Modeling of Lightning Strike Events, and it’s Correlational
with Power Outages in South-West Coast, Nigeria
Melodi A. O.1
, Oyeleye M. O.2
Department of Electrical and Electronics Engineering, Federal University of Technology, P.M.B. 704, Akure,
Ondo State, Nigeria
Article Info ABSTRACT
Article history:
Received Nov 1, 2016
Revised Nov 27, 2016
Accepted Jan 5, 2017
This paper aimed to model lightning strike events and evaluate its correlation
with power outages in a Nigerian power distribution system. A specified
coastal distribution network of southwest Nigeria was selected as a case
study. Zone-specific records of cloud-to-ground lightning strikes for 84
months were obtained from the Nigerian Meteorological Agency (NiMet);
records of power outage frequencies and durations for 36 months were
obtained at the substations of the selected distribution network. Using
numerical statistical analysis techniques, lightning activity in the system area
were characterized in relative frequency terms, and correlation statistics were
evaluated and analyzed for power outages and lightning events on the 11kV,
33kV, and 132kV voltage levels. An analysis of the results shows that the
modelled lightning strike events patterns are closely related but the expected
frequencies vary from one zone to another; and there is correlation between
lightning strike and power outages in the distribution networks, which is
strong and positive at the 33 kV and 132 kV circuits. In essence, the results
provided salient information, useful for power systems lightning protection
review, management and planning in the area.
Keyword:
Lightning strike
Cloud-ground flash
Coastal power grid
Power outage
Power outage duration
Power outage frequency
Correlation
Relative intensity
Metrological zones
Lightning protection
Copyright © 2017 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
Melodi A.O.,
Department of Electrical and Electronics Engineering,
Federal University of Technology,
Akure, PMB 704, Nigeria.
Email: melodiadegoke@yahoo.com
1. INTRODUCTION
Power system unavailability index in Nigeria is high, especially at the distribution systems. An
alleged contributor to this is lightning activity or atmospheric electric discharges during thunderstorms. Over
the years, numerous instances of damage to (critical) equipment were reported across a wide spectrum of
systems, networks and applications in Nigeria due largely to occurrences of intense lightning activity.
Generally, this study juxtaposes the lightning activity data and the power outage problem in order to establish
and evaluate the links between the two in statistical and technical terms.
Theoretically, lightning strike (LS) is characterized by currents in terms of kA and ultra high
temperatures. Though lightning flashes occur in the clouds, the flash between cloud and ground (LS) pose a
greater challenge to PS safety. According to [1], lightning discharges are characterized by short duration of
high electric voltage and current pulses. Also, lightning event is arbitrary, unpredictable and can strike
anywhere on earth with current value that could exceed 40kA, induce temperature up to 50,000 degrees
Fahrenheit, and move at speed closing to 33% speed of light [1],[2]. Lightning is the transient passage of
electrical current between a cloud and either the surface of the earth, another cloud, or an object in or near a
cloud. Lightning is most commonly associated with thunderstorms and can occur at any time and can strike
anywhere on the earth surface [1],[3],[4]. According to [5], primarily, lightning occurs either within a large
IJECE ISSN: 2088-8708 
Modeling of Lightning Strike Events, and it's Correlational with Power Outages .... (Melodi A.O.)
3263
cumulonimbus cloud (cloud-to-cloud, C-C) or between the cloud-to-ground (C-G); secondarily, it occurs
from ground-to-sky (G-S).
In [6], thunder storm occurrence is considered as varying with location. If these lightning pulses are
not effectively discharged to the ground, they usually result in loss or damage of valuable equipment or
power systems, and even loss of human life. Such objects are protected by installing protective devices that
arrest LS either directly or indirectly based on principles of atmospheric electrostatic discharges and surge
modification. The C-G has the greatest effects on electrical systems and its statistics of occurrence,
correlation with power outages on coastal power distribution systems are the scope of this study.
Lightning strikes, especially C-G, has continued to be subject of studies in different locations and
conditions as depicted in [2],[5],[7]-[9]; especially as it impacts protective grounding designs and locations;
empirical intensities, physical processes in different geographical locations have been the foci. These mostly
location specific foci and approaches are particularly central for sub-saharan Africa studies, where
dependence on foreign models and technologies are predominant.
An earlier study on Nigeria southwest coast, [5], reported on C-G lightning strike frequency with
respect to periods of the year, which was generalized for the entire southwest coast without consideration for
subregion-specific data. Also, there were no specific relations established with respect to power supply and
installations. However, it was assumed that lightning related faults would be expectedly high during the peak
periods of lightning events in the year.
Lightning data is relevant for evaluation of the performance of protection designs [10]; and can also
be used to generate variation of annual lighting stroke frequency and annual variation of number of
thunderstorm day [11]. These are applicable to power systems objects and location considered in this paper;
owing to the huge costs of equipment and power failures and danger on 11-132kV power lines, protective
devices on power installations need to be evaluated in terms of standard requirement and efficacy.
The coastal regions of Nigeria are subjected to thunderstorms originating from Atlantic Ocean
