www.energyetc.com SMART SYSTEMS….. Smart Future! Phone: 510.487.1876 Fax: 510.487.1878
OVERVIEW
This site consists of multiple single story buildings with multiple tenants. The previous automation system consisted of a
JACE with a tenant override option, 2 JCI NCM’s, 58 UNT controllers and 1 DX9100 controller. The UNTs were deployed
across the N2 channels of NCMs.
The Tridium JACE failed after a power cycle which left the building running 24/7 and without onsite WEB access to control
systems and tenant after-hours override and capability. This was probably due to the aged technology and installed
environment. No data backups were available.
Energy ETC was contacted by the servicing mechanical contractor to see what solutions were available to resolve the
issue.
CUSTOMER NEEDS / REQUIREMENTS
• INTERNET WEB GRAPHICAL PRESENTATION OF ALL SYSTEMS.
• TENANT AFTERHOURS TRACKING and INVOICING SOLUTION.
• STABLE and SUSTAINABLE HARDWARE DESIGN.
• ABILITY TO EXPAND to support DEMAND LIMITING / DEMAND RESPONSE.
• NEEDED to be COST EFFICIENT.
C A S E S T U D Y
Project Type : INTEGRATION
Facility Type : 5 Building Campus, Multiple Tenants
Location : San Francisco Bay Area
Management : Offsite Property Management
PREVIOUS SYSTEM ANALYSIS
Hardware : Jace, NCM-30’s, UNT’s, DX9100
Software : Local Web Interface, Tenant Override Billing
Type : Hybrid - Legacy
Vintage : 2000
Service Factor : 4 – Relatively High Cost
Migration Plan : Keep JCI Hardware, Replace Failed JACE.
CURRENT SYSTEM ANALYSIS
Hardware : Dell 1U Server Class PC in Co-location Ctr.
: Linksys VPN Routers
: S4 Open: OPC-N2 Router, UNT’s, DX9100
Software : ASI WebLink Interface w/ LinkOPC – Hosted
: ASI Zonedial Override Billing - Hosted
Type : Hybrid - Legacy
Vintage : 2009 Software / Hardware & 2000 JCI H/W
Service Factor : 2 – Relatively Low Cost due to HOSTING
Migration Plan : Replace JCI Field Devices with OPEN LON
www.energyetc.com SMART SYSTEMS….. Smart Future! Phone: 510.487.1876 Fax: 510.487.1878
THE APPROACH
There were several challenges in this integration:
• Integrate the N2 Devices without the need for the NCM’s. This solution needed to support:
OPC Server Connectivity to all discovered devices.
Remote Terminal Access Support over IP.
Connecting Multiple N2 Channels into 1 common device.
Auto discovery of the N2 controllers and associated data points.
Virtual Addressing support for duplicate N2 controller addresses.
Auto building of the point tree under the controllers.
Auto association with N2 controller internal application type with appropriate point templates.
• Design a PC / network configuration solution that provides for a low cost, low maintenance reliable model.
Needed to be offsite. There is no local onsite management.
Needed to be remotely managed for all software updates.
Needed to have 99.999% uptime services. (Power & ISP).
Needed to be located in a controlled environment. Due to previous failure.
• Implement a User Friendly and sustainable Graphical User Interface
Must be accessible from the Internet 24/7 with a standard web browser.
Must email and text message alarms.
Must support long term data trending.
Must be easily expandable.
Needed to have Help Desk support for Tenant and Management Questions.
Needed to integrate a Web Based Tenant Override / Invoice solution.
THE SOLUTION
Energy ETC, as a Smart Building System Integrator, has several product relationships from which to choose the
optimal configuration of software and hardware components to meet the customer requirements. All solutions we
design and implement are based on sustainability. The system as a whole cannot become obsolete. There must
always be a cost effective migration path for the various components that integrates into the existing configuration.
The key system components required were:
1. N2 connectivity over IP with OPC.
2. Provide a HOSTED or SaaS connection to the site from a secure co-location facility with Help Desk Support.
3. A 24/7 WEB based User Interface (UI) in a managed environment.
4. A WEB based Tenant Override / Invoice that would integrate to the UI and N2 devices.
www.energyetc.com SMART SYSTEMS….. Smart Future! Phone: 510.487.1876 Fax: 510.487.1878
