The paper gives a presentation of some most important properties of the enamel insulated rectangular wire windings. The basic paper insulation in the winding conductors is replaced completely by PVA (polyvinyl acetal) of thermal class E (120˚C). Single- and double threaded helical windings are dealt with. The active part of the transformer is immersed in mineral oil of thermal class A. The main properties and benefits from the perspective of dielectric, thermal and dynamic strength of the winding are noted. According to the hot-spot criteria, the relative ageing rate of the enamel insulation is noted. Measurements of the withstand voltage of the enamel insulation, taken according to our own procedure in our high-voltage laboratory, are noted comparatively to the IEC standard. In conclusion, an overview of the quantity of windings between 2001 and 2012 is given, together with an estimate of the influence of input costs. With regard to our up-to-date production and experience, an evaluation of the further use of windings without paper insulation is given.
Key words: Power Transformer, Helical Winding, Enamel Insulation, Withstand Voltage
EKSPERIMENTALNI REZULTATI MJERENJA ODZIVA NAMOTAJA TRANSFORMATORA PRI OSCILAT...
Power Transformer Windings without Paper Insulation
1. 11. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Laško 2013
CIGRE ŠK A2 – 03
1
Navitja močnostnih transformatorjev brez papirne izolacije
Juso IKANOVIĆ
KOLEKTOR ETRA Energetski transformatorji, d.o.o.
juso.ikanovic@kolektor.com
Istok JERMAN
KOLEKTOR ETRA Energetski transformatorji, d.o.o.
istok.jerman@kolektor.com
Povzetek: V članku so predstavljene nekatere pomembnejše lastnostinavitij izdelanih iz pravokotne žice, izolirane z
lakom. Osnovna papirna izolacija na vodnikih v navitju je v celoti opuščena in nadomeščena z izolacijo iz umetne
snovi PVA (polyvinyl acetal) termičnega razreda E (120˚C). Obravnavano je vijačno navitje v enohodni ali dvohodni
izvedbi. Aktivni del transformatorja je zalit z mineralnim oljem termičnega razreda A. Opisane so glavne značilnosti
in pridobitve s stališča dielektrične, termičnein dinamične trdnosti navitja. Po kriteriju najtoplejše točke je ocenjeno
relativno staranje lak izolacije. Primerjalno s standardom IEC so opisane meritve dielektrične vzdržnosti lak
izolacije, ki so bile opravljene po lastnem postopku v našem visokonapetostnem laboratoriju. Na koncu je podan
količinskipreglednavitij, izdelanih včasovnem obdobju od leta 2001 do leta 2012 in ocenjen vpliv na vstopne stroške.
Na podlagi dosedanjih proizvodnih in obratovalnih izkušenj je podana ocena nadaljnje uporabnosti navitij brez
papirne izolacije.
Ključne besede: močnostni transformator, vijačno navitje, lak izolacija, dielektrična vzdržnost
Power Transformer Windings without Paper Insulation
Juso IKANOVIĆ
KOLEKTOR ETRA Energetski transformatorji, d.o.o.
juso.ikanovic@kolektor.com
Istok JERMAN
KOLEKTOR ETRA Energetski transformatorji, d.o.o.
istok.jerman@kolektor.com
Abstract: The paper gives a presentation of some most important properties of the enamel insulatedrectangularwire
windings. The basic paper insulation in the winding conductors is replaced completely by PVA (polyvinyl acetal) of
thermal class E (120˚C). Single- anddouble threaded helical windings are dealt with. The active part of the
transformer is immersedin mineral oil of thermal class A. The main properties and benefits from the perspective of
dielectric, thermal anddynamic strength of the winding are noted. According to the hot-spot criteria, the relative
ageing rate of the enamel insulationis noted. Measurementsof the withstandvoltage of the enamel insulation, taken
according to our own procedure in our high-voltage laboratory, are noted comparatively to the IEC standard. In
conclusion, an overview of the quantity of windings between 2001 and 2012 is given, togetherwith an estimate of the
influence of input costs. With regard to our up-to-date production and experience, an evaluation of the furtheruse of
windings without paper insulation is given.
