SlideShare a Scribd company logo
1 of 9
Download to read offline
Relink icon




    1                                                                            4



        1. From the Quark file, make sure all logos and graphics are in place.

        Through InDesign CS2, convert the Quark to an InDesign file.
        Use this converted InDesign file for reference only.



                                                                                     4. If any logos or graphics are missing or modified in the converted InDesign
                                                                                        file, navigate to where they reside using the Links palette “Relink” icon.
                                                                                        You can then use the screen below for the next missing graphic(s).
2



        2. If any graphic files are missing you will see this message.
           Click OK to repair the links in InDesign later.




    3



        3. If there are grouped or locked objects in the converted Quark
           file you will see this message. Often there are warning messages
           because of minor conversion issues.


                                                             Workshop 1 • Getting Started
7

5

                                                                                            7. Confirm all preferences including Baseline Grid.
                                                                                               Under Edit menu > Preferences > General, Type, etc.
    5. Create a new, clean InDesign document which will be used as
       a master template incorporating all swatches and most styles.
       Under File > New > Document. Set specifications.




    6



    6. Save and name preset.                                                                                                                    Libraries
                                                                                                                                                must be
                                                                                 8. Use only CMYK color swatches.
    Each document will be one section of the publication.                                                                                       created
                                                                                    Delete any rgb swatches.                                   in current
                                                                                                                                               application
    To prepare document you also need access to your live Quark and Word files
                                                                                                                                                 version
    (suggest creating desktop shortcut for easier navigation).                                              8

    Use real text, not dummy text (to later check paragraph styles and the
    hyphenation & justification values within the paragraph styles).


                                         Workshop 1 • Create the InDesign Document
Codes & Standards
   Standard column configurations     Non-printing layout margins &                 The Debate Over Circuit Breakers vs.
   are created for whatever is        columns for inside, outside, top
                                                                                    Fused Solutions Continues
   present in the magazine:           and bottom set to live area.
   (2 col, 3 col, 2 + 3 col, etc.)    Column numbers are set on                     By First Last, Italic Byline [c-s]




                                                                                   I 
   We use one text box with column    individual master pages for                        have a number of reservations about the tech-          ally take less total space than CB switchgear and 
   and gutter settings, rather than   standard column configurations.                    nical issues in Mr. Lane’s articles, which broke       be less expensive. The use of Class-J time-delay 
                                                                                         down changes to the NEC and suggested fused            current-limiting fuses may also reduce the size of 
   multiple threaded frames.          Temporary guides are sometimes                     distribution may not always be necessary when          equipment. What about the short-circuit rating 
                                      set to mark important guides,                 considering selective coordination requirements.            of other components such as busway? How will 
                                                                                        Both  circuit  breaker  (CB)  and  fused  systems       they be affected by the short-delay trips? It is com-
                                      such as for rules in column                   provide safe and reliable overcurrent protection            mon in high-rise construction to run busway from 
                                      gutters, etc.                                 when systems are carefully engineered, installed            the main switchgear to distribution panels or to 
                                                                                    and maintained. But there are significant differ-           use plug-in busway to feed main-lug only (MLO) 
                                                                                    ences that must be recognized.                              branch panels.
                                                                                        The first problem with all three articles is they do 
                                                                                                                                                (Subhead) unnecessary risks
                                                                                    not look at a complete system. The one-line diagram      
                                                                                    in part two of the series, “The Skinny on Switchgear           The same diagram shows an 800-amp CB with 
                                                                                    and the New NEC,” (CSE 9/05, p.15), shows a feeder          short delay trips protecting the automatic transfer 
                                                                                    breaker in the main switchgear (not switchboard) of         switch (ATS). Will the ATS have an adequate  short-
                                                                                    800 amps, but neither the size of the main breaker          circuit rating? One ATS manufacturer tests and UL 
                                                                                    is indicated, nor  whether there is a main breaker or       lists its units only when protected by current-lim-
                                                                                    a sequence service. Is there coordination between           iting fuses or CB with clearing times of less than 
                                                                                    the 800-amp feeder breaker and the main breaker?            three cycles. Generators commonly have short-n 
                                                                                    To achieve this, the main breaker would require a           is there. It is almost a knee-jerk response. While 
                                                                                    short delay trip set at 12 cycles. The vast majority of     some industries have planned shutdowns for ser-
                                                                                    transformers in commercial and industrial systems           vice and maintenance purposes, commercial and 
                                                                                                                                                other industries seldom can do so except at late 
                                                                                                                                                hours. This , it should be included in every project 
                                                                         Considering only space, fused switchboards can
                                                                                                                                                specification. To do less is to increase hazard to 
                                                                         take up less total space than CB switchgear, cost
                                                                                                                                                personnel. No engineer can do so and meet the 
                                                                         less and require no need for rear access.
                                                                                                                                                ethics of his profession.


                                                                                                                                                   Author Keith Lane responds: My intent was 
                                                                                    are protected on the primary side by current-limiting 
                                                                                    fuses. What would the coordination be? It’s difficult       to solicit good conversation in the engineering 
                                                                                    enough to coordinate CB having instantaneous trips          community, which I think my article has succeeded 
                                                                                    with primary current-limiting fuses.                        in doing. I am certainly not against AHJs adopting 
                                                                                       If the primary fuses open—admittedly, this rarely        the 2005 NEC. The heart of the piece was the issue 
                                                                                    happens—the system is down until the utility replac-        of selective coordination but neither the size of the 
                                                                                    es the fuses, and only after determining there is no        main breaker is indicated, nor  whether there is a 
                                                                                    problem in the transformer or main switchgear.              main breaker or a sequence service. Is there coor-
                                                                                       Any  facility  requiring  an  800-amp  CB  for  the      dination between the 800-amp feeder breakerAs 
                                                                                    emergency system must be fairly large. It is reason-        noted  in  my  conclusion,  I  am  in  favor  of  good 
                                                                                    able to assume a 2.5% impedance high-efficiency             engineering analysis, which would include a com-
                                                                                    1,500- or 2,000-kVA transformer. Available short-           prehensive fault current calculation, coordination 
                                                                                    circuit current could easily be more than 75,000            study and  appropriate settinehensive fault current 
                                                                                    amps. What is the cost of CB switchgear-type con-           analysis, priate setting of the breakers or with the 

Workshop 1 • Master page A with 2 column configuration, baseline grid and live text for mockup
                                                                                    struction opposed to a bolted pressure switch and           use of fused distribution, the reliability of electrical 
                                                                                    fuse switchboard? Considering only space, fused             distribution systems would be increased over what 
                                                                                    switchboards are readily available. They may actu-          is required by the NEC prior to 2005.