currents, hence they are all prone to intense lightning activities, 15 flash/km2
/yr [5], [12]. Lagos State of
Nigeria is located in the southwest coast at 6°35′N 3°45′E; and its land area is 3474km2
[13]. Based on LS
data from Nigeria Meteorological Agency (NiMet), the State is divided into three zones: Marine (Victoria
Island, Lekki, Epe and Ikorodu towns; over 2,000km2
), Lagos Roof (Mainland; 19km2
), and Ikeja (46km2
)
zones. Thes zones are denoted Z1, Z2, and Z3 respectively. Figure 1 presents a sketch of Southwest coast or
Lagos region showing the three metrological zones. In addition, Lagos State consumes 43-52% of the
National power company’s power output [14]. It is distinctly marked by the relatively high density of
infrastructure comprising HV power transmission substations, heavy industries, numerous communication
networks, the sea and reports of residents on damage to appliances due to lightning strike in this region.
Figure 1. A Sketch of Southwest Coast showing three Metrological Zones (Z1-Z3)
50 km
30000
0
68000
42000
Z 1
Z 3
32000 34000
36000
38000
40000
66000
64000
62000
Z1
Z2
Z3
Atlantic
Ocean
 ISSN: 2088-8708
IJECE Vol. 7, No. 6, December 2017 : 3262 – 3270
3264
Consequent on the above, this study aimed to model C-G LS events for the coastal region using new
data, and to to evaluate the correlation of LS events and power outage in the 11-132kV distribution systems
of Nigeria using specified installations in Z1 of the coastal region as case study. For the purpose of this study,
Z1’s Ikorodu Transmission Substation (ITS) and distribution substation (IDS) records were applied.
Figure 2 illustrates connection structure of 11–132kV systems and exposure to thunderstorms in the
region.
The ITS, commissioned in 1976, feeds three 132kV delivery stations in the zone including the IDS.
The IDS feeds the township distribution networks. Over a period of 35 years, the ITS capacity grew from 2 x
15MVA (1976) to 3 x 60MVA (2011). The ITS shares 220MW among its average 400MW power
requirement by its customers. The IDS feeds 13 lines with 684x11/0.4kV distribution transformers (DTs) and
5 lines with 10x33/11kV substations. The power supplied grew from 20MW (2007) to 30MW (2010) and
55MW (2012). From the operators’ experiences, observed problems include frequent tripping of feeders,
lightning events and faults (particularly recent serious instances), falling of tree on line pole damages,
earthing failures, disc and pot shattering, and transformer damages; transformer damages were severe in wet
season than in dry season. This is similar to other cases in the region.
Figure 2. Connection Structure of Z1’s Ikorodu Transmission and Distribution Substations Network
Revenue from electricity is basically the product of unit energy consumed and kWhr cost of energy.
In order to know the approximate monthly revenue that is obtainable from a transmission substation as in
Figure 2 and that would be lost due to outage, Equation (1) is applied.
Rm = co PdTmavLF = kco PdTaLF = k co (Padd − Psdd )Ta LF (1)
where Rm is monthly revenue, ₦; k – time (duration) reduction factor (k=0.083); co –cost of unit energy
supplied, ₦/kWhr; Pd – average peak power supplied daily, Tmav – average hr. in a month, Ta –hour in a year
(8960), Padd– actual peak demand per day, Psdd peak supply deficit per day, LF is load factor (approx.. 0.9).
Monthly revenue loss due to supply deficit or suppressed demand, 𝑅𝐿 𝑚:
RLm = kco PsddTaLF, (2)
Potential monthly revenue due to actual system demand (Rpot.(m)):
Rpot.(m) = Rm + RLm, (3)
Rm, RLm, and Rpot.(m) were evaluated for the selected ITS-IDS and shown in Table 1.
Surge
Diverter
Thunder cloud
132kV
132/33kV; 3x60MVA
33/11kV
11/0.4kV
Industrial customers
To other TS
Incoming Lines
To other
11kV
DTs
LV
users
ITS IDS
IJECE ISSN: 2088-8708 
Modeling of Lightning Strike Events, and it's Correlational with Power Outages .... (Melodi A.O.)
3265
Table 1. Estimates of 𝑅 𝑚 and 𝑅𝐿 𝑚 (at 𝑐 𝑜=24.08, naira/kWHr)
Object Pd MW Ta , hr
CO,
naira/kWHr
Padd,
MW
Psdd,
MW
k LF Rm , naira RLm’,naira Rpot.(m), naira
ITS 220 8760 24.08 400 180 0.0833 0.9 3,479,130,990.72 2,846,561,719.68 6,325,692,710.40
The RLm value for ITS is approximately 2.85 billion naira. This 45% monthly revenue loss due to
prevailing inadequate supply capacity is very large and should not be aggravated by outages due to
atmospheric factor as lightning. The cost of 4 x 60MVA transformers alone in 132/33kV substation is ₦1.8
billion. As earlier indicated, the considered coastal regions lie in the tropics and are subjected to intense
thunderstorms [5]; consequently, power installations are prone to lightning incidences in the region.
Therefore, protection of apparent capital intensive electric power network installations and systems
operations reliability will mitigate costs and save huge revenue.
2. RESEARCH METHOD
In order to model C-G LS events for the coastal region using new data, C-G LS records (2006-2012)
for the specified coastal area were considered and obtained from the Nigerian Metrological Agency (NiMet).
A survey of installations shows unavailability of LS counter records. Therefore, to obtain the correlation of
LS events and power outage in the 11-132kV systems, outage data for 11-132kV power supply stations and
associated lines in a metrological zone of the area (i.e., Z1) were extracted from respective stations’ records;
and evaluated for correlation with obtained zonal C-G LS records, using inferential statistical concepts
(relative frequency and correlational statistical techniques) [15]. The algorithm was implemented with
proprietary MS-Excel software.
2.1. Relative Intensity Statistic
Relative intensity of C-G LS for each month of the year was evaluated in terms of relative lightning
frequency. Relative lightning frequency for a given zone (z), month (m), and year (y) was defined and
evaluated as 𝑅𝐿𝐹𝑚
(𝑍)
using:
𝑅𝐿𝐹𝑚
(𝑍)
=
∑ 𝑄𝐿𝑆 𝑚,𝑦
(𝑍)7
𝑦=1
∑ 𝑄𝐿𝑆 𝑦
(𝑍)7
𝑦=1
, (4)
where 𝑄𝐿𝑆 𝑚,𝑦
(𝑍)
– quantity of C-G LS for given zone, month, and year; and 𝑄𝐿𝑆 𝑦