Key words: Power Transformer, Helical Winding, Enamel Insulation, Withstand Voltage
2. 11. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Laško 2013
CIGRE ŠK A2 – 03
2
I. UVOD
Izolacijski sistem z vodniki, izoliranimi z lakom, in
transformatorskim oljem je pol hibridna termična
izolacija, ki jo tvorita lak termičnega razreda E
(120 ˚C) in olje z dovoljenim segrevanjem 100˚C,
razreda A [11]. Izolacijski sklop lak - olje
predstavlja v naravi oljni kanal med ovoji vijačnega
navitja, v katerem papirna izolacija ni prisotna.
Radialni kanal mora imeti čim večjo dielektrično
trdnost in mora hkrati omogočiti zadosten pretok
olja po hladilnih kanalih za učinkovito hlajenje
navitja. Širino kanala projektant optimizira z
upoštevanjem dielektričnih in termičnih zahtev.
Izračuni so pokazali, da dosegamo najboljši
polnilni faktor pri minimalnih radialnih kanalih z
uporabo enega ali več aksialnih hladilnih kanalov.
Na začetku smo si zastavili vprašanje: kakšna je
minimalna širina radialnega kanala in kakšna je
njegova dielektrična vzdržnost? Z upoštevanjem
termičnih kriterijev smo določili minimalni radialni
kanal širine 1,5 mm, ki še omogoča zadosten pretok
olja v navitju. Za izolacijo na vodnikih je
uporabljen lak PVA, grade 1.
Z razvojem navitij brez papirne izolacije smo začeli
v letu 2000, ko so bile opravljene prve meritve in
preverjanja pravokotnih vodnikov, izoliranih z
lakom. Meritve so bile vzorčne, izvedene v realnem
okolju na desetih enakih vzorcih z oljnim kanalom
širine 1,5 mm. Pridobljeni rezultati so projektantom
omogočili pravilno načrtovanje faktorja varnosti,
kar je za industrijsko okolje vedno aktualna tema.
Uporaba vodnikov, izoliranih z lakom, je bila
zaradi varnosti in pomanjkanja zanesljivih
podatkov omejena na navitja, ki ne presegajo
napetostnega razreda 20 kV [10].
Slika 1: Prva navitja z lak izolacijo iz leta 2001
(RT 50 MVA- 77/10,5 kV)
Prva navitja brez papirne izolacije na vodnikih, za
transformatorje večjih moči, smo v tovarni izdelali
v letu 2001. Ideja o opuščanju papirne izolacije na
vodnikih je nastala v času, ko smo se ukvarjali z
optimiziranjem konstrukcij z visokimi stopnjami
vrednotenja izgub. Obdelava in primerjava večjega
števila izračunov nas je vodila v smeri izboljšanja
obstoječega polnilnega faktorja navitij. Predvsem
so to navitja bližje magnetnemu krogu, v večini
primerov navitja nižjega napetostnega razreda 10 in
20 kV nazivne napetosti. Že prvi primerjalni
izračuni navitij z izboljšanim polnilnim faktorjem
so pokazali pomembne gospodarske in druge
koristi [10].
II. OPIS MERITEV
Postopek IEC
Na sliki 2 je prikazan preizkus dielektrične
vzdržnosti lak izolacije po postopku, opisanem v
standardu IEC 60851- 5 [1].
Slika 2: Postopek meritev po IEC standardu
Proizvajalci žice so obvezni izvajati preizkuse
dielektrične trdnosti lak izolacije po opisanem
postopku. Radij ukrivljenja žice ustreza
dimenzijam izbrane preizkusne žice. Preizkusno
žico zakrivijo po debelini v obliki črke U in jo
namestijo v kad, napolnjeno s kovinskimi
kroglicami predpisane velikosti. Pritisnjena
napetost je izmenična napetost industrijske
frekvence, ki se dviguje postopoma s korakom
100 V/s do končnega preboja izolacije. Z lakom
izolirana pravokotna žica je svojo množično
uporabo našla v suhih transformatorjih, kjer se za
izolacijo na žici praviloma zahteva višji termični
razred in dielektrične lastnosti merjene v zraku.
Preizkusijo pet vzorcev, od katerih morajo štirje
zdržati predpisano minimalno napetost, s tem da
peti vzorec ne sme prebiti izolacije pod 50
odstotkov predpisane napetosti. Končni izid
3. 11. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Laško 2013
CIGRE ŠK A2 – 03
3
meritev je minimalna prebojna napetost lak
izolacije, ki mora biti v zraku večja ali enaka:
Upr 1000V (grade 1) in Upr 2000V (grade 2).