THE SOLUTION
1. In order to meet the needs of item 1 we selected the S4 Open: OPC-N2 ROUTER. While other N2
connectivity options were available the OPC-N2 device provided optimal functionality and time saving
implementation features such as:
Auto discovery of the N2 controllers.
Virtual Addressing support for duplicate N2 controller addresses.
Auto building of the point tree under the controllers.
Auto association with N2 controller internal application type with appropriate point templates.
Remote connectivity via OPC through a VPN tunnel.
The S4 Interface Console software was easy to use and once installed on the PC server provided the required
OPC Server “tunneling” connectivity of the N2 points from the S4 Open: OPC-N2 Router to the Web User
Interface. Other solutions would not have been as clean to implement resulting in additional material and labor
costs.
2. To provide the requirements of Item 2 we selected a premier state-of- the-art internet data center located in
the heart to of Silicon Valley. This center provides:
AC power distributed via redundant MGE UPS (uninterrupted power supply) systems.
2 Megawatts of diesel generator backup power.
In excess of 24 hours of generator fuel on-site; contracts with multiple fuel providers.
100% facilities uptime SLA.
Power configured to meet customer specifications.
Fully redundant dual A+B power distribution.
Fully redundant chilled water system, chillers, pumps, and towers.
N+1 redundant air handlers.
Direct Connections to Third-Party Providers allowing for dedicated connectivity from a number
of vendors in the facility.
Speed connectivity options up to 10Gbit at the server points of connection.
A DELL® 1U class server running Microsoft® Business Class Server 2003 was installed at the data center to
run the applications. The consistency of the operating system bundled with the server and integrity of the data
center provided a low cost, low maintenance, high performance solution.
Energy ETC’s HOSTED-HELPDESK™ provides account services for:
Data integrity and offsite back-ups.
Monitoring of system and network operations.
Daily review of building operations and equipment conditions.
Operational Q&A support to the HOSTED client and client customers.
Changes to the system for site expansions and modifications.
www.energyetc.com SMART SYSTEMS….. Smart Future! Phone: 510.487.1876 Fax: 510.487.1878
THE SOLUTION
3. For Item 3 we selected the WebLink software solution from ASI Controls. WebLink provides:
A consistent User Interface to monitor and control the lower tier devices.
Global site Operational Scheduling control.
Alarm management, historical reporting and real-time email/ SMS annunciation.
Integration into the Tenant Override / Invoicing System.
Acceptable cost / performance pricing.
Other WEB based solutions were available yet WebLink was selected for its’ straight forward integration into
the tenant override / invoicing solution. Other solutions would have required an additional software driver layer
which would have resulted in additional costs.
4. In selecting the Tenant Override / Invoicing system there are several available on the market at various price
ranges but only one met the price / performance requirements and supported 3rd
party connectivity through
OPC. Our choice for this application was the ZoneDial Energy Accounting and Invoicing software solution
from ASI Controls. This solution provides for:
Schedule zone activation; invoice for energy costs.
Web browser interface with phone option.
Optional tenant self-administration.
Tenants schedule, and pay for, energy use.
Generate & print invoices.
Pre-scheduled or immediate activation.
Supports recurring overrides.
Tracks every user interaction.
Print instruction cards for each user.
Fully customizable rates, schedules and holidays.
SUMMARY
All components of the solution continue to perform to the client’s expectation.
The HOSTED model has been solid and continues to emphasize the benefits of
of the solution compared to the legacy configuration of installing the
components on a client site.
ORIGINAL ONSITE DESIGN NEW HOSTED DESIGN

