Field Assessment of
Cold-Climate Air-Source Heat Pumps
in Minnesota
March 2019
Center for Energy and Environment
Why ASHPs in MN?
• Cold-climate technology improvements
• Significant amounts of electric heating
• Growing discussion around fuel switching
– Electric grid getting greener
– Delivered fuels can be expensive
• CEE’s initial work started in response to propane
shortages in winter of 2014
Study Overview
• Field Study
– 8 ccASHP in a variety of MN
residences
• 6 ducted whole house system
• 2 ductless mini-split systems
– Monitor installed field
performance of ASHP & backup
• Incorporate into utility energy
conservation program
• Climate zones 6 & 7
• Detailed monitoring system
installed at each site
Ducted Whole House Installation
Flex Fuel Systems
Ducted Whole House Installation
All Electric Systems
Installation Considerations
Control and Operation Integration with backup
Sizing
• Trade-offs between
HP size and fraction of
heating load meet
• Rule of thumb: Sizing
for heating increases
HP size by 1-ton over
sizing for cooling
Design and Sizing for Ducted Systems
Percentage of heating
load meet by ASHP:
4 ton ~ 86%,
3 ton ~ 77%
2 ton ~ 60%
• Trade-offs between
HP size and fraction of
heating load meet
• Rule of thumb: Sizing
for heating increases
HP size by 1-ton over
sizing for cooling
Design and Sizing for Ducted Systems
Percentage of heating
load meet by ASHP:
4 ton ~ 86%,
3 ton ~ 77%
2 ton ~ 60%
Furnace back-up heating
• Trade-offs between
HP size and fraction of
heating load meet
• Rule of thumb: Sizing
for heating increases
HP size by 1-ton over
sizing for cooling
Design and Sizing for Ducted Systems
Percentage of heating
load meet by ASHP:
4 ton ~ 86%,
3 ton ~ 77%
2 ton ~ 60%
Electric booster heating
Heating cycle COP of a flex fuel system
Heating Cycle COP of all electric
Annual Characteristics and Savings
• Ducted Flex fuel ccASHP compared to condensing
furnace (LP)
– Annual COP improved to 1.3 (over 0.85)
– ~40% site energy reduction
– ~30% cost reduction
– ~60% reduction in propane use
– ~5% reduction in emissions (J. Edwards Thurs 8/16,
Session 2)
• All-electric Ducted ccASHP
– Annual COP ~1.9
– ~60% site energy reduction
Conclusions
• Heat pump’s preformed as expected when heating
• Annual COPs are lower than HSPF ratings due integration
with auxiliary heating and freeze protection
• Flex Fuel ccASHPs can heat below 5F, all electric systems
below -13F
• Paybacks are attractive when existing heating or cooling
system need to be replaced
Percentage Reductions for ccASHPs
Site Energy Source Energy Homeowner Cost Emissions
Dual fuel
ASHP vs
Prop. Furn.
40% 10% 30% 5%
All elect.
ducted &
ductless vs
elect.
resistance
55% 55% 55% 55%
What’s Next?
Study Overview
• Field Study
– 8 ccASHP in a variety of MN
residences
• 6 ducted whole house system
• 2 ductless mini-split systems
– Monitor installed field
performance of ASHP & backup
• Incorporate into utility energy
conservation program
• Climate zones 6 & 7
• Detailed monitoring system
installed at each site
Beneficial Electrification
• When is fuels switching beneficial?
– Reductions in
• Emissions
• Source energy
• Homeowner cost
• Biggest market in MN: Propane furnaces
• Potential market: AC and should heating for
nat. gas furnaces
www.mncee.org/heat_pumps
Ben Schoenbauer:
bschoenbauer@mncee.org
extras
Installation Considerations
• Controls :
– Ducted Systems: automated controls to bring up
backup
– Ductless Systems: manual action by homeowner
• Interaction with back-up systems
– Ducted Systems: Integrated installs with shared
controls
– Ductless Systems: Separate systems
• Sizing
– Ducted Systems: Contractors typically sized for cooling
– Ductless: Partial or full load design
Replacement System Install Costs
• For the 4 ducted systems:
– Our average cost was ~$14,000*
• NREL Residential equipment install database:
– $6,340 for ducted 3ton ccASHP
– $4,000 for a new condensing propane furnace ($3,000 for an 80%).
• $10,340 Total
– $5,540 for a new comparable SEER A/C
• $800 incremental for ccASHP
• Limited installs leading to higher costs
• Requirement for new air handler or furnace increases costs
considerably
Instrumentation
1 2 3
4
5
6 7
8 11
12
13
14
15
Power Measurements:
1) Outdoor unit
2) Indoor unit
3) Indoor fan
4) Reversing valve
Temperatures:
5) Supply Air
6) Return Air
7) Mechanical area ambient
8) Conditioned space
Additional:
9) Back up fuel consumption
10) Delivered air flow
11) NOAA data
Site Equipment
Whole house ducted systems
Site Number ASHP System ASHP Size ASHP Type Backup
1
Carrier Infinity with
Greenspeed [25VNA048A003] 4 ton Ducted LP Cond. Furnace
2
Bryant Extreme Heat Pump
[280ANV048] 4 ton Ducted LP Cond. Furnace
3
Carrier Infinity with
Greenspeed [25VNA036A003] 3 ton Ducted LP 80% Furnace
4
Trane XV20i
[4TWV0036A] 3 ton Ducted LP Cond. Furnace
5
Mitsibishi Ductless Hyper Heat
[MUZ-FH18NAH] 1.5 ton Ductless
Electric
Resistance
6
Mitsibishi Ductless Hyper Heat
[MSZ-FH12NA]
1 ton
(2 units) Ductless
Electric
Resistance
7
Mitsubishi Hyper Heat
System [PVA-A30AA7] 3 ton Ducted Electric Booster
8
Mitsubishi Hyper Heat
System [PVA-A30AA7] 3 ton Ducted Electric Booster
Ducted Whole House Installation
Flex Fuel Systems
Ducted Whole House Installation
Flex Fuel Systems
Cold Temperature Performance of ASHPs
• Ducted ASHPs were
capable of delivering
heat at outdoor temps
from 5 to 10 F
• Ductless systems
operated below -13 F.
• Homeowner in WI has
removed several ER baseboards
System Performance
Annual COP: ductless ~1.9 to 2.1
Flex Fuel ~1.2 to 1.3