Preizkus pri višji temperaturi in v olju izvajajo
proizvajalci lak žice na posebno zahtevo naročnika.
Dovoljen padec prebojne napetosti pri povišani
temperaturi 120˚C, ne sme biti večji od 25% [5].
Razvidno je, da se prebojna napetost ugotavlja med
vodnikom, izoliranim z lakom enostransko, in
kovinskimi kroglicami, kot maso na drugi strani.
Podatki o dielektrični vzdržnosti lak izolacije,
pridobljeni s tem postopkom, potrjujejo predpisan
nivo dielektrične kakovosti laka na žici. Če so
predpisane vrednosti presežene, so dobra podlaga
za primerjave med posameznimi proizvajalci žice,
kar je prej izjema kot pravilo kajti, večina
proizvajalcev žice podaja s standardom zajamčene
vrednosti dielektrične vzdržnosti. Za projektantsko
prakso rezultati teh meritev ne morejo biti trdna
podlaga za dimenzioniranje izolacije v navitju.
Zaradi tega smo se odločili izvesti preizkuse po
lastnem postopku, prirejenim našim projektantskim
potrebam. IEC postopek smo uporabili le kot
kriterij sprejemljivosti rezultatov naših meritev.
Postopek Kolektor Etra
Projektante navitij zanima dielektrična vzdržnost
lak izolacije med ovoji v kanalu lak - olje v
realnem okolju, saj mora ta ustrezati dielektričnim
obremenitvam izolacije v času preizkusa
transformatorja z udarno napetostjo. Ker preizkusi
s standardno obliko udarne napetosti 1,2/50 µs niso
izvedljivi, smo preizkuse opravili z izmenično
napetostjo industrijske frekvence v trajanju ene
minute in vzdržno napetost AC (1 min) preračunali
v vzdržno udarno napetost (LI),
Uvz (LI) / Uvz (AC) = 2,5.
Slika 3: Postopek meritev Kolektor Etra
Za razliko od preizkusa po postopku IEC, kjer se
napetost dviguje po korakih do končnega preboja,
so bili naši vzorci izpostavljeni napetosti v trajanju
ene minute, kar nam je omogočalo preračun
napetosti AC v LI. Pravilno dimenzioniranje
notranje izolacije v navitju je ključnega pomena za
preizkus in kasnejše varno obratovanje
transformatorja, zlasti ko gre za izolacijo med ovoji
ali svitki v navitju.
Postopek meritev, ki smo ga tukaj uvedli, je izvirna
praktična rešitev, saj so vsi modeli izdelani po
lastnem tehnološkem postopku, ki velja za
navijanje vijačnih navitij v redni proizvodnji. V
naravi pomenijo preskušani vzorci en izsek iz
vijačnega navitja realne velikosti, z distančnikom
1,5 mm med hodoma. Z uporabo realnih dimenzij
smo se izognili zamudnemu preračunavanju
modelnih parametrov in zmanjšali negotovost v
sprejemljivostirezultatov. Za izdelavo preizkušancev
je uporabljena žica iz redne proizvodnje, 6,3 mm x
2,12 mm, izolirana z lakom PVA, (Damid, grade1).
En svitek tvori snop enajstih žic radialno. Vmesni
distančniki za tvorbo radialnega kanala so iz
tlačene lepenke kakovosti T IV.
Preizkušanci so bili zaliti s primerno posušenim
transformatorskim oljem Nynas Nytro 10X, ki je
bilo po končnem preboju izolacije vsakega
preizkušanca zamenjano. Iz prve serije
preizkušancev so odvzeti vzorci olja za plinsko
kromatografsko preiskavo. Analiza rezultatov je
pokazala, da v olju, razen pričakovanih nizko
energetskih praznjenj, ni prišlo do razvoja plinov,
ki bi nakazovali povečanja delnih praznjenj. Vsi
preboji so bili plazeči in so se razvili v območju
stičnih površin žic z distančniki.
Vsi materiali in postopki uporabljeni za izdelavo
preizkušancev se uporabljajo v redni proizvodnji.
Meritve so bile opravljene v lastnem preizkusnem
laboratoriju pri sobni temperaturi. Preizkušeno je
bilo deset vzorcev po naključnem zaporedju od 1
do 10 kot je to razvidno iz slike 4.