More Related Content

What's hot

Software defined networking (sdn) deep dive 3rd-party ecosystem apps and the ...
Software defined networking (sdn) deep dive 3rd-party ecosystem apps and the ...Software defined networking (sdn) deep dive 3rd-party ecosystem apps and the ...
Software defined networking (sdn) deep dive 3rd-party ecosystem apps and the ...Aruba, a Hewlett Packard Enterprise company
 
Extend mobility to remote branch networks with Aruba's new cloud services con...
Extend mobility to remote branch networks with Aruba's new cloud services con...Extend mobility to remote branch networks with Aruba's new cloud services con...
Extend mobility to remote branch networks with Aruba's new cloud services con...Aruba, a Hewlett Packard Enterprise company
 
Mobile Experience Management and Network Services Health Check with Aruba Air...
Mobile Experience Management and Network Services Health Check with Aruba Air...Mobile Experience Management and Network Services Health Check with Aruba Air...
Mobile Experience Management and Network Services Health Check with Aruba Air...Aruba, a Hewlett Packard Enterprise company
 
Panduit EMEA SI Webinar 8
Panduit EMEA SI Webinar 8Panduit EMEA SI Webinar 8
Panduit EMEA SI Webinar 8Panduit
 
2596 - Integrating PureApplication System Into Your Network
2596 - Integrating PureApplication System Into Your Network2596 - Integrating PureApplication System Into Your Network
2596 - Integrating PureApplication System Into Your NetworkHendrik van Run
 
Best practices in deploying and managing aruba bluetooth low energy (ble) bea...
Best practices in deploying and managing aruba bluetooth low energy (ble) bea...Best practices in deploying and managing aruba bluetooth low energy (ble) bea...
Best practices in deploying and managing aruba bluetooth low energy (ble) bea...Aruba, a Hewlett Packard Enterprise company
 
WWTC_implementation_plan_Group5_FINAL
WWTC_implementation_plan_Group5_FINALWWTC_implementation_plan_Group5_FINAL
WWTC_implementation_plan_Group5_FINALJohn Bernal
 
Industrial Automation rtPAC System
Industrial Automation  rtPAC SystemIndustrial Automation  rtPAC System
Industrial Automation rtPAC Systemsanjaya1984
 
Corexchange Data Center Tour
Corexchange Data Center TourCorexchange Data Center Tour
Corexchange Data Center Tourtpersky
 
Ba cnet bldg_auto_solutions_brochure_sb008_a
Ba cnet bldg_auto_solutions_brochure_sb008_aBa cnet bldg_auto_solutions_brochure_sb008_a
Ba cnet bldg_auto_solutions_brochure_sb008_aalfmich
 
Foxboro Evo DCS - Εκδήλωση Explore Innovation - Αθήνα, Ιούνιος 2016
Foxboro Evo DCS - Εκδήλωση Explore Innovation - Αθήνα, Ιούνιος 2016Foxboro Evo DCS - Εκδήλωση Explore Innovation - Αθήνα, Ιούνιος 2016
Foxboro Evo DCS - Εκδήλωση Explore Innovation - Αθήνα, Ιούνιος 2016Schneider Electric
 
How Schneider Electric sees Ethernet in the Industrial Environment - Part 1
How Schneider Electric sees Ethernet in the Industrial Environment - Part 1How Schneider Electric sees Ethernet in the Industrial Environment - Part 1
How Schneider Electric sees Ethernet in the Industrial Environment - Part 1Schneider Electric
 
ArcSight Management Center 2.1 Release Notes
ArcSight Management Center 2.1 Release NotesArcSight Management Center 2.1 Release Notes
ArcSight Management Center 2.1 Release NotesProtect724mouni
 
Banking and ATM networking reports
Banking and ATM networking reportsBanking and ATM networking reports
Banking and ATM networking reportsShakib Ansaar
 

What's hot (18)

Software defined networking (sdn) deep dive 3rd-party ecosystem apps and the ...
Software defined networking (sdn) deep dive 3rd-party ecosystem apps and the ...Software defined networking (sdn) deep dive 3rd-party ecosystem apps and the ...
Software defined networking (sdn) deep dive 3rd-party ecosystem apps and the ...
 
Extend mobility to remote branch networks with Aruba's new cloud services con...
Extend mobility to remote branch networks with Aruba's new cloud services con...Extend mobility to remote branch networks with Aruba's new cloud services con...
Extend mobility to remote branch networks with Aruba's new cloud services con...
 
Mobile Experience Management and Network Services Health Check with Aruba Air...
Mobile Experience Management and Network Services Health Check with Aruba Air...Mobile Experience Management and Network Services Health Check with Aruba Air...
Mobile Experience Management and Network Services Health Check with Aruba Air...
 