                                                                                                                                                                                                            A
                                                                                                                                                   Consulting-Specifying Engineer • MONTH, 2006
Codes & Standards                                                                                                                               Codes & Standards
       It was quite obvious that the contrac-       ing the contractor’s work.                     that the contractor is responsible for the          It was quite obvious that the contrac-       ing the contractor’s work.                     that the contractor is responsible for the 
    tor  had  installed  bolts  that  were  too        But  let’s  return  in  time  to  the       methods and materials of constructing            tor  had  installed  bolts  that  were  too        But  let’s  return  in  time  to  the       methods and materials of constructing 
    short to fully engage the threads of the        developer’s initial concern about the struc-   the project. But as soon as an engineer          short to fully engage the threads of the        developer’s initial concern about the struc-   the project. But as soon as an engineer 
    nut. While on the site, the engineer also       tural connection. The engineer observes        states, even in ambiguous terms, that the        nut. While on the site, the engineer also       tural connection. The engineer observes        states, even in ambiguous terms, that the 
    noted that the stucco lath and moisture         the same condition, but this time offers       work is “complete,” he or she has joined         noted that the stucco lath and moisture         the same condition, but this time offers       work is “complete,” he or she has joined 
    barrier operations had been completed.          a substantially different report about the     right in on the responsib. Designers and         barrier operations had been completed.          a substantially different report about the     right in on the responsib. Designers and 
    In his follow-up report of the site visit,      stucco: “Stucco lath and moisture barrier      specifiers should maintain strict control        In his follow-up report of the site visit,      stucco: “Stucco lath and moisture barrier      specifiers should maintain strict control 
    the engineer cited the bolting deficiency,      work appears complete. Since structural        over the actual duties that they assume,         the engineer cited the bolting deficiency,      work appears complete. Since structural        over the actual duties that they assume, 
    with a correction, and also wrote that          integrity of the building depends on the       and they should avoid even the appear-           with a correction, and also wrote that          integrity of the building depends on the       and they should avoid even the appear-
    “the stucco cladding paper and lath is          fastener use and placement for positive        ance of approving an owner’s. By simply          “the stucco cladding paper and lath is          fastener use and placement for positive        ance of approving an owner’s. By simply 
    complete,  ready  for  the  scratch  coat.”     attachment to the frame, it is strongly        adding, “The Owner should verify with            complete,  ready  for  the  scratch  coat.”     attachment to the frame, it is strongly        adding, “The Owner should verify with 
    This report became a key issue in the case      recommended that you verify through            the equipment manufacturer’s represen-           This report became a key issue in the case      recommended that you verify through            the equipment manufacturer’s represen-
    against  the  designer,  as  the  structural    the  building  department  or  a  deputy       tative that all connecr this application,”       against  the  designer,  as  the  structural    the  building  department  or  a  deputy       tative that all connecr this application,” 
    design allowed for the stucco cladding to       inspector that the details of the specifi-     the engineer places responsibility better        design allowed for the stucco cladding to       inspector that the details of the specifi-     the engineer places responsibility better 
    participate in the building’s lateral force     cations were faithfully adhered to.”           informed and in a better position where          participate in the building’s lateral force     cations were faithfully adhered to.”           informed and in a better position where 
    resistance system.                                 The  engineer  has  just  directed  the     it belongs—back with the owner.                  resistance system.                                 The  engineer  has  just  directed  the     it belongs—back with the owner.
       Two  years  later,  when  cracks  in  the    owner or developer to verify compliance                                                            Two  years  later,  when  cracks  in  the    owner or developer to verify compliance 
                                                                                                   Recommendations                                                                                                                                 Recommendations
    stucco and other collateral finishes were       with some other entity and has pointed                                                          stucco and other collateral finishes were       with some other entity and has pointed 
    observed, it was determined by forensic         out that it is a critical component of the        The  use  of  “recommendation”  lan-          observed, it was determined by forensic         out that it is a critical component of the        The  use  of  “recommendation”  lan-
    experts that the attachment of the lath         building’s design. Thus, the liability has     guage cannot be emphasized enough,               experts that the attachment of the lath         building’s design. Thus, the liability has     guage cannot be emphasized enough, 
    to the wood frame employed staples that         been kept in the lap of the owner. The         not only for observation reports of site vis-    to the wood frame employed staples that         been kept in the lap of the owner. The         not only for observation reports of site vis-
    were  too  short,  and  that  the  fastener     same  use  of  “recommendations”  can          its, but also certificates for payment and       were  too  short,  and  that  the  fastener     same  use  of  “recommendations”  can          its, but also certificates for payment and 
    spacing exceeded the design specifica-                                                                                    written requests      spacing exceeded the design specifica-                                                                                    written requests 
    tions. Essentially, the weight of the stucco                                                                              for  information      tions. Essentially, the weight of the stucco                                                                              for  information 
                                                     Considering only space, fused switchboards can                                                                                                 Considering only space, fused switchboards can
    exceeded the capacity of the fasteners                                                                                    from the contrac-     exceeded the capacity of the fasteners                                                                                    from the contrac-
                                                     take up less total space than CB switchgear, cost                                                                                              take up less total space than CB switchgear, cost
    to secure it to the frame. The engineer’s                                                                                 tors. By including    to secure it to the frame. The engineer’s                                                                                 tors. By including 
                                                     less and require no need for rear access.                                                                                                      less and require no need for rear access.
    written report of observation was inter-                                                                                  a  recommenda-        written report of observation was inter-                                                                                  a  recommenda-
    preted by the developer’s attorney as an                                                                                  tion  to  verify,     preted by the developer’s attorney as an                                                                                  tion  to  verify, 
    endorsement of the contractor’s adher-          charge  the  owner  to  seek  verification  confirm,  validate  appropriate,  design            endorsement of the contractor’s adher-          charge  the  owner  to  seek  verification  confirm,  validate  appropriate,  design 
    ence to the structural design.                  from the contractor, thus asserting that  professionals place themselves one step               ence to the structural design.                  from the contractor, thus asserting that  professionals place themselves one step 
       Attorneys for the developer cited the        the engineer’s observation was not an  further from the inevitable dispute. The                    Attorneys for the developer cited the        the engineer’s observation was not an  further from the inevitable dispute. The 
    field report, indicating that it provided       inspection. More importantly, it estab- following is a suggested checklist:                     field report, indicating that it provided       inspection. More importantly, it estab- following is a suggested checklist:
    a  representation  that  all  of  the  work     lishes that inspection of the work is out-        ●  Limit  observations  and  report  lan-     a  representation  that  all  of  the  work     lishes that inspection of the work is out-        ●  Limit  observations  and  report  lan-

    observed by the engineer was consistent         side of the engineer’s scope.                  guage to the purpose o.                          observed by the engineer was consistent         side of the engineer’s scope.                  guage to the purpose o.
    with industry practices and wisdom. They           The key to this area of practice is to         ●  Limit  oral  conversations  with  the      with industry practices and wisdom. They           The key to this area of practice is to         ●  Limit  oral  conversations  with  the 

    argued  that  the  engineer’s  comment          be always mindful of the duty that one  contractor to basic items. Follow low up                argued  that  the  engineer’s  comment          be always mindful of the duty that one  contractor to basic items. Follow low up 
    that  “...the  stucco  cladding  paper  and     can  end  up  assuming  as  a  result  of  a  substantive  questions  every  report  or         that  “...the  stucco  cladding  paper  and     can  end  up  assuming  as  a  result  of  a  substantive  questions  every  report  or 
    lath is complete” additionally inferred,        simple  conversation  or  a  brief  written  written oral conversation.                         lath is complete” additionally inferred,        simple  conversation  or  a  brief  written  written oral conversation.
    “...according to building codes and my          memo.  Once  again,  although  the  case          ●  Include “recommendations to verify”        “...according to building codes and my          memo.  Once  again,  although  the  case          ●  Include “recommendations to verify” 

    specs.” The court agreed and held that no       involved  a  structural  design  issue,  the  in every report or written correspondence         specs.” The court agreed and held that no       involved  a  structural  design  issue,  the  in every report or written correspondence 
    other individual was better informed and        same  practice  should  be  incorporated  dealing with contractor rify through the              other individual was better informed and        same  practice  should  be  incorporated  dealing with contractor rify through the 
    in a better position to observe a defect        into the standard policies of all disciplines  building department or a deputy inspec-          in a better position to observe a defect        into the standard policies of all disciplines  building department or a deputy inspec-
    in the application of the lath than the         of engineering. Designers and specifiers  tor that performance.                                 in the application of the lath than the         of engineering. Designers and specifiers  tor that performance.
    engineer. The engineer was found by the         should maintain strict control over the           ●  Follow  up  in  writing,  asking  the      engineer. The engineer was found by the         should maintain strict control over the           ●  Follow  up  in  writing,  asking  the 

    court to have contributed substantially to      actual duties that they assume, and they  owner/developer if their verification of              court to have contributed substantially to      actual duties that they assume, and they  owner/developer if their verification of 
    the failures of the stucco attac ures of the    should  avoid  even  the  appearance  of  the work confirmed compliance by the                  the failures of the stucco attac ures of the    should  avoid  even  the  appearance  of  the work confirmed compliance by the 
    stucco attachment.                              approving an owner’s and contractor’s  contractor, manufacturer or fabricator.                  stucco attachment.                              approving an owner’s and contractor’s  contractor, manufacturer or fabricator.
                                                    work.  Otherwise,  the  other  players  in        ●  Limit the construction-phase services                                                      work.  Otherwise,  the  other  players  in        ●  Limit the construction-phase services 

    Avoiding risk                                                                                                                                   Avoiding risk
                                                    the construction drama will be delighted  wherever possible. The project rarely has                                                             the construction drama will be delighted  wherever possible. The project rarely has 
       How could this liability risk have been      to hand the engineer their responsibili- a sufficient budget to allow for detailed                 How could this liability risk have been      to hand the engineer their responsibili- a sufficient budget to allow for detailed 
    avoided? It’s all about duty. In this situa-    ties  and receive the endorsement of the  verification of design compliance.                    avoided? It’s all about duty. In this situa-    ties  and receive the endorsement of the  verification of design compliance.

    Workshop 1 • Master page B with 3 column configuration, baseline grid and live text for mockup
    tion, the engineer snatched liability away      design  professional  for  the  work  they        The key to this area of practice is to        tion, the engineer snatched liability away      design  professional  for  the  work  they        The key to this area of practice is to 
    from the contractor and the developer by        have  just  completed.  The  construction  be always mins a result conversation or              from the contractor and the developer by        have  just  completed.  The  construction  be always mins a result conversation or 
    voluntarily assuming the duty of evaluat-       industry  has  established  the  standard  a brief written memo. Once again,                    voluntarily assuming the duty of evaluat-       industry  has  established  the  standard  a brief written memo. Once again, 

                                                                                                                                                                                                                                                                                                    B
B                                                                                                                                                                                                                                            Consulting-Specifying Engineer • MONTH, 2006
    Consulting-Specifying Engineer • MONTH, 2006
Codes & Standards
                                                          p-style                                                       c-style
                                                          Section                                                    Bold Section




                                                   The Debate Over Circuit Breakers vs.
                                   p-style
                                   Head

                                                   Fused Solutions Continues
                                                   ByLine [p-styLe], Italic Byline [c-style]