More Related Content

What's hot

Stefan jensen high performance energy low charge nh3 systems_160403
Stefan jensen high performance energy low charge nh3 systems_160403Stefan jensen high performance energy low charge nh3 systems_160403
Stefan jensen high performance energy low charge nh3 systems_160403ARAaus
 
Duncan cairnie ccm energy solutions hvacr seminar- april 2016
Duncan cairnie ccm energy solutions   hvacr seminar- april 2016Duncan cairnie ccm energy solutions   hvacr seminar- april 2016
Duncan cairnie ccm energy solutions hvacr seminar- april 2016ARAaus
 
Enhancing performance of transcritical CO2 heat pumps with heat recovery
Enhancing performance of transcritical CO2 heat pumps with heat recoveryEnhancing performance of transcritical CO2 heat pumps with heat recovery
Enhancing performance of transcritical CO2 heat pumps with heat recoveryATMOsphere Conferences & Events
 
Energy modelling of a three-story primary school building located in Phoenix,...
Energy modelling of a three-story primary school building located in Phoenix,...Energy modelling of a three-story primary school building located in Phoenix,...
Energy modelling of a three-story primary school building located in Phoenix,...Kirtan Gohel
 
Gas vs. Electricity for Heat Treatment Furnacces
Gas vs. Electricity for  Heat Treatment FurnaccesGas vs. Electricity for  Heat Treatment Furnacces
Gas vs. Electricity for Heat Treatment FurnaccesHTCourses
 
Integrated CO2 systems for warm climates
Integrated CO2 systems for warm climatesIntegrated CO2 systems for warm climates
Integrated CO2 systems for warm climatesCAREL Industries S.p.A
 
Feedwater heater control: Level
Feedwater heater control: LevelFeedwater heater control: Level
Feedwater heater control: LevelShari Worthington
 
Performance and Optimization of Residential Condensing Combi Systems
Performance and Optimization of Residential Condensing Combi SystemsPerformance and Optimization of Residential Condensing Combi Systems
Performance and Optimization of Residential Condensing Combi SystemsCenter for Energy and Environment
 
UW- Energy Audit Class Lowell Hall TeamB 080715
UW- Energy Audit Class Lowell Hall TeamB 080715UW- Energy Audit Class Lowell Hall TeamB 080715
UW- Energy Audit Class Lowell Hall TeamB 080715Paul R. White, PE
 
Ian schmahmann hawk eye-800 presentation 3
Ian schmahmann hawk eye-800 presentation 3Ian schmahmann hawk eye-800 presentation 3
Ian schmahmann hawk eye-800 presentation 3ARAaus
 
Field Study of an Intelligent, Networked, Retrofittable Water Heater Controller
Field Study of an Intelligent, Networked, Retrofittable Water Heater ControllerField Study of an Intelligent, Networked, Retrofittable Water Heater Controller
Field Study of an Intelligent, Networked, Retrofittable Water Heater ControllerCenter for Energy and Environment
 
DOE NREL TEST Report 2014
DOE NREL TEST Report 2014DOE NREL TEST Report 2014
DOE NREL TEST Report 2014Charles Rice
 
Overview of a Strategy to Exempt Multiple Process Heaters from the “Boiler MA...
Overview of a Strategy to Exempt Multiple Process Heaters from the “Boiler MA...Overview of a Strategy to Exempt Multiple Process Heaters from the “Boiler MA...
Overview of a Strategy to Exempt Multiple Process Heaters from the “Boiler MA...Antea Group
 
Sans healthcare watch
Sans healthcare watchSans healthcare watch
Sans healthcare watchSA FHE
 

What's hot (20)

Cold Cliamte Air Source Heat Pumps: Study Update
Cold Cliamte Air Source Heat Pumps: Study UpdateCold Cliamte Air Source Heat Pumps: Study Update
Cold Cliamte Air Source Heat Pumps: Study Update
 
INVISTA
INVISTAINVISTA
INVISTA
 
Stefan jensen high performance energy low charge nh3 systems_160403
Stefan jensen high performance energy low charge nh3 systems_160403Stefan jensen high performance energy low charge nh3 systems_160403
Stefan jensen high performance energy low charge nh3 systems_160403
 
Duncan cairnie ccm energy solutions hvacr seminar- april 2016
Duncan cairnie ccm energy solutions   hvacr seminar- april 2016Duncan cairnie ccm energy solutions   hvacr seminar- april 2016
Duncan cairnie ccm energy solutions hvacr seminar- april 2016
 