Panduit EMEA SI Webinar 8
Panduit EMEA SI Webinar 8Panduit EMEA SI Webinar 8
Panduit EMEA SI Webinar 8
 
2596 - Integrating PureApplication System Into Your Network
2596 - Integrating PureApplication System Into Your Network2596 - Integrating PureApplication System Into Your Network
2596 - Integrating PureApplication System Into Your Network
 
N
NN
N
 
Deep visibility to secure network access with aruba ClearPass Insight
Deep visibility to secure network access with aruba ClearPass InsightDeep visibility to secure network access with aruba ClearPass Insight
Deep visibility to secure network access with aruba ClearPass Insight
 
EMEA Airheads- Aruba OS- Mobile First Platform– Aruba OS 8.0 introduction
EMEA Airheads- Aruba OS- Mobile First Platform– Aruba OS 8.0 introductionEMEA Airheads- Aruba OS- Mobile First Platform– Aruba OS 8.0 introduction
EMEA Airheads- Aruba OS- Mobile First Platform– Aruba OS 8.0 introduction
 
Best practices in deploying and managing aruba bluetooth low energy (ble) bea...
Best practices in deploying and managing aruba bluetooth low energy (ble) bea...Best practices in deploying and managing aruba bluetooth low energy (ble) bea...
Best practices in deploying and managing aruba bluetooth low energy (ble) bea...
 
WWTC_implementation_plan_Group5_FINAL
WWTC_implementation_plan_Group5_FINALWWTC_implementation_plan_Group5_FINAL
WWTC_implementation_plan_Group5_FINAL
 
Industrial Automation rtPAC System
Industrial Automation  rtPAC SystemIndustrial Automation  rtPAC System
Industrial Automation rtPAC System
 
Corexchange Data Center Tour
Corexchange Data Center TourCorexchange Data Center Tour
Corexchange Data Center Tour
 
Ba cnet bldg_auto_solutions_brochure_sb008_a
Ba cnet bldg_auto_solutions_brochure_sb008_aBa cnet bldg_auto_solutions_brochure_sb008_a
Ba cnet bldg_auto_solutions_brochure_sb008_a
 
Adapting to evolving user, security, and business needs with aruba clear pass
Adapting to evolving user, security, and business needs with aruba clear passAdapting to evolving user, security, and business needs with aruba clear pass
Adapting to evolving user, security, and business needs with aruba clear pass
 
Foxboro Evo DCS - Εκδήλωση Explore Innovation - Αθήνα, Ιούνιος 2016
Foxboro Evo DCS - Εκδήλωση Explore Innovation - Αθήνα, Ιούνιος 2016Foxboro Evo DCS - Εκδήλωση Explore Innovation - Αθήνα, Ιούνιος 2016
Foxboro Evo DCS - Εκδήλωση Explore Innovation - Αθήνα, Ιούνιος 2016
 
How Schneider Electric sees Ethernet in the Industrial Environment - Part 1
How Schneider Electric sees Ethernet in the Industrial Environment - Part 1How Schneider Electric sees Ethernet in the Industrial Environment - Part 1
How Schneider Electric sees Ethernet in the Industrial Environment - Part 1
 
ArcSight Management Center 2.1 Release Notes
ArcSight Management Center 2.1 Release NotesArcSight Management Center 2.1 Release Notes
ArcSight Management Center 2.1 Release Notes
 
Banking and ATM networking reports
Banking and ATM networking reportsBanking and ATM networking reports
Banking and ATM networking reports
 

Viewers also liked

ENTEC Case Study
ENTEC Case StudyENTEC Case Study
ENTEC Case StudySteve Jones
 
Case Study ATS Jackson Federal Building
Case Study ATS Jackson Federal BuildingCase Study ATS Jackson Federal Building
Case Study ATS Jackson Federal BuildingSteve Jones
 
final draft Wonderlich-Malec case study
final draft Wonderlich-Malec  case studyfinal draft Wonderlich-Malec  case study
final draft Wonderlich-Malec case studySteve Jones
 
Chipkin Automation - S4 Case Study - Calgary International Airport
Chipkin Automation - S4 Case Study - Calgary International AirportChipkin Automation - S4 Case Study - Calgary International Airport
Chipkin Automation - S4 Case Study - Calgary International AirportSteve Jones
 
S4 Value Proposition
S4 Value PropositionS4 Value Proposition
S4 Value PropositionSteve Jones
 
