NREL PVWatts©
Calculator
Introduction to the PVWatts
Calculator - replaced legacy
Versions 1 and 2 in 2015
Disclaimer
• Disclaimer of Endorsement
– Reference herein to any specific commercial products, process,
or service by trade name, trademark, manufacturer, or
otherwise, does not necessarily constitute or imply its
endorsement, recommendation, or favoring by the New Jersey
Board of Public Utilities (NJBPU), Office of Clean Energy
(NJOCE), or Clean Energy Program™ (NJCEP). The views and
opinions of authors expressed in the available or referenced
documents do not necessarily state or reflect those of the
NJBPU, NJOCE, or NJCEP.
NJCEP Requirements
Mandatory
• “Ideal” PVWatts
– DC System Size (kW)
• “As Built” PVWatts (Per Array Plane)
– DC System Size (kW)
– Array Type (fixed, 1-axis, 2-axis, etc.)
– System Losses % (DC-to-AC Derate Factor)
– Tilt (°)
– Azimuth (°)
– Inverter Efficiency (%)
• “As Built” Loss Calc. (derate calculator)
– (PV Module) Nameplate (DC) rating (%)
– Shading (%) [not “Solar Access” %]
Optional
• “Ideal” PVWatts
– “Draw Your System”
• “As Built” PVWatts
– “Draw your System”
• Do not alter any
further values or
options when
submitting to the
NJCEP.
• The guidelines have changed regarding hard-copy submittal of
PVWatts and Shading Report. Hard copies are not required to
be submitted with the final As-Built packet. BUT…
• The NJCEP reserves the right to request a complete copy of
production estimates, a full shade analysis, or any relevant
documentation from the installer at any time.
NJCEP Requirements
NREL Hyperlinks
• Current NREL Versions accepted by NJCEP
– NREL PVWatts Calculator
• http://pvwatts.nrel.gov/ (standard interface-click this link to follow
slides)
– NREL System Advisor Model (SAM)
• https://sam.nrel.gov/ (advanced design interface)
• Legacy Calculators
– PVWatts Version 1 (RETIRED 2015)
• http://rredc.nrel.gov/solar/calculators/PVWATTS/version1/
– PVWatts Version 2 (RETIRED 2015)
• http://gisatnrel.nrel.gov/PVWatts_Viewer/index.html
PVWatts Calculator
Release
The newest revised version of PVWatts uses updated values. More
information on value changes (http://pvwatts.nrel.gov/version_5.php). (click
“Close” to continue on the site)
NREL’s PVWatts Calculator
To begin, enter the address of the job site,
then click on “GO >>”.
75 Lincoln Hwy, Iselin, NJ 08830
NREL’s PVWatts Calculator
Confirm that the default weather station is optimal for the site address. Select
“Go To system info” to continue.
“Ideal” PVWatts Calculator
For “Ideal” PVWatts, only change “DC System Size (kW)”. All other values
remain default. System Losses (%) remains “14”. Click on “Loss Calc.” to view.
“Ideal” Derate Calculator
For “Ideal” PVWatts, no values should be altered. The “Estimated DC to AC
Factor” should remain “14%.” Screen capture of the “Ideal Derate Calculator”
is not required. Click “Cancel” to return to previous page without changes.
“Ideal” PVWatts Calculator
Verify only the “DC System Size (kW)” changed. Then click “Go to
PVWatts results” to generate “Ideal” summary.
“Ideal” PVWatts Calculator
The results page displays the “Ideal Estimated Annual Production” required on
the NJCEP Final As Built Technical Worksheet, Page 2, Section D, 2b.
Roof Azimuth
Capture the Azimuth measurement either on-site or by utilizing an available
online measurement tool. For this example, we will use orientation 228.1°.
(Example screen capture from Solmetric.com, Roof Azimuth Tool)
“As Built” PVWatts Calculator
• For “As Built” PVWatts, change all system information, as permissible within
NJCEP. Input “Inverter Efficiency (%)”, based upon manufacturer-specification.
• Update Derate Factor to reflect equipment and shading using the “Loss
Calulator”. Click on “Loss Calculator” to view.
“As Built” Derate Calculator
• “As Built” PVWatts, only change “(PV Module) Nameplate Rating (%)”
[i.e.. power tolerance factor], and Shading (%) [not Solar Access %].
• Save a Screen Capture of the “As Built Derate Calculator”.
• Click “Save” to apply the updated “Derate Factor”/System Losses.
“Draw Your System” (Optional)
You may optionally “Draw Your System” using the corresponding button, but
this feature does not print out with the summary report. Not NJCEP-required.
“As Built” PVWatts Calculator
Verify the “System Info” is all correct. Confirm that the “System Losses (%)”
represents the final value from the Loss Calculator. Scroll down the screen.
“As Built” PVWatts Calculator
Scrolling down further on the page will reveal information that is not required to
be selected or altered. Not required by the NJCEP. Finally, click “Go to
pvwatts results” to generate “As Built” PVWatts summary.
PVWatts Summary Page
(Example of the “As-Built” PVWatts Results Page)
“As Built” PVWatts Summary
The results page displays the “As-Built Estimated Annual Production” required
on the NJCEP Final As Built Technical Worksheet, Page 3, Section D, 2a.
“As Built” PVWatts Summary
For a “Monthly” or “Hourly” report, click on the coordinating button to save/print.
“As Built” PVWatts Summary
The “Monthly” or “Hourly” report can be saved/printed from the generated
spreadsheet, which may be used in advanced design planning. Not NJCEP-
Required.
Verify all information was entered properly and measurements are accurate.
Save a copy of the “As-Built” and “Ideal” PVWatts summary pages for your
records.
“As Built” PVWatts Summary
PVWatts Feedback
For feedback regarding the PVWatts Calculator, email comments to
PVWatts@nrel.gov.
Questions?
For questions pertaining to the NJCEP requirements within Final As Built
Completion Packets, please refer to the following:
• SREC Registration Program Guidebook
http://www.njcleanenergy.com/files/file/Renewable_Programs/RE%20Forms/
2012/SRP_Guidebook_2012_Ch8revrr_6_26_12.pdf
• SREC Registration Program Checklist
– Solar SRP Final As-Built Forms (updated Jan 2015) - .xlsx version (Excel 2010)
– Solar SRP Final As-Built Forms (updated Jan 2015) - .xls version (Excel 2003-2007)
• Note: Microsoft provides an Office Compatibility Pack for those users that are still using the
earlier version of Excel (.xls).
• call: 866-NJSMART (866-657-6278)