Showcase ppt ver 8
Showcase ppt ver 8Showcase ppt ver 8
Showcase ppt ver 8
 
Combi Systems: Lessons Learned from the Field
Combi Systems: Lessons Learned from the FieldCombi Systems: Lessons Learned from the Field
Combi Systems: Lessons Learned from the Field
 
Enhancing performance of transcritical CO2 heat pumps with heat recovery
Enhancing performance of transcritical CO2 heat pumps with heat recoveryEnhancing performance of transcritical CO2 heat pumps with heat recovery
Enhancing performance of transcritical CO2 heat pumps with heat recovery
 
Energy modelling of a three-story primary school building located in Phoenix,...
Energy modelling of a three-story primary school building located in Phoenix,...Energy modelling of a three-story primary school building located in Phoenix,...
Energy modelling of a three-story primary school building located in Phoenix,...
 
COEFFICATION OF HEAT ENGIN Aniket jaiswal. class b.sc sec. semester
COEFFICATION OF HEAT ENGIN Aniket jaiswal. class  b.sc sec. semesterCOEFFICATION OF HEAT ENGIN Aniket jaiswal. class  b.sc sec. semester
COEFFICATION OF HEAT ENGIN Aniket jaiswal. class b.sc sec. semester
 
Gas vs. Electricity for Heat Treatment Furnacces
Gas vs. Electricity for  Heat Treatment FurnaccesGas vs. Electricity for  Heat Treatment Furnacces
Gas vs. Electricity for Heat Treatment Furnacces
 
Field Performance of Hybrid Gas Water Heaters
Field Performance of Hybrid Gas Water Heaters Field Performance of Hybrid Gas Water Heaters
Field Performance of Hybrid Gas Water Heaters
 
Integrated CO2 systems for warm climates
Integrated CO2 systems for warm climatesIntegrated CO2 systems for warm climates
Integrated CO2 systems for warm climates
 
Feedwater heater control: Level
Feedwater heater control: LevelFeedwater heater control: Level
Feedwater heater control: Level
 
Performance and Optimization of Residential Condensing Combi Systems
Performance and Optimization of Residential Condensing Combi SystemsPerformance and Optimization of Residential Condensing Combi Systems
Performance and Optimization of Residential Condensing Combi Systems
 
UW- Energy Audit Class Lowell Hall TeamB 080715
UW- Energy Audit Class Lowell Hall TeamB 080715UW- Energy Audit Class Lowell Hall TeamB 080715
UW- Energy Audit Class Lowell Hall TeamB 080715
 
Ian schmahmann hawk eye-800 presentation 3
Ian schmahmann hawk eye-800 presentation 3Ian schmahmann hawk eye-800 presentation 3
Ian schmahmann hawk eye-800 presentation 3
 
Field Study of an Intelligent, Networked, Retrofittable Water Heater Controller
Field Study of an Intelligent, Networked, Retrofittable Water Heater ControllerField Study of an Intelligent, Networked, Retrofittable Water Heater Controller
Field Study of an Intelligent, Networked, Retrofittable Water Heater Controller
 
DOE NREL TEST Report 2014
DOE NREL TEST Report 2014DOE NREL TEST Report 2014
DOE NREL TEST Report 2014
 
Overview of a Strategy to Exempt Multiple Process Heaters from the “Boiler MA...
Overview of a Strategy to Exempt Multiple Process Heaters from the “Boiler MA...Overview of a Strategy to Exempt Multiple Process Heaters from the “Boiler MA...
Overview of a Strategy to Exempt Multiple Process Heaters from the “Boiler MA...
 
Sans healthcare watch
Sans healthcare watchSans healthcare watch
Sans healthcare watch
 

Similar to Field Assessment of Cold-Climate Air-Source Heat Pumps in Minnesota

Quantifying Energy Savings from Heat Pump Water Heaters in Cold Climate Homes
Quantifying Energy Savings from Heat Pump Water Heaters in Cold Climate HomesQuantifying Energy Savings from Heat Pump Water Heaters in Cold Climate Homes
Quantifying Energy Savings from Heat Pump Water Heaters in Cold Climate HomesCenter for Energy and Environment
 
NESEA Building Energy 2015: PV and Heat Pumps
NESEA Building Energy 2015: PV and Heat PumpsNESEA Building Energy 2015: PV and Heat Pumps
NESEA Building Energy 2015: PV and Heat Pumpsfortunatmueller
 
Air Source Heat Pumps Field Studies A Systematic Literature Review
Air Source Heat Pumps Field Studies  A Systematic Literature ReviewAir Source Heat Pumps Field Studies  A Systematic Literature Review
Air Source Heat Pumps Field Studies A Systematic Literature ReviewCynthia King
 
Energy Simulation of High-Rise Residential Buildings: Lessons Learned
Energy Simulation of High-Rise Residential Buildings: Lessons LearnedEnergy Simulation of High-Rise Residential Buildings: Lessons Learned
Energy Simulation of High-Rise Residential Buildings: Lessons LearnedRDH Building Science
 
16th Elec Pwr Conf. 4-3-2014 SJ FINAL
16th Elec Pwr Conf. 4-3-2014 SJ FINAL16th Elec Pwr Conf. 4-3-2014 SJ FINAL
16th Elec Pwr Conf. 4-3-2014 SJ FINALSuresh Jambunathan
 