Pacific Brochure Products
Pacific Brochure ProductsPacific Brochure Products
Pacific Brochure ProductsJason Salsbury
 
Jarrell Case Study
Jarrell Case StudyJarrell Case Study
Jarrell Case StudySteve Jones
 
S4 Open Appliances V7
S4 Open Appliances V7S4 Open Appliances V7
S4 Open Appliances V7Steve Jones
 

Viewers also liked (11)

ENTEC Case Study
ENTEC Case StudyENTEC Case Study
ENTEC Case Study
 
Case Study ATS Jackson Federal Building
Case Study ATS Jackson Federal BuildingCase Study ATS Jackson Federal Building
Case Study ATS Jackson Federal Building
 
final draft Wonderlich-Malec case study
final draft Wonderlich-Malec  case studyfinal draft Wonderlich-Malec  case study
final draft Wonderlich-Malec case study
 
Chipkin Automation - S4 Case Study - Calgary International Airport
Chipkin Automation - S4 Case Study - Calgary International AirportChipkin Automation - S4 Case Study - Calgary International Airport
Chipkin Automation - S4 Case Study - Calgary International Airport
 
CV MARR ING
CV MARR INGCV MARR ING
CV MARR ING
 
S4 Value Proposition
S4 Value PropositionS4 Value Proposition
S4 Value Proposition
 
Pacific Brochure Products
Pacific Brochure ProductsPacific Brochure Products
Pacific Brochure Products
 
Jarrell Case Study
Jarrell Case StudyJarrell Case Study
Jarrell Case Study
 
S4 Open Appliances V7
S4 Open Appliances V7S4 Open Appliances V7
S4 Open Appliances V7
 
Primicias Año 2015
Primicias Año 2015Primicias Año 2015
Primicias Año 2015
 
Secretos de la santa cena
Secretos de la santa cenaSecretos de la santa cena
Secretos de la santa cena
 

Similar to CaseStudy_EnergyETC

Switch Automation Case study v2.0
Switch Automation Case study v2.0Switch Automation Case study v2.0
Switch Automation Case study v2.0Oleh Mykhaylovych
 
AppViewX|Case study - Largest US telecommunication company builds agile adc i...
AppViewX|Case study - Largest US telecommunication company builds agile adc i...AppViewX|Case study - Largest US telecommunication company builds agile adc i...
AppViewX|Case study - Largest US telecommunication company builds agile adc i...AppViewX
 
The Art of Displaying Industrial Data
The Art of Displaying Industrial DataThe Art of Displaying Industrial Data
The Art of Displaying Industrial DataInductive Automation
 
10 Steps to Architecting a Sustainable SCADA System
10 Steps to Architecting a Sustainable SCADA System10 Steps to Architecting a Sustainable SCADA System
10 Steps to Architecting a Sustainable SCADA SystemInductive Automation
 
PME 2021 Design & Quote.pptx
PME 2021 Design & Quote.pptxPME 2021 Design & Quote.pptx
PME 2021 Design & Quote.pptxNavedKhan659845
 
High Scalability Network Monitoring for Communications Service Providers
High Scalability Network Monitoring for Communications Service ProvidersHigh Scalability Network Monitoring for Communications Service Providers
High Scalability Network Monitoring for Communications Service ProvidersCA Technologies
 
10 Steps to Architecting a Sustainable SCADA System
10 Steps to Architecting a Sustainable SCADA System10 Steps to Architecting a Sustainable SCADA System
10 Steps to Architecting a Sustainable SCADA SystemInductive Automation
 
Smallworld_Network_Inventory_Brochure_-_print-HR_with_bleed_for_printers_0
Smallworld_Network_Inventory_Brochure_-_print-HR_with_bleed_for_printers_0Smallworld_Network_Inventory_Brochure_-_print-HR_with_bleed_for_printers_0
Smallworld_Network_Inventory_Brochure_-_print-HR_with_bleed_for_printers_0Mitchell Menezes
 
VMworld 2013: Architecting the Software-Defined Data Center
VMworld 2013: Architecting the Software-Defined Data Center VMworld 2013: Architecting the Software-Defined Data Center
VMworld 2013: Architecting the Software-Defined Data Center VMworld
 
High Scalability Network Performance Management for Enterprises
High Scalability Network Performance Management for EnterprisesHigh Scalability Network Performance Management for Enterprises
High Scalability Network Performance Management for EnterprisesCA Technologies
 