III. FAKTOR VARNOSTI
Vsak projektant transformatorja se pri svojem delu
srečuje s pojmom faktorja varnosti, zlasti na
področju strojnih konstrukcij in dimenzioniranju
dielektrične trdnosti izolacije v navitju. Postopek se
začne z izračuni, ki morajo upoštevati realne
proizvodne kriterije, zlasti so tukaj pomembne
lastne proizvodne tolerance. Veliko pripomore
poznavanje obratovalne zgodovine transformatorja,
ki je skupaj s tovarniškimi preizkusi najboljša
podlaga za določanje novih ali preverjanje že
sprejetih kriterijev varnosti. Kriterij sprejemljivosti
rezultatov izračunov ali meritev je v projektantski
4. 11. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Laško 2013
CIGRE ŠK A2 – 03
4
praksi temeljno vprašanje vsake konstrukcije.
Kriterij sprejemljivosti nekega rezultata je podlaga
za določitev faktorja varnosti, ki lahko prepreči
nezaželene porušitve konstrukcij, obenem pa, če je
ta visoko odmerjen, povečuje stroške izdelave in
projektanta potiska v drugo miselno smer.
Tukaj opisan IEC postopek 1 postavlja mejo
sprejemljivosti za minimalno prebojno napetost lak
izolacije enostransko. Če IEC priporočilo
sprejmemo kot podlago za določitev minimalne
prebojne napetosti tudi za naše preizkuse bi
prebojna merjena napetost znašala 17,5 kV (slika 4).
Po postopku IEC se napetost dviguje do preboja
izolacije, v našem postopku je bilo treba napetost
dvigniti do določene izbrane vrednosti in jo
zadržati eno minuto. Začeli smo s petimi kilovolti
in v presledkih po 2,5 kV prve preboje zabeležili na
petih vzorcih (vzorec: 1, 3, 7, 8, 10) pri napetosti
17,5 kV. Napetosti 17,5 kV nismo sprejeli kot
minimalno prebojno napetost za naše izračune.
Ugotovili smo, da obstaja območje nepreverjenih
možnih prebojev pod mejo izmerjenih minimalnih
prebojev,
15 kV < Upr < 17,5 kV.
Zaradi tega smo v skupini petih najslabših vzorcev
izvršili popravek izmerjene prebojne napetosti
navzdol in za minimalno prebojno vrednost
napetost določili srednjo računsko vrednost;
Upr = 16,25 kV.
Napetost 15 kV smo zabeležili kot najnižjo
izmerjeno vzdržno napetost, ki so jo uspešno
zdržali vsi preizkušanci. Zaradi relativno ozke meje
med vzdržnostjo in prebojem (1,25 kV), izmerjena
vzdržna napetost 15 kV ni bila sprejeta kot vzdržna
napetost, ki bi bila merodajna za dimenzioniranje
izolacije.
Projektanti se pri svojem delu ukvarjamo s pojmom
vzdržne napetosti (Uvz), ki jo s prebojno napetostjo
povezuje faktor dielektrične varnosti kV E,
Upr / Uvz = kV E , Uvz = Upr / kV E . (1)
Za dimenzioniranje notranje izolacije v navitjih
izoliranih s papirjem je v uporabi faktor
dielektrične varnosti;
kV E = 1,5.
V navitjih z lak izolacijo je sprejet enak faktor
varnosti kV E = 1,5 in izračunani vzdržni napetosti
AC in LI;
Uvz (AC) 10,8 kV in Uvz (LI) 27,1 kV.
Oljni kanal, lak - olje širine 1,5 mm, v navitju
dimenzioniramo tako, da se v njem pri preizkusih
izolacije ne pojavi udarna napetost večja od 27,1 kV.
Dielektrična vzdržnost ekvivalentnega oljnega
kanala papir - olje, ki jo projektanti uporabljamo v
izračunih papirne izolacije je približno enaka zgoraj
izračunani. Izid je bil pričakovan, saj je delež
izolacije 0,1 mm v kanalu 1,5 mm relativno nizek.
Največji prispevek v skupni dielektrični vzdržnosti
kanala doprinese olje, ne glede ali je v njem lak ali
papirna izolacija.
Na podlagi analize olja je ocenjeno, da pričakovane
meje za nastanek delnih praznjenj (PD) segajo
preko prebojnih merjenih napetosti 17,5 kV in
izračunane vzdržne napetosti,
UPD (AC) > 17,5kV >> Uvz (AC).