                                                  I 
                                                                          p-style
                                                        have a number of reservations about the tech-          ally take less total space than CB switchgear and 
                                                                     Text DropCap
                                                        nical issues in Mr. Lane’s articles, which broke       be less expensive. The use of Class-J time-delay 
                                                                     [nested DropCap]
                                                        down changes to the NEC and suggested fused            current-limiting fuses may also reduce the size of 
                                                        distribution may not always be necessary when          equipment. What about the short-circuit rating 
                                                   considering selective coordination requirements.            of other components such as busway? How will 
                                                       Both  circuit  breaker  (CB)  and  fused  systems       they be affected by the short-delay trips? It is com-
                                                   provide safe and reliable overcurrent protection            mon in high-rise construction to run busway from 
                                                                          p-style
                                                   when systems are carefully engineered, installed            the main switchgear to distribution panels or to 
                                                                           Text
                                                   and maintained. But there are significant differ-           use plug-in busway to feed main-lug only (MLO) 
                                                                                                                      p-style
                                                   ences that must be recognized.                              branch panels.
                                                                                                                    Subhead
                                                       The first problem with all three articles is they do 
                                                                                                               (Subhead) unnecessary risks
                                                   not look at a complete system. The one-line diagram      
                                                   in part two of the series, “The Skinny on Switchgear           The same diagram shows an 800-amp CB with 
                                                   and the New NEC,” (CSE 9/05, p.15), shows a feeder          short delay trips protecting the automatic transfer 
                                                   breaker in the main switchgear (not switchboard) of         switch (ATS). Will the ATS have an adequate  short-
                                                   800 amps, but neither the size of the main breaker          circuit rating? One ATS manufacturer tests and UL 
                                                   is indicated, nor  whether there is a main breaker or       lists its units only when protected by current-lim-
                                                   a sequence service. Is there coordination between           iting fuses or CB with clearing times of less than 
                                                   the 800-amp feeder breaker and the main breaker?            three cycles. Generators commonly have short-n 
                                                   To achieve this, the main breaker would require a           is there. It is almost a knee-jerk response. While 
                                                   short delay trip set at 12 cycles. The vast majority of     some industries have planned shutdowns for ser-
                                                   transformers in commercial and industrial systems           vice and maintenance purposes, commercial and 
                                                                                                               other industries seldom can do so except at late 
                                                                                                                        p-style
                                                                   p-style                                     hours. This , it should be included in every project 
                                        Considering only space, fused switchboards can                                   Text
                                                                  PullQuote                                    specification. To do less is to increase hazard to 
                                        take up less total space than CB switchgear, cost
                                                                                                                        c-style
                                                                                                               personnel. No engineer can do so and meet the 
                                        less and require no need for rear access.
                                                                                                                     Bold Text
                                                                                                               ethics of his profession.


                                                                                                                  Author Keith Lane responds: My intent was 
                                                   are protected on the primary side by current-limiting 
                                                   fuses. What would the coordination be? It’s difficult       to solicit good conversation in the engineering 
                                                   enough to coordinate CB having instantaneous trips          community, which I think my article has succeeded 
                                                   with primary current-limiting fuses.                        in doing. I am certainly not against AHJs adopting 
                                                      If the primary fuses open—admittedly, this rarely        the 2005 NEC. The heart of the piece was the issue 
                                                   happens—the system is down until the utility replac-        of selective coordination but neither the size of the 
                                                   es the fuses, and only after determining there is no        main breaker is indicated, nor  whether there is a 
                                                   problem in the transformer or main switchgear.              main breaker or a sequence service. Is there coor-
                                                      Any  facility  requiring  an  800-amp  CB  for  the      dination between the 800-amp feeder breakerAs 
                                                   emergency system must be fairly large. It is reason-        noted  in  my  conclusion,  I  am  in  favor  of  good 
                                                   able to assume a 2.5% impedance high-efficiency             engineering analysis, which would include a com-
                                                   1,500- or 2,000-kVA transformer. Available short-           prehensive fault current calculation, coordination 
                                                   circuit current could easily be more than 75,000            study and  appropriate settinehensive fault current 
                                                   amps. What is the cost of CB switchgear-type con-           analysis, priate setting of the breakers or with the 

Workshop 2 • RBI Paragraph & Character Styles for Master page A
                                                   struction opposed to a bolted pressure switch and           use of fused distribution, the reliability of electrical 
                                                   fuse switchboard? Considering only space, fused             distribution systems would be increased over what 
                                                   switchboards are readily available. They may actu-          is required by the NEC prior to 2005.

                                                                                                                                                                           A
                                                                                                                  Consulting-Specifying Engineer • MONTH, 2006
Codes & Standards
                                                                 p-style                                                        c-style
                                                                 Section                                                     Bold Section




                                                          The Debate Over Circuit Breakers vs.
                                         p-style
                                         Head

                                                          Fused Solutions Continues
                                         c-style          ByLine [p-styLe], Italic Byline [c-style]
                                       BoldItalics
                                       NotesEditor        Editor’s note: This month’s Codes & Standards, following the tone set in Letters (p.7), is an in-depth rebut-
                                         [nested]
                                                          tal to Keith Lane’s August-through-October series analyzing the 2005 edition of the NEC. A response from Mr.
                                         p-style          Lane follows. It should be noted that Lane’s original article was run in three parts because of length.
                                       NotesEditor




                                                         I 
                                                             have a number of reservations about the tech-            size of the main breaker is indicated, nor  whether 
                                                                               p-style
                                                                          Text DropCap
                                                             nical issues in Mr. Lane’s articles, which broke         there is a main breaker or a sequence service. Is 
                                                                          [nested DropCap]
                                                             down changes to the NEC and suggested fused              there coordination between the 800-amp feeder 
                                                             distribution may not always be necessary when            breaker and the main breaker? To achieve this, the 
                                                          considering selective coordination requirements.            main breaker would require a short delay trip set 
                                                            Both  circuit  breaker  (CB)  and  fused  systems         at 12 cycles. The vast majority of transformers in 
                                                          provide safe and reliable overcurrent protection            commercial and industrial systems are protected 
                                                                               p-style
                                                          when systems are carefully engineered, installed            on the primary side by current-limiting fuses. What 
                                                                                Text
                                                          and maintained. But there are significant differ-           would the coordination be? It’s difficult enough 
                                                          ences that must be recognized.                              to coordinate CB having instantaneous trips with 
                                                                                                                             p-style
                                                            The first problem with all three articles is they         primary current-limiting fuses.
                                                                                                                            Subhead

                                                                          p-style                                     (Subhead) unnecessary risks
                                               Considering only space, fused switchboards can
                                                                         PullQuote                                       The same diagram shows an 800-amp CB with 
                                               take up less total space than CB switchgear, cost
                                                                                                                      short delay trips protecting the automatic trans-
                                               less and require no need for rear access.
                                                                                                                      fer switch (ATS). Will the ATS have an adequate     
                                                                                                                      short-there is no problem in the transformer or 
                                                          do not look at a complete system. The one-line              main switchgmp fault on the load side of a branch 
                                                          diagram  in part two of the series, “The Skinny on          breaker may cause all three CBs to open. If power 
                                                          Switchgear and the New NEC,” (CSE 9/05, p.15),              look? After the fa removed, the switches and CBs 
                                                          shows a feeder breaker in the main switchgear               trical distribution systems would be increased over 
                                                          (not switchboard) of 800 amps, but neither the              what is required by the NEC prior to 2005.




                                                                             p-style
                                                                         GraphicCaption

                                                          1,250-hp, 3600-rpm, 2,300-volt, WP-1 enclosure, constant-speed motor drives an aeration blower at Weyerhaeuser’s
                                                          Longview Complex.




Workshop 2 • RBI Paragraph & Character Styles for optional Master Page A
                                                                                                                                                                             A
                                                                                                                          Consulting-Specifying Engineer • MONTH, 2006
Codes & Standards
                                                                                     element label
                                                                                        Section




                                                                                   The Debate Over Circuit Breakers vs.
                                                                element label
                                                                    Head

                                                                                   Fused Solutions Continues
                                                                element label
                                                                                   ByLine [p-styLe], Italic Byline [c-style]
                                                                   Byline
                                                                                   Editor’s note: This month’s Codes & Standards, following the tone set in Letters (p.7), is an in-depth rebut-
                                                                element label
                                                                                   tal to Keith Lane’s August-through-October series analyzing the 2005 edition of the NEC. A response from Mr.
                                                                    Intro
                                                                                   Lane follows. It should be noted that Lane’s original article was run in three parts because of length.




                                                                                  I 
                                                                                      have a number of reservations about the tech-            size of the main breaker is indicated, nor  whether 
                                                                                                   element label
                                                                                      nical issues in Mr. Lane’s articles, which broke         there is a main breaker or a sequence service. Is 
                                                                                                        Body
                                                                                      down changes to the NEC and suggested fused              there coordination between the 800-amp feeder 
                                                                                      distribution may not always be necessary when            breaker and the main breaker? To achieve this, the 
                                                                                   considering selective coordination requirements.            main breaker would require a short delay trip set 
                                                                                     Both  circuit  breaker  (CB)  and  fused  systems         at 12 cycles. The vast majority of transformers in 
                                                                                   provide safe and reliable overcurrent protection            commercial and industrial systems are protected 
                                                                element label
                                                                                   when systems are carefully engineered, installed            on the primary side by current-limiting fuses. What 
                                                                   Graphic
                                                                                   and maintained. But there are significant differ-           would the coordination be? It’s difficult enough 
                                                                                   ences that must be recognized.                              to coordinate CB having instantaneous trips with 
                                                                                     The first problem with all three articles is they         primary current-limiting fuses.


                                                                                                element label                                  (Subhead) unnecessary risks
                                                                        Considering only space, fused switchboards can
Accurate element labels must be included for all text and                                         Pullquote                                       The same diagram shows an 800-amp CB with 
                                                                        take up less total space than CB switchgear, cost
graphic frames. Under Window > Show Element Labels                                                                                             short delay trips protecting the automatic trans-
                                                                        less and require no need for rear access.
                                                                                                                                               fer switch (ATS). Will the ATS have an adequate     
(this feature for Smart Connection Enterprise rollout).                                                                                        short-there is no problem in the transformer or 
                                                                                   do not look at a complete system. The one-line              main switchgmp fault on the load side of a branch 
Do not group frames because element labels will be disgarded.                      diagram  in part two of the series, “The Skinny on          breaker may cause all three CBs to open. If power 
                                                                                   Switchgear and the New NEC,” (CSE 9/05, p.15),              look? After the fa removed, the switches and CBs 
                                                                                   shows a feeder breaker in the main switchgear               trical distribution systems would be increased over 
                                                                                   (not switchboard) of 800 amps, but neither the              what is required by the NEC prior to 2005.


