example an
impellor balanced in a balancing machine on a short spindle due to machine size
constrains, will not maintain the same balance class if installed on a longer shaft where
the distance between the locating bearings and the impeller is greater. The moment acting
in such installed situation will be greater, proportional to the distance apart.
This report describes some basic theory on pumps, methods to measure flow and
pressures, basic theory on balancing of rotating discs and lessons learnt from Malabar
Odour project while conducting fan testing.
For further reading on pipe losses and balancing theory, literature can be obtained from
books mentioned in the Reference Section of this report.
Page 3 of 3
CHAPTER 1
FAN AND SYSTEM CHARACTERISTICS
1.1 Pressure Drop in Pipes (system resistance)
The term system resistance (graphically shown as system curve) is the sum of pressure
losses in a system of pipe work which transports fluid from point 1 to point 2. The
resistance is a function of the configuration of pipes and the fittings used such as elbows,
valves etc. and pipe elevations.
In modeling steady flow for pipe networks, normally the energy form of the Bernoulli’s
equation is used,
where subscripts 1 and 2 are for upstream and downstream locations as shown in Figure
1, P is the pressure, f is the friction factor, L is the length of the pipe, D is the diameter of
the pipe, and K is the local energy loss factor, is the density of the fluid, g is the
gravitation acceleration, z1 and z2 are the heights, and V1 and V2 are the velocities. In this
form the energy equation relates the pressure, velocity and elevation at different points of
the flow, with the frictional and local losses.
In Equation (1.0), the first summation is the energy loss due to friction in pipes of
different diameter and length and the second is the energy losses due to local disturbances
to the flow. These could include local disturbances such as valves, elbows, and sudden
constrictions and enlargements.
(1.0)
Page 4 of 4
Z 1
Z 2
1
2
Figure 1 Flow in pipe from point 1 to point 2
Page 5 of 5
The head loss due to friction can be expressed by Darcy’s equation,
where f is the friction factor. Different equations exist for friction factor f, depending on
whether the flow is laminar or turbulent. For laminar flow in a smooth pipe, where Re is
≤ 2000, a commonly used equation is
where
here is the dynamic viscosity and Re is the Reynolds Number.
For turbulent flow where Re is > 2000, and the friction factor is dependent on relative
roughness and Reynolds number, Colebrook equation can be used (Australian Pump
Technical Handbook, fourth Edition)
Here is the absolute roughness (mm)
(2.7)
(1.1)
(1.3)
(1.2)
(1.4)
Page 6 of 6
1.2 Fan Characteristics (Fan Curve)
Fan curve is a performance curve for a particular fan under specific set conditions. A fan
curve is generated by measuring and plotting the volume discharge rate (m3
/s) versus the
static pressure developed at that setting.
The static pressure and flow can be measured by using a Pitot tube and a manometer.
There are a number of advantages using a Pitot tube such as;
• An average velocity can be determined hence an average flowrate can be
calculated by taking reading across a pipe or a duct. This is necessary when
working with large cross section areas of pipe and ducts.
• A Pitot tube can be inserted in a duct by drilling a small diameter hole, usually
just big enough for the Pitot tube to pass through. This eliminates the need to
change duct sections to install flow meters when flowrate measurements are
required.
• A Pitot tube usually will not interfere or impede the flow regimes.
1.3 Pitot Tube
A Pitot tube, when aligned with the flow, measures the local velocity by means of
pressure difference. It has side holes to measure the static pressure Ps in the moving
stream and a hole in the front to measure the stagnation pressure Po, separately.
The difference in the pressures (Ps - Po) measured by the manometer and the velocity (V)
are determined by using the equations:
(1.5)
(1.6)
Page 7 of 7
Flow rate is then calculated by the equation
Here Q is the flowrate and A is the cross section area of the duct or the pipe.
1.4 Flowrate and Pressure Reading
It is important to know where the flow rate and pressure reading needs to be taken or else
the fan curve generated will not represent the actual performance of the system.
Figure 2 below shows a typical setup.
Flow and pressure reading should be taken with damper positions at fully closed, fully
open and a few positions in between. The number of positions in between fully open and
fully close depends upon how accurate the fan curve needs to be. The damper positions
fully open and fully close are important; this is because the data collated (pressure and
flowrate) in these two positions will be same or very close to factory tests regardless of
the in situ test set up errors. However, care must be taken whilst taking readings when the
damper is in fully open position. There should be no obvious impedance to flow drown
stream of the damper.
It is also important be aware of the different terms used by the fan suppliers when asked
to supply the fan characteristics curve, especially the pressure values.
Quite often the fan curve values shown in the fan curve graphs do not mention whether
the pressure values are Total Static Pressure or Differential Pressure. The fan curves
differ considerably and can be misleading.
These phenomenon are discussed later in the chapters which discusses on lessons learnt
during testing and data gathering conducted at Malabar Odour Control System
(1.7)
Page 8 of 8
Fan discharge
Figure 2 showing typical set up to measure Static Pressure and Flowrate
Fan intake
Pressure
measuring point
Fan
Flow rate
measuring point
Damper
Page 9 of 9
CHAPTER 2
IMPELLER BALANCING
Balancing is the procedure of measuring vibration and adding or removing weight to
adjust the mass distribution. The goal is to reduce vibration.
Centrifugal force is the operative force that causes vibration due to unbalance. The
magnitude of the out of balance centrifugal force can be calculated by the equation
Here Fc = centrifugal force
M= mass
R = radius from the centre of rotation
= speed in rad/s
The out of balance centrifugal force can also be represented by a vector and its resultant
therefore can be calculated. The magnitude of the counter weight can thus be determined
and placed to have a counter effect and therefore cancel the effects of unbalance. This is
illustrated in figure 3.
(2.0)
Page 10 of 10
2.1 Terms of unbalance
2.1.1 Static Unbalance
Static unbalance is when the principal mass axis is displaced parallel to the shaft
axis. See figure 2.1
Figure 2.0 Vector representation of out of balance forces; after Victor Wowk,
Machinery Vibration & Balancing ,1994.
Page 11 of 11
2.1.2 Quasi –static
Quasi – static is the condition for which the principal axis intersects the shaft axis
at a point other than the centre of gravity.
2.1.3 Couple Unbalance
Couple unbalance is when the principal mass axis intersects the shaft axis at the
centre of gravity. See figure 2.2
Figure 2.1 Static unbalance on a disk and on a drum
Page 12 of 12
2.1.4 Dynamic Unbalance
Dynamic unbalance is a combination of static and couple unbalance. In this
situation the principal mass axis and the rotating shaft centreline do not coincide
or touch.
Dynamic unbalance is the most common condition found in virtually all rotors
(Victor Wowk, 1994).
2.2 Causes of Unbalance
• Less perfect manufacturing
• Porosity , especially in castings
• Eccentricity
Figure 2.2 Two cases of couple unbalance
Page 13 of 13
• Keys and Keyways- different manufactures balance with no key, half key, or full
key. When parts are assembled, they could have a built-in unbalance.
• Distortion
• Deposit build-up
• Runout
2.3 Balance Class
The term "unbalance" is referred to two quantities. First is the balancing
acceptance limit of a rotor and is usually called permissible or allowable
unbalance. Second is the existing or residual unbalance in a rotor.
Unbalance amount is expressed as:
where,
U = unbalance amount
m = unbalance mass
e= distance from unbalance mass to shaft/rotor centreline
Balancing standard provides generalized grades for which rotor application, mass,
and speed can tailored for specific cases.
In general, the larger the rotor mass, the greater the permissible residual
unbalance.
To relate the value of the total permissible unbalance, U, to the rotor mass, M, the
term specific permissible unbalance value, u, is defined. It is the maximum limit
of unbalance amount per unit mass of the rotor.
u = (∆eper=) U/M
(2.1)
(2.2)
Page 14 of 14
The permissible unbalance can be determined based on :
1. History and/or experiments done on several similar machines (vibration limits can be
extracted from the history)
2. Pre-specified permissible bearing forces in the stage of bearing selection
3. Standards like 1940/1 (typically followed in industry)
Quality grade or balance class G (diagonal the lines in figure 2.3) relates max service
speed to the permissible specific unbalance. For a specific grade, as the speed of the rotor
increases (rightwards in the figure), u gets tighter (downwards). This means that the
unbalance amount allowed deceases as machine speed increases.
Figure 2.3 Permissible eccentricities for ISO quality grades; after Woods Practical Guide to Fan
Engineering, 1992.
Page 15 of 15
2.4 Balancing methods (Static and Dynamic)
Rotating components are balanced either statically or dynamically depending on the type
of out of balance exists as discussed in section 2.2.
Static Balancing is the process of checking a rotor’s balance by seeing if it stops in the
same position when rotated; if it does, a small weight is attached to the rim opposite the
heavy area (i.e. opposite the bottom of the rotor when it stops rotating). A rotor is in static
balance when the weight of the wheel is evenly distributed around the axis of rotation.
Dynamic Balancing is a method of balancing rotating components by using a balancing
machine which spins the component and detects any running -out of true which indicates
imbalance. This method may require balancing to be done on several planes of the
component to balance the effects of coupled unbalance.
2.5 Permissible forces on bearing
One of the contributing factors on bearing reaction forces is the centrifugal force. This
centrifugal force is exerted on the bearing will be proportional to residual unbalance (e).
Therefore the specific permissible unbalance (u) is determined accordingly to comply
with bearing loading criteria.
It must be understood that when the value of u is determined by selecting the class of
balance (G) on a rotor, (as shown in figure 2.3), the reaction forces on the bearings
should be within the limits of bearing specification when the rotor is assembled and run
at the maximum duty speed.
This phenomenon is often misunderstood especially when the rotor is in over hung
position. For this reason only the overhung arrangement is discussed here.
Page 16 of 16
2.6 Over hung Rotors
Figure 2.4 illustrates a vertical over hung rotor. This configuration is one where most of
the dynamic rotor force is increased by the factor proportional to the distance (moment)
from the rotor to the bearing. Mathematically expressed as;
L
Shaft
Bearing
Rotor
Figure 2.4 showing an overhung rotor arrangement
Page 17 of 17
Combining equations 2.0 and 2.2
Here Br = bearing reaction.
(2.3)
(2.4)
Page 18 of 18
CHAPTER 3
LESSONS LEARNT FROM MALABAR ODOUR CONTROL FAN
REFURBISHMENT
This chapter discusses the skills and lessons learnt when fan tests were done to determine
its performance at the Sydney Water Odour Control Site in Malabar, Sydney.
	