(𝑍)
- quantity of C-G LS for
given zone and year. The values for 𝑄𝐿𝑆 𝑚,𝑦
(𝑍)
and 𝑄𝐿𝑆 𝑦
(𝑍)
were obtained from NiMet records for 2006 to 2012
years. The values obtained for 𝑅𝐿𝐹𝑚
(𝑍)
are presented in Figure 3 and analysed.
2.2. Zonal and Monthly Probabilities of C-G LS Event
Probability of C-G LS event for a given zone (Z) and month was defined and evaluated as
𝑃(𝑍)(𝐿𝑆 𝑚 > 𝑛) using:
𝑃(𝑧)(𝐿𝑆 𝑚 > 𝑛) =
𝑞(𝑧)(𝐿𝑆 𝑚>𝑛)
𝑞(𝑧)(𝐿𝑆 𝑚)
; 𝑛 = (0, 1, 2) (5)
where 𝑞(𝑧)(𝐿𝑆 𝑚 > 𝑛) is quantity of LS events greater than n, and 𝑞(𝑧)(𝐿𝑆 𝑚) – qty. of LS events in month m
for the entire data period. Values obtained for 𝑃(𝐿𝑆 𝑚 > 𝑛) are presented in Figures 4 to 6 and analysed for n
= (0, 1, 2) and profiles the probability of LS in each of the month of a year for the study zones.
2.3. Zonal and Monthly Average and Range Statistics of LS Events
The monthly and annual averages of LS, 𝐴𝐿𝑆 𝑚 and 𝐴𝐿𝑆 𝑌 respectively, were evaluated as in:
𝐴𝐿𝑆 𝑚 =
∑ 𝐿𝑆 𝑚,𝑦
𝑌
𝑦=1
𝑌
; 𝑌 = 7 (6)
where 𝐿𝑆 𝑚,𝑦 -lightning strike events in given month and year y; Y – number of years y in data period.
Average annual LS events for the data period:
 ISSN: 2088-8708
IJECE Vol. 7, No. 6, December 2017 : 3262 – 3270
3266
𝐴𝐿𝑆 𝑌 =
∑ 𝐴𝐿𝑆,𝑦
𝑌
𝑦
𝑌
; 𝐴𝐿𝑆 𝑦 = ∑ 𝐴𝐿𝑆 𝑦,𝑚𝑚 (7)
where 𝐴𝐿𝑆 𝑦 - average LS event for year y, 𝐴𝐿𝑆 𝑦,𝑚 is average LS for given year and month. Results of
𝐴𝐿𝑆 𝑚, 𝐴𝐿𝑆 𝑦 are presented in Figures 7 to 9.
2.4. Correlation Analysis Of C-G LS And Outage Data
Data of power outage durations on 11kV, 33kV, and 132kV lines were extracted from system daily
records and summarized for each of the three years. Correlation between these data and corresponding data
on C-G LS events were evaluated correlation function as in MS Excel (2013):
𝐶𝑜𝑟𝑟𝑒𝑙(𝑃𝑂𝑦,𝑚, 𝐿𝑆 𝑦,𝑚) =
∑(𝑃𝑂 𝑦,𝑚−𝐴𝑃𝑂 𝑦)(𝐿𝑆 𝑦,𝑚−𝐴𝐿𝑆 𝑦)
√∑(𝑃𝑂 𝑦,𝑚−𝐴𝑃𝑂 𝑦)
2
∑(𝐿𝑆 𝑦,𝑚−𝐴𝐿𝑆 𝑦)
2
(8)
where 𝑃𝑂𝑦,𝑚 –power outage for a particular year and particular month; 𝐴𝑃𝑂𝑦 –average power output for
corresponding year; 𝐿𝑆 𝑦,𝑚 –Lightning strike for a particular year and particular month. The result is
presented in Table 2.
3. RESULTS AND ANALYSIS
Results obtained from evaluation of C-G lightning st rike in study location and correlation with power
outages on 11-132 kV network are as in Figures 3 to 9 and Table 2. Figure 3 presents monthly RLFs of zones Z1 to
Z3 respectively. Figures 4 to 6 present the monthly probabilities of LS in the three mentioned zones respectively.
Analogically, Figures 7 to 9 present the monthly and annual LS averages for the same zones.
Figure 3. Obtained Monthly RLFs for Zones 1 to 3, Lagos State, southwest coast, Nigeria
Figure 3 values for zone Z1 show that LS events can be expected throughout the year. However, the
intensity varies: 0-5% of annual total of LS is expected in 5 months of every year: January to March; August
to September; and December. These include dry season and rain break months for the region. More LS
events are expected April, July, and November. Figure 3 further shows that RLF variation patterns for Z2 and Z3
are similar to that of Z1 but vary in magnitudes. Also, the peak for Z1 comes a month earlier. The highest magnitude
is in June; while for the other zones it can be expected in both May and June.
Figure 4 to 6 presents monthly probabilities of three categories of LS frequencies: LS>0; LS>1; and LS>2. It
is notable in Figure 4 that for zone Z1, the probability of LS event exceeding twice in February, March, August, and
September, is nil. Figure 6 shows that zone Z3 has the highest probabilities of higher (>2) LS frequencies for all
months.
0.00
0.05
0.10
0.15
0.20
0.25
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
Rel.Freq
month
Rel.Freq_zI Rel.Freq_zII Rel.Freq_zIII
IJECE ISSN: 2088-8708 
Modeling of Lightning Strike Events, and it's Correlational with Power Outages .... (Melodi A.O.)
3267
Figure 4. Monthly Probabilities of LS occurring at least once (LS>0); twice (L>1); and thrice LS>2) in Zone Z1
Figure 5. Probability of LS occurring at least once (LS>0); twice (L>1); and thrice LS>2) in in Zone Z2
Figure 6. Probability of LS occurring at least once (LS>0); twice (L>1); and thrice LS>2) in in Zone Z3
Figure 7 to 9 show that: for zone Z1, ALSm can range from 1 to 7 events per month, with peak expected in
June; for zone Z2, ALSm can range from 1 to 6 events, with peak expected in June, July, and September; and for zone
Z3, ALSm can range from 4 to 22 events, with peak expected in June and October. Annualy, ALSy can have the
following monthly ranges: (11, 27) events, (11,31) events, and (81, 145) events for zones Z1, Z2, and Z3
0.00
0.20
0.40
0.60
0.80
1.00
Probability
Months
P(LS>2)
P(LS>1)
P(LS>0)
0.00
0.20
0.40
0.60
0.80
1.00
Probability
Months
P(LS>2)
P(LS>1)
P(LS>0)
0.00
0.50
1.00
Probability
Months
P(LS>2)
P(LS>1)
P(LS>0)
 ISSN: 2088-8708
IJECE Vol. 7, No. 6, December 2017 : 3262 – 3270
3268
respectively. These values ascertained that lightning intensity varies from one location to another location. The
seasonality should be considered when planning annual maintenance strategies of protective installations.
Figure 7. Monthly Average LS`` strike in Zone Z1
Figure 8. Monthly Average LS strike in Zone Z2
Figure 9. Monthly Average LS strike in Zone Z3
19.1
27.4
10.91.7
0.8
1.5
2.8
6.1 6.5
4.7
0.8 1.0
5.2
2.3
0.6
-1.0
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0
5
10
15
20
25
30
jan feb mar apr may jun jul aug sep oct nov dec Year
LightningStrike
Months
Yr. av.
Yr. max(av.)
Yr. min(av.)
Monthly av.
monthly min(av.)
Monthly max(av.)
20.9
30.5
11.2
0.7
1.6 1.5
2.4
4.3
6.0 6.1
1.4
6.0
3.9
2.0
0.5
-1.0
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0
5
10
15
20
25
30
35
jan feb mar apr may jun jul aug sep oct nov dec Year
LightningFreq.
Months
Yr. av.
Yr. max(av.)
Yr. min(av.)
Monthly av.
monthly min(av.)
Monthly max(av.)
113.1
145.1
81.2
3.6
9.0
14.7 14.8
19.0
20.5
11.5
6.4
12.5
21.6
15.2
5.9
0.0
5.0
10.0
15.0
20.0
25.0
0
20
40
60
80
100
120
140
160
jan feb mar apr may jun jul aug sep oct nov dec Year
LightningFreq.
Months
Yr. av.
Yr. max(av.)
Yr. min(av.)
Monthly av.