More Related Content

Viewers also liked

10 undp bi h sust energy in see - sanjin avdic undp co bih 071213
10 undp bi h sust energy in see - sanjin avdic undp co bih 07121310 undp bi h sust energy in see - sanjin avdic undp co bih 071213
10 undp bi h sust energy in see - sanjin avdic undp co bih 071213UNDPhr
 
2 davor kunc wbif presentation to undp edited
2 davor kunc wbif presentation to undp   edited2 davor kunc wbif presentation to undp   edited
2 davor kunc wbif presentation to undp editedUNDPhr
 
11 undp fyrom zagreb 8 9 dec.2013
11 undp fyrom zagreb 8 9 dec.201311 undp fyrom zagreb 8 9 dec.2013
11 undp fyrom zagreb 8 9 dec.2013UNDPhr
 
17 lin herencic green jobs calculator, se4_all, 9.12.2013.
17 lin herencic green jobs calculator, se4_all, 9.12.2013.17 lin herencic green jobs calculator, se4_all, 9.12.2013.
17 lin herencic green jobs calculator, se4_all, 9.12.2013.UNDPhr
 
Copy Of Pv Calc For Sri Lanka Home
Copy Of Pv Calc For Sri Lanka HomeCopy Of Pv Calc For Sri Lanka Home
Copy Of Pv Calc For Sri Lanka HomePrivate Consultants
 
Stakeholder Workshop (Naidoo, Ouchi)
Stakeholder Workshop (Naidoo, Ouchi)Stakeholder Workshop (Naidoo, Ouchi)
Stakeholder Workshop (Naidoo, Ouchi)UNDPhr
 