  
3.1 Malabar Sewerage Treatment Plant
Malabar STP is owned and operated by Sydney Water and is located in the Sydney
municipality of Randwick. The treatment plant provides high rate primary treatment of
sewage generated from a 1.7million equivalent person residential, commercial and
industrial catchment. The plant treats an average daily dry weather flow of approximately
456 ML/d and discharges to ocean through a 3.6 km deep water ocean outfall pipe.
Wastewater treatment facilities are predominately located underground. Sludge
processing, consisting of digestion and biosolids handling, is located above ground.
The existing main odour treatment facility at Malabar STP has poor odour removal
performance due to incoming loads exceeding treatment capacity, and is nearing the end
of its operational life.
The liquid stream odour scrubbing system at Malabar STP treats 180m3
/s of foul air, in
six scrubbers, operating in parallel in a Duty/Duty /Duty/Duty/Standby/Standby
configuration. The total capacity of the treatment with all six scrubbers operating is
972,000m3/h of foul air (45m3/s per scrubber).
The scrubber discharge does not meet the requirements of the Department of
Environment Climate Change and Water (DECCW) with respect to odour levels at the
nearest sensitive receptor. A new arrangement to collect the treated air with scrubber
outlet ducts and a tall vent stack allow improved dispersion to the atmosphere.
Page 19 of 19
This upgrade is considered an interim step to extend the asset life of the facility, allowing
SWC to meet its (DECCW) requirements, yet deferring a full upgrade of the system. A
full replacement of the facility is planned to be undertaken at +10 years from this upgrade
(when the plant is at the end of its extended asset life), and is part of the overall Sydney
Water odour management plan for Malabar STP.
The six Odour Control Facility (OCF) wet chemical scrubbers at Malabar sewerage
Treatment Plant are equipped with individual fans. It was required to; (a) determine
whether the current fan were capable to perform at the elevated duty points and (b)
establish a baseline of the performance of the fans.
3.2 Fan Performance Test
The scrubber fans had to be tested in situ since a test rig could not be set up due to its
size. Setting up a test rig of such magnitude would impact the project for time and costs.
A copy of the manufacture’s performance curve (figure 3.1) of the same model was
requrested so that compassions could be made with the curve generated from test data. It
was realised that the data collated during the test will differ compared to data supplied by
the supplier due to test set up, therefore the tests had to be conducted in such a way so
that this difference was kept to the minimum.
3.3 Test Procedure
The details of the test procedure carried out on the day were:
1. 4 No. holes of 22mm diameter were drilled across the side face of the discharge
duct on one side. These holes were to allow a Pitot tube to be inserted into the
duct to measure the gas velocity in the duct. This allowed for the gas flowrate to
be calculated.
2. With the fan running at test speeds pressure drop across the scrubber was
measured. It was found the pressure drop was very small however this was kept in
mind to be considered when making comparisons with suppliers fan curve.
Page 20 of 20
3. Hydrogen sulphide monitoring instrumentation was removed from the flange on
the discharge ductwork from the fan. The removal of this instrumentation
allowed for the measurement of static pressure on the discharge of the fan without
drilling additional holes into the ductwork.
4. The fan was set to operate at a normal running speed of 900rpm and the
experiment was repeated at a speed of 960 rpm
5. Static pressure and velocity was measured with damper positions at fully open,
33% open, 66% open and fully closed.
6. Gas velocities were measured (along the width as shown in figure 3.0) at four
evenly spaced positions, including the centre of the duct. This was repeated in the
four holes across the face of the duct. The velocity readings were collated and
average value was calculated. The reason for this was that the flow in the duct
was very turbulent and therefore difficult to get an accurate reading.
7. Graphs were plotted, pressure vs flowrate.
Out of the six fans in operation, only two of the fans could be tested. The other fans
could not be shut down due to the duty requirements.
Normally all the fans should have been tested, however, in this instant the data
collated from the two fans showed significant discrepancies when compared to
suppliers data. This lead to a major investigation in order to justify the results
obtained.
Page 21 of 21
Figure 3.0 showing Pitot tube positions
Holes in the side face
of the duct for the
Pitot tube to go
through
Pitot tube positions to
determine velocity
Pitot Tube
Manometer
Duct
Roy Singh
Page 22 of 22
3.4 Analysis
Figure 3.1 Suppliers Fan Performance Curve
Pressure and flow measurement – Malabar Odour Control Duct
Page 23 of 23
Testing on FAN 9512, and FAN9562 (scrubbers 1, and 6 respectively) showed that
the fans are not performing as the manufacturer’s curves supplied during the concept
design.
Error! Reference source not found. shows that there are two separate issues with
the fans that were tested.
The performance of FAN9512 (scrubber 1) is approximately 50% less that FAN9562
(scrubber 6) when subjected to the same loads.
The current performance of FAN9562 achieves approximately 50% of the anticipated
flow of 45m3
/s
Figure 3.2 Fan Performance Curve generated from Fan Tests.
Page 24 of 24
	
