Ensure
Smooth Plant Operation
thanks to the most suitable
Critical Power Solution
Matthias Dreier
Technology Manager
GUTOR Electronic LLC
Switzerland
page 2 │17
Topics of this Presentation
Introduction
UPS Load Types
UPS Power Networks
UPS Configurations
Configuration Comparison
Conclusion
page 3 │17
Introduction
UPS = Uninterruptible Power Supply for critical AC-loads
UPS main duties
Secure continuous power to critical loads
Act as a mains filter
UPS environment
Upstream feeding concept
Downstream distribution set-up
UPS loads
Input topology / Current characteristics
There is no „one and only“ solution
page 4 │17
UPS Load Types
Linear Loads
Sinusoidal input current / no harmonics feed back
Traditional loads and power factor corrected (PFC) loads
Single- or dual inputs
PFC
PFC
AC Input 2
AC Input 1
Linear Load with dual inputs
page 5 │17
UPS Load Types
Non-linear Loads
Distorted input current with high crest factor
Non power factor corrected SMPS loads
Single- or dual inputs
AC Input
Converter
+
Switched
Mode
Power
Supply
90º
Peak value
RMS value
Peak value
x1,41
x3 - 5
Current Crest Factor
page 6 │17
UPS Power Networks
Upstream Supply Set-up
Source 1
Bus 1
Source 2
Bus 2
Tie-up
UPS Rectifier Input UPS Bypass Input
UPS
page 7 │17
UPS Power Networks
Downstream Distribution Set-up
UPS 1 UPS 2
Safe Bus 1 Safe Bus 2
Single Input Load
Tie-up
Dual Input Load
Single Input Load
page 8 │17
UPS Configurations
Single Unit Configuration
Secured Load Bus
Bypass Input
Rectifier Input
Rectifier Inverter
Manual Bypass Switch
Static Switch
Battery
Double Conversion UPS System with PWM Inverter
Battery Operation
Bypass Operation
Normal Operation
page 9 │17
UPS Configurations
Cascade or Hot-standby Configuration
Secured Load Bus
Rectifier Input
Master
Master UPS Module
Load on Master UPS
Load on Slave UPS
Bypass Input
Rectifier Input
Slave
Slave UPS Module
page 10 │17
UPS Configurations
Parallel Redundant Configuration
Bypass Input
Secured Load Bus
Rectifier Input
Module A
UPS Module A
Rectifier Input
Module B
UPS Module B
50 %
50 %
page 11 │17
UPS Configurations
Dual UPS Configuration
Bypass Input
Module B
Rectifier Input
Module B
Secured Load Bus B
UPS Module B
Rectifier Input
Module A
UPS Module A
Bypass Input
Module A
Secured Load Bus A
page 12 │17
UPS Configuration Comparison
Functionality
Ability of a UPS System to supply the loads uninterrupted
Immunity against external influences (supply, environment)
53Dual Units
44Parallel Redundant
33Cascade
33Single Unit
Dual Feed LoadsSingle Feed LoadsConfiguration
Score RatesUPS
page 13 │17
UPS Configuration Comparison
Reliability
Continuous UPS up-time duration between critical failures
MTBF figure (Mean Time Between Failure) for load supply
52Dual Units
44Parallel Redundant
33Cascade
22Single Unit
Dual Feed LoadsSingle Feed LoadsConfiguration
Score RatesUPS
page 14 │17
UPS Configuration Comparison
Maintainability
Safe UPS maintenance work without disturbing the load
Switching procedures reduced to an absolute minimum
52Dual Units
44Parallel Redundant
33Cascade
22Single Unit
Dual Feed LoadsSingle Feed LoadsConfiguration
Score RatesUPS
page 15 │17
UPS Configuration Comparison
Operability
User friendly operation- and monitoring scheme
Co-ordinated operation mode control between UPS modules
33Dual Units
44Parallel Redundant
33Cascade
44Single Unit
Dual Feed LoadsSingle Feed LoadsConfiguration
Score RatesUPS
page 16 │17
UPS Configuration Comparison
System- and Installation Costs
UPS solution costs scaled to single unit with single feed loads
Including power distribution network- and installation costs
220 %200 %Dual Units
200 %180 %Parallel Redundant
200 %180 %Cascade
120 %100 %Single Unit
Dual Feed LoadsSingle Feed LoadsConfiguration
Relative Solution CostsUPS
page 17 │17
Conclusion
UPS solutions must be considered in their entirety
Final judgement on „what is always best“ is impossible
Parallel Redundant Systems are very suitable for any loads
Dual Units with pure Dual Feed Loads is the „high-end“ choice
The most expensive & complex solution is not always best
Investing in the right UPS solution is a good insurance