                                                                                                    element label
                                                                                                       Graphic




                                                                                                    element label
                                                                                                       Caption

                                                                                   1,250-hp, 3600-rpm, 2,300-volt, WP-1 enclosure, constant-speed motor drives an aeration blower at Weyerhaeuser’s
                                                                                   Longview Complex.




                    Workshop 2 • RBI Element labels for Smart Connection Enterprise
                                                                                                                                                                                                      A
                                                                                                                                                   Consulting-Specifying Engineer • MONTH, 2006
p-style


                                                                                                                              Codes & Standards
                                                                                                       Section
                                                                                                                                                                      c-style
FIlE PREPaRaTIoN FoR E-loGIC REvIEw
                                                                                                                                                                   Bold Section
                                                                                                  element label
1. Review ALL documents with art director and CMS prior to e-Logic review.                           Section

2. All mockups will be sent to e-Logic with complete paragraph and character
   styles and element labels in place.
                                                                                                The Debate Over Circuit Breakers vs.
3. Suggest locking frames on Master Pages that don’t move, such as a folio or                   Fused Solutions Continues
   section name.
                                                                                                ByLine [p-styLe], Italic Byline [c-style]
4. With all document pages highlighted in pages palette, Override All Master
   Page Items on document pages for e-Logic review. Pages palette > Fly out                     Editor’s note: This month’s Codes & Standards, following the tone set in Letters (p.7), is an in-depth rebut-
                                                                                                tal to Keith Lane’s August-through-October series analyzing the 2005 edition of the NEC. A response from Mr.
   menu > Override All Master Page Items (Alt+Shift-Ctr+L). This must be                        Lane follows. It should be noted that Lane’s original article was run in three parts because of length.
   done because e-Logic reviews document pages, not master pages.


                                                                                               I 
                                                                                                   have a number of reservations about the tech-            size of the main breaker is indicated, nor  whether 
5. Make revisions as required by e-Logic report.                                                   nical issues in Mr. Lane’s articles, which broke         there is a main breaker or a sequence service. Is 
                                                                                                   down changes to the NEC and suggested fused              there coordination between the 800-amp feeder 
                                                                                                   distribution may not always be necessary when            breaker and the main breaker? To achieve this, the 
  Save and keep all documents with live text (mockup) prior to stripping out the                considering selective coordination requirements.            main breaker would require a short delay trip set 
  text. These files are the ones that get sent to e-Logic, with complete paragraph                Both  circuit  breaker  (CB)  and  fused  systems         at 12 cycles. The vast majority of transformers in 
  and character styles and element labels in place.                                             provide safe and reliable overcurrent protection            commercial and industrial systems are protected 
                                                                                                when systems are carefully engineered, installed            on the primary side by current-limiting fuses. What 
                                                                                                and maintained. But there are significant differ-           would the coordination be? It’s difficult enough 
                                                                                                ences that must be recognized.                              to coordinate CB having instantaneous trips with 
                                        4
                                                                                                  The first problem with all three articles is they         primary current-limiting fuses.


                                                                                                                                                            (Subhead) unnecessary risks
                                                                                     Considering only space, fused switchboards can
                                                                                                                                                               The same diagram shows an 800-amp CB with 
                                                                                     take up less total space than CB switchgear, cost
                                                                                                                                                            short delay trips protecting the automatic trans-
                                                                                     less and require no need for rear access.
                                                                                                                                                            fer switch (ATS). Will the ATS have an adequate     
                                                                                                                                                            short-there is no problem in the transformer or 
                                                                                                do not look at a complete system. The one-line              main switchgmp fault on the load side of a branch 
                                                                                                diagram  in part two of the series, “The Skinny on          breaker may cause all three CBs to open. If power 
                                                                                                Switchgear and the New NEC,” (CSE 9/05, p.15),              look? After the fa removed, the switches and CBs 
                                                                                                shows a feeder breaker in the main switchgear               trical distribution systems would be increased over 
                                                                                                (not switchboard) of 800 amps, but neither the              what is required by the NEC prior to 2005.




      4




                                                                                                1,250-hp, 3600-rpm, 2,300-volt, WP-1 enclosure, constant-speed motor drives an aeration blower at Weyerhaeuser’s
                                                                                                Longview Complex.




                              Workshop 3 • Mockup to art director, CMS, e-Logic for review
                                                                                                                                                                                                                   A
                                                                                                                                                                Consulting-Specifying Engineer • MONTH, 2006
Codes & Standards
aFTER DoCumENT aPPRoval By E-loGIC CREaTE THE aCTual TEmPlaTE                                                     3


1. In each master page, create dummy text in all frames—dummy text is
   the actual name of the style sheet used (text is stripped out except for
   style names).
                                                                                                 Head
                                                                                         2
2. Examples: in the head frame you would type Head; in the Byline
   frame type Byline, Italic Byline [c-style]; in the NotesEditor frame type
   NotesEditor; in the body frame type Text DropCap, Text, Subhead, etc.                 2       ByLine [p-styLe], Italic Byline [c-style]
   (using the appropriate paragraph styles, see samples).
                                                                                                 Editor’s note: NotesEditor
3. There are some exceptions such as the name of the Section and Editor’s
   Note (a nested c-style), which don’t change. In these cases—when the                                 3             2




                                                                                                T
                                                                                                 
   text doesn’t change—leave the live text intact.                                       2               ext DropCap 
                                                                                                           Text
4. Document pages must be revised to the format of the updated Master
   Pages.                                                                                                Subhead
                                                                                                           Text 
5. All templates will have complete paragraph and character styles and
   element labels in place.




                                                                                       PullQuote PullQuote


    Save and keep all documents with live text (mockup) prior to stripping out the
    text. These files are the ones that get sent to e-Logic, with complete paragraph
    and character styles and element labels in place.




                                                                                                                                                                     Remember,
                                                                                                                                                                      InDesign
                                                                                                                                                                         has
                                                                                                                                                                      unlimited
                                                                                                                                                                        undos
                                                                                                                                                                        (ctr-z)



                                                                                                 GraphicCaption




                                                         Workshop 3 • Create actual template
                                                                                                                                                                                            A
                                                                                                                                             Consulting-Specifying Engineer • MONTH, 2006

More Related Content

Viewers also liked

Work Sch Collection
Work Sch CollectionWork Sch Collection
Work Sch Collectionnadin86
 
Auckland’s Governance Reforms
Auckland’s Governance ReformsAuckland’s Governance Reforms
Auckland’s Governance Reformsadalziel
 
Организация работы ресурсного центра "Тьютор", г. Омск
Организация работы ресурсного центра  "Тьютор", г. ОмскОрганизация работы ресурсного центра  "Тьютор", г. Омск
Организация работы ресурсного центра "Тьютор", г. Омскnadin86
 
Burn Wcms0708
Burn Wcms0708Burn Wcms0708
Burn Wcms0708tvhs2012
 
Michele DeSoto
Michele DeSotoMichele DeSoto
Michele DeSotomdesoto
 
Edson Consulting Intro 9 May09
Edson Consulting Intro 9 May09Edson Consulting Intro 9 May09
Edson Consulting Intro 9 May09guest6cc137
 
Pray for indonesia - The BIGGEST Charity Seminar 2010 in Indonesia!
Pray for indonesia - The BIGGEST Charity Seminar 2010 in Indonesia!Pray for indonesia - The BIGGEST Charity Seminar 2010 in Indonesia!
Pray for indonesia - The BIGGEST Charity Seminar 2010 in Indonesia!lexusb
 
Why do usability problems go unfixed?
Why do usability problems go unfixed?Why do usability problems go unfixed?
Why do usability problems go unfixed?Steve Krug
 
Steve Krug Explains It All for You - SxSW 2011
Steve Krug Explains It All for You - SxSW 2011Steve Krug Explains It All for You - SxSW 2011
Steve Krug Explains It All for You - SxSW 2011Steve Krug
 
Steve Krug: Lazy Person's Guide to a Better World - UX Lisbon 2010
Steve Krug: Lazy Person's Guide to a Better World - UX Lisbon 2010Steve Krug: Lazy Person's Guide to a Better World - UX Lisbon 2010
Steve Krug: Lazy Person's Guide to a Better World - UX Lisbon 2010Steve Krug
 

Viewers also liked (12)

Work Sch Collection
Work Sch CollectionWork Sch Collection
Work Sch Collection
 
Auckland’s Governance Reforms
Auckland’s Governance ReformsAuckland’s Governance Reforms
Auckland’s Governance Reforms
 
Plan de estudios verano
Plan de estudios veranoPlan de estudios verano
Plan de estudios verano
 
Ershov
ErshovErshov
Ershov
 
Организация работы ресурсного центра "Тьютор", г. Омск
Организация работы ресурсного центра  "Тьютор", г. ОмскОрганизация работы ресурсного центра  "Тьютор", г. Омск
Организация работы ресурсного центра "Тьютор", г. Омск
 
Burn Wcms0708
Burn Wcms0708Burn Wcms0708
Burn Wcms0708
 
Michele DeSoto
Michele DeSotoMichele DeSoto
Michele DeSoto
 
Edson Consulting Intro 9 May09
Edson Consulting Intro 9 May09Edson Consulting Intro 9 May09
Edson Consulting Intro 9 May09
 
Pray for indonesia - The BIGGEST Charity Seminar 2010 in Indonesia!
Pray for indonesia - The BIGGEST Charity Seminar 2010 in Indonesia!Pray for indonesia - The BIGGEST Charity Seminar 2010 in Indonesia!
Pray for indonesia - The BIGGEST Charity Seminar 2010 in Indonesia!
 