   	
   	
   	
   	
  
3.5 Investigations and Findings
Further investigation was carried out to find the root causes of the lack of
performance of Fan 9512 . The following issues were identified.
• In inlet cone that directs the flow into the impeller is missing, as shown in
figure 3.3
Missing inlet cone
Figure 3.3 showing inlet cone missing
Page 25 of 25
• The width of the impellers of the fans tested (scrubbers 1 and 6) are
approximately 90mm narrower than the specification of the impeller that
Howden (supplier) provided fan curves for during concept design.
It is not known why these narrower impellers have been fitted or when. Of the 2 spare
fans on site, one impeller is as per the fan curve supplied during concept design, and
one is of the narrower type. The widths of the impellers on the fans for scrubbers 2 to
5 are unknown.
3.6 Impeller Balance Issues
ISO Standard 1940 states that the balance class of a motor rotor shall be within G 2.5 and
any system attached to the motor shaft shall not alter the balance class when subjected to
the working speed range.
Howden (Fan supplier) was questioned on the class of balance of the fan impeller.
Howden replied that all fan impellers were balanced within G 2.5. Howden was further
questioned whether the balance class was maintained when subjected to the speeds and
most importantly the way the impellers were installed, i.e. vertically over hung.
Howden agreed that it such case the system did not retain the G 2.5 balance class, due to
the reasons discussed in section 2.6.
This issue was mitigated by recommending the final balancing to be conducted in situ
with the fan running at its maximum duty speed of 990 rpm.
In situ balancing is a technique commonly used where an accelerometer is place on the
bearing housing and out of balance force thus detected. Further literature on the subject is
available in internet.
Page 26 of 26
CHAPTER 4
CONCLUSION
Fan performance tests were carried out on two Scrubber Fans of Malabar Odour
Control facility. The purpose was to establish a base line of the fan characteristics,
however, after analysing the data other issues were exposed such as critical parts
missing (inlet guide cone), and differences in impeller sizes. It was also realised that
the required speed for the elevated duty point needed to be increased. The speed
required to be increased to 990 rpm from the current speed of 900rpm.
The client (Sydney Water) was concerned when told about the increase in fan speeds.
Their concern was an increase in vibration as a consequence of increase of speed,
which already is a concern at the current speeds.
This is where the client lacked the knowledge in balancing theory. This was discussed
with the client as in chapter 2 of this report. The client was explained that the
vibration severity can be reduced, lower than current levels regardless of the speed.
The supplier was also consulted regarding the findings. It was agreed by the supplier
that the current system is inefficient and there are room for improvements, starting
from a new type of impeller.
The supplier supplied data on an aerofoil type impeller which are more efficient than
the current type by about 10%.
The supplier also agreed to final balance the system at G2.5 in situ.
Having analysed and discussed the findings of the tests it was possible to make a
decision as to which direction to take on the fans. The following decisions were
made;
Page 27 of 27
• Aerofoil type impeller to be used
• Fan speed to be at 990rpm
• Balance class to be maintained at class G2.5 when installed
• Balancing to achieve to G2.5 by final balancing carried out in situ
A Fan Specification was drafted with above statements included in the data sheet for
the project. The aim of the specification was to provide all the relevant technical
information to a supplier so that the supplier could price the works.
Page 28 of 28
REFERENCES	
  