More Related Content

What's hot

30167812 short-circuit-ppt
30167812 short-circuit-ppt30167812 short-circuit-ppt
30167812 short-circuit-pptAnto Damanik
 
2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revb2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revbVan Phuong Pham
 
2016.10.05 LED, dioder, zenerdioder og likerettere - studieveiledning for o...
2016.10.05   LED, dioder, zenerdioder og likerettere - studieveiledning for o...2016.10.05   LED, dioder, zenerdioder og likerettere - studieveiledning for o...
2016.10.05 LED, dioder, zenerdioder og likerettere - studieveiledning for o...Sven Åge Eriksen
 
Principles of Cable Sizing
Principles of Cable SizingPrinciples of Cable Sizing
Principles of Cable SizingLeonardo ENERGY
 
Effect of change in burden and power factor on CTs
Effect of change in burden and power factor on  CTsEffect of change in burden and power factor on  CTs
Effect of change in burden and power factor on CTsManish Sadhu
 
Wireless Power Transmission Using Resonant Inductive Coupling
Wireless Power Transmission Using Resonant Inductive Coupling Wireless Power Transmission Using Resonant Inductive Coupling
Wireless Power Transmission Using Resonant Inductive Coupling Kavinchakkaravarthi S
 
The working principle of ups
The working principle of upsThe working principle of ups
The working principle of upsjayonline_4u
 
summer internship report on erection, commissioning and pre-comissioning of50...
summer internship report on erection, commissioning and pre-comissioning of50...summer internship report on erection, commissioning and pre-comissioning of50...
summer internship report on erection, commissioning and pre-comissioning of50...Rahul Akinapelli
 
Power system analysis material -Mathankumar.s VMKVEC
Power system analysis material -Mathankumar.s  VMKVECPower system analysis material -Mathankumar.s  VMKVEC
Power system analysis material -Mathankumar.s VMKVECMathankumar S
 
Cable fault location methods (Megger)
Cable fault location methods (Megger)Cable fault location methods (Megger)
Cable fault location methods (Megger)AHMED MOHAMED HEGAB
 
Electrical Circuit.pdf
Electrical Circuit.pdfElectrical Circuit.pdf
Electrical Circuit.pdfssuserf798a5
 
TOWNSEND"S (FIRST)PRIMARY & SECONDARY IONIZATION COEFFICIENT|DERIVATION|HIGH ...
TOWNSEND"S (FIRST)PRIMARY & SECONDARY IONIZATION COEFFICIENT|DERIVATION|HIGH ...TOWNSEND"S (FIRST)PRIMARY & SECONDARY IONIZATION COEFFICIENT|DERIVATION|HIGH ...
TOWNSEND"S (FIRST)PRIMARY & SECONDARY IONIZATION COEFFICIENT|DERIVATION|HIGH ...Prasant Kumar
 

What's hot (20)

Earthing.ppt
Earthing.pptEarthing.ppt
Earthing.ppt
 
30167812 short-circuit-ppt
30167812 short-circuit-ppt30167812 short-circuit-ppt
30167812 short-circuit-ppt
 
2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revb2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revb
 
2016.10.05 LED, dioder, zenerdioder og likerettere - studieveiledning for o...
2016.10.05   LED, dioder, zenerdioder og likerettere - studieveiledning for o...2016.10.05   LED, dioder, zenerdioder og likerettere - studieveiledning for o...
2016.10.05 LED, dioder, zenerdioder og likerettere - studieveiledning for o...
 
