1. Spectra Solar Park Ltd
Sungrow Power (Singapore) PTE Ltd
GIS Inspection Report
Date : 21-January-2023
GIS Name / Fedeer Name : ITC-1 GIS/A01
SL No. Checking iteam Conditions Result Remark
1 GIS Panel Working
2 DC Panel Working
3 UPS MK box Working
4 GIS Inverter Condition Working
5 UPS Battery Working
6 Gas Pressure BP1 (Breaker chambe Healthy Green Zone
7 Gas Pressure BP2 (Busbar chamber Healthy Green Zone
8 Breaker Operation (Count) - 127
9 Com 100 Communication Working
10 Sungrow Logger 3000 Working
11 Temperature Controller Healthy 24℃
Compartment
Tempurature
>25℃ start
Exhust fan
12 Temperature Probe Working
13 Exhaust Fan Working
14 Indoor Light 2 set (4 Nos) Good
15 Emergency Light 1 set (2 nos) Good
16 Grounding Good
17 Over all physical Good
2. Inspected by DPM PM CE
Imamul Haque
Jenarul Islam
Spectra Solar Park Ltd
Sungrow Power (Singapore) PTE Ltd
GIS Inspection Report
Date : 21-January-2023
GIS Name / Fedeer Name : ITC-2 GIS/A02
SL No. Checking iteam Conditions Result Remark
1 GIS Panel Working
2 DC Panel Working
3 UPS MK box Working
4 GIS Inverter Condition Working
5 UPS Battery Working
6 Gas Pressure BP1 (Breaker chambe Healthy Green Zone
7 Gas Pressure BP2 (Busbar chamber Healthy Green Zone
3. 8 Breaker Operation (Count) - 111
9 Com 100 Communication Working
10 Sungrow Logger 3000 Working
11 Temperature Controller Healthy 24.6℃
Compartment
Tempurature
>25℃ start
Exhust fan
12 Temperature Probe Working
13 Exhaust Fan Working
14 Indoor Light 2 set (4 Nos) Good
15 Emergency Light 1 set (2 nos) Good
16 Grounding Good
17 Over all physical Good
Inspected by DPM PM CE
Imamul Haque
Jenarul Islam
4. Spectra Solar Park Ltd
Sungrow Power (Singapore) PTE Ltd
GIS Inspection Report
Date : 21-January-2023
GIS Name / Fedeer Name : ITC-3 GIS/A03
SL No. Checking iteam Conditions Result Remark
1 GIS Panel Working
2 DC Panel Working
3 UPS MK box Working
4 GIS Inverter Condition Working
5 UPS Battery Working
6 Gas Pressure BP1 (Breaker chambe Healthy Green Zone
7 Gas Pressure BP2 (Busbar chamber Healthy Green Zone
8 Breaker Operation (Count) - 91
9 Com 100 Communication Working
10 Sungrow Logger 3000 Working
11 Temperature Controller Healthy 23.9℃
Compartment
Tempurature
>25℃ start
Exhust fan
12 Temperature Probe Working
13 Exhaust Fan Working 2 nos
14 Indoor Light 2 set (4 Nos) Good
15 Emergency Light 1 set (2 nos) working 1 nos light damage
16 Grounding Good
17 Over all physical Good
5. Inspected by DPM PM CE
Imamul Haque
Jenarul Islam
Spectra Solar Park Ltd
Sungrow Power (Singapore) PTE Ltd
GIS Inspection Report
Date : 21-January-2023
GIS Name / Fedeer Name : ITC-4 GIS/A18
SL No. Checking iteam Conditions Result Remark
1 GIS Panel Working
2 DC Panel Working
3 UPS MK box Working
4 GIS Inverter Condition Working
5 UPS Battery Working
6 Gas Pressure BP1 (Breaker chambe Healthy Green Zone
7 Gas Pressure BP2 (Busbar chamber Healthy Green Zone
8 Breaker Operation (Count) - 117
9 Com 100 Communication Working
6. 10 Sungrow Logger 3000 Working
Data addition
work on going
11 Temperature Controller Working 25.6℃
Compartment
Tempurature
>25℃ start
Exhust fan
12 Temperature Probe Working
13 Exhaust Fan Working
14 Indoor Light 2 set (4 Nos) Good
15 Emergency Light 1 set (2 nos) Working 2 nos light damage
16 Grounding Good
17 Over all physical Good
Inspected by DPM PM CE
Imamul Haque
Jenarul Islam
7. Spectra Solar Park Ltd
Sungrow Power (Singapore) PTE Ltd
GIS Inspection Report
Date : 21-January-2023
GIS Name / Fedeer Name : ITC-5 GIS/A17
SL No. Checking iteam Conditions Result Remark
1 GIS Panel Working
2 DC Panel Working
3 UPS MK box Working
4 GIS Inverter Condition Working
5 UPS Battery Working
6 Gas Pressure BP1 (Breaker chambe Healthy Green Zone
7 Gas Pressure BP2 (Busbar chamber Healthy Green Zone
8 Breaker Operation (Count) - 108
9 Com 100 Communication Working
10 Sungrow Logger 3000 Working
11 Temperature Controller Working 24.5℃
Compartment
Tempurature
>25℃ start
Exhust fan
12 Temperature Probe Working
13 Exhaust Fan Working 2 nos
14 Indoor Light 2 set (4 Nos) Good
15 Emergency Light 1 set (2 nos) Good
16 Grounding Good
17 Over all physical Good
8. Inspected by DPM PM CE
Imamul Haque
Jenarul Islam
Spectra Solar Park Ltd
Sungrow Power (Singapore) PTE Ltd
GIS Inspection Report
Date : 21-January-2023
GIS Name / Fedeer Name : ITC-6 GIS/A16
SL No. Checking iteam Conditions Result Remark
1 GIS Panel Working
2 DC Panel Working
3 UPS MK box Working
4 GIS Inverter Condition Working
5 UPS Battery Working
6 Gas Pressure BP1 (Breaker chambe Damage Faulty
7 Gas Pressure BP2 (Busbar chamber Healthy Green Zone
8 Breaker Operation (Count) - 139
9 Com 100 Communication Working
9. 10 Sungrow Logger 3000 Working
11 Temperature Controller Working 24.5℃
Compartment
Tempurature
>25℃ start
Exhust fan
12 Temperature Probe Working
13 Exhaust Fan Working 2 nos
14 Indoor Light 2 set (4 Nos) Good
15 Emergency Light 1 set (2 nos) Good
16 Grounding Good
17 Over all physical Good
Inspected by DPM PM CE
Imamul Haque
Jenarul Islam