1 daniela carrington undp b&h se4 all conference zagreb 2013_dc-final
1 daniela carrington undp b&h se4 all conference zagreb 2013_dc-final1 daniela carrington undp b&h se4 all conference zagreb 2013_dc-final
1 daniela carrington undp b&h se4 all conference zagreb 2013_dc-finalUNDPhr
 

Viewers also liked (7)

10 undp bi h sust energy in see - sanjin avdic undp co bih 071213
10 undp bi h sust energy in see - sanjin avdic undp co bih 07121310 undp bi h sust energy in see - sanjin avdic undp co bih 071213
10 undp bi h sust energy in see - sanjin avdic undp co bih 071213
 
2 davor kunc wbif presentation to undp edited
2 davor kunc wbif presentation to undp   edited2 davor kunc wbif presentation to undp   edited
2 davor kunc wbif presentation to undp edited
 
11 undp fyrom zagreb 8 9 dec.2013
11 undp fyrom zagreb 8 9 dec.201311 undp fyrom zagreb 8 9 dec.2013
11 undp fyrom zagreb 8 9 dec.2013
 
17 lin herencic green jobs calculator, se4_all, 9.12.2013.
17 lin herencic green jobs calculator, se4_all, 9.12.2013.17 lin herencic green jobs calculator, se4_all, 9.12.2013.
17 lin herencic green jobs calculator, se4_all, 9.12.2013.
 
Copy Of Pv Calc For Sri Lanka Home
Copy Of Pv Calc For Sri Lanka HomeCopy Of Pv Calc For Sri Lanka Home
Copy Of Pv Calc For Sri Lanka Home
 
Stakeholder Workshop (Naidoo, Ouchi)
Stakeholder Workshop (Naidoo, Ouchi)Stakeholder Workshop (Naidoo, Ouchi)
Stakeholder Workshop (Naidoo, Ouchi)
 
1 daniela carrington undp b&h se4 all conference zagreb 2013_dc-final
1 daniela carrington undp b&h se4 all conference zagreb 2013_dc-final1 daniela carrington undp b&h se4 all conference zagreb 2013_dc-final
1 daniela carrington undp b&h se4 all conference zagreb 2013_dc-final
 

Similar to NJCEPPVWattsCalculatorTraining21815

New IGBT Gate Driver Software
New IGBT Gate Driver SoftwareNew IGBT Gate Driver Software
New IGBT Gate Driver SoftwareJuan Munoz
 
Introduction to the VEDA TIMES-Starter Model Platform
Introduction to the VEDA TIMES-Starter Model PlatformIntroduction to the VEDA TIMES-Starter Model Platform
Introduction to the VEDA TIMES-Starter Model PlatformIEA-ETSAP
 
Po3660 Krogstad Vm World 2008
Po3660 Krogstad Vm World 2008Po3660 Krogstad Vm World 2008
Po3660 Krogstad Vm World 2008kkroggy
 
Original Voltage Regulator & Controller IC TPS54231DR 54231DR 54231 SOP-8 Ne...
Original  Voltage Regulator & Controller IC TPS54231DR 54231DR 54231 SOP-8 Ne...Original  Voltage Regulator & Controller IC TPS54231DR 54231DR 54231 SOP-8 Ne...
Original Voltage Regulator & Controller IC TPS54231DR 54231DR 54231 SOP-8 Ne...AUTHELECTRONIC
 
Introduction of CHEMcAD Software
Introduction of CHEMcAD Software Introduction of CHEMcAD Software
Introduction of CHEMcAD Software MyTech8
 
Uav Stability Augmentation System Usas
Uav Stability Augmentation System   UsasUav Stability Augmentation System   Usas
Uav Stability Augmentation System Usasahmad bassiouny
 
Agilaire 8872 Data Logger
Agilaire 8872 Data LoggerAgilaire 8872 Data Logger
Agilaire 8872 Data LoggerAgilaire LLC
 
Achieving Excellence IESVE for HVAC Simulation.pdf
Achieving Excellence IESVE for HVAC Simulation.pdfAchieving Excellence IESVE for HVAC Simulation.pdf
Achieving Excellence IESVE for HVAC Simulation.pdfIES VE
 
Presentation v mware roi tco calculator
Presentation   v mware roi tco calculatorPresentation   v mware roi tco calculator
Presentation v mware roi tco calculatorsolarisyourep
 