Why do usability problems go unfixed?
Why do usability problems go unfixed?Why do usability problems go unfixed?
Why do usability problems go unfixed?
 
Steve Krug Explains It All for You - SxSW 2011
Steve Krug Explains It All for You - SxSW 2011Steve Krug Explains It All for You - SxSW 2011
Steve Krug Explains It All for You - SxSW 2011
 
Steve Krug: Lazy Person's Guide to a Better World - UX Lisbon 2010
Steve Krug: Lazy Person's Guide to a Better World - UX Lisbon 2010Steve Krug: Lazy Person's Guide to a Better World - UX Lisbon 2010
Steve Krug: Lazy Person's Guide to a Better World - UX Lisbon 2010
 

Similar to Template Building Workshop

Smart Client Development
Smart Client DevelopmentSmart Client Development
Smart Client DevelopmentTamir Khason
 
Rails Conf Europe 2007 Notes
Rails Conf  Europe 2007  NotesRails Conf  Europe 2007  Notes
Rails Conf Europe 2007 NotesRoss Lawley
 
ParaForming - Patterns and Refactoring for Parallel Programming
ParaForming - Patterns and Refactoring for Parallel ProgrammingParaForming - Patterns and Refactoring for Parallel Programming
ParaForming - Patterns and Refactoring for Parallel Programmingkhstandrews
 
Gigigo Workshop - Create an iOS Framework, document it and not die trying
Gigigo Workshop - Create an iOS Framework, document it and not die tryingGigigo Workshop - Create an iOS Framework, document it and not die trying
Gigigo Workshop - Create an iOS Framework, document it and not die tryingAlex Rupérez
 
HowTo Build an OSGI EJB3 Server
HowTo Build an OSGI EJB3 ServerHowTo Build an OSGI EJB3 Server
HowTo Build an OSGI EJB3 Serverekkehard gentz
 
Php Development With Eclipde PDT
Php Development With Eclipde PDTPhp Development With Eclipde PDT
Php Development With Eclipde PDTBastian Feder
 
symfony: An Open-Source Framework for Professionals (Dutch Php Conference 2008)
symfony: An Open-Source Framework for Professionals (Dutch Php Conference 2008)symfony: An Open-Source Framework for Professionals (Dutch Php Conference 2008)
symfony: An Open-Source Framework for Professionals (Dutch Php Conference 2008)Fabien Potencier
 
Hadoop and Marklogic: Using the Genetic Algorithm to generate Source Code
Hadoop and Marklogic: Using the Genetic Algorithm to generate Source CodeHadoop and Marklogic: Using the Genetic Algorithm to generate Source Code
Hadoop and Marklogic: Using the Genetic Algorithm to generate Source Codejimfuller2009
 
The Tantric Team: Getting Your Automated Build Groove On
The Tantric Team: Getting Your Automated Build Groove OnThe Tantric Team: Getting Your Automated Build Groove On
The Tantric Team: Getting Your Automated Build Groove OnAtlassian
 
Peer Code Review: In a Nutshell and The Tantric Team: Getting Your Automated ...
Peer Code Review: In a Nutshell and The Tantric Team: Getting Your Automated ...Peer Code Review: In a Nutshell and The Tantric Team: Getting Your Automated ...
Peer Code Review: In a Nutshell and The Tantric Team: Getting Your Automated ...Atlassian
 
Eclipse Pdt2.0 26.05.2009
Eclipse Pdt2.0 26.05.2009Eclipse Pdt2.0 26.05.2009
Eclipse Pdt2.0 26.05.2009Bastian Feder
 
Angular JS in 2017
Angular JS in 2017Angular JS in 2017
Angular JS in 2017Ayush Sharma
 
APPLE NetApp Runbook Style Guide_20150206_FINAL
APPLE NetApp Runbook Style Guide_20150206_FINALAPPLE NetApp Runbook Style Guide_20150206_FINAL
APPLE NetApp Runbook Style Guide_20150206_FINALJennifer Gallagher
 
Maintainable CSS
Maintainable CSSMaintainable CSS
Maintainable CSSStephen Hay
 
Java Builds with Maven and Ant
Java Builds with Maven and AntJava Builds with Maven and Ant
Java Builds with Maven and AntDavid Noble
 
Road to sbt 1.0 paved with server
Road to sbt 1.0   paved with serverRoad to sbt 1.0   paved with server
Road to sbt 1.0 paved with serverEugene Yokota
 
Craftsmanship in Computational Work
Craftsmanship in Computational WorkCraftsmanship in Computational Work
Craftsmanship in Computational WorkYung-Yu Chen
 

Similar to Template Building Workshop (20)

Smart Client Development
Smart Client DevelopmentSmart Client Development
Smart Client Development
 
Rails Conf Europe 2007 Notes
Rails Conf  Europe 2007  NotesRails Conf  Europe 2007  Notes
Rails Conf Europe 2007 Notes
 
ParaForming - Patterns and Refactoring for Parallel Programming
ParaForming - Patterns and Refactoring for Parallel ProgrammingParaForming - Patterns and Refactoring for Parallel Programming
ParaForming - Patterns and Refactoring for Parallel Programming
 
Gigigo Workshop - Create an iOS Framework, document it and not die trying
Gigigo Workshop - Create an iOS Framework, document it and not die tryingGigigo Workshop - Create an iOS Framework, document it and not die trying
Gigigo Workshop - Create an iOS Framework, document it and not die trying
 
HowTo Build an OSGI EJB3 Server
HowTo Build an OSGI EJB3 ServerHowTo Build an OSGI EJB3 Server
HowTo Build an OSGI EJB3 Server
 
Os Wilhelm
Os WilhelmOs Wilhelm
Os Wilhelm
 
Php Development With Eclipde PDT
Php Development With Eclipde PDTPhp Development With Eclipde PDT
Php Development With Eclipde PDT
 
symfony: An Open-Source Framework for Professionals (Dutch Php Conference 2008)
symfony: An Open-Source Framework for Professionals (Dutch Php Conference 2008)symfony: An Open-Source Framework for Professionals (Dutch Php Conference 2008)
symfony: An Open-Source Framework for Professionals (Dutch Php Conference 2008)
 
Hadoop and Marklogic: Using the Genetic Algorithm to generate Source Code
Hadoop and Marklogic: Using the Genetic Algorithm to generate Source CodeHadoop and Marklogic: Using the Genetic Algorithm to generate Source Code
Hadoop and Marklogic: Using the Genetic Algorithm to generate Source Code
 
Performance
PerformancePerformance
Performance
 
The Tantric Team: Getting Your Automated Build Groove On
The Tantric Team: Getting Your Automated Build Groove OnThe Tantric Team: Getting Your Automated Build Groove On
The Tantric Team: Getting Your Automated Build Groove On
 
Peer Code Review: In a Nutshell and The Tantric Team: Getting Your Automated ...
Peer Code Review: In a Nutshell and The Tantric Team: Getting Your Automated ...Peer Code Review: In a Nutshell and The Tantric Team: Getting Your Automated ...
Peer Code Review: In a Nutshell and The Tantric Team: Getting Your Automated ...
 
Eclipse Pdt2.0 26.05.2009
Eclipse Pdt2.0 26.05.2009Eclipse Pdt2.0 26.05.2009
Eclipse Pdt2.0 26.05.2009
 
Angular JS in 2017
Angular JS in 2017Angular JS in 2017
Angular JS in 2017
 
APPLE NetApp Runbook Style Guide_20150206_FINAL
APPLE NetApp Runbook Style Guide_20150206_FINALAPPLE NetApp Runbook Style Guide_20150206_FINAL
APPLE NetApp Runbook Style Guide_20150206_FINAL
 
Maintainable CSS
Maintainable CSSMaintainable CSS
Maintainable CSS
 
Java Builds with Maven and Ant
Java Builds with Maven and AntJava Builds with Maven and Ant
Java Builds with Maven and Ant
 
Road to sbt 1.0 paved with server
Road to sbt 1.0   paved with serverRoad to sbt 1.0   paved with server
Road to sbt 1.0 paved with server
 
Craftsmanship in Computational Work
Craftsmanship in Computational WorkCraftsmanship in Computational Work
Craftsmanship in Computational Work
 
Ibm redbook
Ibm redbookIbm redbook
Ibm redbook
 

Recently uploaded

[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdfhans926745
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024The Digital Insurer
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking MenDelhi Call girls
 
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure serviceWhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure servicePooja Nehwal
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)Gabriella Davis
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘RTylerCroy
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountPuma Security, LLC
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking MenDelhi Call girls
 
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...gurkirankumar98700
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptxHampshireHUG
 
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...shyamraj55
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationMichael W. Hawkins
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityPrincipled Technologies
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitecturePixlogix Infotech
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking MenDelhi Call girls
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Miguel Araújo
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerThousandEyes
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonetsnaman860154
 
SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024Scott Keck-Warren
 

Recently uploaded (20)

[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
 
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure serviceWhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
WhatsApp 9892124323 ✓Call Girls In Kalyan ( Mumbai ) secure service
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path Mount
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men
 
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
 
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivity
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC Architecture
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonets
 
SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024
 

Template Building Workshop

  • 1. Relink icon 1 4 1. From the Quark file, make sure all logos and graphics are in place. Through InDesign CS2, convert the Quark to an InDesign file. Use this converted InDesign file for reference only. 4. If any logos or graphics are missing or modified in the converted InDesign file, navigate to where they reside using the Links palette “Relink” icon. You can then use the screen below for the next missing graphic(s). 2 2. If any graphic files are missing you will see this message. Click OK to repair the links in InDesign later. 3 3. If there are grouped or locked objects in the converted Quark file you will see this message. Often there are warning messages because of minor conversion issues. Workshop 1 • Getting Started
  • 2. 7 5 7. Confirm all preferences including Baseline Grid. Under Edit menu > Preferences > General, Type, etc. 5. Create a new, clean InDesign document which will be used as a master template incorporating all swatches and most styles. Under File > New > Document. Set specifications. 6 6. Save and name preset. Libraries must be 8. Use only CMYK color swatches. Each document will be one section of the publication. created Delete any rgb swatches. in current application To prepare document you also need access to your live Quark and Word files version (suggest creating desktop shortcut for easier navigation). 8 Use real text, not dummy text (to later check paragraph styles and the hyphenation & justification values within the paragraph styles). Workshop 1 • Create the InDesign Document
  • 3. Codes & Standards Standard column configurations Non-printing layout margins & The Debate Over Circuit Breakers vs. are created for whatever is columns for inside, outside, top Fused Solutions Continues present in the magazine: and bottom set to live area. (2 col, 3 col, 2 + 3 col, etc.) Column numbers are set on By First Last, Italic Byline [c-s] I  We use one text box with column individual master pages for have a number of reservations about the tech- ally take less total space than CB switchgear and  and gutter settings, rather than standard column configurations. nical issues in Mr. Lane’s articles, which broke  be less expensive. The use of Class-J time-delay  down changes to the NEC and suggested fused  current-limiting fuses may also reduce the size of  multiple threaded frames. Temporary guides are sometimes distribution may not always be necessary when  equipment. What about the short-circuit rating  set to mark important guides, considering selective coordination requirements. of other components such as busway? How will  Both  circuit  breaker  (CB)  and  fused  systems  they be affected by the short-delay trips? It is com- such as for rules in column provide safe and reliable overcurrent protection  mon in high-rise construction to run busway from  gutters, etc. when systems are carefully engineered, installed  the main switchgear to distribution panels or to  and maintained. But there are significant differ- use plug-in busway to feed main-lug only (MLO)  ences that must be recognized.  branch panels. The first problem with all three articles is they do  (Subhead) unnecessary risks not look at a complete system. The one-line diagram    in part two of the series, “The Skinny on Switchgear  The same diagram shows an 800-amp CB with  and the New NEC,” (CSE 9/05, p.15), shows a feeder  short delay trips protecting the automatic transfer  breaker in the main switchgear (not switchboard) of  switch (ATS). Will the ATS have an adequate  short- 800 amps, but neither the size of the main breaker  circuit rating? One ATS manufacturer tests and UL  is indicated, nor  whether there is a main breaker or  lists its units only when protected by current-lim- a sequence service. Is there coordination between  iting fuses or CB with clearing times of less than  the 800-amp feeder breaker and the main breaker?  three cycles. Generators commonly have short-n  To achieve this, the main breaker would require a  is there. It is almost a knee-jerk response. While  short delay trip set at 12 cycles. The vast majority of  some industries have planned shutdowns for ser- transformers in commercial and industrial systems  vice and maintenance purposes, commercial and  other industries seldom can do so except at late  hours. This , it should be included in every project  Considering only space, fused switchboards can specification. To do less is to increase hazard to  take up less total space than CB switchgear, cost personnel. No engineer can do so and meet the  less and require no need for rear access. ethics of his profession. Author Keith Lane responds: My intent was  are protected on the primary side by current-limiting  fuses. What would the coordination be? It’s difficult  to solicit good conversation in the engineering  enough to coordinate CB having instantaneous trips  community, which I think my article has succeeded  with primary current-limiting fuses. in doing. I am certainly not against AHJs adopting  If the primary fuses open—admittedly, this rarely  the 2005 NEC. The heart of the piece was the issue  happens—the system is down until the utility replac- of selective coordination but neither the size of the  es the fuses, and only after determining there is no  main breaker is indicated, nor  whether there is a  problem in the transformer or main switchgear.  main breaker or a sequence service. Is there coor- Any  facility  requiring  an  800-amp  CB  for  the  dination between the 800-amp feeder breakerAs  emergency system must be fairly large. It is reason- noted  in  my  conclusion,  I  am  in  favor  of  good  able to assume a 2.5% impedance high-efficiency  engineering analysis, which would include a com- 1,500- or 2,000-kVA transformer. Available short- prehensive fault current calculation, coordination  circuit current could easily be more than 75,000  study and  appropriate settinehensive fault current  amps. What is the cost of CB switchgear-type con- analysis, priate setting of the breakers or with the  Workshop 1 • Master page A with 2 column configuration, baseline grid and live text for mockup struction opposed to a bolted pressure switch and  use of fused distribution, the reliability of electrical  fuse switchboard? Considering only space, fused  distribution systems would be increased over what  switchboards are readily available. They may actu- is required by the NEC prior to 2005. A Consulting-Specifying Engineer • MONTH, 2006
  • 4. Codes & Standards Codes & Standards It was quite obvious that the contrac- ing the contractor’s work. that the contractor is responsible for the  It was quite obvious that the contrac- ing the contractor’s work. that the contractor is responsible for the  tor  had  installed  bolts  that  were  too  But  let’s  return  in  time  to  the  methods and materials of constructing  tor  had  installed  bolts  that  were  too  But  let’s  return  in  time  to  the  methods and materials of constructing  short to fully engage the threads of the  developer’s initial concern about the struc- the project. But as soon as an engineer  short to fully engage the threads of the  developer’s initial concern about the struc- the project. But as soon as an engineer  nut. While on the site, the engineer also  tural connection. The engineer observes  states, even in ambiguous terms, that the  nut. While on the site, the engineer also  tural connection. The engineer observes  states, even in ambiguous terms, that the  noted that the stucco lath and moisture  the same condition, but this time offers  work is “complete,” he or she has joined  noted that the stucco lath and moisture  the same condition, but this time offers  work is “complete,” he or she has joined  barrier operations had been completed.  a substantially different report about the  right in on the responsib. Designers and  barrier operations had been completed.  a substantially different report about the  right in on the responsib. Designers and  In his follow-up report of the site visit,  stucco: “Stucco lath and moisture barrier  specifiers should maintain strict control  In his follow-up report of the site visit,  stucco: “Stucco lath and moisture barrier  specifiers should maintain strict control  the engineer cited the bolting deficiency,  work appears complete. Since structural  over the actual duties that they assume,  the engineer cited the bolting deficiency,  work appears complete. Since structural  over the actual duties that they assume,  with a correction, and also wrote that  integrity of the building depends on the  and they should avoid even the appear- with a correction, and also wrote that  integrity of the building depends on the  and they should avoid even the appear- “the stucco cladding paper and lath is  fastener use and placement for positive  ance of approving an owner’s. By simply  “the stucco cladding paper and lath is  fastener use and placement for positive  ance of approving an owner’s. By simply  complete,  ready  for  the  scratch  coat.”  attachment to the frame, it is strongly  adding, “The Owner should verify with  complete,  ready  for  the  scratch  coat.”  attachment to the frame, it is strongly  adding, “The Owner should verify with  This report became a key issue in the case  recommended that you verify through  the equipment manufacturer’s represen- This report became a key issue in the case  recommended that you verify through  the equipment manufacturer’s represen- against  the  designer,  as  the  structural  the  building  department  or  a  deputy  tative that all connecr this application,”  against  the  designer,  as  the  structural  the  building  department  or  a  deputy  tative that all connecr this application,”  design allowed for the stucco cladding to  inspector that the details of the specifi- the engineer places responsibility better  design allowed for the stucco cladding to  inspector that the details of the specifi- the engineer places responsibility better  participate in the building’s lateral force  cations were faithfully adhered to.” informed and in a better position where  participate in the building’s lateral force  cations were faithfully adhered to.” informed and in a better position where  resistance system. The  engineer  has  just  directed  the  it belongs—back with the owner. resistance system. The  engineer  has  just  directed  the  it belongs—back with the owner. Two  years  later,  when  cracks  in  the  owner or developer to verify compliance  Two  years  later,  when  cracks  in  the  owner or developer to verify compliance  Recommendations Recommendations stucco and other collateral finishes were  with some other entity and has pointed  stucco and other collateral finishes were  with some other entity and has pointed  observed, it was determined by forensic  out that it is a critical component of the  The  use  of  “recommendation”  lan- observed, it was determined by forensic  out that it is a critical component of the  The  use  of  “recommendation”  lan- experts that the attachment of the lath  building’s design. Thus, the liability has  guage cannot be emphasized enough,  experts that the attachment of the lath  building’s design. Thus, the liability has  guage cannot be emphasized enough,  to the wood frame employed staples that  been kept in the lap of the owner. The  not only for observation reports of site vis- to the wood frame employed staples that  been kept in the lap of the owner. The  not only for observation reports of site vis- were  too  short,  and  that  the  fastener  same  use  of  “recommendations”  can  its, but also certificates for payment and  were  too  short,  and  that  the  fastener  same  use  of  “recommendations”  can  its, but also certificates for payment and  spacing exceeded the design specifica- written requests  spacing exceeded the design specifica- written requests  tions. Essentially, the weight of the stucco  for  information  tions. Essentially, the weight of the stucco  for  information  Considering only space, fused switchboards can Considering only space, fused switchboards can exceeded the capacity of the fasteners  from the contrac- exceeded the capacity of the fasteners  from the contrac- take up less total space than CB switchgear, cost take up less total space than CB switchgear, cost to secure it to the frame. The engineer’s  tors. By including  to secure it to the frame. The engineer’s  tors. By including  less and require no need for rear access. less and require no need for rear access. written report of observation was inter- a  recommenda- written report of observation was inter- a  recommenda- preted by the developer’s attorney as an  tion  to  verify,  preted by the developer’s attorney as an  tion  to  verify,  endorsement of the contractor’s adher- charge  the  owner  to  seek  verification  confirm,  validate  appropriate,  design  endorsement of the contractor’s adher- charge  the  owner  to  seek  verification  confirm,  validate  appropriate,  design  ence to the structural design.  