ACT’s Sealed Enclosure Coolers are available in high efficiency heat sink or compact heat pipe designs with capacity 440 – 1,600 Watts. Units are available for applications in NEMA 12, 3R, 4 and 4X installations. Sealed enclosure coolers transfer heat from the inside cabinet space to the outside environment while maintaining air & water tight mounting seal.

Published in: Engineering
  • Be the first to comment

  • Be the first to like this

Sealed Enclosure Cooling Units

  1. 1. Application & Specification Guide Sealed Enclosure Cooling ACT Heat Sink Cooler Series ACT Heat Pipe Cooler Series Dual axial ball bearing fans for years of maintenance free operation 1-Year Warranty Sealed Enclosure Coolers Keep The Inside of your Enclosure Free of Dirt & Debris NEMA 2, 4, 4X and 3R models available Operating Voltages: 2VDC, 24VDC, 48VDC, 5VAC and 230VAC ADVANCED COOLING TECHNOLOGIES The Thermal Management Experts 1 1 11 SA44609 UL US LISTEDC
  2. 2. www.1-ACT.com/Enclosure-Cooling ACT-HSC Series Features and Options ACT-HSC Heat Sink Cooler Series Passive sealed enclosure coolers consisting of two high performance, aluminum finned heat sinks bonded to the opposite sides of a common mounting plate High performance/cost ratios due to the innovative use of advanced heat transfer and manufacturing technologies “Thin profile”, i.e., only 3.70” intrusion into the enclosure Minimum number of penetrations by cover fasteners, mounting fasteners and external fan wires Dual axial ball bearing fans for years of maintenance free operation Easy to install 1-Year Warranty (see ACT's Terms and Conditions) Patent Pending HSC-22 HSC-45 HSC-68 Part Number Thermal Conductance Watts/°C Thermal Capacity Watts @ 20°C ΛT Weight (lbs.) ACT-HSC-22 ACT-HSC-45 ACT-HSC-68 45.0 68.0 22.0 440 900 1,360 51.0 17.0 35.0 *Extends 3.70” into the cabinet H (in”) D* (in”) 12.00 W (in”) 12.00 12.00 12.00 7.88 7.88 7.88 22.75 31.38 Environment………....……….…………………….......….........................Indoor or Outdoor Use Electrical Configuration..........................................................................115VAC, 230VAC, 12VDC, 24VDC and 48VDC - AC units arrive with 6ft. long 3-pronged plug - DC units arrive with bare lead wires UL Listing & UL Recognition..................................................................The 115VAC units received a UL listing mark. All other versions (230VAC, 12VDC, 24VDC, and 48VDC) are UL Rated/UL Recognized NEMA Options.......................................................................................12, 3R, 4 and 4X, UL50E Certified Fans.......................................................................................................UL Listed 6.0” dual ball bearing type axial fans (dry & wet locations) Mounting Plate.......................................................................................Aircraft quality 6061 aluminum HSC Housing.........................................................................................Powder coated aluminum, Optional: stainless steel Mounting Options..................................................................................Top, side, front or back Accessories.......................................................................................Rain guards and removable filters SEALED ENCLOSURE COOLING SA44609 UL US LISTEDC
  3. 3. 3ADVANCED COOLING TECHNOLOGIES, INC. ACT-HSC Heat Sink Cooler Series 12.0” 12.0” 4.19” 3.70” 7.89” SIDEFRONT 12.0” 21.75” SIDE 4.19” 3.70” ACT-HSC-45 12.0” 31.375” SIDEFRONT 4.19” 3.70” 7.89” ACT-HSC-68 FRONT 7.89” ENCLOSURE CUTOUT TEMPLATE ACT- HSC Heat Pipe Cooler Series - Dimensions & Installation ACT-HSC-22 SEALED ENCLOSURE COOLING ENCLOSURE CUTOUT TEMPLATE ENCLOSURE CUTOUT TEMPLATE 0 0 5.69” 9.44” 0.25” 19.19” 6.25” 10.56” 11.38” 1.94” 0.25” 14.88” 1.94” 21.13” 10.88” 20.63” 0 0 0.25” 1.81” 5.69” 9.56” 11.38” 13.44” 21.19” 25.06” 28.94” 30.75” 0.25” 1.94” 5.69” 9.44” 17.31” 10.88” 0.221” THRU22X 30.25” 9.44” 11.38” 0 0 1.94” 5.69” 9.44” 11.38” 0.25” 1.94” 5.69” 0.25” 10.88” 10.88” 12X 0.221” THRU 16X 0.221” THRU