Benedict, R. (1980) Fundamentals of Pipe Flow, 3rd
edition. A. Wiley – Inter
Sciences
Crowe, C. T., and Robertson, J.A.. (1985) Engineering Fluid Mechanics, 5th
edition.
Houghton Mifflin Company.
Daly, B. B. (1992) Woods Practical Guide to Fan Engineering, 5th
edition.
Woods of Colchester Limited.
ISO Standard, 1940, Mechanical Vibration- Balance Quality Requirements for
Motors
Singh, R. K. (2009) A Study of Air Flow in a Network of Pipes used in Aspirated
smoke Detectors, Master of Mechanical Engineering Thesis, Victoria University,
Australia
Wowk, Victor, (1994) Machinery Vibration and Balance Quality
McGraw Hill

More Related Content

What's hot

[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar ii[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar iiLuis Luis
 
pipe stress analysis for piping engineering
pipe stress analysis for piping engineeringpipe stress analysis for piping engineering
pipe stress analysis for piping engineeringYoga Sathish
 
S3 Minor Losses Assignment
S3 Minor Losses AssignmentS3 Minor Losses Assignment
S3 Minor Losses Assignmentno suhaila
 
Various Load Cases In Pipe Stress Analysis
Various Load Cases In Pipe Stress AnalysisVarious Load Cases In Pipe Stress Analysis
Various Load Cases In Pipe Stress Analysisjudithmorrison01
 
Ducted fans
Ducted fansDucted fans
Ducted fanstiemples
 
Fluid Mech. Presentation 2nd year B.Tech.
Fluid Mech. Presentation 2nd year B.Tech.Fluid Mech. Presentation 2nd year B.Tech.
Fluid Mech. Presentation 2nd year B.Tech.shivam gautam
 
Single phase flow line sizing
Single phase flow line sizingSingle phase flow line sizing
Single phase flow line sizingVikram Sharma
 
Analysis About Losses of Centrifugal Pump by Matlab
Analysis About Losses of Centrifugal Pump by MatlabAnalysis About Losses of Centrifugal Pump by Matlab
Analysis About Losses of Centrifugal Pump by Matlabijceronline
 
Understanding Stress Analysis Topics
Understanding Stress Analysis TopicsUnderstanding Stress Analysis Topics
Understanding Stress Analysis TopicsZachary Swartz
 
Impeller Design
Impeller DesignImpeller Design
Impeller DesignKiruba193
 
Darcy weisbach formula
Darcy weisbach formulaDarcy weisbach formula
Darcy weisbach formulaHarkat Bouaddi
 
Fatigue analysis using caesar ii
Fatigue analysis using caesar iiFatigue analysis using caesar ii
Fatigue analysis using caesar iiRem Elems
 
Flow In Pipes
Flow In PipesFlow In Pipes
Flow In PipesIla Lee
 
final friction in pipes
final friction in pipesfinal friction in pipes
final friction in pipesAbhishek Dabas
 
manual stress analysis
manual stress analysismanual stress analysis
manual stress analysisBHARAT BELLAD
 

What's hot (20)

[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar ii[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar ii
 
pipe stress analysis for piping engineering
pipe stress analysis for piping engineeringpipe stress analysis for piping engineering
pipe stress analysis for piping engineering
 
S3 Minor Losses Assignment
S3 Minor Losses AssignmentS3 Minor Losses Assignment
S3 Minor Losses Assignment
 
Various Load Cases In Pipe Stress Analysis
Various Load Cases In Pipe Stress AnalysisVarious Load Cases In Pipe Stress Analysis
Various Load Cases In Pipe Stress Analysis
 
Ducted fans
Ducted fansDucted fans
Ducted fans
 
Fluid Mech. Presentation 2nd year B.Tech.
Fluid Mech. Presentation 2nd year B.Tech.Fluid Mech. Presentation 2nd year B.Tech.
Fluid Mech. Presentation 2nd year B.Tech.
 
Single phase flow line sizing
Single phase flow line sizingSingle phase flow line sizing
Single phase flow line sizing
 
Analysis About Losses of Centrifugal Pump by Matlab
Analysis About Losses of Centrifugal Pump by MatlabAnalysis About Losses of Centrifugal Pump by Matlab
Analysis About Losses of Centrifugal Pump by Matlab
 
Pipe sizing
Pipe sizingPipe sizing
Pipe sizing
 
Flow through pipes
Flow through pipesFlow through pipes
Flow through pipes
 
Understanding Stress Analysis Topics
Understanding Stress Analysis TopicsUnderstanding Stress Analysis Topics
Understanding Stress Analysis Topics
 
Impeller Design
Impeller DesignImpeller Design
Impeller Design
 
Darcy weisbach formula
Darcy weisbach formulaDarcy weisbach formula
Darcy weisbach formula
 
Fatigue analysis using caesar ii
Fatigue analysis using caesar iiFatigue analysis using caesar ii
Fatigue analysis using caesar ii
 
Flow In Pipes
Flow In PipesFlow In Pipes
Flow In Pipes
 
final friction in pipes
final friction in pipesfinal friction in pipes
final friction in pipes
 
Hydraulic losses in pipe
Hydraulic losses in pipeHydraulic losses in pipe
Hydraulic losses in pipe
 
Flow Through Pipe
Flow Through PipeFlow Through Pipe
Flow Through Pipe
 
Flow in Pipes
Flow in PipesFlow in Pipes
Flow in Pipes
 
manual stress analysis
manual stress analysismanual stress analysis
manual stress analysis
 

Similar to 110207 Fan Testing at Malabar Odor Control Site Sydney

391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdf391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdfBlentBulut5
 
5_ISMTII2015_1281_VAWT_ShiehHsiao_et.al_manuscript_15Juli2015_vorlage
5_ISMTII2015_1281_VAWT_ShiehHsiao_et.al_manuscript_15Juli2015_vorlage5_ISMTII2015_1281_VAWT_ShiehHsiao_et.al_manuscript_15Juli2015_vorlage
5_ISMTII2015_1281_VAWT_ShiehHsiao_et.al_manuscript_15Juli2015_vorlageDoug Yang-Hsu Liao
 
Experimental investigation of air flow characteristics in rectangular channel...
Experimental investigation of air flow characteristics in rectangular channel...Experimental investigation of air flow characteristics in rectangular channel...
Experimental investigation of air flow characteristics in rectangular channel...eSAT Journals
 
