2. Introduction
WSOS is a software package developed
by Nu-Lec Industries to support their
range of automatic circuit reclosers and
sectionalisers with intelligent electronic
controllers.
More recently WSOS has developed its
own features for which the controllers
must provide software support.
3. Features
This presentation provides an
introduction to the following WSOS
software functions:
User Defined Curves
Automatic Data Retrieval
Batch Change
Configurable IOEX
Configurable DNP3
Change of State Monitoring System
4. User Defined Curves
This feature is two tools in one:
Curve Viewer
Curve Editor
The Curve Viewer allows WSOS users to
view standard and modified curves.
The Curve Editor allows standard curves
to be edited or new curves to be created
graphically.
This feature requires WSOS 4.14+
5. Curve Viewer Overview
The Curve Viewer is designed to show
graphically how a protection curve’s
shape is affected when curve modifiers
are applied.
Phase and Earth protection settings can
be modified in WSOS and the changes
viewed straight away.
Other curves can be displayed on the
same graph to allow comparisons with
settings for other trips on the same or
other reclosers.
6. Viewing Curves
To view a protection curve it is
first necessary to select a
protection group and a trip
number/type from within WSOS
to display the Trip 1, 2, 3, 4,
Single Shot or Work Tag
Settings screen
From here the Curve Viewer can
be launched by clicking the
“View Curve” button.
7. Curve Viewer
When launched the Curve Viewer displays
the selected Trip number’s curve with all
modifier settings applied.
300A
17.19s
13. User Defined Curve Editor Overview
The curve editor is a Microsoft Excel
based application launched from within
WSOS.
It is used to edit user defined protection
curves by typing values into a table or by
dragging individual points on the graph
itself.
Built-in functions allow the curve to be
manipulated around a selected point on
the curve.
Range functions allow the curve to be
modified across a number of points.
17. Creating New Curves
The easiest way to create a new curve is to:
load a comparison curve,
match the User Defined Curve to it,
Hide the Comparison Curve,
make edits to the User Defined Curve,
save the curve under a new name.
20. Select User Defined Curves
Curve Selection attaches user defined curves to WSOS
switchgear files which can then be written to switchgear
controllers.
22. Automatic Data Retrieval
Uploading history files such as the Event
Log and Maximum Demand records from
remote switchgear is a costly time
consuming exercise.
Automatic Data Retrieval was developed
to automate this process.
24. Automatic Data Retrieval - Overview
Automatic Data Retrieval allows selected
history files to be automatically uploaded
from selected switchgear during pre-
determined time periods on a regular
basis.
The current status of the upload
procedure for each switchgear can be
displayed by WSOS.
If WSOS can communicate with the
switchgear this feature can be used.
A level 50 WSOS licence is required for
ADR.
25. Automatic Data Retrieval Screens
There are three ADR screens that are
launched from the Customise menu.
Option Configuration
– Select which data you want
uploaded from each device.
Switchgear Selection
– Select when and how often to
upload from each device.
Switchgear Status
– A summary on the status of the
Automatic Data Retrieval for each
device.
27. Option Configuration Screen
This screen is used to
configure what is to
be automatically
uploaded for each
switchgear.
Communications
settings for ADR can be
different to the default
settings for the
switchgear.
29. Switchgear Selection Screen
This screen is used to configure what day and times the data is to be
automatically uploaded for each switchgear.
30. Switchgear Selection Setup
This screen is used to configure what day and times the data is to be
automatically uploaded for each switchgear.
31. Global ADR On/Off Control
ADR in the Title Bar indicates that a Level 50 licence
is installed
A global ‘Automatic Data Retrieval’ On/Off switch is
located below the Title Bar
34. Batch Change
The WSOS Batch Change feature allows
remote users to make changes to critical
settings in a group of automatic circuit
reclosers and/or load break switches
where these changes are deemed
necessary due to expected events such as
bushfires or storms.
The required setting changes for each
switchgear device can be configured in
advance at the remote WSOS computer
and the changes for all devices executed
with a single command or at a
predetermined time.