Using IESVE for Loads, Sizing and Heat Pump Modeling to Achieve Decarbonization
Using IESVE for Loads, Sizing and Heat Pump Modeling to Achieve DecarbonizationUsing IESVE for Loads, Sizing and Heat Pump Modeling to Achieve Decarbonization
Using IESVE for Loads, Sizing and Heat Pump Modeling to Achieve DecarbonizationIES VE
 
Oasis heat presentation v3
Oasis heat presentation v3Oasis heat presentation v3
Oasis heat presentation v3Todd Hixon
 
Energy Trust New Buildings: Technical Updates for Modelers and Engineers
Energy Trust New Buildings: Technical Updates for Modelers and EngineersEnergy Trust New Buildings: Technical Updates for Modelers and Engineers
Energy Trust New Buildings: Technical Updates for Modelers and Engineersenergytrustor
 
Making Sense of Metering Data
Making Sense of Metering DataMaking Sense of Metering Data
Making Sense of Metering DataCharles Simchick
 
Energy optimization & building ventilation systems 10.02.2020
Energy optimization & building ventilation systems   10.02.2020Energy optimization & building ventilation systems   10.02.2020
Energy optimization & building ventilation systems 10.02.2020Consistent Engineering Consultants
 
Co-generation and trigeneration by Varun Pratap Singh
Co-generation and trigeneration by Varun Pratap SinghCo-generation and trigeneration by Varun Pratap Singh
Co-generation and trigeneration by Varun Pratap SinghVarun Pratap Singh
 
GSHP Training for Plumbcenter - Delivered by Kensa Heat Pumps - November 2011
GSHP Training for Plumbcenter - Delivered by Kensa Heat Pumps - November 2011GSHP Training for Plumbcenter - Delivered by Kensa Heat Pumps - November 2011
GSHP Training for Plumbcenter - Delivered by Kensa Heat Pumps - November 2011kensaheatpumps
 
Stoney River Energy Analysis
Stoney River Energy AnalysisStoney River Energy Analysis
Stoney River Energy Analysisscottthorpe
 

Similar to Field Assessment of Cold-Climate Air-Source Heat Pumps in Minnesota (20)

Quantifying Energy Savings from Heat Pump Water Heaters in Cold Climate Homes
Quantifying Energy Savings from Heat Pump Water Heaters in Cold Climate HomesQuantifying Energy Savings from Heat Pump Water Heaters in Cold Climate Homes
Quantifying Energy Savings from Heat Pump Water Heaters in Cold Climate Homes
 
Zero Carbon technology
Zero Carbon technologyZero Carbon technology
Zero Carbon technology
 
NESEA Building Energy 2015: PV and Heat Pumps
NESEA Building Energy 2015: PV and Heat PumpsNESEA Building Energy 2015: PV and Heat Pumps
NESEA Building Energy 2015: PV and Heat Pumps
 
Condensing Boiler Optimization
Condensing Boiler OptimizationCondensing Boiler Optimization
Condensing Boiler Optimization
 
Air Source Heat Pumps Field Studies A Systematic Literature Review
Air Source Heat Pumps Field Studies  A Systematic Literature ReviewAir Source Heat Pumps Field Studies  A Systematic Literature Review
Air Source Heat Pumps Field Studies A Systematic Literature Review
 
Energy Simulation of High-Rise Residential Buildings: Lessons Learned
Energy Simulation of High-Rise Residential Buildings: Lessons LearnedEnergy Simulation of High-Rise Residential Buildings: Lessons Learned
Energy Simulation of High-Rise Residential Buildings: Lessons Learned
 
16th Elec Pwr Conf. 4-3-2014 SJ FINAL
16th Elec Pwr Conf. 4-3-2014 SJ FINAL16th Elec Pwr Conf. 4-3-2014 SJ FINAL
16th Elec Pwr Conf. 4-3-2014 SJ FINAL
 
Showcase ppt ver 8
Showcase ppt ver 8Showcase ppt ver 8
Showcase ppt ver 8
 
Using IESVE for Loads, Sizing and Heat Pump Modeling to Achieve Decarbonization
Using IESVE for Loads, Sizing and Heat Pump Modeling to Achieve DecarbonizationUsing IESVE for Loads, Sizing and Heat Pump Modeling to Achieve Decarbonization
Using IESVE for Loads, Sizing and Heat Pump Modeling to Achieve Decarbonization
 
Oasis heat presentation v3
Oasis heat presentation v3Oasis heat presentation v3
Oasis heat presentation v3
 
Condensing Boiler Optimization
Condensing Boiler OptimizationCondensing Boiler Optimization
Condensing Boiler Optimization
 
Heatreflex
HeatreflexHeatreflex
Heatreflex
 
Energy Trust New Buildings: Technical Updates for Modelers and Engineers
Energy Trust New Buildings: Technical Updates for Modelers and EngineersEnergy Trust New Buildings: Technical Updates for Modelers and Engineers
Energy Trust New Buildings: Technical Updates for Modelers and Engineers
 
Making Sense of Metering Data
Making Sense of Metering DataMaking Sense of Metering Data
Making Sense of Metering Data
 
Energy optimization & building ventilation systems 10.02.2020
Energy optimization & building ventilation systems   10.02.2020Energy optimization & building ventilation systems   10.02.2020
Energy optimization & building ventilation systems 10.02.2020
 
Best practices for food service applications
Best practices for food service applicationsBest practices for food service applications
Best practices for food service applications
 