Slika 4: Rezultati meritev
Faktor varnosti se nanaša na varnost za notranjo
izolacijo in pokriva vsa odstopanja in skrite napake
v materialih, ki jih v proces lahko vnesejo:
dobavitelj žice, dobavitelj izolacije in lastna
proizvodnja. Morebitni preboji izolacije v
notranjosti navitij in njih popravila bi povzročili
znatne stroške večjih razsežnosti in motnje na
različnih segmentih proizvodnje.
Žal faktorja dielektrične varnosti ne določa noben
standard ali tehnični predpis, temveč je ta lastna
0
5
10
15
20
25
30
0 1 2 3 4 5 6 7 8 9 10
NapetostAC(1min)[kV]
Številka preiskušanca
Vzdržna napetost (merjena)
Prebojna napetost (merjena)
5. 11. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Laško 2013
CIGRE ŠK A2 – 03
5
matrika vsakega proizvajalca, sestavljena iz
velikega števila različnih med seboj odvisnih
elementov. Najpomembnejše elemente matrike
varnosti najbolje pozna projektant. Med zunanjimi
presojevalci tehničnih izračunov, ki zastopajo
interese uporabnikov, vedno obstaja zanimanje o
vgrajenem faktorju varnosti, po navadi v njegovi
najpreprostejši relativni obliki, kot je to prikazano v
enačbi (1).
Vzdržnost izolacije v naših preizkusih je nihala
med maksimalno prebojno napetostjo Upr maks
(25 kV) in minimalno prebojno napetostjo Upr min
(17,5 kV). Razmerje teh dveh skrajnih vrednosti je
primerljivo s sprejetim faktorjem varnosti kVE;
Upr maks / Upr min = 1,43 < kV E .
Izbran faktor varnosti kVE = 1,5 pokriva
nezanesljivost v vzdržnosti izolacije po celotnem
obsegu meritev.
IV. GLAVNE LASTNOSTI LAKA
Lak izolacija na vodnikih je že vrsto let znan
izolacijski material, ki se je na področju
močnostnih transformatorjev najprej uveljavil pri
transponiranem vodniku, kjer en vodnik tvori več z
lakom izoliranih vzporednih vodnikov s skupnim
povitjem iz papirne izolacije. Med navitja z lak
izolacijo štejemo le tista navitja, ki so izdelana le z
lakiranimi vodniki brez prisotnosti papirne
izolacije. V sedanji fazi razvoja so to predvsem
enostavnejša navitja: vijačna enohodna in več
hodna navitja.
Lak izolacija sodi v skupino umetnih polimerov, v
literaturi in rabi jo zasledimo v treh glavnih
skupinah: polyvinyl acetal (PVA), polyvinyl
butyral (PVB) in polyvinyl formal (PVF). Za
elektrotehniške namene sta v uporabi PVA in PVF.
Od komercialnih znamk so znani laki: LE, Damid,
Formvar, Magneform F120, Formvex itd. Med
seboj se razlikujejo zlasti v termični odpornosti, ki
je razvrščena po termičnih indeksih: 120°C, 180°C
in 200°C . V naših transformatorjih uporabljamo
polyvinyl acetal (PVA) termičnega razreda E
(120°C).
Polimerizacija izolacijskega papirja
Polimerizacija izolacijskega papirja je škodljiv
pojav, ki se pri papirju na zunaj kaže s spremembo
in izgubo mehanskih lastnosti. Gre za slabitev
molekularnih vezi (hidrogenske OH povezave) v
notranji strukturi celuloze [8]. V praksi se preverja
in dokazuje z meritvijo stopnje polimerizacije. V
tovarniških sušilnih komorah se pri izsuševanju
izolacije aktivni del segreje do 125°C kar za
izolacijski papir termičnega razreda 105°C
predstavlja precejšnjo termično preobremenitev in
posledično pričakovan padec stopnje polimerizacije
tudi do 30%. Že pred samim začetkom življenja
transformatorja je izguba življenjske dobe papirja
precejšnja.
Za lak izolacijo PVA termičnega razreda 120°C
postopektovarniškega sušenja izolacije ne predstavlja
večje toplotne preobremenitve. Med obratovanjem
transformatorja lak na žici počiva v zavetju termičnega
razreda 105°C tako imenovane pol hibridne izolacije
[11]. Izguba življenjske dobe PVA izolacije po
kriteriju stopnje polimerizacije ni aktualna.