monthly min(av.)
Monthly max(av.)
IJECE ISSN: 2088-8708 
Modeling of Lightning Strike Events, and it's Correlational with Power Outages .... (Melodi A.O.)
3269
Generally, these values and analyses, depicted by Figures 4 to 10, indicate that C-G LS intensity is
significant in the study location and adequate measures should be developed to curtail them for the power
installations. This justifies a need to investigate the adequacy of existing LPS installations.
Table 2 shows that correlation between C-G LF and power outage duration in zone Z1 (Ikorodu) is: weakly
positive for 11kV installations (0.08-0.39); strong and positive for 33kV installations (0.45-0.85); and moderately
positive for 132 kV installations (0.3-0.55, in 2012). These values generally show that the relationships between
LS and PO are positive linear relationships, being strongest in 33 and 132kV systems. In addition, Table 3
shows that the correlation outcome between C-G LF and outage frequency is equally significant for 33 kV and 132
kV installations. This observation indicates that the existing lightning protective schemes are unreliable and
validates a need to evaluate the active efficiency of existing lightning protection schemes on the PDNs in the
coastal area, and by extension, Nigeria.
Table 2. Correlation for C-G LF and Power Outage Events Duration on 11kV, 33kV and 132kV Systems,
2010-2012
System
Correlation Coeffiscients p-values (at alpha = 0.05)
Correlation Status and Significance
2010 2011 2012 2010 2011 2012
11kV 0.08 0.23 0.39 0.79664 0.46975 0.21227 weak & insignificant (,,)
33kV 0.45 0.85 0.70 0.13789 0.00050 0.01148 strong positive & significant (,2011,2012)
132kV 0.30 0.47 0.55 0.34148 0.12582 0.06498 moderate positive & insignificant (,,)
Table 3. Correlation for C-G LF and Power Outage Events Frequency on 11kV, 33kV and 132kV Systems,
2010-2012
System
Correlation Coeffiscients p-values (at alpha = 0.05)
Correlation Status and Significance
2010 2011 2012 2010 2011 2012
11kV - - - - - - No data available
33kV 0.93 0.54 0.70 0.000012 0.072539 0.011680 Strong positive & significant(2010,,2012)
132kV 0.36 0.62 0.68 0.252851 0.031330 0.015534 Moderate positive & significant(,2011,2012)
4. CONCLUSION
The focus of this paper has been on obtaining model quantitative values and patterns for C-G LS
events useful for system design, planning, and maintenance schedules; and to establish a possible correlation
with incessant power outages in the specified coastal region, which should be factored-in in the critical
search for power outage mitigating measures in present Nigeria systems. From the analyses of the results, it
is ascertained that lightning strikes vary from one location or zone to the other. LS events are significantly
intense in the studied region and contribute to power outage at 11-132kV installations. Model range values of
C-G LS events is (11,145) events per month. 33 kV and 132 kV installations have the highest correlation of
outage with LS events in the region. 11kV installations are weakly correlated, indicating that other factors are
more salient contributors to outages at this level. Graphical and numerical models of C-G LS events are
provided for application in planned LPS installation and maintenance for Nigerian southwest coast. This
correlation analyses of lightning events and power outages in 11-132kV networks along Nigerian coast
establish the degree of lightning disturbances on power availability and by implication, insight into the
effectiveness or adequacy of existing lightning protection scheme in the system.
REFERENCES
[1] R. Kithil, “Fundamentals of Lightning Protection,” National Lightning Safety Institute (NLSI), 2010.
[2] S. N. Nikolovski, et al., “Frequency and Time Response of Power Plant Grounding System Exposed to Lightning
Strike,” International Journal of Electrical and Computer Engineering, vol/issue: VI(2), pp. 512-525, 2016.
[3] B. S. Ronald, “Consulting on lightning damage or injury, Ph.D Thesis,” 2011.
[4] C. E. Dick, “An Analysis of the impact and predictability of lightning strikes in Tallahassee, Florida,” 2011.
[5] A. I. Mowete and M. A. K. Adelabu, “Assessment of lightning and other electromagnetic disturbances along the
coast of south west Nigeria,” XIX-th International Conference on Electromagnetic, pp. 200-203, 2009.
[6] V. Cooray, “The Lightning Flash,” IEE Power and Energy, vol. 34, pp. 574-579, 2003.
[7] B. R. P. da Rocha, et al., “Lightning Characteristics Time Distribution over Four Locations in Eastern Amazonia,”
in IX International Symposium on Lightning Protection (IX SIPDA), Foz do Iguaçu (Brazil), 2007.
[8] J. O. Adepitan and F. O. Ogunsanwo, “Investigating the Relationship between some Thunderstorm Parameters and
Ground Flash Density,” The Pacific Journal of Science and Technology, vol/issue: 13(2), pp. 148-150, 2012.
[9] C. L. Wooi, et al., “Statistical Analysis on Preliminary Breakdown Pulses of Positive Cloud-to-Ground Lightning in
Malaysia,” International Journal of Electrical and Computer Engineering, vol/issue: VI(2), pp. 844-850, 2016.
 ISSN: 2088-8708
IJECE Vol. 7, No. 6, December 2017 : 3262 – 3270
3270
[10] F. A. Auditore, “Refurbishment and Upgrading Design Options-lightning Mast VersusOverhead Sheilding
Conductor,” in EEA Conference, 2009.
[11] S. Yakoyama, “Lightning Detection and LightningProtection of Power System in Japan Panel Paper,” in IEEE PES
Transmission and Distribution, Asia Pacific Yakohama, 2002.
[12] Geology.com, “World Lightning Map,” 2013.
[13] O. Leke and E. Gbenga, “Effects of Global Economy on Spatial Structure of Ikeja, Lagos,” in Department of Urban
and Regional Planning, Faculty of Environmental Sciences, University of Lagos, Akoka., Lagos, 2013.
[14] I. O. Megbowon and T. O. Oyebisi, “A Reliability Assessment of South West Transmission Lines of the Nigerian
National Grid,” FUTAJEET, vol/issue: IV(1), pp. 17-22, 2005.
[15] G. Keller and B. Warrack, “Statistics for Management and Economics,” Pacific Grove, USA, Thompson Learning
Inc, pp. 832, 2003.