Co-generation and trigeneration by Varun Pratap Singh
Co-generation and trigeneration by Varun Pratap SinghCo-generation and trigeneration by Varun Pratap Singh
Co-generation and trigeneration by Varun Pratap Singh
 
GSHP Training for Plumbcenter - Delivered by Kensa Heat Pumps - November 2011
GSHP Training for Plumbcenter - Delivered by Kensa Heat Pumps - November 2011GSHP Training for Plumbcenter - Delivered by Kensa Heat Pumps - November 2011
GSHP Training for Plumbcenter - Delivered by Kensa Heat Pumps - November 2011
 
Stoney River Energy Analysis
Stoney River Energy AnalysisStoney River Energy Analysis
Stoney River Energy Analysis
 
Product
ProductProduct
Product
 

More from Center for Energy and Environment

Presentation for Home Energy and Climate Finance and Policy Committee
Presentation for Home Energy and Climate Finance and Policy CommitteePresentation for Home Energy and Climate Finance and Policy Committee
Presentation for Home Energy and Climate Finance and Policy CommitteeCenter for Energy and Environment
 
Results from Commercial Energy Code Compliance Pilot Program
Results from Commercial Energy Code Compliance Pilot ProgramResults from Commercial Energy Code Compliance Pilot Program
Results from Commercial Energy Code Compliance Pilot ProgramCenter for Energy and Environment
 
Humidification Retrofits Deliver Residential Furnace Efficiency
Humidification Retrofits Deliver Residential Furnace EfficiencyHumidification Retrofits Deliver Residential Furnace Efficiency
Humidification Retrofits Deliver Residential Furnace EfficiencyCenter for Energy and Environment
 
Automated House Sealing - Aerosol Envelope Sealing of New Homes
Automated House Sealing - Aerosol Envelope Sealing of New HomesAutomated House Sealing - Aerosol Envelope Sealing of New Homes
Automated House Sealing - Aerosol Envelope Sealing of New HomesCenter for Energy and Environment
 
Demand Control Systems Deliver Efficiency in Commercial Hot Water Use
Demand Control Systems Deliver Efficiency in Commercial Hot Water UseDemand Control Systems Deliver Efficiency in Commercial Hot Water Use
Demand Control Systems Deliver Efficiency in Commercial Hot Water UseCenter for Energy and Environment
 
New Technology for Efficient Multifamily Building Envelope Sealing
New Technology for Efficient Multifamily Building Envelope SealingNew Technology for Efficient Multifamily Building Envelope Sealing
New Technology for Efficient Multifamily Building Envelope SealingCenter for Energy and Environment
 
Project Kickoff Webinar Slides: MN Energy Efficiency & Carbon Saving Potentia...
Project Kickoff Webinar Slides: MN Energy Efficiency & Carbon Saving Potentia...Project Kickoff Webinar Slides: MN Energy Efficiency & Carbon Saving Potentia...
Project Kickoff Webinar Slides: MN Energy Efficiency & Carbon Saving Potentia...Center for Energy and Environment
 
Mid-size City Benchmarking Workshop: Institute for Market Transformation
Mid-size City Benchmarking Workshop: Institute for Market TransformationMid-size City Benchmarking Workshop: Institute for Market Transformation
Mid-size City Benchmarking Workshop: Institute for Market TransformationCenter for Energy and Environment
 

More from Center for Energy and Environment (20)

Presentation for Home Energy and Climate Finance and Policy Committee
Presentation for Home Energy and Climate Finance and Policy CommitteePresentation for Home Energy and Climate Finance and Policy Committee
Presentation for Home Energy and Climate Finance and Policy Committee
 
Achieving a Healthy Low-Carbon Economy in Minnesota
Achieving a Healthy Low-Carbon Economy in MinnesotaAchieving a Healthy Low-Carbon Economy in Minnesota
Achieving a Healthy Low-Carbon Economy in Minnesota
 
Condensing Boilers: Are they cost effective?
Condensing Boilers: Are they cost effective?Condensing Boilers: Are they cost effective?
Condensing Boilers: Are they cost effective?
 
Results from Commercial Energy Code Compliance Pilot Program
Results from Commercial Energy Code Compliance Pilot ProgramResults from Commercial Energy Code Compliance Pilot Program
Results from Commercial Energy Code Compliance Pilot Program
 
Really Selling Efficiency
Really Selling EfficiencyReally Selling Efficiency
Really Selling Efficiency
 
CEE's Strategic Electrification Forum
CEE's Strategic Electrification ForumCEE's Strategic Electrification Forum
CEE's Strategic Electrification Forum
 
Humidification Retrofits Deliver Residential Furnace Efficiency
Humidification Retrofits Deliver Residential Furnace EfficiencyHumidification Retrofits Deliver Residential Furnace Efficiency
Humidification Retrofits Deliver Residential Furnace Efficiency
 
Automated House Sealing - Aerosol Envelope Sealing of New Homes
Automated House Sealing - Aerosol Envelope Sealing of New HomesAutomated House Sealing - Aerosol Envelope Sealing of New Homes
Automated House Sealing - Aerosol Envelope Sealing of New Homes
 
Demand Control Systems Deliver Efficiency in Commercial Hot Water Use
Demand Control Systems Deliver Efficiency in Commercial Hot Water UseDemand Control Systems Deliver Efficiency in Commercial Hot Water Use
Demand Control Systems Deliver Efficiency in Commercial Hot Water Use
 