Termična odpornost laka (heat shock)
Večje termično breme mora prenesti lak žica, ki ji
standard IEC [6], [5] nalaga preizkus PVA izolacije
na žici pri povišani temperaturi 155°C. Nanos laka
ne sme pokazati razpok tudi tedaj, ko se preskušana
žica navije po višini na radij, ki je enak šestkratni
debelini žice (za žico debeline 2 mm, je radij navijanja
enak 12 mm). Zahteva po tako strogem preizkusu
se vodnikom s papirno izolacijo sploh ne postavlja.
Odpornost na transformatorsko olje
Vse ocene iz preizkusov lakov različnih proizvajalcev
so dobre ali zelo dobre, najboljše lastnosti izkazuje
uporabljeni lak PVA, ki je ocenjen z odlično.
Toplotna vodljivost
Pomembna lastnost za učinkovito odvajanje toplote
iz navitja je visoka specifična toplotna prevodnost
laka, ki se giblje okrog vrednosti 0,35 W/m°C. V
primerjavi s papirjem, z vrednostjo 0,14 W/m°C,
izkazuje lak bistveno boljše toplotne lastnosti.
Gledano s stališča koeficienta toplotne prevodnosti,
so bila naša začetna pričakovanja kar precejšnja.
Kasnejši izračuni so pokazali, da pretežni del
temperaturnega padca odpade na padec olje–lak,
padec baker–lak je neznaten kar je, glede na delež
lak izolacije 0,1 mm v oljnem kanalu širine 1,5
mm, tudi razumljivo. Z uporabo programskih
orodij, ki jih uporabljamo za izračun temperatur v
navitju, in na vzorcu desetih različnih navitij
vgrajenih v transformatorje povprečne moči
50 MVA, smo izračunali, da je temperaturni padec
navitje olje za navitje izdelano z lak izolacijo v
povprečju nižji za 2 K. Sorazmerno temu se
temperatura najtoplejše točke v povprečju zniža za
3 K. Izračune smo izvedli ob predpostavki, da je
prirast izolacije iz papirja 0,1 mm na žici
tehnološko izvedljiv.
6. 11. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Laško 2013
CIGRE ŠK A2 – 03
6
Aksialna tlačna sila
Po IEC standardu [2] aksialna tlačna sila na
radialne distančnike v kratkostičnih razmerah naj
ne bi presegala vrednosti:
σsp, act 80 MPa, za navitja s prisotnostjo papirja in
σsp, act 120 MPa za navitja z lak izolacijo brez
prisotnosti papirja.
Navitja izdelana z lakiranimi vodniki in brez
uporabe papirja prenesejo petdeset odstotkov večje
tlačne obremenitve. Možnost trganja lak izolacije v
dinamičnih kratkostičnih razmerah je bistveno
zmanjšana. S stališča odpornosti navitij na
kratkostične sile odsotnost papirne izolacije v
navitju pripomore k stabilnejšemu vpetju navitja.
Korozijska odpornost
Tankoslojni nanos laka na vodnikih preprečuje
pojav oksidacije in korozije bakra v navitju, ki
lahko postane aktualen pri nekaterih zahtevnejših
pogonih z visokimi termičnimi obremenitvami kot
so to pečni transformatorji v jeklarski industriji.
Vzrok za pojav korozije je lahko tudi iztrošeno olje
zlasti, če je slabše kakovosti. Težave s korozijo
bakra proizvajalci sodobnih olj uspešno rešujejo z
različnimi aditivi 9. Nekateri, sicer redki,
naročniki vztrajno zahtevajo za vsa navitja lak
izolacijo. Z lakom izolirana žica izpolnjuje tudi te
zahteve.
Preizkus odpornosti laka na upogib (Mandrel
winding test)
Odpornost nanosa se preverja s preizkusom
zvijanja vodnika po višini in debelini. Lak mora
prenesti upogib žice na radij enak dvakratni
debelini vodnika, ne glede na debelino vodnika,
brez vidnih poškodb laka 6. Zahteva za takšnim
preizkusom se vodnikom s papirno izolacijo sploh
ne postavlja, kajti natezna trdnost papirja je
neprimerljivo manjša od natezne trdnosti laka.
Izdelavne prednosti
Zaradi odsotnosti papirja v navitju so postopki
sušenja občutno skrajšani in so potrebni samo
zaradi vmesnih distančnikov v hladilnih kanalih.