POWER QUALITY IMPROVEMENT IN ELECTRICAL RAILWAY POWER SYSTEM
POWER QUALITY IMPROVEMENT IN ELECTRICAL RAILWAY POWER SYSTEMPOWER QUALITY IMPROVEMENT IN ELECTRICAL RAILWAY POWER SYSTEM
POWER QUALITY IMPROVEMENT IN ELECTRICAL RAILWAY POWER SYSTEMIRJET Journal
 
Manoj Ahire-Resume
Manoj Ahire-ResumeManoj Ahire-Resume
Manoj Ahire-ResumeManoj Ahire
 
Topological Advancement in DVR; A review
Topological Advancement in DVR; A reviewTopological Advancement in DVR; A review
Topological Advancement in DVR; A reviewIRJET Journal
 
Energy measuring insulation monitoring programmable controller melsec-q seri...
Energy measuring  insulation monitoring programmable controller melsec-q seri...Energy measuring  insulation monitoring programmable controller melsec-q seri...
Energy measuring insulation monitoring programmable controller melsec-q seri...Dien Ha The
 
ETAP - Power system modeling
ETAP - Power system modelingETAP - Power system modeling
ETAP - Power system modelingHimmelstern
 
Generator Sizing Pitfalls
Generator Sizing PitfallsGenerator Sizing Pitfalls
Generator Sizing Pitfallsmichaeljmack
 

Similar to NJCEPPVWattsCalculatorTraining21815 (20)

2014 PV Performance Modeling Workshop: Optimizing PV Designs with HelioScope:...
2014 PV Performance Modeling Workshop: Optimizing PV Designs with HelioScope:...2014 PV Performance Modeling Workshop: Optimizing PV Designs with HelioScope:...
2014 PV Performance Modeling Workshop: Optimizing PV Designs with HelioScope:...
 
2014 PV Distribution System Modeling Workshop: High Penetration PV Control Co...
2014 PV Distribution System Modeling Workshop: High Penetration PV Control Co...2014 PV Distribution System Modeling Workshop: High Penetration PV Control Co...
2014 PV Distribution System Modeling Workshop: High Penetration PV Control Co...
 
New IGBT Gate Driver Software
New IGBT Gate Driver SoftwareNew IGBT Gate Driver Software
New IGBT Gate Driver Software
 
Introduction to the VEDA TIMES-Starter Model Platform
Introduction to the VEDA TIMES-Starter Model PlatformIntroduction to the VEDA TIMES-Starter Model Platform
Introduction to the VEDA TIMES-Starter Model Platform
 
Po3660 Krogstad Vm World 2008
Po3660 Krogstad Vm World 2008Po3660 Krogstad Vm World 2008
Po3660 Krogstad Vm World 2008
 
Original Voltage Regulator & Controller IC TPS54231DR 54231DR 54231 SOP-8 Ne...
Original  Voltage Regulator & Controller IC TPS54231DR 54231DR 54231 SOP-8 Ne...Original  Voltage Regulator & Controller IC TPS54231DR 54231DR 54231 SOP-8 Ne...
Original Voltage Regulator & Controller IC TPS54231DR 54231DR 54231 SOP-8 Ne...
 
Introduction of CHEMcAD Software
Introduction of CHEMcAD Software Introduction of CHEMcAD Software
Introduction of CHEMcAD Software
 
Uav Stability Augmentation System Usas
Uav Stability Augmentation System   UsasUav Stability Augmentation System   Usas
Uav Stability Augmentation System Usas
 
Ijeet 06 08_008
Ijeet 06 08_008Ijeet 06 08_008
Ijeet 06 08_008
 
Agilaire 8872 Data Logger
Agilaire 8872 Data LoggerAgilaire 8872 Data Logger
Agilaire 8872 Data Logger
 
Achieving Excellence IESVE for HVAC Simulation.pdf
Achieving Excellence IESVE for HVAC Simulation.pdfAchieving Excellence IESVE for HVAC Simulation.pdf
Achieving Excellence IESVE for HVAC Simulation.pdf
 