Energy Fit Homes - Realtor Benefits
Energy Fit Homes - Realtor BenefitsEnergy Fit Homes - Realtor Benefits
Energy Fit Homes - Realtor Benefits
 
Optimized Operation of Indoor Public Pool Facilities
Optimized Operation of Indoor Public Pool FacilitiesOptimized Operation of Indoor Public Pool Facilities
Optimized Operation of Indoor Public Pool Facilities
 
Deep Carbonization
Deep CarbonizationDeep Carbonization
Deep Carbonization
 
Small Embedded Data Center Pilot
Small Embedded Data Center PilotSmall Embedded Data Center Pilot
Small Embedded Data Center Pilot
 
The Ons & Offs of ERV Effectiveness
The Ons & Offs of ERV EffectivenessThe Ons & Offs of ERV Effectiveness
The Ons & Offs of ERV Effectiveness
 
New Technology for Efficient Multifamily Building Envelope Sealing
New Technology for Efficient Multifamily Building Envelope SealingNew Technology for Efficient Multifamily Building Envelope Sealing
New Technology for Efficient Multifamily Building Envelope Sealing
 
Cost-Effective Duct Retrofit & Leakage Reduction
Cost-Effective Duct Retrofit & Leakage ReductionCost-Effective Duct Retrofit & Leakage Reduction
Cost-Effective Duct Retrofit & Leakage Reduction
 
Supporting energy design performance thru code compliance
Supporting energy design performance thru code complianceSupporting energy design performance thru code compliance
Supporting energy design performance thru code compliance
 
Commercial Condensing Boiler Optimization
Commercial Condensing Boiler OptimizationCommercial Condensing Boiler Optimization
Commercial Condensing Boiler Optimization
 
Project Kickoff Webinar Slides: MN Energy Efficiency & Carbon Saving Potentia...
Project Kickoff Webinar Slides: MN Energy Efficiency & Carbon Saving Potentia...Project Kickoff Webinar Slides: MN Energy Efficiency & Carbon Saving Potentia...
Project Kickoff Webinar Slides: MN Energy Efficiency & Carbon Saving Potentia...
 
Mid-size City Benchmarking Workshop: Institute for Market Transformation
Mid-size City Benchmarking Workshop: Institute for Market TransformationMid-size City Benchmarking Workshop: Institute for Market Transformation
Mid-size City Benchmarking Workshop: Institute for Market Transformation
 

Recently uploaded

GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756dollysharma2066
 
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
Call On 6297143586 Pimpri Chinchwad Call Girls In All Pune 24/7 Provide Call...
Call On 6297143586  Pimpri Chinchwad Call Girls In All Pune 24/7 Provide Call...Call On 6297143586  Pimpri Chinchwad Call Girls In All Pune 24/7 Provide Call...
Call On 6297143586 Pimpri Chinchwad Call Girls In All Pune 24/7 Provide Call...tanu pandey
 
Verified Trusted Kalyani Nagar Call Girls 8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...
Verified Trusted Kalyani Nagar Call Girls  8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...Verified Trusted Kalyani Nagar Call Girls  8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...
Verified Trusted Kalyani Nagar Call Girls 8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...tanu pandey
 
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...SUHANI PANDEY
 
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...MOHANI PANDEY
 
Get Premium Attur Layout Call Girls (8005736733) 24x7 Rate 15999 with A/c Roo...
Get Premium Attur Layout Call Girls (8005736733) 24x7 Rate 15999 with A/c Roo...Get Premium Attur Layout Call Girls (8005736733) 24x7 Rate 15999 with A/c Roo...
Get Premium Attur Layout Call Girls (8005736733) 24x7 Rate 15999 with A/c Roo...MOHANI PANDEY
 
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...rajputriyana310
 
CSR_Tested activities in the classroom -EN
CSR_Tested activities in the classroom -ENCSR_Tested activities in the classroom -EN
CSR_Tested activities in the classroom -ENGeorgeDiamandis11
 
Call Girls In Okhla DELHI ~9654467111~ Short 1500 Night 6000
Call Girls In Okhla DELHI ~9654467111~ Short 1500 Night 6000Call Girls In Okhla DELHI ~9654467111~ Short 1500 Night 6000
Call Girls In Okhla DELHI ~9654467111~ Short 1500 Night 6000Sapana Sha
 
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Services
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts ServicesBOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Services
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Servicesdollysharma2066
 
VVIP Pune Call Girls Moshi WhatSapp Number 8005736733 With Elite Staff And Re...
VVIP Pune Call Girls Moshi WhatSapp Number 8005736733 With Elite Staff And Re...VVIP Pune Call Girls Moshi WhatSapp Number 8005736733 With Elite Staff And Re...
VVIP Pune Call Girls Moshi WhatSapp Number 8005736733 With Elite Staff And Re...SUHANI PANDEY
 
Call Girls Talegaon Dabhade Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Talegaon Dabhade Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Talegaon Dabhade Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Talegaon Dabhade Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Proposed Amendments to Chapter 15, Article X: Wetland Conservation Areas
Proposed Amendments to Chapter 15, Article X: Wetland Conservation AreasProposed Amendments to Chapter 15, Article X: Wetland Conservation Areas
Proposed Amendments to Chapter 15, Article X: Wetland Conservation Areas💥Victoria K. Colangelo
 
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night StandHot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Standkumarajju5765
 