Če nam uspe obstoječe distančnike nadomestiti z
neceluloznim materialom, bi vmesni postopek
sušenja notranje izolacije v navitjih pred stiskanjem
le teh odpadel. Navitja izdelana iz vodnikov,
izoliranih z lakom, so dimenzijsko stabilna in z
zanemarljivimi proizvodnimi odstopanji.
Nastavitve višine po končanemsušenju in stiskanju
navitij večinoma niso potrebne.
Relativno staranje laka (Relative ageing rate)
Najbolj pomembni vprašanji za uporabnika sta
obratovalna zanesljivost transformatorja in staranje
izolacije v njem. Staranje je zapleten naravni pojav
odvisen od velikega števila različnih dejavnikov.
Ne glede na relativnostno teorijo o staranju, imata
največji vpliv na staranje izolacije količina vlage v
transformatorju in temperatura najtoplejše točke.
Pri določenem tehnološkem postopku sušenja
izolacije je absolutna količina vlage vedno premo
sorazmerna količini vgrajene celulozne izolacije v
aktivnem delu. Tudi danes je izolacijski papir
izdelan na osnovi celuloze in kot tak izkazuje
visoko stopnjo vpojnosti vlage, ki v zraku pri 50
odstotni vlažnosti okolice znaša približno
7 odstotkov. Izračuni kažejo, da je opuščanje
papirne izolacije v samo enem nizkonapetostnem
navitju pripomoglo k sedem odstotnemu
zmanjšanju mase notranje izolacije v navitjih in
posledično 5 odstotnemu zmanjšanju skupne
količine vlage v transformatorju.
Lak izolacija dopušča večje termične obremenitve.
Pri navitjih brez papirne izolacije, smo izračunali
pripadajoče staranje izolacije po kriteriju
najtoplejše točke 11. Z vidika uporabnika in
izkoriščenosti življenjske dobe transformatorja je
uporaba laka na navitjih brez papirne izolacije zelo
opravičljiva. Relativno staranje izolacije na navitjih
smo zmanjšali iz V= 1 na V= 0,21, kar znese le 21
odstotkov enotnega staranja izolacije. V normalnih
obratovalnih pogojih transformatorja, pri
pričakovani življenjski dobi 40 let in enotnem
staranju izolacije V= 1, bo izguba življenjske dobe
v enakem časovnem obdobju znašala le 8,4 let.
Spremljanje staranja izolacije v navitjih, izdelanih
iz vodnikov z lak izolacijo, v normalnih pogojih
obratovanja, po kriteriju najtoplejše točke, nima
več praktičnega pomena.
V. PREGLED IZDELANIH NAVITIJ
V času izdelave vijačnih navitij nismo zabeležili
večjih izdelavnih težav, tudi tedaj, ko je šlo za
izdelavo navitij s štiriinšestdesetimi vzporednimi
vodniki. Vedno je uporabljen lak PVA z enkratnim
nanosom nominalne debeline 0,085 mm (grade 1).
Prebojev izolacije znotraj navitja v času
dielektričnih preizkusov izolacije ali v obratovanju
transformatorjev nismo zabeležili. V zadnjem
desetletju je dvohodno vijačno navitje uporabljeno
v številnih projektih in sicer kot rešitev s prioriteto,
torej uporabljeno povsod, kjer je bilo to tehnološko
še izvedljivo. Navitje v obliki preproste vijačnice,
kot je to vijačno navitje, je skrajni domet
enostavnosti k čemer projektanti vedno stremimo.
Na sliki 5 je prikazana proizvodnja navitij brez
papirne izolacije po posameznih letih od leta 2001
7. 11. KONFERENCA SLOVENSKIH ELEKTROENERGETIKOV – Laško 2013
CIGRE ŠK A2 – 03
7
do zaključka leta 2012. Opazen je povečan trend
rasti zlasti v zadnjih petih letih (2008 do 2012), s
povprečno proizvodnjo nad 190 navitij letno.
Slika 5: Proizvodnja navitij brez papirne izolacije po
posameznih letih v obdobju od 2001. do 2012. leta
Po dvanajstih letih uporabe navitij brez papirne
izolacije njihova uporabnost narašča, delno
zahvaljujoč ugodnemu polnilnemu faktorju, delno
pa tudi relativno sprejemljivi tržni ceni lak žice. V
obravnavanem časovnem obdobju dvanajstih let je
bilo izdelanih več kot 1400 navitij.