Principles of Cable Sizing
Principles of Cable SizingPrinciples of Cable Sizing
Principles of Cable Sizing
 
Mv design guide
Mv design guideMv design guide
Mv design guide
 
Effect of change in burden and power factor on CTs
Effect of change in burden and power factor on  CTsEffect of change in burden and power factor on  CTs
Effect of change in burden and power factor on CTs
 
Partial discharge testing
Partial discharge testingPartial discharge testing
Partial discharge testing
 
Wireless Power Transmission Using Resonant Inductive Coupling
Wireless Power Transmission Using Resonant Inductive Coupling Wireless Power Transmission Using Resonant Inductive Coupling
Wireless Power Transmission Using Resonant Inductive Coupling
 
The working principle of ups
The working principle of upsThe working principle of ups
The working principle of ups
 
summer internship report on erection, commissioning and pre-comissioning of50...
summer internship report on erection, commissioning and pre-comissioning of50...summer internship report on erection, commissioning and pre-comissioning of50...
summer internship report on erection, commissioning and pre-comissioning of50...
 
EEE 2
EEE 2EEE 2
EEE 2
 
IEEE 519 92 vs 14
IEEE 519 92 vs 14IEEE 519 92 vs 14
IEEE 519 92 vs 14
 
Ehv ac transmission line
Ehv ac transmission lineEhv ac transmission line
Ehv ac transmission line
 
Basic Ups
Basic UpsBasic Ups
Basic Ups
 
presentation on UPs
presentation on UPspresentation on UPs
presentation on UPs
 
Power system analysis material -Mathankumar.s VMKVEC
Power system analysis material -Mathankumar.s  VMKVECPower system analysis material -Mathankumar.s  VMKVEC
Power system analysis material -Mathankumar.s VMKVEC
 
Cable fault location methods (Megger)
Cable fault location methods (Megger)Cable fault location methods (Megger)
Cable fault location methods (Megger)
 
Electrical Circuit.pdf
Electrical Circuit.pdfElectrical Circuit.pdf
Electrical Circuit.pdf
 
TOWNSEND"S (FIRST)PRIMARY & SECONDARY IONIZATION COEFFICIENT|DERIVATION|HIGH ...
TOWNSEND"S (FIRST)PRIMARY & SECONDARY IONIZATION COEFFICIENT|DERIVATION|HIGH ...TOWNSEND"S (FIRST)PRIMARY & SECONDARY IONIZATION COEFFICIENT|DERIVATION|HIGH ...
TOWNSEND"S (FIRST)PRIMARY & SECONDARY IONIZATION COEFFICIENT|DERIVATION|HIGH ...
 

Similar to Intro ups

PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmPC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmElektrumlv
 
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...IJERD Editor
 
 Running UPS in Economy Mode To Save Energy
 Running UPS in Economy Mode To Save Energy Running UPS in Economy Mode To Save Energy
 Running UPS in Economy Mode To Save Energyjerianasmith
 
6dec2011 - Power Back-up_2
6dec2011 - Power Back-up_26dec2011 - Power Back-up_2
6dec2011 - Power Back-up_2Agora Group
 
Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design ConsiderationsSchneider Electric
 
UPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with JenUPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with Jen42U Data Center Solutions
 
Schneider Electric risinājumi serveru telpu infrastruktūrai
Schneider Electric risinājumi serveru telpu infrastruktūraiSchneider Electric risinājumi serveru telpu infrastruktūrai
Schneider Electric risinājumi serveru telpu infrastruktūraiElektrumlv
 
ELECTRICAL INST Power systems and Electrical equipment lecture 3 -.ppt
ELECTRICAL INST Power systems and Electrical equipment  lecture 3 -.pptELECTRICAL INST Power systems and Electrical equipment  lecture 3 -.ppt
ELECTRICAL INST Power systems and Electrical equipment lecture 3 -.pptNelyJay
 