Cheap Call Girls in Dubai %(+971524965298 )# Dubai Call Girl Service By Rus...
Cheap Call Girls  in Dubai %(+971524965298 )#  Dubai Call Girl Service By Rus...Cheap Call Girls  in Dubai %(+971524965298 )#  Dubai Call Girl Service By Rus...
Cheap Call Girls in Dubai %(+971524965298 )# Dubai Call Girl Service By Rus...Escorts Call Girls
 
Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.cojitesh
 
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...kauryashika82
 
Booking open Available Pune Call Girls Budhwar Peth 6297143586 Call Hot Indi...
Booking open Available Pune Call Girls Budhwar Peth  6297143586 Call Hot Indi...Booking open Available Pune Call Girls Budhwar Peth  6297143586 Call Hot Indi...
Booking open Available Pune Call Girls Budhwar Peth 6297143586 Call Hot Indi...Call Girls in Nagpur High Profile
 

Recently uploaded (20)

(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7
(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7
(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7
 
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
 
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Call On 6297143586 Pimpri Chinchwad Call Girls In All Pune 24/7 Provide Call...
Call On 6297143586  Pimpri Chinchwad Call Girls In All Pune 24/7 Provide Call...Call On 6297143586  Pimpri Chinchwad Call Girls In All Pune 24/7 Provide Call...
Call On 6297143586 Pimpri Chinchwad Call Girls In All Pune 24/7 Provide Call...
 
Verified Trusted Kalyani Nagar Call Girls 8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...
Verified Trusted Kalyani Nagar Call Girls  8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...Verified Trusted Kalyani Nagar Call Girls  8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...
Verified Trusted Kalyani Nagar Call Girls 8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...
 
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
 
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
 
Get Premium Attur Layout Call Girls (8005736733) 24x7 Rate 15999 with A/c Roo...
Get Premium Attur Layout Call Girls (8005736733) 24x7 Rate 15999 with A/c Roo...Get Premium Attur Layout Call Girls (8005736733) 24x7 Rate 15999 with A/c Roo...
Get Premium Attur Layout Call Girls (8005736733) 24x7 Rate 15999 with A/c Roo...
 
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...
 
CSR_Tested activities in the classroom -EN
CSR_Tested activities in the classroom -ENCSR_Tested activities in the classroom -EN
CSR_Tested activities in the classroom -EN
 
Call Girls In Okhla DELHI ~9654467111~ Short 1500 Night 6000
Call Girls In Okhla DELHI ~9654467111~ Short 1500 Night 6000Call Girls In Okhla DELHI ~9654467111~ Short 1500 Night 6000
Call Girls In Okhla DELHI ~9654467111~ Short 1500 Night 6000
 
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Services
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts ServicesBOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Services
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Services
 
VVIP Pune Call Girls Moshi WhatSapp Number 8005736733 With Elite Staff And Re...
VVIP Pune Call Girls Moshi WhatSapp Number 8005736733 With Elite Staff And Re...VVIP Pune Call Girls Moshi WhatSapp Number 8005736733 With Elite Staff And Re...
VVIP Pune Call Girls Moshi WhatSapp Number 8005736733 With Elite Staff And Re...
 
Call Girls Talegaon Dabhade Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Talegaon Dabhade Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Talegaon Dabhade Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Talegaon Dabhade Call Me 7737669865 Budget Friendly No Advance Boo...
 
Proposed Amendments to Chapter 15, Article X: Wetland Conservation Areas
Proposed Amendments to Chapter 15, Article X: Wetland Conservation AreasProposed Amendments to Chapter 15, Article X: Wetland Conservation Areas
Proposed Amendments to Chapter 15, Article X: Wetland Conservation Areas
 
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night StandHot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Stand
 
Cheap Call Girls in Dubai %(+971524965298 )# Dubai Call Girl Service By Rus...
Cheap Call Girls  in Dubai %(+971524965298 )#  Dubai Call Girl Service By Rus...Cheap Call Girls  in Dubai %(+971524965298 )#  Dubai Call Girl Service By Rus...
Cheap Call Girls in Dubai %(+971524965298 )# Dubai Call Girl Service By Rus...
 
Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.
 
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...
 
Booking open Available Pune Call Girls Budhwar Peth 6297143586 Call Hot Indi...
Booking open Available Pune Call Girls Budhwar Peth  6297143586 Call Hot Indi...Booking open Available Pune Call Girls Budhwar Peth  6297143586 Call Hot Indi...
Booking open Available Pune Call Girls Budhwar Peth 6297143586 Call Hot Indi...
 