Ocena vstopnih stroškov
Uvedba navitij brez papirne izolacije je pripomogla
k pet odstotnemu povprečnemu zmanjšanju
vstopnih stroškov za žico.
Pod pojmom vstopni stroški je treba razumeti
stroške, ki pokrivajo nabavno ceno žice. Izračuni se
nanašajo na enoten cenovni ekvivalent omreženega
transponiranega vodnika s predpostavko, da je
vsako dvohodno ali enohodno navitje z lak
izolacijo možno nadomestiti z omreženim
transponiranim vodnikom. Takšna preprosta
zamenjava v praksi pogosto ni izvedljiva vendar je
bila tukaj nujna, če smo želeli podati oceno tega
pomembnega dejavnika. Podana ocena vstopnih
stroškov zajema povprečje izračunov na 467
transformatorjih izdelanih v obdobju med 2001 in
2012.
VI. ZAKLJUČKI
Pričakujemo, da se bo tehnologija tankoslojnih
nanosov iz umetnih polimerov še naprej
izpopolnjevala in da bo v gradnji sodobnih
močnostnih transformatorjev ravno lak izolacija
omogočila nove razvojne premike. Vsi do sedaj
obravnavani kazalci govorijo, da je treba obstoječo
tehnologijo izdelave vijačnih navitij še dograjevati
in izpopolniti do te mere, da bo transponirani
vodnik, kot višja tehnološka in cenovna stopnja,
nadomeščen z uporabo vijačnih navitij iz
pravokotne žice.
Najmanj trije razlogi nas zavezujejo k nadaljevanju
začetega razvoja: želimo odpreti možnost uporabi
lak izolacije za višje napetostne nivoje, še
občutneje omejiti porabo papirne izolacije v navitju
in omogočiti nadaljnja izboljšanja polnilnega
faktorja. Meje uporabnosti lak izolacije se bodo
premikale proti višjim napetostim, kjer bodo
dielektrične konstrukcije lak - olje vedno pogosteje
izpodrivale klasično izolacijo papir - olje. V ta
namen v tovarni že preizkušamo konstrukcije s
povečanim nanosom laka (grade 2) in radialnimi
kanali različnih širin. Rezultate meritev bomo
obdelali po statistični metodologiji z namenom, da
računsko ugotovimo povezavo med faktorjem
varnosti in verjetnostjo preboja izolacije.
Dosedanje proizvodne in obratovalne izkušnje iz
obdobja preteklih dvanajstih let in več kot 1400
izdelanih navitij niso pokazali nobenega slabega
dogodka, ki bi bil povezan z uporabo navitij brez
papirne izolacije.
REFERENCE
[1] IEC 60851- 5, 2011: Winding wires- Test
methods.
[2] IEC 60076- 5, 2006: Ability to withstand
short circuit.
[3] IEEE standard C57.91: 1995, IEEE Guide for
loading mineral oil- immersed transformers.
[4] IEC TS 60076- 14, 2004: Guide for the design
and application of liquid- immersed power
transformers using high- temperature
insulation materials.
[5] IEC 60317- 0 – 2, 2000: Enamelled
rectangular copper wire.
[6] IEC 60317- 18, 2004: Polyvinyl acetal
enamelled rectangular copper wire, class 120.
[7] R. P. Marek, Dupont USA, Power transformer
refurbishment: the benefits of hybrid
insulation, CIGRE 2004.
[8] D. H. Shroff, A. W. Stannet: A review of
paper aging in power transformers, IEEE,
vol.132A, 1985.
[9] M. Eklund, New transformer oil specifications
needed to meet current demands, Nynas
Naphthenics 3/2005.
[10] J. Ikanović: Izboljšan polnilni faktor navitij
energetskih transformatorjev, Elektrotehniški
vestnik 68(5), 2001.
[11] J. Ikanović, I. Jerman: Navitja močnostnih
transformatorjev zizolacijo različnih termičnih
razredov, Cigre ŠK A2- PT8, Čatež 2007.
27 24 18
48
60
129
141
201
135
162
174
282
0
50
100
150
200
250
300
350
1 2 3 4 5 6 7 8 9 10 11 12
Številoizdelanihnavitij
Leto izdelave
Skupaj navitij: 1401