More Related Content

Similar to Modeling of Lightning Strike Events, and it’s Correlational with Power Outages in South-West Coast, Nigeria

Protection for 330 kV transmission line and recommendation for Nigerian tran...
Protection for 330 kV transmission line and recommendation  for Nigerian tran...Protection for 330 kV transmission line and recommendation  for Nigerian tran...
Protection for 330 kV transmission line and recommendation for Nigerian tran...IJECEIAES
 
Lightning threat and protection from lightning information and product by jm...
Lightning threat and  protection from lightning information and product by jm...Lightning threat and  protection from lightning information and product by jm...
Lightning threat and protection from lightning information and product by jm...Mahesh Chandra Manav
 
Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...
Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...
Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...IRJET Journal
 
On the applicability of some existing tropospheric scintillation prediction ...
On the applicability of some existing tropospheric scintillation  prediction ...On the applicability of some existing tropospheric scintillation  prediction ...
On the applicability of some existing tropospheric scintillation prediction ...IJECEIAES
 
A novel model for solar radiation prediction
A novel model for solar radiation predictionA novel model for solar radiation prediction
A novel model for solar radiation predictionTELKOMNIKA JOURNAL
 
Effectiveness of energy sector quality management systems in response to elec...
Effectiveness of energy sector quality management systems in response to elec...Effectiveness of energy sector quality management systems in response to elec...
Effectiveness of energy sector quality management systems in response to elec...ELIJAH ONYANGO STANDSLAUSE ODHIAMBO
 
Water Treatment Plant Protection
Water Treatment Plant ProtectionWater Treatment Plant Protection
Water Treatment Plant ProtectionMike Nager
 
Energy generation by crystalline silicon photovoltaic network per meter squa...
Energy generation by crystalline silicon photovoltaic network  per meter squa...Energy generation by crystalline silicon photovoltaic network  per meter squa...
Energy generation by crystalline silicon photovoltaic network per meter squa...IJECEIAES
 
A Case-Study on Blackout
A Case-Study on BlackoutA Case-Study on Blackout
A Case-Study on Blackoutijtsrd
 
The impact of integration of solar farms on the power losses, voltage profile...
The impact of integration of solar farms on the power losses, voltage profile...The impact of integration of solar farms on the power losses, voltage profile...
The impact of integration of solar farms on the power losses, voltage profile...journalBEEI
 
An Extended Tropospheric Scintillation Model for Free Space Optical Communica...
An Extended Tropospheric Scintillation Model for Free Space Optical Communica...An Extended Tropospheric Scintillation Model for Free Space Optical Communica...
An Extended Tropospheric Scintillation Model for Free Space Optical Communica...ijeei-iaes
 
Guo dust weather conditions PV performance SGRE2015
Guo dust weather conditions PV performance SGRE2015Guo dust weather conditions PV performance SGRE2015
Guo dust weather conditions PV performance SGRE2015Saadat Khan
 
Power distribution system fault monitoring device for supply networks in Nigeria
Power distribution system fault monitoring device for supply networks in NigeriaPower distribution system fault monitoring device for supply networks in Nigeria
Power distribution system fault monitoring device for supply networks in NigeriaIJECEIAES
 
(U fouo) dhs infrastructure protection note- most significant tactics against...
(U fouo) dhs infrastructure protection note- most significant tactics against...(U fouo) dhs infrastructure protection note- most significant tactics against...
(U fouo) dhs infrastructure protection note- most significant tactics against...RepentSinner
 
(U fouo) dhs infrastructure protection note- most significant tactics against...
(U fouo) dhs infrastructure protection note- most significant tactics against...(U fouo) dhs infrastructure protection note- most significant tactics against...
(U fouo) dhs infrastructure protection note- most significant tactics against...AnonDownload
 
Long term power transmission failures in southeastern brazil and the geophysi...
Long term power transmission failures in southeastern brazil and the geophysi...Long term power transmission failures in southeastern brazil and the geophysi...
Long term power transmission failures in southeastern brazil and the geophysi...Carlos Bella
 
Solar Superstorms: Planning for an Internet Apocalypse
Solar Superstorms: Planning for an Internet ApocalypseSolar Superstorms: Planning for an Internet Apocalypse
Solar Superstorms: Planning for an Internet ApocalypseGuy Boulianne
 

Similar to Modeling of Lightning Strike Events, and it’s Correlational with Power Outages in South-West Coast, Nigeria (20)

Protection for 330 kV transmission line and recommendation for Nigerian tran...
Protection for 330 kV transmission line and recommendation  for Nigerian tran...Protection for 330 kV transmission line and recommendation  for Nigerian tran...
Protection for 330 kV transmission line and recommendation for Nigerian tran...
 
Lightning threat and protection from lightning information and product by jm...
Lightning threat and  protection from lightning information and product by jm...Lightning threat and  protection from lightning information and product by jm...
Lightning threat and protection from lightning information and product by jm...
 
Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...
Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...
Islanding Detection and Controlled Islanding in Emerging Power Systems Key Is...
 
On the applicability of some existing tropospheric scintillation prediction ...
On the applicability of some existing tropospheric scintillation  prediction ...On the applicability of some existing tropospheric scintillation  prediction ...
On the applicability of some existing tropospheric scintillation prediction ...
 
A novel model for solar radiation prediction
A novel model for solar radiation predictionA novel model for solar radiation prediction
A novel model for solar radiation prediction
 
L0102189100
L0102189100L0102189100
L0102189100
 
Effectiveness of energy sector quality management systems in response to elec...
Effectiveness of energy sector quality management systems in response to elec...Effectiveness of energy sector quality management systems in response to elec...
Effectiveness of energy sector quality management systems in response to elec...
 