3 1 wittmer_p_vsyst_pvpmc_2016
3 1 wittmer_p_vsyst_pvpmc_20163 1 wittmer_p_vsyst_pvpmc_2016
3 1 wittmer_p_vsyst_pvpmc_2016
 
Company profile solar
Company profile solarCompany profile solar
Company profile solar
 
Presentation v mware roi tco calculator
Presentation   v mware roi tco calculatorPresentation   v mware roi tco calculator
Presentation v mware roi tco calculator
 
POWER QUALITY IMPROVEMENT IN ELECTRICAL RAILWAY POWER SYSTEM
POWER QUALITY IMPROVEMENT IN ELECTRICAL RAILWAY POWER SYSTEMPOWER QUALITY IMPROVEMENT IN ELECTRICAL RAILWAY POWER SYSTEM
POWER QUALITY IMPROVEMENT IN ELECTRICAL RAILWAY POWER SYSTEM
 
Manoj Ahire-Resume
Manoj Ahire-ResumeManoj Ahire-Resume
Manoj Ahire-Resume
 
Topological Advancement in DVR; A review
Topological Advancement in DVR; A reviewTopological Advancement in DVR; A review
Topological Advancement in DVR; A review
 
Energy measuring insulation monitoring programmable controller melsec-q seri...
Energy measuring  insulation monitoring programmable controller melsec-q seri...Energy measuring  insulation monitoring programmable controller melsec-q seri...
Energy measuring insulation monitoring programmable controller melsec-q seri...
 
ETAP - Power system modeling
ETAP - Power system modelingETAP - Power system modeling
ETAP - Power system modeling
 
Generator Sizing Pitfalls
Generator Sizing PitfallsGenerator Sizing Pitfalls
Generator Sizing Pitfalls
 