Effect of flow coefficient and loading coefficient on
Effect of flow coefficient and loading coefficient onEffect of flow coefficient and loading coefficient on
Effect of flow coefficient and loading coefficient oneSAT Publishing House
 
Effect of flow coefficient and loading coefficient on the radial inflow turbi...
Effect of flow coefficient and loading coefficient on the radial inflow turbi...Effect of flow coefficient and loading coefficient on the radial inflow turbi...
Effect of flow coefficient and loading coefficient on the radial inflow turbi...eSAT Journals
 
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM Data
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM DataPredicting Performance Curves of Centrifugal Pumps in the Absence of OEM Data
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM DataVijay Sarathy
 
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM Data
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM DataPredicting Performance Curves of Centrifugal Pumps in the Absence of OEM Data
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM DataVijay Sarathy
 
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...IJERA Editor
 
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...IJERA Editor
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Variable Area Flowmeter Basics: Fundamentals and Descriptions
Variable Area Flowmeter Basics: Fundamentals and DescriptionsVariable Area Flowmeter Basics: Fundamentals and Descriptions
Variable Area Flowmeter Basics: Fundamentals and DescriptionsThompson Equipment Company
 
An Investigation on the Performance Characteristics of a Centrifugal Compressor
An Investigation on the Performance Characteristics of a Centrifugal CompressorAn Investigation on the Performance Characteristics of a Centrifugal Compressor
An Investigation on the Performance Characteristics of a Centrifugal CompressorIJERD Editor
 
IRJET - Analysis and Designing of Diaphragm Spring Washers
IRJET -  	  Analysis and Designing of Diaphragm Spring WashersIRJET -  	  Analysis and Designing of Diaphragm Spring Washers
IRJET - Analysis and Designing of Diaphragm Spring WashersIRJET Journal
 
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...IRJET Journal
 
CFD analysis of flow through T-Junction of pipe
CFD analysis of flow through  T-Junction of pipeCFD analysis of flow through  T-Junction of pipe
CFD analysis of flow through T-Junction of pipeIRJET Journal
 

Similar to 110207 Fan Testing at Malabar Odor Control Site Sydney (20)

391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdf391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdf
 
5_ISMTII2015_1281_VAWT_ShiehHsiao_et.al_manuscript_15Juli2015_vorlage
5_ISMTII2015_1281_VAWT_ShiehHsiao_et.al_manuscript_15Juli2015_vorlage5_ISMTII2015_1281_VAWT_ShiehHsiao_et.al_manuscript_15Juli2015_vorlage
5_ISMTII2015_1281_VAWT_ShiehHsiao_et.al_manuscript_15Juli2015_vorlage
 
Presentation - energy lose
Presentation - energy losePresentation - energy lose
Presentation - energy lose
 
Experimental investigation of air flow characteristics in rectangular channel...
Experimental investigation of air flow characteristics in rectangular channel...Experimental investigation of air flow characteristics in rectangular channel...
Experimental investigation of air flow characteristics in rectangular channel...
 
Effect of flow coefficient and loading coefficient on
Effect of flow coefficient and loading coefficient onEffect of flow coefficient and loading coefficient on
Effect of flow coefficient and loading coefficient on
 
Effect of flow coefficient and loading coefficient on the radial inflow turbi...
Effect of flow coefficient and loading coefficient on the radial inflow turbi...Effect of flow coefficient and loading coefficient on the radial inflow turbi...
Effect of flow coefficient and loading coefficient on the radial inflow turbi...
 
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM Data
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM DataPredicting Performance Curves of Centrifugal Pumps in the Absence of OEM Data
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM Data
 
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM Data
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM DataPredicting Performance Curves of Centrifugal Pumps in the Absence of OEM Data
Predicting Performance Curves of Centrifugal Pumps in the Absence of OEM Data
 
M01312106112
M01312106112M01312106112
M01312106112
 
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...
 
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...
Fluid Structural Modal Coupled Numerical Investigation of Transonic Flutterin...
 
E1072850
E1072850E1072850
E1072850
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Variable Area Flowmeter Basics: Fundamentals and Descriptions
Variable Area Flowmeter Basics: Fundamentals and DescriptionsVariable Area Flowmeter Basics: Fundamentals and Descriptions
Variable Area Flowmeter Basics: Fundamentals and Descriptions
 
An Investigation on the Performance Characteristics of a Centrifugal Compressor
An Investigation on the Performance Characteristics of a Centrifugal CompressorAn Investigation on the Performance Characteristics of a Centrifugal Compressor
An Investigation on the Performance Characteristics of a Centrifugal Compressor
 
IRJET - Analysis and Designing of Diaphragm Spring Washers
IRJET -  	  Analysis and Designing of Diaphragm Spring WashersIRJET -  	  Analysis and Designing of Diaphragm Spring Washers
IRJET - Analysis and Designing of Diaphragm Spring Washers
 
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...
 
Ku2418231829
Ku2418231829Ku2418231829
Ku2418231829
 
Artigo sea
Artigo seaArtigo sea
Artigo sea
 
CFD analysis of flow through T-Junction of pipe
CFD analysis of flow through  T-Junction of pipeCFD analysis of flow through  T-Junction of pipe
CFD analysis of flow through T-Junction of pipe
 