35. Batch Change Operation
ACR001
ACR002
ACR003
Configuration: ACR001 A/R On ->Off
ACR002 A/R On -> Off
ACR002 A/R On -> Off
Setting Change Options:
Auto Reclose On/Off
Earth Protection On/Off
SEF Protection On/Off
Active Protection Group A.B..J
Loop Automation On/Off
NPS Protection On/Off/Alarm
43. Input/Output Expander Module (IOEX Module)
The Input Output Expander (IOEX) card
enables easy interfacing of additional
external equipment to Nu-Lec’s Pole Top
Control Cubicle (PTCC).
This module allows the power utility to
connect items such as external
protection relays or an RTU as required.
The IOEX has:
12 optically isolated inputs and
8 voltage free output contacts.
44. IOEX Standard Map Inputs and Outputs
Standard Mapping has 8 used
inputs and 4 spare
Some inputs have logic
conditions applied
Standard Mapping
uses all 8 available
outputs.
Output 8 operates
according to
applied logic.
Inputs
Outputs
45. IOEX Standard Map Inputs and Outputs
Up to 8 outputs
can be configured.
Each output can
be configured to
operate for a given
status.
Outputs
Output 1 Switchgear Tripped
Output 4 Lockout
Output 8 Maintenance Required
46. Configurable IOEX
Custom maps can now be created for an
IOEX card and loaded into a CAPM
directly from WSOS.
The types of actions that can be mapped
to each input or output is dependent on
the software version loaded in the
CAPM.
When the tool is started the user is
asked to input the software version.
This is then used to retrieve a valid set of
points to use when constructing logic
within the tool.
47. Saved
IOEX
Mapping
Overview of IOEX Configuration
Launch IOEX
Tool from
WSOS
Switchgear
Device Points
Attach Mapping to
Switchgear Configuration
Write Mapping to tool for
editing
Read and Write IOEX
Mappings with Switchgear
Configurations
Switchgear
Configuration
WSOS
Configurable IOEX Tool
49. Configurable IOEX Scope
The Configurable IOEX tool allows WSOS
users to generate custom I/O mappings for
an Input Output Expander Card (IOEX).
Logic can be applied to each point with up to
five sets of logic or “actions” for each input
and one trigger action for each output.
The Configurable IOEX Tool can only create
mappings that are compatible with CAPM
software versions 027-07.xx (CAPM 4) and
527-07.xx (CAPM 5) or higher.
The Tool can be used to read mappings from
previous versions of software but can only
create files for use with the newer software
versions.
51. Distributed Network Protocol (DNP3)
DNP3 is a communications protocol
commonly used in the Electricity Supply
Industry for the control and monitoring of
switchgear devices.
The Nu-Lec DNP3 implementation allows
users to interface their controllers to a
SCADA system with a DNP3 master station.
The implementation includes a standard map
of points for this purpose.
Binary Input Points
Analogue Input Points
Counter Points
Binary Output Points
Analogue Output Points
53. Configurable DNP3
Custom DNP3 maps can now be created and
loaded into a controller directly from WSOS.
The mappings and I/O logic are created using
the tool and saved to a DNP3 mapping file on
the WSOS computer.
Once a valid file has been created, it is linked
to the switchgear device configuration in
WSOS and written into the controller.
The types of actions that can be mapped are
dependent on the software version loaded in
the Switchgear Devices controller.
When the tool is started the user is asked to
input the software version.
This is then used to retrieve a valid set of
points to use when constructing mappings
within the tool.
54. Saved
DNP3
Mapping
Overview of Configurable DNP3 Tool
Launch IOEX
Tool from
WSOS
Attach Mapping to
Switchgear Configuration
Write Mapping to tool for
editing
Read and Write DNP3
Mappings with Switchgear
Configurations
Switchgear
Configuration
WSOS
Configurable DNP3 Tool
55. Configurable DNP3 Scope
The Configurable DNP3 tool allows
WSOS users to generate custom DNP3
I/O mappings and load them into a
switchgear controller.
The Configurable DNP3 Tool can only
create mappings that are compatible
with CAPM software versions 028-01.xx
(CAPM4) and 528-01.xx (CAPM5) or
higher.
The Tool is available with WSOS 4.20 or
later and will work on Microsoft Windows
98, NT4, 2000 and XP.