IoT Lighting Control Development, Deployment and Scalability by Beatrice Witz...
IoT Lighting Control Development, Deployment and Scalability by Beatrice Witz...IoT Lighting Control Development, Deployment and Scalability by Beatrice Witz...
IoT Lighting Control Development, Deployment and Scalability by Beatrice Witz...Cindy Foster-Warthen
 
Realtime-Online Tenant Billing solution
Realtime-Online Tenant Billing solutionRealtime-Online Tenant Billing solution
Realtime-Online Tenant Billing solutionNigel Dawson
 
CoreSite Interconnect Gateway (CIG)
CoreSite Interconnect Gateway (CIG)CoreSite Interconnect Gateway (CIG)
CoreSite Interconnect Gateway (CIG)Mike Trawick
 
Telecoms Service Assurance & Service Fulfillment with Neo4j Graph Database
Telecoms Service Assurance & Service Fulfillment with Neo4j Graph DatabaseTelecoms Service Assurance & Service Fulfillment with Neo4j Graph Database
Telecoms Service Assurance & Service Fulfillment with Neo4j Graph DatabaseNeo4j
 

Similar to CaseStudy_EnergyETC (20)

Project1
Project1Project1
Project1
 
Switch Automation Case study v2.0
Switch Automation Case study v2.0Switch Automation Case study v2.0
Switch Automation Case study v2.0
 
AppViewX|Case study - Largest US telecommunication company builds agile adc i...
AppViewX|Case study - Largest US telecommunication company builds agile adc i...AppViewX|Case study - Largest US telecommunication company builds agile adc i...
AppViewX|Case study - Largest US telecommunication company builds agile adc i...
 
The Art of Displaying Industrial Data
The Art of Displaying Industrial DataThe Art of Displaying Industrial Data
The Art of Displaying Industrial Data
 
Bj4101347351
Bj4101347351Bj4101347351
Bj4101347351
 
10 Steps to Architecting a Sustainable SCADA System
10 Steps to Architecting a Sustainable SCADA System10 Steps to Architecting a Sustainable SCADA System
10 Steps to Architecting a Sustainable SCADA System
 
PME 2021 Design & Quote.pptx
PME 2021 Design & Quote.pptxPME 2021 Design & Quote.pptx
PME 2021 Design & Quote.pptx
 
High Scalability Network Monitoring for Communications Service Providers
High Scalability Network Monitoring for Communications Service ProvidersHigh Scalability Network Monitoring for Communications Service Providers
High Scalability Network Monitoring for Communications Service Providers
 
10 Steps to Architecting a Sustainable SCADA System
10 Steps to Architecting a Sustainable SCADA System10 Steps to Architecting a Sustainable SCADA System
10 Steps to Architecting a Sustainable SCADA System
 
Smallworld_Network_Inventory_Brochure_-_print-HR_with_bleed_for_printers_0
Smallworld_Network_Inventory_Brochure_-_print-HR_with_bleed_for_printers_0Smallworld_Network_Inventory_Brochure_-_print-HR_with_bleed_for_printers_0
Smallworld_Network_Inventory_Brochure_-_print-HR_with_bleed_for_printers_0
 
VMworld 2013: Architecting the Software-Defined Data Center
VMworld 2013: Architecting the Software-Defined Data Center VMworld 2013: Architecting the Software-Defined Data Center
VMworld 2013: Architecting the Software-Defined Data Center
 
High Scalability Network Performance Management for Enterprises
High Scalability Network Performance Management for EnterprisesHigh Scalability Network Performance Management for Enterprises
High Scalability Network Performance Management for Enterprises
 
IoT Lighting Control Development, Deployment and Scalability by Beatrice Witz...
IoT Lighting Control Development, Deployment and Scalability by Beatrice Witz...IoT Lighting Control Development, Deployment and Scalability by Beatrice Witz...
IoT Lighting Control Development, Deployment and Scalability by Beatrice Witz...
 