110207 Fan Testing at Malabar Odor Control Site Sydney

  • 1.   Fan  Testing  at  Malabar  Odor  Control  Site,  Sydney       Roy  Singh     7th  February,  2011    
  • 2. Page 2 of 2 INTRODUCTION The purpose of this report is to capture the knowledge, skills and lessons learnt when fan tests were done to determine its performance at the Sydney Water Odour Control Site in Malabar, Sydney. Often the data provided by the manufactures regarding the performance can be misleading. This could be due to the way the test was done by the supplier or the data provided was obsolete. Tests were required to be carried out to determine the base line before and after the refurbishment and also to determine if the current fan or a pump can be used when subjected to elevated duty points. There are situations where the test rig set up in house is not possible due to the size of the system. A good example is the Malabar Odour Control Project in Sydney. The fan assemblies were just too large for a temporary test rig to be set up, however, tests were carried out with the fans in its installed arrangement and the testing method applied, provided results which were comparable with the factory data and decisions could be made with high level of confidence. It is also important to understand the balancing theory of rotating discs so that the balance class of the impeller of a blower or a pump can be determined correctly. For example an impellor balanced in a balancing machine on a short spindle due to machine size constrains, will not maintain the same balance class if installed on a longer shaft where the distance between the locating bearings and the impeller is greater. The moment acting in such installed situation will be greater, proportional to the distance apart. This report describes some basic theory on pumps, methods to measure flow and pressures, basic theory on balancing of rotating discs and lessons learnt from Malabar Odour project while conducting fan testing. For further reading on pipe losses and balancing theory, literature can be obtained from books mentioned in the Reference Section of this report.
  • 3. Page 3 of 3 CHAPTER 1 FAN AND SYSTEM CHARACTERISTICS 1.1 Pressure Drop in Pipes (system resistance) The term system resistance (graphically shown as system curve) is the sum of pressure losses in a system of pipe work which transports fluid from point 1 to point 2. The resistance is a function of the configuration of pipes and the fittings used such as elbows, valves etc. and pipe elevations. In modeling steady flow for pipe networks, normally the energy form of the Bernoulli’s equation is used, where subscripts 1 and 2 are for upstream and downstream locations as shown in Figure 1, P is the pressure, f is the friction factor, L is the length of the pipe, D is the diameter of the pipe, and K is the local energy loss factor, is the density of the fluid, g is the gravitation acceleration, z1 and z2 are the heights, and V1 and V2 are the velocities. In this form the energy equation relates the pressure, velocity and elevation at different points of the flow, with the frictional and local losses. In Equation (1.0), the first summation is the energy loss due to friction in pipes of different diameter and length and the second is the energy losses due to local disturbances to the flow. These could include local disturbances such as valves, elbows, and sudden constrictions and enlargements. (1.0)
  • 4. Page 4 of 4 Z 1 Z 2 1 2 Figure 1 Flow in pipe from point 1 to point 2
  • 5. Page 5 of 5 The head loss due to friction can be expressed by Darcy’s equation, where f is the friction factor. Different equations exist for friction factor f, depending on whether the flow is laminar or turbulent. For laminar flow in a smooth pipe, where Re is ≤ 2000, a commonly used equation is where here is the dynamic viscosity and Re is the Reynolds Number. For turbulent flow where Re is > 2000, and the friction factor is dependent on relative roughness and Reynolds number, Colebrook equation can be used (Australian Pump Technical Handbook, fourth Edition) Here is the absolute roughness (mm) (2.7) (1.1) (1.3) (1.2) (1.4)
  • 6. Page 6 of 6 1.2 Fan Characteristics (Fan Curve) Fan curve is a performance curve for a particular fan under specific set conditions. A fan curve is generated by measuring and plotting the volume discharge rate (m3 /s) versus the static pressure developed at that setting. The static pressure and flow can be measured by using a Pitot tube and a manometer. There are a number of advantages using a Pitot tube such as; • An average velocity can be determined hence an average flowrate can be calculated by taking reading across a pipe or a duct. This is necessary when working with large cross section areas of pipe and ducts. • A Pitot tube can be inserted in a duct by drilling a small diameter hole, usually just big enough for the Pitot tube to pass through. This eliminates the need to change duct sections to install flow meters when flowrate measurements are required. • A Pitot tube usually will not interfere or impede the flow regimes. 1.3 Pitot Tube A Pitot tube, when aligned with the flow, measures the local velocity by means of pressure difference. It has side holes to measure the static pressure Ps in the moving stream and a hole in the front to measure the stagnation pressure Po, separately. The difference in the pressures (Ps - Po) measured by the manometer and the velocity (V) are determined by using the equations: (1.5) (1.6)
  • 7. Page 7 of 7 Flow rate is then calculated by the equation Here Q is the flowrate and A is the cross section area of the duct or the pipe. 1.4 Flowrate and Pressure Reading It is important to know where the flow rate and pressure reading needs to be taken or else the fan curve generated will not represent the actual performance of the system. Figure 2 below shows a typical setup. Flow and pressure reading should be taken with damper positions at fully closed, fully open and a few positions in between. The number of positions in between fully open and fully close depends upon how accurate the fan curve needs to be. The damper positions fully open and fully close are important; this is because the data collated (pressure and flowrate) in these two positions will be same or very close to factory tests regardless of the in situ test set up errors. However, care must be taken whilst taking readings when the damper is in fully open position. There should be no obvious impedance to flow drown stream of the damper. It is also important be aware of the different terms used by the fan suppliers when asked to supply the fan characteristics curve, especially the pressure values. Quite often the fan curve values shown in the fan curve graphs do not mention whether the pressure values are Total Static Pressure or Differential Pressure. The fan curves differ considerably and can be misleading. These phenomenon are discussed later in the chapters which discusses on lessons learnt during testing and data gathering conducted at Malabar Odour Control System (1.7)
  • 8. Page 8 of 8 Fan discharge Figure 2 showing typical set up to measure Static Pressure and Flowrate Fan intake Pressure measuring point Fan Flow rate measuring point Damper
  • 9. Page 9 of 9 CHAPTER 2 IMPELLER BALANCING Balancing is the procedure of measuring vibration and adding or removing weight to adjust the mass distribution. The goal is to reduce vibration. Centrifugal force is the operative force that causes vibration due to unbalance. The magnitude of the out of balance centrifugal force can be calculated by the equation Here Fc = centrifugal force M= mass R = radius from the centre of rotation = speed in rad/s The out of balance centrifugal force can also be represented by a vector and its resultant therefore can be calculated. The magnitude of the counter weight can thus be determined and placed to have a counter effect and therefore cancel the effects of unbalance. This is illustrated in figure 3. (2.0)