LPS study
LPS studyLPS study
LPS study
 
Water Treatment Plant Protection
Water Treatment Plant ProtectionWater Treatment Plant Protection
Water Treatment Plant Protection
 
Energy generation by crystalline silicon photovoltaic network per meter squa...
Energy generation by crystalline silicon photovoltaic network  per meter squa...Energy generation by crystalline silicon photovoltaic network  per meter squa...
Energy generation by crystalline silicon photovoltaic network per meter squa...
 
A Case-Study on Blackout
A Case-Study on BlackoutA Case-Study on Blackout
A Case-Study on Blackout
 
The impact of integration of solar farms on the power losses, voltage profile...
The impact of integration of solar farms on the power losses, voltage profile...The impact of integration of solar farms on the power losses, voltage profile...
The impact of integration of solar farms on the power losses, voltage profile...
 
An Extended Tropospheric Scintillation Model for Free Space Optical Communica...
An Extended Tropospheric Scintillation Model for Free Space Optical Communica...An Extended Tropospheric Scintillation Model for Free Space Optical Communica...
An Extended Tropospheric Scintillation Model for Free Space Optical Communica...
 
Guo dust weather conditions PV performance SGRE2015
Guo dust weather conditions PV performance SGRE2015Guo dust weather conditions PV performance SGRE2015
Guo dust weather conditions PV performance SGRE2015
 
Power distribution system fault monitoring device for supply networks in Nigeria
Power distribution system fault monitoring device for supply networks in NigeriaPower distribution system fault monitoring device for supply networks in Nigeria
Power distribution system fault monitoring device for supply networks in Nigeria
 
(U fouo) dhs infrastructure protection note- most significant tactics against...
(U fouo) dhs infrastructure protection note- most significant tactics against...(U fouo) dhs infrastructure protection note- most significant tactics against...
(U fouo) dhs infrastructure protection note- most significant tactics against...
 
(U fouo) dhs infrastructure protection note- most significant tactics against...
(U fouo) dhs infrastructure protection note- most significant tactics against...(U fouo) dhs infrastructure protection note- most significant tactics against...
(U fouo) dhs infrastructure protection note- most significant tactics against...
 
Long term power transmission failures in southeastern brazil and the geophysi...
Long term power transmission failures in southeastern brazil and the geophysi...Long term power transmission failures in southeastern brazil and the geophysi...
Long term power transmission failures in southeastern brazil and the geophysi...
 
Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...
Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...
Impacts of Photovoltaic Distributed Generation Location and Size on Distribut...
 
Solar Superstorms: Planning for an Internet Apocalypse
Solar Superstorms: Planning for an Internet ApocalypseSolar Superstorms: Planning for an Internet Apocalypse
Solar Superstorms: Planning for an Internet Apocalypse
 

More from IJECEIAES

Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...IJECEIAES
 
Prediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionPrediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionIJECEIAES
 
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...IJECEIAES
 
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...IJECEIAES
 
Improving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningImproving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningIJECEIAES
 
Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...IJECEIAES
 
Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...IJECEIAES
 
Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...IJECEIAES
 
Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...IJECEIAES
 
A systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyA systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyIJECEIAES
 
Agriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationAgriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationIJECEIAES
 
Three layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceThree layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceIJECEIAES
 
Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...IJECEIAES
 
Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...IJECEIAES
 
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...IJECEIAES
 
Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...IJECEIAES
 
On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...IJECEIAES
 
Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...IJECEIAES
 
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...IJECEIAES
 
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...IJECEIAES
 

More from IJECEIAES (20)

Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...
 
Prediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionPrediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regression
 
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
 
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
 
Improving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningImproving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learning
 
Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...
 
Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...
 
Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...
 
Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...
 
A systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyA systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancy
 
Agriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationAgriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimization
 
Three layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceThree layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performance
 
Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...
 
Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...
 
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
 
Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...
 
On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...
 
Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...
 
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
 
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
 

Recently uploaded

AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGSIVASHANKAR N
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 

Recently uploaded (20)

DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 

Modeling of Lightning Strike Events, and it’s Correlational with Power Outages in South-West Coast, Nigeria