Simplify Power Disruption Management for Higher Efficiency and Lower Cost wit...
Simplify Power Disruption Management for Higher Efficiency and Lower Cost wit...Simplify Power Disruption Management for Higher Efficiency and Lower Cost wit...
Simplify Power Disruption Management for Higher Efficiency and Lower Cost wit...Delta Electronics Power Supply
 
UPS efficiency CEMEP 2005
UPS efficiency CEMEP 2005UPS efficiency CEMEP 2005
UPS efficiency CEMEP 2005Gimélec
 
2009-dec02_OnDuty
2009-dec02_OnDuty2009-dec02_OnDuty
2009-dec02_OnDutyAgora Group
 

Similar to Intro ups (20)

PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmPC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
 
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
 
 Running UPS in Economy Mode To Save Energy
 Running UPS in Economy Mode To Save Energy Running UPS in Economy Mode To Save Energy
 Running UPS in Economy Mode To Save Energy
 
6dec2011 - Power Back-up_2
6dec2011 - Power Back-up_26dec2011 - Power Back-up_2
6dec2011 - Power Back-up_2
 
UPS
UPSUPS
UPS
 
Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design Considerations
 
10027042_USV_Argument_gb
10027042_USV_Argument_gb10027042_USV_Argument_gb
10027042_USV_Argument_gb
 
UPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with JenUPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with Jen
 
Schneider Electric risinājumi serveru telpu infrastruktūrai
Schneider Electric risinājumi serveru telpu infrastruktūraiSchneider Electric risinājumi serveru telpu infrastruktūrai
Schneider Electric risinājumi serveru telpu infrastruktūrai
 
ELECTRICAL INST Power systems and Electrical equipment lecture 3 -.ppt
ELECTRICAL INST Power systems and Electrical equipment  lecture 3 -.pptELECTRICAL INST Power systems and Electrical equipment  lecture 3 -.ppt
ELECTRICAL INST Power systems and Electrical equipment lecture 3 -.ppt
 
A Novel Low Power-Application UPS Consisting of an APF - Correction Circuit &...
A Novel Low Power-Application UPS Consisting of an APF - Correction Circuit &...A Novel Low Power-Application UPS Consisting of an APF - Correction Circuit &...
A Novel Low Power-Application UPS Consisting of an APF - Correction Circuit &...
 
Simplify Power Disruption Management for Higher Efficiency and Lower Cost wit...
Simplify Power Disruption Management for Higher Efficiency and Lower Cost wit...Simplify Power Disruption Management for Higher Efficiency and Lower Cost wit...
Simplify Power Disruption Management for Higher Efficiency and Lower Cost wit...
 
ups pcb
ups pcbups pcb
ups pcb
 
Data Center UPS System Upgrade
Data Center UPS System UpgradeData Center UPS System Upgrade
Data Center UPS System Upgrade
 
F010344049
F010344049F010344049
F010344049
 
UPS efficiency CEMEP 2005
UPS efficiency CEMEP 2005UPS efficiency CEMEP 2005
UPS efficiency CEMEP 2005
 
Delta products overview
Delta products overviewDelta products overview
Delta products overview
 