57. Change of State Monitoring System
The Switchgear Monitoring System is
used to setup and operate a Change Of
State reporting system for Nu-Lec
switchgear using modems and radios.
This tool allows the user to configure
switchgear devices out in the field to
automatically dial in and report abnormal
conditions.
Network operators can respond to
reported events locally or be contacted
automatically if they are not in the office.
Automatic notification options include
e-mail, recorded messages over a phone
system or through a pager.
58. The monitoring system
requires a level 60
WSOS licence
Switchgear
being monitored
must be
capable of
WSOS
communications
with the PC
Communications
could be via
radios, landlines,
GSM phones
etc.
In Call-Out mode,
operators can be
notified by SMS or
pager.
On call operators
can also receive a
voice message via
phone
Automatic E-mails can
notify engineers of any
alarms that have been
generated
60. Monitoring System Configuration
Each device to be monitored by the
system needs to be configured so the
Monitoring System knows how to
respond whenever a defined event
occurs.
61. Action Profiles
Action Profiles are used to define what
action the Monitoring System will take
when an event is reported by the
switchgear device.
The action can be E-Mail, Dial Out
(phone), SMS/Pager message, A
combination of the above
This action will occur after a
set time period has passed
without the condition being
acknowledged locally at the
WSOS PC itself.
62. Monitoring System - Summary
The monitoring system can be used in
two ways – locally or callout.
When used locally an operator is at the
WSOS computer and responds to
abnormal conditions using WSOS.
If the callout mode is being used the
WSOS computer is left unattended and
the system reports abnormal conditions
by sending e-mail, SMS messages,
Pager messages or recorded messages
over a phone.
63. Questions?
User Defined Curves
Automatic Data Retrieval
Configurable IOEX
Configurable DNP3
Change of State Monitoring System
Editor's Notes
Tool Bar
This is located at the top left of the screen. The buttons are used to view a Print Preview, Print, Exit the viewer and Zoom.
Point Values Table
This two column table is located on the left of the screen. It displays all 30 normalised Current and Time values for the curve displayed in the graph.
Graph
The graph is situated in the centre of the window and displays the curve being edited plus any comparison curve that may have been loaded. The x-axis is the normalised current and the y-axis is time in seconds.
Options Panel
This is located on the right hand side of the screen. The buttons and drop down lists in this panel allow the user to select comparison graphs, apply functions to the graph, set time and current values and save the results.
To open an existing User Defined Curve for editing, select a curve from the “Select Curve to Open” dropdown list in the Options Panel. The new curve will then be plotted onto the graph and the Time and Current values will be displayed in the Point Values Table. The "Select Curve to Open" dropdown list can be refreshed by clicking on the "Refresh" button in the top right hand corner of the Options Panel.
Any of the standard protection curves can be displayed for comparison purposes by selecting them from the ‘Select Comparison Curve’ drop down list.
Switchgear List
This is a list of all the switchgear in the current working folder. You can highlight one or more on this list and then select the option you require.
Event Log, Average Demand, Weekly Demand, Monthly Demand, Configurable History,
These records will be uploaded after automatically on-line.
Read Switchgear Settings
All the switchgear settings will be uploaded (and saved to off-line data and the hard disk) after automatically going on-line.
Compare Switchgear SettingsAll the switchgear settings will be uploaded and compared to the off-line data. If there is a difference this will be shown on the Switchgear Status screen.
PC Clock Synchronisation
The PC clock will be used to set the clock in the CAPM.
Use Default Settings
Pressing this button will set the options to a previously saved file.
Save As Default
Pressing this button will save the options to a previously saved default.
Default Communications Settings
When this is selected, the communication settings used to go on-line automatically are the same as when you manually go on-line.
ADR Custom Communications Settings
When this is selected, the communication setting used to go on-line automatically are different to the settings when you manually go on-line. The Configure button is used to set the communications parameters. The communication screens are the same as the default communication screens.
Retry Time
This is the base number of minutes delay before attempting to automatically retrieve the data after a failure.
This is only used if there is a communications failure, or some other condition that prevented the automatic data retrieval. For example someone else is connected to the switchgear at the same time via modem.