  • 1. International Journal of Electrical and Computer Engineering (IJECE) Vol. 7, No. 6, December 2017, pp. 3262~3270 ISSN: 2088-8708, DOI: 10.11591/ijece.v7i6.pp3262-3270  3262 Journal homepage: http://iaesjournal.com/online/index.php/IJECE Modeling of Lightning Strike Events, and it’s Correlational with Power Outages in South-West Coast, Nigeria Melodi A. O.1 , Oyeleye M. O.2 Department of Electrical and Electronics Engineering, Federal University of Technology, P.M.B. 704, Akure, Ondo State, Nigeria Article Info ABSTRACT Article history: Received Nov 1, 2016 Revised Nov 27, 2016 Accepted Jan 5, 2017 This paper aimed to model lightning strike events and evaluate its correlation with power outages in a Nigerian power distribution system. A specified coastal distribution network of southwest Nigeria was selected as a case study. Zone-specific records of cloud-to-ground lightning strikes for 84 months were obtained from the Nigerian Meteorological Agency (NiMet); records of power outage frequencies and durations for 36 months were obtained at the substations of the selected distribution network. Using numerical statistical analysis techniques, lightning activity in the system area were characterized in relative frequency terms, and correlation statistics were evaluated and analyzed for power outages and lightning events on the 11kV, 33kV, and 132kV voltage levels. An analysis of the results shows that the modelled lightning strike events patterns are closely related but the expected frequencies vary from one zone to another; and there is correlation between lightning strike and power outages in the distribution networks, which is strong and positive at the 33 kV and 132 kV circuits. In essence, the results provided salient information, useful for power systems lightning protection review, management and planning in the area. Keyword: Lightning strike Cloud-ground flash Coastal power grid Power outage Power outage duration Power outage frequency Correlation Relative intensity Metrological zones Lightning protection Copyright © 2017 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: Melodi A.O., Department of Electrical and Electronics Engineering, Federal University of Technology, Akure, PMB 704, Nigeria. Email: melodiadegoke@yahoo.com 1. INTRODUCTION Power system unavailability index in Nigeria is high, especially at the distribution systems. An alleged contributor to this is lightning activity or atmospheric electric discharges during thunderstorms. Over the years, numerous instances of damage to (critical) equipment were reported across a wide spectrum of systems, networks and applications in Nigeria due largely to occurrences of intense lightning activity. Generally, this study juxtaposes the lightning activity data and the power outage problem in order to establish and evaluate the links between the two in statistical and technical terms. Theoretically, lightning strike (LS) is characterized by currents in terms of kA and ultra high temperatures. Though lightning flashes occur in the clouds, the flash between cloud and ground (LS) pose a greater challenge to PS safety. According to [1], lightning discharges are characterized by short duration of high electric voltage and current pulses. Also, lightning event is arbitrary, unpredictable and can strike anywhere on earth with current value that could exceed 40kA, induce temperature up to 50,000 degrees Fahrenheit, and move at speed closing to 33% speed of light [1],[2]. Lightning is the transient passage of electrical current between a cloud and either the surface of the earth, another cloud, or an object in or near a cloud. Lightning is most commonly associated with thunderstorms and can occur at any time and can strike anywhere on the earth surface [1],[3],[4]. According to [5], primarily, lightning occurs either within a large
  • 2. IJECE ISSN: 2088-8708  Modeling of Lightning Strike Events, and it's Correlational with Power Outages .... (Melodi A.O.) 3263 cumulonimbus cloud (cloud-to-cloud, C-C) or between the cloud-to-ground (C-G); secondarily, it occurs from ground-to-sky (G-S). In [6], thunder storm occurrence is considered as varying with location. If these lightning pulses are not effectively discharged to the ground, they usually result in loss or damage of valuable equipment or power systems, and even loss of human life. Such objects are protected by installing protective devices that arrest LS either directly or indirectly based on principles of atmospheric electrostatic discharges and surge modification. The C-G has the greatest effects on electrical systems and its statistics of occurrence, correlation with power outages on coastal power distribution systems are the scope of this study. Lightning strikes, especially C-G, has continued to be subject of studies in different locations and conditions as depicted in [2],[5],[7]-[9]; especially as it impacts protective grounding designs and locations; empirical intensities, physical processes in different geographical locations have been the foci. These mostly location specific foci and approaches are particularly central for sub-saharan Africa studies, where dependence on foreign models and technologies are predominant. An earlier study on Nigeria southwest coast, [5], reported on C-G lightning strike frequency with respect to periods of the year, which was generalized for the entire southwest coast without consideration for subregion-specific data. Also, there were no specific relations established with respect to power supply and installations. However, it was assumed that lightning related faults would be expectedly high during the peak periods of lightning events in the year. Lightning data is relevant for evaluation of the performance of protection designs [10]; and can also be used to generate variation of annual lighting stroke frequency and annual variation of number of thunderstorm day [11]. These are applicable to power systems objects and location considered in this paper; owing to the huge costs of equipment and power failures and danger on 11-132kV power lines, protective devices on power installations need to be evaluated in terms of standard requirement and efficacy. The coastal regions of Nigeria are subjected to thunderstorms originating from Atlantic Ocean currents, hence they are all prone to intense lightning activities, 15 flash/km2 /yr [5], [12]. Lagos State of Nigeria is located in the southwest coast at 6°35′N 3°45′E; and its land area is 3474km2 [13]. Based on LS data from Nigeria Meteorological Agency (NiMet), the State is divided into three zones: Marine (Victoria Island, Lekki, Epe and Ikorodu towns; over 2,000km2 ), Lagos Roof (Mainland; 19km2 ), and Ikeja (46km2 ) zones. Thes zones are denoted Z1, Z2, and Z3 respectively. Figure 1 presents a sketch of Southwest coast or Lagos region showing the three metrological zones. In addition, Lagos State consumes 43-52% of the National power company’s power output [14]. It is distinctly marked by the relatively high density of infrastructure comprising HV power transmission substations, heavy industries, numerous communication networks, the sea and reports of residents on damage to appliances due to lightning strike in this region. Figure 1. A Sketch of Southwest Coast showing three Metrological Zones (Z1-Z3) 50 km 30000 0 68000 42000 Z 1 Z 3 32000 34000 36000 38000 40000 66000 64000 62000 Z1 Z2 Z3 Atlantic Ocean