Realtime-Online Tenant Billing solution
Realtime-Online Tenant Billing solutionRealtime-Online Tenant Billing solution
Realtime-Online Tenant Billing solution
 
CBEC-LAN-v9-0.ppt
CBEC-LAN-v9-0.pptCBEC-LAN-v9-0.ppt
CBEC-LAN-v9-0.ppt
 
CHILLER PLANT MANAGER
CHILLER PLANT MANAGERCHILLER PLANT MANAGER
CHILLER PLANT MANAGER
 
Taw opening session
Taw opening sessionTaw opening session
Taw opening session
 
CoreSite Interconnect Gateway (CIG)
CoreSite Interconnect Gateway (CIG)CoreSite Interconnect Gateway (CIG)
CoreSite Interconnect Gateway (CIG)
 
Project
ProjectProject
Project
 
Telecoms Service Assurance & Service Fulfillment with Neo4j Graph Database
Telecoms Service Assurance & Service Fulfillment with Neo4j Graph DatabaseTelecoms Service Assurance & Service Fulfillment with Neo4j Graph Database
Telecoms Service Assurance & Service Fulfillment with Neo4j Graph Database
 

CaseStudy_EnergyETC

  • 1. www.energyetc.com SMART SYSTEMS….. Smart Future! Phone: 510.487.1876 Fax: 510.487.1878 OVERVIEW This site consists of multiple single story buildings with multiple tenants. The previous automation system consisted of a JACE with a tenant override option, 2 JCI NCM’s, 58 UNT controllers and 1 DX9100 controller. The UNTs were deployed across the N2 channels of NCMs. The Tridium JACE failed after a power cycle which left the building running 24/7 and without onsite WEB access to control systems and tenant after-hours override and capability. This was probably due to the aged technology and installed environment. No data backups were available. Energy ETC was contacted by the servicing mechanical contractor to see what solutions were available to resolve the issue. CUSTOMER NEEDS / REQUIREMENTS • INTERNET WEB GRAPHICAL PRESENTATION OF ALL SYSTEMS. • TENANT AFTERHOURS TRACKING and INVOICING SOLUTION. • STABLE and SUSTAINABLE HARDWARE DESIGN. • ABILITY TO EXPAND to support DEMAND LIMITING / DEMAND RESPONSE. • NEEDED to be COST EFFICIENT. C A S E S T U D Y Project Type : INTEGRATION Facility Type : 5 Building Campus, Multiple Tenants Location : San Francisco Bay Area Management : Offsite Property Management PREVIOUS SYSTEM ANALYSIS Hardware : Jace, NCM-30’s, UNT’s, DX9100 Software : Local Web Interface, Tenant Override Billing Type : Hybrid - Legacy Vintage : 2000 Service Factor : 4 – Relatively High Cost Migration Plan : Keep JCI Hardware, Replace Failed JACE. CURRENT SYSTEM ANALYSIS Hardware : Dell 1U Server Class PC in Co-location Ctr. : Linksys VPN Routers : S4 Open: OPC-N2 Router, UNT’s, DX9100 Software : ASI WebLink Interface w/ LinkOPC – Hosted : ASI Zonedial Override Billing - Hosted Type : Hybrid - Legacy Vintage : 2009 Software / Hardware & 2000 JCI H/W Service Factor : 2 – Relatively Low Cost due to HOSTING Migration Plan : Replace JCI Field Devices with OPEN LON
  • 2. www.energyetc.com SMART SYSTEMS….. Smart Future! Phone: 510.487.1876 Fax: 510.487.1878 THE APPROACH There were several challenges in this integration: • Integrate the N2 Devices without the need for the NCM’s. This solution needed to support: OPC Server Connectivity to all discovered devices. Remote Terminal Access Support over IP. Connecting Multiple N2 Channels into 1 common device. Auto discovery of the N2 controllers and associated data points. Virtual Addressing support for duplicate N2 controller addresses. Auto building of the point tree under the controllers. Auto association with N2 controller internal application type with appropriate point templates. • Design a PC / network configuration solution that provides for a low cost, low maintenance reliable model. Needed to be offsite. There is no local onsite management. Needed to be remotely managed for all software updates. Needed to have 99.999% uptime services. (Power & ISP). Needed to be located in a controlled environment. Due to previous failure. • Implement a User Friendly and sustainable Graphical User Interface Must be accessible from the Internet 24/7 with a standard web browser. Must email and text message alarms. Must support long term data trending. Must be easily expandable. Needed to have Help Desk support for Tenant and Management Questions. Needed to integrate a Web Based Tenant Override / Invoice solution. THE SOLUTION Energy ETC, as a Smart Building System Integrator, has several product relationships from which to choose the optimal configuration of software and hardware components to meet the customer requirements. All solutions we design and implement are based on sustainability. The system as a whole cannot become obsolete. There must always be a cost effective migration path for the various components that integrates into the existing configuration. The key system components required were: 1. N2 connectivity over IP with OPC. 2. Provide a HOSTED or SaaS connection to the site from a secure co-location facility with Help Desk Support. 3. A 24/7 WEB based User Interface (UI) in a managed environment. 4. A WEB based Tenant Override / Invoice that would integrate to the UI and N2 devices.