Retry Multiplier
This is used to stagger communications retry times. The retry time is multiplied by this value and the attempt count to arrive at a new time to wait before attempting connection.
Attempt Connection
This is the number of retry times to automatically retrieve the data. This is used regardless of the communications medium (direct, modem or radio).
Communications Fail E-mail Enable
When enabled, if the ADR can not communicate with a switchgear then an e-mail message will be sent to the e-mail address entered. If not enabled, no e-mail message will be sent. This is a global setting and not specific to any switchgear.
Note: A MAPI compliant e-mail client application must be running on the ADR PC.
Frequency
This is used to select how often to automatically upload the data.
None – When this is selected, the available switchgear list box contains all the switchgear that have not been configured for automatic data retrieval.
Daily – When this is selected, the selected switchgear list box contains all the switchgear that have been configured to retrieve data each day.
Weekly – When this is selected, the selected switchgear list box contains all the switchgear that have been configured to retrieve data each week. N.B. A day of the week needs to be selected.
Fortnightly – When this is selected, the selected switchgear list box contains all the switchgear that have been configured to retrieve data every fortnight. N.B. A day of the week needs to be selected.
Day of Week
This is used to select the day to begin automatically uploading the required data.
Start time
This is the time that uploading the data will begin. (on hourly basis).
End Time
This is the time that uploading the data will stop (the current upload sequence will run till completion) (on hourly basis).
Available Switchgear
This is a list of the switchgear that have not already been selected. No switchgear can be included in multiple days to upload data. Initially this list contains all the switchgear in the working folder. Multiple switchgear can be selected in the normal Windows manner.
Add Switchgear
Allows a switchgear to be added to the selected switchgear.
Delete Switchgear
Allows a switchgear to be deleted from the selected switchgear list.
Selected Switchgear
This is a list of the selected switchgear for this day. Multiple switchgear can be selected in the normal Windows manner.
Print Configuration
Pressing this button will print the configuration for all the switchgear.
Idle – Not uploading information at this stage.
Starting – Beginning to upload the information (waiting to go on-line to a modem for example.
Uploading Event Log – Currently uploading the Event Log
Uploading Average Demand – Currently uploading the average demand historical data.
Uploading Weekly Demand – Currently uploading the weekly demand historical data.
Uploading Monthly Demand – Currently uploading the monthly demand historical data.
Uploading Configurable History – Currently uploading the configurable history data.
Read Switchgear Settings – Currently uploading the protection and communication data from the switchgear.
Comparing Switchgear Settings – Currently comparing the protection and communication data from the switchgear.
PC Clock Synchronisation – Currently synchronising the CAPM clock with the PC clock
Communications Fail – WSOS was not able to establish communications.
Compare File Different – The comparison found a difference.
Waiting – WSOS was unable to communicate and is still trying.(min left displayed)
Switchgear List
This is a list of the switchgear in the current working folder.
Copy Button
This button will copy the current selected commands to be copied to another switchgear.
Copy All Button
This button will copy the current selected commands for all the switchgear in the working directory.
Delete All Commands Button
This button will delete all the current commands for all the switchgear in the working directory.
Selected Commands
This is the list of selected commands and state that will be sent to the selected switchgear.
Add Button
This button will display the ‘Batch Command Configuration’ screen.
Delete Button
This button will delete all the selected commands.
Delete All Button
This button will delete all the selected commands.
Start Batch Change Button
This button will start the batch change for all the switchgear in the working directory.
Start Time
This allows the batch command to be started at a set time.
Start At Set Time
When selected this will start the batch change at the set time. When the batch change has finished, this is automatically reset to prevent the batch change happening again.
Attempt Connection
This is the number of times batch change will attempt communicating with a switchgear.
Communications Fail E-mail Enable
When enabled, if batch change can not communicate with a switchgear then an e-mail message will be sent to the e-mail address entered, if not enabled, no e-mail message will be sent. This is a global setting and not specific to any switchgear.
Communications Fail E-mail Address
This is the e-mail address used when a communication fail has occurred.