  • 10. Page 10 of 10 2.1 Terms of unbalance 2.1.1 Static Unbalance Static unbalance is when the principal mass axis is displaced parallel to the shaft axis. See figure 2.1 Figure 2.0 Vector representation of out of balance forces; after Victor Wowk, Machinery Vibration & Balancing ,1994.
  • 11. Page 11 of 11 2.1.2 Quasi –static Quasi – static is the condition for which the principal axis intersects the shaft axis at a point other than the centre of gravity. 2.1.3 Couple Unbalance Couple unbalance is when the principal mass axis intersects the shaft axis at the centre of gravity. See figure 2.2 Figure 2.1 Static unbalance on a disk and on a drum
  • 12. Page 12 of 12 2.1.4 Dynamic Unbalance Dynamic unbalance is a combination of static and couple unbalance. In this situation the principal mass axis and the rotating shaft centreline do not coincide or touch. Dynamic unbalance is the most common condition found in virtually all rotors (Victor Wowk, 1994). 2.2 Causes of Unbalance • Less perfect manufacturing • Porosity , especially in castings • Eccentricity Figure 2.2 Two cases of couple unbalance
  • 13. Page 13 of 13 • Keys and Keyways- different manufactures balance with no key, half key, or full key. When parts are assembled, they could have a built-in unbalance. • Distortion • Deposit build-up • Runout 2.3 Balance Class The term "unbalance" is referred to two quantities. First is the balancing acceptance limit of a rotor and is usually called permissible or allowable unbalance. Second is the existing or residual unbalance in a rotor. Unbalance amount is expressed as: where, U = unbalance amount m = unbalance mass e= distance from unbalance mass to shaft/rotor centreline Balancing standard provides generalized grades for which rotor application, mass, and speed can tailored for specific cases. In general, the larger the rotor mass, the greater the permissible residual unbalance. To relate the value of the total permissible unbalance, U, to the rotor mass, M, the term specific permissible unbalance value, u, is defined. It is the maximum limit of unbalance amount per unit mass of the rotor. u = (∆eper=) U/M (2.1) (2.2)
  • 14. Page 14 of 14 The permissible unbalance can be determined based on : 1. History and/or experiments done on several similar machines (vibration limits can be extracted from the history) 2. Pre-specified permissible bearing forces in the stage of bearing selection 3. Standards like 1940/1 (typically followed in industry) Quality grade or balance class G (diagonal the lines in figure 2.3) relates max service speed to the permissible specific unbalance. For a specific grade, as the speed of the rotor increases (rightwards in the figure), u gets tighter (downwards). This means that the unbalance amount allowed deceases as machine speed increases. Figure 2.3 Permissible eccentricities for ISO quality grades; after Woods Practical Guide to Fan Engineering, 1992.
  • 15. Page 15 of 15 2.4 Balancing methods (Static and Dynamic) Rotating components are balanced either statically or dynamically depending on the type of out of balance exists as discussed in section 2.2. Static Balancing is the process of checking a rotor’s balance by seeing if it stops in the same position when rotated; if it does, a small weight is attached to the rim opposite the heavy area (i.e. opposite the bottom of the rotor when it stops rotating). A rotor is in static balance when the weight of the wheel is evenly distributed around the axis of rotation. Dynamic Balancing is a method of balancing rotating components by using a balancing machine which spins the component and detects any running -out of true which indicates imbalance. This method may require balancing to be done on several planes of the component to balance the effects of coupled unbalance. 2.5 Permissible forces on bearing One of the contributing factors on bearing reaction forces is the centrifugal force. This centrifugal force is exerted on the bearing will be proportional to residual unbalance (e). Therefore the specific permissible unbalance (u) is determined accordingly to comply with bearing loading criteria. It must be understood that when the value of u is determined by selecting the class of balance (G) on a rotor, (as shown in figure 2.3), the reaction forces on the bearings should be within the limits of bearing specification when the rotor is assembled and run at the maximum duty speed. This phenomenon is often misunderstood especially when the rotor is in over hung position. For this reason only the overhung arrangement is discussed here.
  • 16. Page 16 of 16 2.6 Over hung Rotors Figure 2.4 illustrates a vertical over hung rotor. This configuration is one where most of the dynamic rotor force is increased by the factor proportional to the distance (moment) from the rotor to the bearing. Mathematically expressed as; L Shaft Bearing Rotor Figure 2.4 showing an overhung rotor arrangement
  • 17. Page 17 of 17 Combining equations 2.0 and 2.2 Here Br = bearing reaction. (2.3) (2.4)
  • 18. Page 18 of 18 CHAPTER 3 LESSONS LEARNT FROM MALABAR ODOUR CONTROL FAN REFURBISHMENT This chapter discusses the skills and lessons learnt when fan tests were done to determine its performance at the Sydney Water Odour Control Site in Malabar, Sydney.   3.1 Malabar Sewerage Treatment Plant Malabar STP is owned and operated by Sydney Water and is located in the Sydney municipality of Randwick. The treatment plant provides high rate primary treatment of sewage generated from a 1.7million equivalent person residential, commercial and industrial catchment. The plant treats an average daily dry weather flow of approximately 456 ML/d and discharges to ocean through a 3.6 km deep water ocean outfall pipe. Wastewater treatment facilities are predominately located underground. Sludge processing, consisting of digestion and biosolids handling, is located above ground. The existing main odour treatment facility at Malabar STP has poor odour removal performance due to incoming loads exceeding treatment capacity, and is nearing the end of its operational life. The liquid stream odour scrubbing system at Malabar STP treats 180m3 /s of foul air, in six scrubbers, operating in parallel in a Duty/Duty /Duty/Duty/Standby/Standby configuration. The total capacity of the treatment with all six scrubbers operating is 972,000m3/h of foul air (45m3/s per scrubber). The scrubber discharge does not meet the requirements of the Department of Environment Climate Change and Water (DECCW) with respect to odour levels at the nearest sensitive receptor. A new arrangement to collect the treated air with scrubber outlet ducts and a tall vent stack allow improved dispersion to the atmosphere.