  • 3. www.energyetc.com SMART SYSTEMS….. Smart Future! Phone: 510.487.1876 Fax: 510.487.1878 THE SOLUTION 1. In order to meet the needs of item 1 we selected the S4 Open: OPC-N2 ROUTER. While other N2 connectivity options were available the OPC-N2 device provided optimal functionality and time saving implementation features such as: Auto discovery of the N2 controllers. Virtual Addressing support for duplicate N2 controller addresses. Auto building of the point tree under the controllers. Auto association with N2 controller internal application type with appropriate point templates. Remote connectivity via OPC through a VPN tunnel. The S4 Interface Console software was easy to use and once installed on the PC server provided the required OPC Server “tunneling” connectivity of the N2 points from the S4 Open: OPC-N2 Router to the Web User Interface. Other solutions would not have been as clean to implement resulting in additional material and labor costs. 2. To provide the requirements of Item 2 we selected a premier state-of- the-art internet data center located in the heart to of Silicon Valley. This center provides: AC power distributed via redundant MGE UPS (uninterrupted power supply) systems. 2 Megawatts of diesel generator backup power. In excess of 24 hours of generator fuel on-site; contracts with multiple fuel providers. 100% facilities uptime SLA. Power configured to meet customer specifications. Fully redundant dual A+B power distribution. Fully redundant chilled water system, chillers, pumps, and towers. N+1 redundant air handlers. Direct Connections to Third-Party Providers allowing for dedicated connectivity from a number of vendors in the facility. Speed connectivity options up to 10Gbit at the server points of connection. A DELL® 1U class server running Microsoft® Business Class Server 2003 was installed at the data center to run the applications. The consistency of the operating system bundled with the server and integrity of the data center provided a low cost, low maintenance, high performance solution. Energy ETC’s HOSTED-HELPDESK™ provides account services for: Data integrity and offsite back-ups. Monitoring of system and network operations. Daily review of building operations and equipment conditions. Operational Q&A support to the HOSTED client and client customers. Changes to the system for site expansions and modifications.
  • 4. www.energyetc.com SMART SYSTEMS….. Smart Future! Phone: 510.487.1876 Fax: 510.487.1878 THE SOLUTION 3. For Item 3 we selected the WebLink software solution from ASI Controls. WebLink provides: A consistent User Interface to monitor and control the lower tier devices. Global site Operational Scheduling control. Alarm management, historical reporting and real-time email/ SMS annunciation. Integration into the Tenant Override / Invoicing System. Acceptable cost / performance pricing. Other WEB based solutions were available yet WebLink was selected for its’ straight forward integration into the tenant override / invoicing solution. Other solutions would have required an additional software driver layer which would have resulted in additional costs. 4. In selecting the Tenant Override / Invoicing system there are several available on the market at various price ranges but only one met the price / performance requirements and supported 3rd party connectivity through OPC. Our choice for this application was the ZoneDial Energy Accounting and Invoicing software solution from ASI Controls. This solution provides for: Schedule zone activation; invoice for energy costs. Web browser interface with phone option. Optional tenant self-administration. Tenants schedule, and pay for, energy use. Generate & print invoices. Pre-scheduled or immediate activation. Supports recurring overrides. Tracks every user interaction. Print instruction cards for each user. Fully customizable rates, schedules and holidays. SUMMARY All components of the solution continue to perform to the client’s expectation. The HOSTED model has been solid and continues to emphasize the benefits of of the solution compared to the legacy configuration of installing the components on a client site. ORIGINAL ONSITE DESIGN NEW HOSTED DESIGN