NJCEPPVWattsCalculatorTraining21815

  • 1. NREL PVWatts© Calculator Introduction to the PVWatts Calculator - replaced legacy Versions 1 and 2 in 2015
  • 2. Disclaimer • Disclaimer of Endorsement – Reference herein to any specific commercial products, process, or service by trade name, trademark, manufacturer, or otherwise, does not necessarily constitute or imply its endorsement, recommendation, or favoring by the New Jersey Board of Public Utilities (NJBPU), Office of Clean Energy (NJOCE), or Clean Energy Program™ (NJCEP). The views and opinions of authors expressed in the available or referenced documents do not necessarily state or reflect those of the NJBPU, NJOCE, or NJCEP.
  • 3. NJCEP Requirements Mandatory • “Ideal” PVWatts – DC System Size (kW) • “As Built” PVWatts (Per Array Plane) – DC System Size (kW) – Array Type (fixed, 1-axis, 2-axis, etc.) – System Losses % (DC-to-AC Derate Factor) – Tilt (°) – Azimuth (°) – Inverter Efficiency (%) • “As Built” Loss Calc. (derate calculator) – (PV Module) Nameplate (DC) rating (%) – Shading (%) [not “Solar Access” %] Optional • “Ideal” PVWatts – “Draw Your System” • “As Built” PVWatts – “Draw your System” • Do not alter any further values or options when submitting to the NJCEP.
  • 4. • The guidelines have changed regarding hard-copy submittal of PVWatts and Shading Report. Hard copies are not required to be submitted with the final As-Built packet. BUT… • The NJCEP reserves the right to request a complete copy of production estimates, a full shade analysis, or any relevant documentation from the installer at any time. NJCEP Requirements
  • 5. NREL Hyperlinks • Current NREL Versions accepted by NJCEP – NREL PVWatts Calculator • http://pvwatts.nrel.gov/ (standard interface-click this link to follow slides) – NREL System Advisor Model (SAM) • https://sam.nrel.gov/ (advanced design interface) • Legacy Calculators – PVWatts Version 1 (RETIRED 2015) • http://rredc.nrel.gov/solar/calculators/PVWATTS/version1/ – PVWatts Version 2 (RETIRED 2015) • http://gisatnrel.nrel.gov/PVWatts_Viewer/index.html
  • 6. PVWatts Calculator Release The newest revised version of PVWatts uses updated values. More information on value changes (http://pvwatts.nrel.gov/version_5.php). (click “Close” to continue on the site)
  • 7. NREL’s PVWatts Calculator To begin, enter the address of the job site, then click on “GO >>”. 75 Lincoln Hwy, Iselin, NJ 08830
  • 8. NREL’s PVWatts Calculator Confirm that the default weather station is optimal for the site address. Select “Go To system info” to continue.
  • 9. “Ideal” PVWatts Calculator For “Ideal” PVWatts, only change “DC System Size (kW)”. All other values remain default. System Losses (%) remains “14”. Click on “Loss Calc.” to view.
  • 10. “Ideal” Derate Calculator For “Ideal” PVWatts, no values should be altered. The “Estimated DC to AC Factor” should remain “14%.” Screen capture of the “Ideal Derate Calculator” is not required. Click “Cancel” to return to previous page without changes.
  • 11. “Ideal” PVWatts Calculator Verify only the “DC System Size (kW)” changed. Then click “Go to PVWatts results” to generate “Ideal” summary.
  • 12. “Ideal” PVWatts Calculator The results page displays the “Ideal Estimated Annual Production” required on the NJCEP Final As Built Technical Worksheet, Page 2, Section D, 2b.
  • 13. Roof Azimuth Capture the Azimuth measurement either on-site or by utilizing an available online measurement tool. For this example, we will use orientation 228.1°. (Example screen capture from Solmetric.com, Roof Azimuth Tool)
  • 14. “As Built” PVWatts Calculator • For “As Built” PVWatts, change all system information, as permissible within NJCEP. Input “Inverter Efficiency (%)”, based upon manufacturer-specification. • Update Derate Factor to reflect equipment and shading using the “Loss Calulator”. Click on “Loss Calculator” to view.
  • 15. “As Built” Derate Calculator • “As Built” PVWatts, only change “(PV Module) Nameplate Rating (%)” [i.e.. power tolerance factor], and Shading (%) [not Solar Access %]. • Save a Screen Capture of the “As Built Derate Calculator”. • Click “Save” to apply the updated “Derate Factor”/System Losses.
  • 16. “Draw Your System” (Optional) You may optionally “Draw Your System” using the corresponding button, but this feature does not print out with the summary report. Not NJCEP-required.
  • 17. “As Built” PVWatts Calculator Verify the “System Info” is all correct. Confirm that the “System Losses (%)” represents the final value from the Loss Calculator. Scroll down the screen.
  • 18. “As Built” PVWatts Calculator Scrolling down further on the page will reveal information that is not required to be selected or altered. Not required by the NJCEP. Finally, click “Go to pvwatts results” to generate “As Built” PVWatts summary.
  • 19. PVWatts Summary Page (Example of the “As-Built” PVWatts Results Page)
  • 20. “As Built” PVWatts Summary The results page displays the “As-Built Estimated Annual Production” required on the NJCEP Final As Built Technical Worksheet, Page 3, Section D, 2a.
  • 21. “As Built” PVWatts Summary For a “Monthly” or “Hourly” report, click on the coordinating button to save/print.
  • 22. “As Built” PVWatts Summary The “Monthly” or “Hourly” report can be saved/printed from the generated spreadsheet, which may be used in advanced design planning. Not NJCEP- Required.
  • 23. Verify all information was entered properly and measurements are accurate. Save a copy of the “As-Built” and “Ideal” PVWatts summary pages for your records. “As Built” PVWatts Summary
  • 24. PVWatts Feedback For feedback regarding the PVWatts Calculator, email comments to PVWatts@nrel.gov.
  • 25. Questions? For questions pertaining to the NJCEP requirements within Final As Built Completion Packets, please refer to the following: • SREC Registration Program Guidebook http://www.njcleanenergy.com/files/file/Renewable_Programs/RE%20Forms/ 2012/SRP_Guidebook_2012_Ch8revrr_6_26_12.pdf • SREC Registration Program Checklist – Solar SRP Final As-Built Forms (updated Jan 2015) - .xlsx version (Excel 2010) – Solar SRP Final As-Built Forms (updated Jan 2015) - .xls version (Excel 2003-2007) • Note: Microsoft provides an Office Compatibility Pack for those users that are still using the earlier version of Excel (.xls). • call: 866-NJSMART (866-657-6278)