Field Assessment of Cold-Climate Air-Source Heat Pumps in Minnesota

  • 1. Field Assessment of Cold-Climate Air-Source Heat Pumps in Minnesota March 2019 Center for Energy and Environment
  • 2. Why ASHPs in MN? • Cold-climate technology improvements • Significant amounts of electric heating • Growing discussion around fuel switching – Electric grid getting greener – Delivered fuels can be expensive • CEE’s initial work started in response to propane shortages in winter of 2014
  • 3. Study Overview • Field Study – 8 ccASHP in a variety of MN residences • 6 ducted whole house system • 2 ductless mini-split systems – Monitor installed field performance of ASHP & backup • Incorporate into utility energy conservation program • Climate zones 6 & 7 • Detailed monitoring system installed at each site
  • 4. Ducted Whole House Installation Flex Fuel Systems
  • 5. Ducted Whole House Installation All Electric Systems
  • 6. Installation Considerations Control and Operation Integration with backup Sizing
  • 7. • Trade-offs between HP size and fraction of heating load meet • Rule of thumb: Sizing for heating increases HP size by 1-ton over sizing for cooling Design and Sizing for Ducted Systems Percentage of heating load meet by ASHP: 4 ton ~ 86%, 3 ton ~ 77% 2 ton ~ 60%
  • 8. • Trade-offs between HP size and fraction of heating load meet • Rule of thumb: Sizing for heating increases HP size by 1-ton over sizing for cooling Design and Sizing for Ducted Systems Percentage of heating load meet by ASHP: 4 ton ~ 86%, 3 ton ~ 77% 2 ton ~ 60% Furnace back-up heating
  • 9. • Trade-offs between HP size and fraction of heating load meet • Rule of thumb: Sizing for heating increases HP size by 1-ton over sizing for cooling Design and Sizing for Ducted Systems Percentage of heating load meet by ASHP: 4 ton ~ 86%, 3 ton ~ 77% 2 ton ~ 60% Electric booster heating
  • 10. Heating cycle COP of a flex fuel system
  • 11. Heating Cycle COP of all electric
  • 12. Annual Characteristics and Savings • Ducted Flex fuel ccASHP compared to condensing furnace (LP) – Annual COP improved to 1.3 (over 0.85) – ~40% site energy reduction – ~30% cost reduction – ~60% reduction in propane use – ~5% reduction in emissions (J. Edwards Thurs 8/16, Session 2) • All-electric Ducted ccASHP – Annual COP ~1.9 – ~60% site energy reduction
  • 13. Conclusions • Heat pump’s preformed as expected when heating • Annual COPs are lower than HSPF ratings due integration with auxiliary heating and freeze protection • Flex Fuel ccASHPs can heat below 5F, all electric systems below -13F • Paybacks are attractive when existing heating or cooling system need to be replaced Percentage Reductions for ccASHPs Site Energy Source Energy Homeowner Cost Emissions Dual fuel ASHP vs Prop. Furn. 40% 10% 30% 5% All elect. ducted & ductless vs elect. resistance 55% 55% 55% 55%
  • 15. Study Overview • Field Study – 8 ccASHP in a variety of MN residences • 6 ducted whole house system • 2 ductless mini-split systems – Monitor installed field performance of ASHP & backup • Incorporate into utility energy conservation program • Climate zones 6 & 7 • Detailed monitoring system installed at each site
  • 16. Beneficial Electrification • When is fuels switching beneficial? – Reductions in • Emissions • Source energy • Homeowner cost • Biggest market in MN: Propane furnaces • Potential market: AC and should heating for nat. gas furnaces
  • 20. Installation Considerations • Controls : – Ducted Systems: automated controls to bring up backup – Ductless Systems: manual action by homeowner • Interaction with back-up systems – Ducted Systems: Integrated installs with shared controls – Ductless Systems: Separate systems • Sizing – Ducted Systems: Contractors typically sized for cooling – Ductless: Partial or full load design
  • 21. Replacement System Install Costs • For the 4 ducted systems: – Our average cost was ~$14,000* • NREL Residential equipment install database: – $6,340 for ducted 3ton ccASHP – $4,000 for a new condensing propane furnace ($3,000 for an 80%). • $10,340 Total – $5,540 for a new comparable SEER A/C • $800 incremental for ccASHP • Limited installs leading to higher costs • Requirement for new air handler or furnace increases costs considerably
  • 22. Instrumentation 1 2 3 4 5 6 7 8 11 12 13 14 15 Power Measurements: 1) Outdoor unit 2) Indoor unit 3) Indoor fan 4) Reversing valve Temperatures: 5) Supply Air 6) Return Air 7) Mechanical area ambient 8) Conditioned space Additional: 9) Back up fuel consumption 10) Delivered air flow 11) NOAA data
  • 23. Site Equipment Whole house ducted systems Site Number ASHP System ASHP Size ASHP Type Backup 1 Carrier Infinity with Greenspeed [25VNA048A003] 4 ton Ducted LP Cond. Furnace 2 Bryant Extreme Heat Pump [280ANV048] 4 ton Ducted LP Cond. Furnace 3 Carrier Infinity with Greenspeed [25VNA036A003] 3 ton Ducted LP 80% Furnace 4 Trane XV20i [4TWV0036A] 3 ton Ducted LP Cond. Furnace 5 Mitsibishi Ductless Hyper Heat [MUZ-FH18NAH] 1.5 ton Ductless Electric Resistance 6 Mitsibishi Ductless Hyper Heat [MSZ-FH12NA] 1 ton (2 units) Ductless Electric Resistance 7 Mitsubishi Hyper Heat System [PVA-A30AA7] 3 ton Ducted Electric Booster 8 Mitsubishi Hyper Heat System [PVA-A30AA7] 3 ton Ducted Electric Booster
  • 24. Ducted Whole House Installation Flex Fuel Systems
  • 25. Ducted Whole House Installation Flex Fuel Systems
  • 26. Cold Temperature Performance of ASHPs • Ducted ASHPs were capable of delivering heat at outdoor temps from 5 to 10 F • Ductless systems operated below -13 F. • Homeowner in WI has removed several ER baseboards
  • 27. System Performance Annual COP: ductless ~1.9 to 2.1 Flex Fuel ~1.2 to 1.3