Switchgear Remote Access Password
Changing settings remotely requires the Remote Access Password to be entered. There is normal one Remote Access Password for all switchgear in a working directory which can be entered here. Default password is 000000.
Start Date/Time
This is the last time data for this switchgear was automatically uploaded.
Time Taken
This is how long it took to complete the batch change.
Force Update
Select a switchgear by highlighting the desired cell or row. Pressing this button will force the batch change to happen immediately.
Abort Update
Select a switchgear by highlighting the desired cell or row. Pressing this button will abort the current batch change.
Status
The current status of the batch change.
Idle – Not uploading information at this stage.
Going on-line – Beginning to upload the information (waiting to go on-line to a modem for example).
Waiting for message queue to empty – Waiting for the messages queued to be sent to the switchgear.
Getting password key – Asking the switchgear for the password key (optional)
Sending switchgear remote access password – Sending the switchgear remote access password to the switchgear (optional)
Sending commands – Send all the batch change commands to the switchgear.
No Action – The switchgear was not configured to send batch change commands.
Finished – Successfully sent all the batch change commands.
Finished (Not all commands sent) – One or more batch change commands was rejected by the switchgear.
Finished (Timed out) – Sending the batch change commands took too long.
The IOEX card has been engineered for safety and reliability.
It is designed to mount into the PTCC radio tray and is provided in a fully sealed enclosure with a cable for connection to the Control and Protection Module (CAPM).
The inputs and outputs of the IOEX are fully configurable using CAPM software V27+.
The mappings and I/O logic are created using the tool and saved to an IOEX mapping file on the WSOS computer. Once a valid file has been created, it is linked to the switchgear device configuration in WSOS and written into the CAPM.
The IOEX Configuration tool is intended to be used Off-Line only. Mappings are created, saved and linked to a WSOS switchgear device configuration while disconnected from the switchgear. Once these tasks have been completed the user connects to the device and writes the new mapping into the CAPM along with the switchgear device configuration.
The types of actions that can be mapped are dependent on the software version loaded in the Switchgear Device’s controller. When the tool is started the user is asked to input the software version. This is then used to retrieve a valid set of points to use when constructing mappings within the tool.
The Configurable DNP3 tool is intended to be used Off-Line only. Mappings are created, saved and linked to a WSOS switchgear device configuration while disconnected from the switchgear. Once these tasks have been completed the user connects to the device and writes the new mapping into the controller along with the switchgear device configuration.
For the Remote Monitoring system to work there must be communications devices installed and configured. The amount and type of devices required depends on how the Remote Monitoring system is to be used. At the minimum there must be a device for communicating with the switchgear being monitored.
Communications hardware must first be installed in the computer in accordance with the manufacturer’s instructions. They are then configured within WSOS in the usual way, see the WSOS help file for communications hardware setup information.
The main exception to the standard setup is when you are using a communications device to send Pager/SMS messages. In this case the TAP protocol communications settings need to be setup in the Telocator Alphanumeric Protocol Configure dialog screen. See section 3.1.6 for a description of TAP settings.
When the system receives an abnormal condition from a switchgear device a wave file is played through the computer’s sound card. Click the “Select Wave File” button to choose which file is played. This may be the standard message supplied by the manufacturer or it may be a message you have recorded yourself. Navigate and select the file then click the “OK” button.
Test the message is the correct one by clicking the “Test Wave File” button.
The “Time Between Sounds” text box is used to enter the time delay between each message. The message is repeated after this period until all abnormal conditions have been acknowledged.
The Switchgear Setup dialog defines what events will be reported as abnormal conditions within the Monitoring System and what actions will be taken as a result. What exactly needs configuring depends on the type of switchgear device, what notification method is defined in the action profile (phone, e-mail, or SMS/Pager) and which events need to be monitored.
The callout groups will display different conditions depending on the type of switchgear selected. For example, if a Load Break Switch is selected there will be “Mechanism Locked” and “Mechanism Unlocked” points available in the Operator Settings Callout group.
Multiple Action Profiles can be defined. Each profile can be used by any number of devices. For example, you may want to assign one action profile to Reclosers located in substations and another for Load Break Switches.
Only one action can be defined per device. It is not possible to assign a different type of action depending on which event the device reported.