  4. 4. 4 www.1-ACT.com/Enclosure-Cooling ACT-HPC Heat Pipe Cooler Series ACT-HPC Series Features and Options Part Number Thermal Conductance Watts/°C Thermal Capacity Watts @ 20°C ΛT Weight (lbs.) H (in”) W (in”) D (in”) ACT-HPC-15 ACT-HPC-40 ACT-HPC-50 40.0 50.0 15.0 300 800 1,000 27.0 7.0 17.0 11.30 15.00 5.145 7.650 5.0 7.5 7.5 ACT-HPC-80 80.0 1,600 37.0 15.00 15.150 7.5 Insertion Depth (in”) Mounting Plate (in”) 5.60 7.40 10.90 7.40 6.75 x 6.75 10.0 x 10.0 10.0 x 10.0 10.0 x 17.5 7.645 22.00 HPC-15 HPC-40 HPC-50 HPC-80 Passive sealed enclosure coolers consisting of a heat pipe heat exchanger core with advanced fin features for enhanced heat transfer performance Optimized for high performance/volume ratios. Best performance when installed vertically through the top wall (roof) of the enclosure Performance may decrease slightly when installed horizontally through a side wall of the enclosure (Please contact ACT for details) Smaller opening footprint on the enclosure wall than the HSC-series Dual axial ball bearing fans for years of maintenance free operation Easy to install 1-Year Warranty (See ACT’s Terms and Conditions) Environment………....……….…………………….......….........................Indoor or Outdoor Use Electrical Configuration..........................................................................115VAC, 230VAC, 12VDC, 24VDC and 48VDC - AC units arrive with 6ft. long 3-pronged plug - DC units arrive with bare lead wires UL Listing & UL Recognition..................................................................The 115VAC units received a UL listing mark. All other versions (230VAC, 12VDC, 24VDC, and 48VDC) are UL Rated/UL Recognized NEMA Options.......................................................................................12, 3R, 4 and 4X, UL50E Certified Fans.......................................................................................................UL Listed 4.0” & 6.0” dual ball bearing type axial fans (dry & wet locations) Mounting Plate.......................................................................................304 stainless steel HSC Housing.........................................................................................Powder coated aluminum, Optional: stainless steel Mounting Options..................................................................................Top (best performance), side, front or back derated performance), contact ACT or use our Online Selection Tool to easily select models Accessories.......................................................................................Rain guards and removable filters SEALED ENCLOSURE COOLING SA44609 UL US LISTEDC
  5. 5. 12X 0.221” THRU ALL ACT-HPC Heat Pipe Cooler Series 5.44” 11.30” FRONT 5.70” 5.60” 6.75” 5.44” 7.94” 15.00” FRONT 7.60” 7.40” 10.0” 10.0” 7.94” ACT-HPC-40 7.94” 22.0” FRONT 11.10” 10.90” ACT-HPC-15 5.40” 6.75” 7.90” 10.0” 10.0” 7.94” 7.90” ACT-HPC-50 AIRFLOW DIRECTION AIRFLOW DIRECTION AIRFLOW DIRECTION ACT- HSC Heat Pipe Cooler Series - Dimensions & Installation SEALED ENCLOSURE COOLING ADVANCED COOLING TECHNOLOGIES, INC. ENCLOSURE CUTOUT TEMPLATE 8.00 8.00 0 0.50 3.00 6.00 8.50 9.00 0 0.50 3.00 6.00 8.50 9.00 ENCLOSURE CUTOUT TEMPLATE ” ” ” ” ” ” ” ” ” ” ” ” 8.00” 8.00” 0 0.50” 3.00” 6.00” 8.50” 9.00” 0 0.50” 3.00” 6.00” 8.50” 9.00” ENCLOSURE CUTOUT TEMPLATE 0 5.50” 6.25” 5.88” 3.13” 0.38” 0 0.38” 3.13” 5.88” 6.25” 5.50” 12X 0.221” THRU ALL 8X 0.221” THRU ALL TOP VIEW TOP VIEW TOP VIEW
  6. 6. 6 www.1-ACT.com/Enclosure-Cooling ACT-HPC Heat Pipe Cooler Series ACT- HPC Heat Pipe Cooler Series - Dimensions & Installation ACT-HPC-80 10.0” 17.50” 7.90” 15.44” 15.0” FRONT 7.60” 7.40” ACT-HPC HEAT PIPE COOLER OPTIONS All HPC series versions are available with an optional 3R rain hood. NEMA 3R Rain Hoods Filter Kit Options for Added Reliability Full Range of HPC Replacement Fans Installed HPC-15 Unit 15.44” AIRFLOW DIRECTION SEALED ENCLOSURE COOLING ENCLOSURE CUTOUT TEMPLATE 0 0 0.50 3.00 6.00 8.50 9.00 0.50 2.75 5.50 8.25 11.00 13.75 16.50 8.00 15.50 ” ” ” ” ” ” ” ” ” ” ” ” ” ” 18X 0.221” THRU ALLTOP VIEW
  7. 7. 7 NEMA 3R Rain Hood Version Filter Kit Options for Added Reliability Full Range of HSC Replacement Fans Installed ACT- HSC-22 Unit ACT-HSC HEAT SINK COOLER OPTIONS NEMA 3R Rain Hood Option ADVANCED COOLING TECHNOLOGIES, INC. SEALED ENCLOSURE COOLING
  8. 8. DOC-ACT-ENC-COOL - 002 I-2017 Easy-to-Use Enclosure Cooling Selection Tool www.1-ACT.com/Enclosure-Cooling/Selection-Tools/ Temperature °C or °F Dimensions in inches or millimeters Cabinet mounting options Application: dry, wet or spray down etc. Watts or Btu/h Calculate your selection Save/Print your selection Submit your selection to ACT for review Quick click to place your order Fast Delivery with Online Ordering www.1-ACT.com/Enclosure-Cooling/Order-Online Advanced Cooling Technologies, Inc. 1046 New Holland Avenue Lancaster, Pennsylvania 17601 Ph: 717.295.6061 | Fax: 717.295.6064 www.1-ACT.com/Enclosure-Cooling Info@1-act.com Represented By: Selection Options:

×