from the contractor, thus asserting that  professionals place themselves one step  ence to the structural design.  from the contractor, thus asserting that  professionals place themselves one step  Attorneys for the developer cited the  the engineer’s observation was not an  further from the inevitable dispute. The  Attorneys for the developer cited the  the engineer’s observation was not an  further from the inevitable dispute. The  field report, indicating that it provided  inspection. More importantly, it estab- following is a suggested checklist: field report, indicating that it provided  inspection. More importantly, it estab- following is a suggested checklist: a  representation  that  all  of  the  work  lishes that inspection of the work is out- ●  Limit  observations  and  report  lan- a  representation  that  all  of  the  work  lishes that inspection of the work is out- ●  Limit  observations  and  report  lan- observed by the engineer was consistent  side of the engineer’s scope. guage to the purpose o. observed by the engineer was consistent  side of the engineer’s scope. guage to the purpose o. with industry practices and wisdom. They  The key to this area of practice is to  ●  Limit  oral  conversations  with  the  with industry practices and wisdom. They  The key to this area of practice is to  ●  Limit  oral  conversations  with  the  argued  that  the  engineer’s  comment  be always mindful of the duty that one  contractor to basic items. Follow low up  argued  that  the  engineer’s  comment  be always mindful of the duty that one  contractor to basic items. Follow low up  that  “...the  stucco  cladding  paper  and  can  end  up  assuming  as  a  result  of  a  substantive  questions  every  report  or  that  “...the  stucco  cladding  paper  and  can  end  up  assuming  as  a  result  of  a  substantive  questions  every  report  or  lath is complete” additionally inferred,  simple  conversation  or  a  brief  written  written oral conversation. lath is complete” additionally inferred,  simple  conversation  or  a  brief  written  written oral conversation. “...according to building codes and my  memo.  Once  again,  although  the  case  ●  Include “recommendations to verify”  “...according to building codes and my  memo.  Once  again,  although  the  case  ●  Include “recommendations to verify”  specs.” The court agreed and held that no  involved  a  structural  design  issue,  the  in every report or written correspondence  specs.” The court agreed and held that no  involved  a  structural  design  issue,  the  in every report or written correspondence  other individual was better informed and  same  practice  should  be  incorporated  dealing with contractor rify through the  other individual was better informed and  same  practice  should  be  incorporated  dealing with contractor rify through the  in a better position to observe a defect  into the standard policies of all disciplines  building department or a deputy inspec- in a better position to observe a defect  into the standard policies of all disciplines  building department or a deputy inspec- in the application of the lath than the  of engineering. Designers and specifiers  tor that performance. in the application of the lath than the  of engineering. Designers and specifiers  tor that performance. engineer. The engineer was found by the  should maintain strict control over the  ●  Follow  up  in  writing,  asking  the  engineer. The engineer was found by the  should maintain strict control over the  ●  Follow  up  in  writing,  asking  the  court to have contributed substantially to  actual duties that they assume, and they  owner/developer if their verification of  court to have contributed substantially to  actual duties that they assume, and they  owner/developer if their verification of  the failures of the stucco attac ures of the  should  avoid  even  the  appearance  of  the work confirmed compliance by the  the failures of the stucco attac ures of the  should  avoid  even  the  appearance  of  the work confirmed compliance by the  stucco attachment. approving an owner’s and contractor’s  contractor, manufacturer or fabricator. stucco attachment. approving an owner’s and contractor’s  contractor, manufacturer or fabricator. work.  Otherwise,  the  other  players  in  ●  Limit the construction-phase services  work.  Otherwise,  the  other  players  in  ●  Limit the construction-phase services  Avoiding risk Avoiding risk the construction drama will be delighted  wherever possible. The project rarely has  the construction drama will be delighted  wherever possible. The project rarely has  How could this liability risk have been  to hand the engineer their responsibili- a sufficient budget to allow for detailed  How could this liability risk have been  to hand the engineer their responsibili- a sufficient budget to allow for detailed  avoided? It’s all about duty. In this situa- ties  and receive the endorsement of the  verification of design compliance. avoided? It’s all about duty. In this situa- ties  and receive the endorsement of the  verification of design compliance. Workshop 1 • Master page B with 3 column configuration, baseline grid and live text for mockup tion, the engineer snatched liability away  design  professional  for  the  work  they  The key to this area of practice is to  tion, the engineer snatched liability away  design  professional  for  the  work  they  The key to this area of practice is to  from the contractor and the developer by  have  just  completed.  The  construction  be always mins a result conversation or  from the contractor and the developer by  have  just  completed.  The  construction  be always mins a result conversation or  voluntarily assuming the duty of evaluat- industry  has  established  the  standard  a brief written memo. Once again,  voluntarily assuming the duty of evaluat- industry  has  established  the  standard  a brief written memo. Once again,  B B Consulting-Specifying Engineer • MONTH, 2006 Consulting-Specifying Engineer • MONTH, 2006
  • 5. Codes & Standards p-style c-style Section Bold Section The Debate Over Circuit Breakers vs. p-style Head Fused Solutions Continues ByLine [p-styLe], Italic Byline [c-style] I  p-style have a number of reservations about the tech- ally take less total space than CB switchgear and  Text DropCap nical issues in Mr. Lane’s articles, which broke  be less expensive. The use of Class-J time-delay  [nested DropCap] down changes to the NEC and suggested fused  current-limiting fuses may also reduce the size of  distribution may not always be necessary when  equipment. What about the short-circuit rating  considering selective coordination requirements. of other components such as busway? How will  Both  circuit  breaker  (CB)  and  fused  systems  they be affected by the short-delay trips? It is com- provide safe and reliable overcurrent protection  mon in high-rise construction to run busway from  p-style when systems are carefully engineered, installed  the main switchgear to distribution panels or to  Text and maintained. But there are significant differ- use plug-in busway to feed main-lug only (MLO)  p-style ences that must be recognized.  branch panels. Subhead The first problem with all three articles is they do  (Subhead) unnecessary risks not look at a complete system. The one-line diagram    in part two of the series, “The Skinny on Switchgear  The same diagram shows an 800-amp CB with  and the New NEC,” (CSE 9/05, p.15), shows a feeder  short delay trips protecting the automatic transfer  breaker in the main switchgear (not switchboard) of  switch (ATS). Will the ATS have an adequate  short- 800 amps, but neither the size of the main breaker  circuit rating? One ATS manufacturer tests and UL  is indicated, nor  whether there is a main breaker or  lists its units only when protected by current-lim- a sequence service. Is there coordination between  iting fuses or CB with clearing times of less than  the 800-amp feeder breaker and the main breaker?  three cycles. Generators commonly have short-n  To achieve this, the main breaker would require a  is there. It is almost a knee-jerk response. While  short delay trip set at 12 cycles. The vast majority of  some industries have planned shutdowns for ser- transformers in commercial and industrial systems  vice and maintenance purposes, commercial and  other industries seldom can do so except at late  p-style p-style hours. This , it should be included in every project  Considering only space, fused switchboards can Text PullQuote specification. To do less is to increase hazard to  take up less total space than CB switchgear, cost c-style personnel. No engineer can do so and meet the  less and require no need for rear access. Bold Text ethics of his profession. Author Keith Lane responds: My intent was  are protected on the primary side by current-limiting  fuses. What would the coordination be? It’s difficult  to solicit good conversation in the engineering  enough to coordinate CB having instantaneous trips  community, which I think my article has succeeded  with primary current-limiting fuses. in doing. I am certainly not against AHJs adopting  If the primary fuses open—admittedly, this rarely  the 2005 NEC. The heart of the piece was the issue  happens—the system is down until the utility replac- of selective coordination but neither the size of the  es the fuses, and only after determining there is no  main breaker is indicated, nor  whether there is a  problem in the transformer or main switchgear.  main breaker or a sequence service. Is there coor- Any  facility  requiring  an  800-amp  CB  for  the  dination between the 800-amp feeder breakerAs  emergency system must be fairly large. It is reason- noted  in  my  conclusion,  I  am  in  favor  of  good  able to assume a 2.5% impedance high-efficiency  engineering analysis, which would include a com- 1,500- or 2,000-kVA transformer. Available short- prehensive fault current calculation, coordination  circuit current could easily be more than 75,000  study and  appropriate settinehensive fault current  amps. What is the cost of CB switchgear-type con- analysis, priate setting of the breakers or with the  Workshop 2 • RBI Paragraph & Character Styles for Master page A struction opposed to a bolted pressure switch and  use of fused distribution, the reliability of electrical  fuse switchboard? Considering only space, fused  distribution systems would be increased over what  switchboards are readily available. They may actu- is required by the NEC prior to 2005. A Consulting-Specifying Engineer • MONTH, 2006