  • 19. Page 19 of 19 This upgrade is considered an interim step to extend the asset life of the facility, allowing SWC to meet its (DECCW) requirements, yet deferring a full upgrade of the system. A full replacement of the facility is planned to be undertaken at +10 years from this upgrade (when the plant is at the end of its extended asset life), and is part of the overall Sydney Water odour management plan for Malabar STP. The six Odour Control Facility (OCF) wet chemical scrubbers at Malabar sewerage Treatment Plant are equipped with individual fans. It was required to; (a) determine whether the current fan were capable to perform at the elevated duty points and (b) establish a baseline of the performance of the fans. 3.2 Fan Performance Test The scrubber fans had to be tested in situ since a test rig could not be set up due to its size. Setting up a test rig of such magnitude would impact the project for time and costs. A copy of the manufacture’s performance curve (figure 3.1) of the same model was requrested so that compassions could be made with the curve generated from test data. It was realised that the data collated during the test will differ compared to data supplied by the supplier due to test set up, therefore the tests had to be conducted in such a way so that this difference was kept to the minimum. 3.3 Test Procedure The details of the test procedure carried out on the day were: 1. 4 No. holes of 22mm diameter were drilled across the side face of the discharge duct on one side. These holes were to allow a Pitot tube to be inserted into the duct to measure the gas velocity in the duct. This allowed for the gas flowrate to be calculated. 2. With the fan running at test speeds pressure drop across the scrubber was measured. It was found the pressure drop was very small however this was kept in mind to be considered when making comparisons with suppliers fan curve.
  • 20. Page 20 of 20 3. Hydrogen sulphide monitoring instrumentation was removed from the flange on the discharge ductwork from the fan. The removal of this instrumentation allowed for the measurement of static pressure on the discharge of the fan without drilling additional holes into the ductwork. 4. The fan was set to operate at a normal running speed of 900rpm and the experiment was repeated at a speed of 960 rpm 5. Static pressure and velocity was measured with damper positions at fully open, 33% open, 66% open and fully closed. 6. Gas velocities were measured (along the width as shown in figure 3.0) at four evenly spaced positions, including the centre of the duct. This was repeated in the four holes across the face of the duct. The velocity readings were collated and average value was calculated. The reason for this was that the flow in the duct was very turbulent and therefore difficult to get an accurate reading. 7. Graphs were plotted, pressure vs flowrate. Out of the six fans in operation, only two of the fans could be tested. The other fans could not be shut down due to the duty requirements. Normally all the fans should have been tested, however, in this instant the data collated from the two fans showed significant discrepancies when compared to suppliers data. This lead to a major investigation in order to justify the results obtained.
  • 21. Page 21 of 21 Figure 3.0 showing Pitot tube positions Holes in the side face of the duct for the Pitot tube to go through Pitot tube positions to determine velocity Pitot Tube Manometer Duct Roy Singh
  • 22. Page 22 of 22 3.4 Analysis Figure 3.1 Suppliers Fan Performance Curve Pressure and flow measurement – Malabar Odour Control Duct
  • 23. Page 23 of 23 Testing on FAN 9512, and FAN9562 (scrubbers 1, and 6 respectively) showed that the fans are not performing as the manufacturer’s curves supplied during the concept design. Error! Reference source not found. shows that there are two separate issues with the fans that were tested. The performance of FAN9512 (scrubber 1) is approximately 50% less that FAN9562 (scrubber 6) when subjected to the same loads. The current performance of FAN9562 achieves approximately 50% of the anticipated flow of 45m3 /s Figure 3.2 Fan Performance Curve generated from Fan Tests.
  • 24. Page 24 of 24           3.5 Investigations and Findings Further investigation was carried out to find the root causes of the lack of performance of Fan 9512 . The following issues were identified. • In inlet cone that directs the flow into the impeller is missing, as shown in figure 3.3 Missing inlet cone Figure 3.3 showing inlet cone missing
  • 25. Page 25 of 25 • The width of the impellers of the fans tested (scrubbers 1 and 6) are approximately 90mm narrower than the specification of the impeller that Howden (supplier) provided fan curves for during concept design. It is not known why these narrower impellers have been fitted or when. Of the 2 spare fans on site, one impeller is as per the fan curve supplied during concept design, and one is of the narrower type. The widths of the impellers on the fans for scrubbers 2 to 5 are unknown. 3.6 Impeller Balance Issues ISO Standard 1940 states that the balance class of a motor rotor shall be within G 2.5 and any system attached to the motor shaft shall not alter the balance class when subjected to the working speed range. Howden (Fan supplier) was questioned on the class of balance of the fan impeller. Howden replied that all fan impellers were balanced within G 2.5. Howden was further questioned whether the balance class was maintained when subjected to the speeds and most importantly the way the impellers were installed, i.e. vertically over hung. Howden agreed that it such case the system did not retain the G 2.5 balance class, due to the reasons discussed in section 2.6. This issue was mitigated by recommending the final balancing to be conducted in situ with the fan running at its maximum duty speed of 990 rpm. In situ balancing is a technique commonly used where an accelerometer is place on the bearing housing and out of balance force thus detected. Further literature on the subject is available in internet.
  • 26. Page 26 of 26 CHAPTER 4 CONCLUSION Fan performance tests were carried out on two Scrubber Fans of Malabar Odour Control facility. The purpose was to establish a base line of the fan characteristics, however, after analysing the data other issues were exposed such as critical parts missing (inlet guide cone), and differences in impeller sizes. It was also realised that the required speed for the elevated duty point needed to be increased. The speed required to be increased to 990 rpm from the current speed of 900rpm. The client (Sydney Water) was concerned when told about the increase in fan speeds. Their concern was an increase in vibration as a consequence of increase of speed, which already is a concern at the current speeds. This is where the client lacked the knowledge in balancing theory. This was discussed with the client as in chapter 2 of this report. The client was explained that the vibration severity can be reduced, lower than current levels regardless of the speed. The supplier was also consulted regarding the findings. It was agreed by the supplier that the current system is inefficient and there are room for improvements, starting from a new type of impeller. The supplier supplied data on an aerofoil type impeller which are more efficient than the current type by about 10%. The supplier also agreed to final balance the system at G2.5 in situ. Having analysed and discussed the findings of the tests it was possible to make a decision as to which direction to take on the fans. The following decisions were made;
  • 27. Page 27 of 27 • Aerofoil type impeller to be used • Fan speed to be at 990rpm • Balance class to be maintained at class G2.5 when installed • Balancing to achieve to G2.5 by final balancing carried out in situ A Fan Specification was drafted with above statements included in the data sheet for the project. The aim of the specification was to provide all the relevant technical information to a supplier so that the supplier could price the works.
  • 28. Page 28 of 28 REFERENCES   Benedict, R. (1980) Fundamentals of Pipe Flow, 3rd edition. A. Wiley – Inter Sciences Crowe, C. T., and Robertson, J.A.. (1985) Engineering Fluid Mechanics, 5th edition. Houghton Mifflin Company. Daly, B. B. (1992) Woods Practical Guide to Fan Engineering, 5th edition. Woods of Colchester Limited. ISO Standard, 1940, Mechanical Vibration- Balance Quality Requirements for Motors Singh, R. K. (2009) A Study of Air Flow in a Network of Pipes used in Aspirated smoke Detectors, Master of Mechanical Engineering Thesis, Victoria University, Australia Wowk, Victor, (1994) Machinery Vibration and Balance Quality McGraw Hill