Power System Review
Power System ReviewPower System Review
Power System Review
 
2009-dec02_OnDuty
2009-dec02_OnDuty2009-dec02_OnDuty
2009-dec02_OnDuty
 
UPS.pptx
UPS.pptxUPS.pptx
UPS.pptx
 

Intro ups

  • 1. page 1 │17 Ensure Smooth Plant Operation thanks to the most suitable Critical Power Solution Matthias Dreier Technology Manager GUTOR Electronic LLC Switzerland
  • 2. page 2 │17 Topics of this Presentation Introduction UPS Load Types UPS Power Networks UPS Configurations Configuration Comparison Conclusion
  • 3. page 3 │17 Introduction UPS = Uninterruptible Power Supply for critical AC-loads UPS main duties Secure continuous power to critical loads Act as a mains filter UPS environment Upstream feeding concept Downstream distribution set-up UPS loads Input topology / Current characteristics There is no „one and only“ solution
  • 4. page 4 │17 UPS Load Types Linear Loads Sinusoidal input current / no harmonics feed back Traditional loads and power factor corrected (PFC) loads Single- or dual inputs PFC PFC AC Input 2 AC Input 1 Linear Load with dual inputs
  • 5. page 5 │17 UPS Load Types Non-linear Loads Distorted input current with high crest factor Non power factor corrected SMPS loads Single- or dual inputs AC Input Converter + Switched Mode Power Supply 90º Peak value RMS value Peak value x1,41 x3 - 5 Current Crest Factor
  • 6. page 6 │17 UPS Power Networks Upstream Supply Set-up Source 1 Bus 1 Source 2 Bus 2 Tie-up UPS Rectifier Input UPS Bypass Input UPS
  • 7. page 7 │17 UPS Power Networks Downstream Distribution Set-up UPS 1 UPS 2 Safe Bus 1 Safe Bus 2 Single Input Load Tie-up Dual Input Load Single Input Load
  • 8. page 8 │17 UPS Configurations Single Unit Configuration Secured Load Bus Bypass Input Rectifier Input Rectifier Inverter Manual Bypass Switch Static Switch Battery Double Conversion UPS System with PWM Inverter Battery Operation Bypass Operation Normal Operation
  • 9. page 9 │17 UPS Configurations Cascade or Hot-standby Configuration Secured Load Bus Rectifier Input Master Master UPS Module Load on Master UPS Load on Slave UPS Bypass Input Rectifier Input Slave Slave UPS Module
  • 10. page 10 │17 UPS Configurations Parallel Redundant Configuration Bypass Input Secured Load Bus Rectifier Input Module A UPS Module A Rectifier Input Module B UPS Module B 50 % 50 %
  • 11. page 11 │17 UPS Configurations Dual UPS Configuration Bypass Input Module B Rectifier Input Module B Secured Load Bus B UPS Module B Rectifier Input Module A UPS Module A Bypass Input Module A Secured Load Bus A
  • 12. page 12 │17 UPS Configuration Comparison Functionality Ability of a UPS System to supply the loads uninterrupted Immunity against external influences (supply, environment) 53Dual Units 44Parallel Redundant 33Cascade 33Single Unit Dual Feed LoadsSingle Feed LoadsConfiguration Score RatesUPS
  • 13. page 13 │17 UPS Configuration Comparison Reliability Continuous UPS up-time duration between critical failures MTBF figure (Mean Time Between Failure) for load supply 52Dual Units 44Parallel Redundant 33Cascade 22Single Unit Dual Feed LoadsSingle Feed LoadsConfiguration Score RatesUPS
  • 14. page 14 │17 UPS Configuration Comparison Maintainability Safe UPS maintenance work without disturbing the load Switching procedures reduced to an absolute minimum 52Dual Units 44Parallel Redundant 33Cascade 22Single Unit Dual Feed LoadsSingle Feed LoadsConfiguration Score RatesUPS
  • 15. page 15 │17 UPS Configuration Comparison Operability User friendly operation- and monitoring scheme Co-ordinated operation mode control between UPS modules 33Dual Units 44Parallel Redundant 33Cascade 44Single Unit Dual Feed LoadsSingle Feed LoadsConfiguration Score RatesUPS
  • 16. page 16 │17 UPS Configuration Comparison System- and Installation Costs UPS solution costs scaled to single unit with single feed loads Including power distribution network- and installation costs 220 %200 %Dual Units 200 %180 %Parallel Redundant 200 %180 %Cascade 120 %100 %Single Unit Dual Feed LoadsSingle Feed LoadsConfiguration Relative Solution CostsUPS
  • 17. page 17 │17 Conclusion UPS solutions must be considered in their entirety Final judgement on „what is always best“ is impossible Parallel Redundant Systems are very suitable for any loads Dual Units with pure Dual Feed Loads is the „high-end“ choice The most expensive & complex solution is not always best Investing in the right UPS solution is a good insurance