  • 6. Codes & Standards p-style c-style Section Bold Section The Debate Over Circuit Breakers vs. p-style Head Fused Solutions Continues c-style ByLine [p-styLe], Italic Byline [c-style] BoldItalics NotesEditor Editor’s note: This month’s Codes & Standards, following the tone set in Letters (p.7), is an in-depth rebut- [nested] tal to Keith Lane’s August-through-October series analyzing the 2005 edition of the NEC. A response from Mr. p-style Lane follows. It should be noted that Lane’s original article was run in three parts because of length. NotesEditor I  have a number of reservations about the tech- size of the main breaker is indicated, nor  whether  p-style Text DropCap nical issues in Mr. Lane’s articles, which broke  there is a main breaker or a sequence service. Is  [nested DropCap] down changes to the NEC and suggested fused  there coordination between the 800-amp feeder  distribution may not always be necessary when  breaker and the main breaker? To achieve this, the  considering selective coordination requirements. main breaker would require a short delay trip set  Both  circuit  breaker  (CB)  and  fused  systems  at 12 cycles. The vast majority of transformers in  provide safe and reliable overcurrent protection  commercial and industrial systems are protected  p-style when systems are carefully engineered, installed  on the primary side by current-limiting fuses. What  Text and maintained. But there are significant differ- would the coordination be? It’s difficult enough  ences that must be recognized.  to coordinate CB having instantaneous trips with  p-style The first problem with all three articles is they  primary current-limiting fuses. Subhead p-style (Subhead) unnecessary risks Considering only space, fused switchboards can PullQuote The same diagram shows an 800-amp CB with  take up less total space than CB switchgear, cost short delay trips protecting the automatic trans- less and require no need for rear access. fer switch (ATS). Will the ATS have an adequate    short-there is no problem in the transformer or  do not look at a complete system. The one-line  main switchgmp fault on the load side of a branch  diagram  in part two of the series, “The Skinny on  breaker may cause all three CBs to open. If power  Switchgear and the New NEC,” (CSE 9/05, p.15),  look? After the fa removed, the switches and CBs  shows a feeder breaker in the main switchgear  trical distribution systems would be increased over  (not switchboard) of 800 amps, but neither the  what is required by the NEC prior to 2005. p-style GraphicCaption 1,250-hp, 3600-rpm, 2,300-volt, WP-1 enclosure, constant-speed motor drives an aeration blower at Weyerhaeuser’s Longview Complex. Workshop 2 • RBI Paragraph & Character Styles for optional Master Page A A Consulting-Specifying Engineer • MONTH, 2006
  • 7. Codes & Standards element label Section The Debate Over Circuit Breakers vs. element label Head Fused Solutions Continues element label ByLine [p-styLe], Italic Byline [c-style] Byline Editor’s note: This month’s Codes & Standards, following the tone set in Letters (p.7), is an in-depth rebut- element label tal to Keith Lane’s August-through-October series analyzing the 2005 edition of the NEC. A response from Mr. Intro Lane follows. It should be noted that Lane’s original article was run in three parts because of length. I  have a number of reservations about the tech- size of the main breaker is indicated, nor  whether  element label nical issues in Mr. Lane’s articles, which broke  there is a main breaker or a sequence service. Is  Body down changes to the NEC and suggested fused  there coordination between the 800-amp feeder  distribution may not always be necessary when  breaker and the main breaker? To achieve this, the  considering selective coordination requirements. main breaker would require a short delay trip set  Both  circuit  breaker  (CB)  and  fused  systems  at 12 cycles. The vast majority of transformers in  provide safe and reliable overcurrent protection  commercial and industrial systems are protected  element label when systems are carefully engineered, installed  on the primary side by current-limiting fuses. What  Graphic and maintained. But there are significant differ- would the coordination be? It’s difficult enough  ences that must be recognized.  to coordinate CB having instantaneous trips with  The first problem with all three articles is they  primary current-limiting fuses. element label (Subhead) unnecessary risks Considering only space, fused switchboards can Accurate element labels must be included for all text and Pullquote The same diagram shows an 800-amp CB with  take up less total space than CB switchgear, cost graphic frames. Under Window > Show Element Labels short delay trips protecting the automatic trans- less and require no need for rear access. fer switch (ATS). Will the ATS have an adequate    (this feature for Smart Connection Enterprise rollout). short-there is no problem in the transformer or  do not look at a complete system. The one-line  main switchgmp fault on the load side of a branch  Do not group frames because element labels will be disgarded. diagram  in part two of the series, “The Skinny on  breaker may cause all three CBs to open. If power  Switchgear and the New NEC,” (CSE 9/05, p.15),  look? After the fa removed, the switches and CBs  shows a feeder breaker in the main switchgear  trical distribution systems would be increased over  (not switchboard) of 800 amps, but neither the  what is required by the NEC prior to 2005. element label Graphic element label Caption 1,250-hp, 3600-rpm, 2,300-volt, WP-1 enclosure, constant-speed motor drives an aeration blower at Weyerhaeuser’s Longview Complex. Workshop 2 • RBI Element labels for Smart Connection Enterprise A Consulting-Specifying Engineer • MONTH, 2006
  • 8. p-style Codes & Standards Section c-style FIlE PREPaRaTIoN FoR E-loGIC REvIEw Bold Section element label 1. Review ALL documents with art director and CMS prior to e-Logic review. Section 2. All mockups will be sent to e-Logic with complete paragraph and character styles and element labels in place. The Debate Over Circuit Breakers vs. 3. Suggest locking frames on Master Pages that don’t move, such as a folio or Fused Solutions Continues section name. ByLine [p-styLe], Italic Byline [c-style] 4. With all document pages highlighted in pages palette, Override All Master Page Items on document pages for e-Logic review. Pages palette > Fly out Editor’s note: This month’s Codes & Standards, following the tone set in Letters (p.7), is an in-depth rebut- tal to Keith Lane’s August-through-October series analyzing the 2005 edition of the NEC. A response from Mr. menu > Override All Master Page Items (Alt+Shift-Ctr+L). This must be Lane follows. It should be noted that Lane’s original article was run in three parts because of length. done because e-Logic reviews document pages, not master pages. I  have a number of reservations about the tech- size of the main breaker is indicated, nor  whether  5. Make revisions as required by e-Logic report. nical issues in Mr. Lane’s articles, which broke  there is a main breaker or a sequence service. Is  down changes to the NEC and suggested fused  there coordination between the 800-amp feeder  distribution may not always be necessary when  breaker and the main breaker? To achieve this, the  Save and keep all documents with live text (mockup) prior to stripping out the considering selective coordination requirements. main breaker would require a short delay trip set  text. These files are the ones that get sent to e-Logic, with complete paragraph Both  circuit  breaker  (CB)  and  fused  systems  at 12 cycles. The vast majority of transformers in  and character styles and element labels in place. provide safe and reliable overcurrent protection  commercial and industrial systems are protected  when systems are carefully engineered, installed  on the primary side by current-limiting fuses. What  and maintained. But there are significant differ- would the coordination be? It’s difficult enough  ences that must be recognized.  to coordinate CB having instantaneous trips with  4 The first problem with all three articles is they  primary current-limiting fuses. (Subhead) unnecessary risks Considering only space, fused switchboards can The same diagram shows an 800-amp CB with  take up less total space than CB switchgear, cost short delay trips protecting the automatic trans- less and require no need for rear access. fer switch (ATS). Will the ATS have an adequate    short-there is no problem in the transformer or  do not look at a complete system. The one-line  main switchgmp fault on the load side of a branch  diagram  in part two of the series, “The Skinny on  breaker may cause all three CBs to open. If power  Switchgear and the New NEC,” (CSE 9/05, p.15),  look? After the fa removed, the switches and CBs  shows a feeder breaker in the main switchgear  trical distribution systems would be increased over  (not switchboard) of 800 amps, but neither the  what is required by the NEC prior to 2005. 4 1,250-hp, 3600-rpm, 2,300-volt, WP-1 enclosure, constant-speed motor drives an aeration blower at Weyerhaeuser’s Longview Complex. Workshop 3 • Mockup to art director, CMS, e-Logic for review A Consulting-Specifying Engineer • MONTH, 2006
  • 9. Codes & Standards aFTER DoCumENT aPPRoval By E-loGIC CREaTE THE aCTual TEmPlaTE 3 1. In each master page, create dummy text in all frames—dummy text is the actual name of the style sheet used (text is stripped out except for style names). Head 2 2. Examples: in the head frame you would type Head; in the Byline frame type Byline, Italic Byline [c-style]; in the NotesEditor frame type NotesEditor; in the body frame type Text DropCap, Text, Subhead, etc. 2 ByLine [p-styLe], Italic Byline [c-style] (using the appropriate paragraph styles, see samples). Editor’s note: NotesEditor 3. There are some exceptions such as the name of the Section and Editor’s Note (a nested c-style), which don’t change. In these cases—when the 3 2 T   text doesn’t change—leave the live text intact. 2 ext DropCap  Text 4. Document pages must be revised to the format of the updated Master Pages. Subhead Text  5. All templates will have complete paragraph and character styles and element labels in place. PullQuote PullQuote Save and keep all documents with live text (mockup) prior to stripping out the text. These files are the ones that get sent to e-Logic, with complete paragraph and character styles and element labels in place. Remember, InDesign has unlimited undos (ctr-z) GraphicCaption Workshop 3 • Create actual template A Consulting-Specifying Engineer • MONTH, 2006