  • 3.  ISSN: 2088-8708 IJECE Vol. 7, No. 6, December 2017 : 3262 – 3270 3264 Consequent on the above, this study aimed to model C-G LS events for the coastal region using new data, and to to evaluate the correlation of LS events and power outage in the 11-132kV distribution systems of Nigeria using specified installations in Z1 of the coastal region as case study. For the purpose of this study, Z1’s Ikorodu Transmission Substation (ITS) and distribution substation (IDS) records were applied. Figure 2 illustrates connection structure of 11–132kV systems and exposure to thunderstorms in the region. The ITS, commissioned in 1976, feeds three 132kV delivery stations in the zone including the IDS. The IDS feeds the township distribution networks. Over a period of 35 years, the ITS capacity grew from 2 x 15MVA (1976) to 3 x 60MVA (2011). The ITS shares 220MW among its average 400MW power requirement by its customers. The IDS feeds 13 lines with 684x11/0.4kV distribution transformers (DTs) and 5 lines with 10x33/11kV substations. The power supplied grew from 20MW (2007) to 30MW (2010) and 55MW (2012). From the operators’ experiences, observed problems include frequent tripping of feeders, lightning events and faults (particularly recent serious instances), falling of tree on line pole damages, earthing failures, disc and pot shattering, and transformer damages; transformer damages were severe in wet season than in dry season. This is similar to other cases in the region. Figure 2. Connection Structure of Z1’s Ikorodu Transmission and Distribution Substations Network Revenue from electricity is basically the product of unit energy consumed and kWhr cost of energy. In order to know the approximate monthly revenue that is obtainable from a transmission substation as in Figure 2 and that would be lost due to outage, Equation (1) is applied. Rm = co PdTmavLF = kco PdTaLF = k co (Padd − Psdd )Ta LF (1) where Rm is monthly revenue, ₦; k – time (duration) reduction factor (k=0.083); co –cost of unit energy supplied, ₦/kWhr; Pd – average peak power supplied daily, Tmav – average hr. in a month, Ta –hour in a year (8960), Padd– actual peak demand per day, Psdd peak supply deficit per day, LF is load factor (approx.. 0.9). Monthly revenue loss due to supply deficit or suppressed demand, 𝑅𝐿 𝑚: RLm = kco PsddTaLF, (2) Potential monthly revenue due to actual system demand (Rpot.(m)): Rpot.(m) = Rm + RLm, (3) Rm, RLm, and Rpot.(m) were evaluated for the selected ITS-IDS and shown in Table 1. Surge Diverter Thunder cloud 132kV 132/33kV; 3x60MVA 33/11kV 11/0.4kV Industrial customers To other TS Incoming Lines To other 11kV DTs LV users ITS IDS
  • 4. IJECE ISSN: 2088-8708  Modeling of Lightning Strike Events, and it's Correlational with Power Outages .... (Melodi A.O.) 3265 Table 1. Estimates of 𝑅 𝑚 and 𝑅𝐿 𝑚 (at 𝑐 𝑜=24.08, naira/kWHr) Object Pd MW Ta , hr CO, naira/kWHr Padd, MW Psdd, MW k LF Rm , naira RLm’,naira Rpot.(m), naira ITS 220 8760 24.08 400 180 0.0833 0.9 3,479,130,990.72 2,846,561,719.68 6,325,692,710.40 The RLm value for ITS is approximately 2.85 billion naira. This 45% monthly revenue loss due to prevailing inadequate supply capacity is very large and should not be aggravated by outages due to atmospheric factor as lightning. The cost of 4 x 60MVA transformers alone in 132/33kV substation is ₦1.8 billion. As earlier indicated, the considered coastal regions lie in the tropics and are subjected to intense thunderstorms [5]; consequently, power installations are prone to lightning incidences in the region. Therefore, protection of apparent capital intensive electric power network installations and systems operations reliability will mitigate costs and save huge revenue. 2. RESEARCH METHOD In order to model C-G LS events for the coastal region using new data, C-G LS records (2006-2012) for the specified coastal area were considered and obtained from the Nigerian Metrological Agency (NiMet). A survey of installations shows unavailability of LS counter records. Therefore, to obtain the correlation of LS events and power outage in the 11-132kV systems, outage data for 11-132kV power supply stations and associated lines in a metrological zone of the area (i.e., Z1) were extracted from respective stations’ records; and evaluated for correlation with obtained zonal C-G LS records, using inferential statistical concepts (relative frequency and correlational statistical techniques) [15]. The algorithm was implemented with proprietary MS-Excel software. 2.1. Relative Intensity Statistic Relative intensity of C-G LS for each month of the year was evaluated in terms of relative lightning frequency. Relative lightning frequency for a given zone (z), month (m), and year (y) was defined and evaluated as 𝑅𝐿𝐹𝑚 (𝑍) using: 𝑅𝐿𝐹𝑚 (𝑍) = ∑ 𝑄𝐿𝑆 𝑚,𝑦 (𝑍)7 𝑦=1 ∑ 𝑄𝐿𝑆 𝑦 (𝑍)7 𝑦=1 , (4) where 𝑄𝐿𝑆 𝑚,𝑦 (𝑍) – quantity of C-G LS for given zone, month, and year; and 𝑄𝐿𝑆 𝑦 (𝑍) - quantity of C-G LS for given zone and year. The values for 𝑄𝐿𝑆 𝑚,𝑦 (𝑍) and 𝑄𝐿𝑆 𝑦 (𝑍) were obtained from NiMet records for 2006 to 2012 years. The values obtained for 𝑅𝐿𝐹𝑚 (𝑍) are presented in Figure 3 and analysed. 2.2. Zonal and Monthly Probabilities of C-G LS Event Probability of C-G LS event for a given zone (Z) and month was defined and evaluated as 𝑃(𝑍)(𝐿𝑆 𝑚 > 𝑛) using: 𝑃(𝑧)(𝐿𝑆 𝑚 > 𝑛) = 𝑞(𝑧)(𝐿𝑆 𝑚>𝑛) 𝑞(𝑧)(𝐿𝑆 𝑚) ; 𝑛 = (0, 1, 2) (5) where 𝑞(𝑧)(𝐿𝑆 𝑚 > 𝑛) is quantity of LS events greater than n, and 𝑞(𝑧)(𝐿𝑆 𝑚) – qty. of LS events in month m for the entire data period. Values obtained for 𝑃(𝐿𝑆 𝑚 > 𝑛) are presented in Figures 4 to 6 and analysed for n = (0, 1, 2) and profiles the probability of LS in each of the month of a year for the study zones. 2.3. Zonal and Monthly Average and Range Statistics of LS Events The monthly and annual averages of LS, 𝐴𝐿𝑆 𝑚 and 𝐴𝐿𝑆 𝑌 respectively, were evaluated as in: 𝐴𝐿𝑆 𝑚 = ∑ 𝐿𝑆 𝑚,𝑦 𝑌 𝑦=1 𝑌 ; 𝑌 = 7 (6) where 𝐿𝑆 𝑚,𝑦 -lightning strike events in given month and year y; Y – number of years y in data period. Average annual LS events for the data period:
  • 5.  ISSN: 2088-8708 IJECE Vol. 7, No. 6, December 2017 : 3262 – 3270 3266 𝐴𝐿𝑆 𝑌 = ∑ 𝐴𝐿𝑆,𝑦 𝑌 𝑦 𝑌 ; 𝐴𝐿𝑆 𝑦 = ∑ 𝐴𝐿𝑆 𝑦,𝑚𝑚 (7) where 𝐴𝐿𝑆 𝑦 - average LS event for year y, 𝐴𝐿𝑆 𝑦,𝑚 is average LS for given year and month. Results of 𝐴𝐿𝑆 𝑚, 𝐴𝐿𝑆 𝑦 are presented in Figures 7 to 9. 2.4. Correlation Analysis Of C-G LS And Outage Data Data of power outage durations on 11kV, 33kV, and 132kV lines were extracted from system daily records and summarized for each of the three years. Correlation between these data and corresponding data on C-G LS events were evaluated correlation function as in MS Excel (2013): 𝐶𝑜𝑟𝑟𝑒𝑙(𝑃𝑂𝑦,𝑚, 𝐿𝑆 𝑦,𝑚) = ∑(𝑃𝑂 𝑦,𝑚−𝐴𝑃𝑂 𝑦)(𝐿𝑆 𝑦,𝑚−𝐴𝐿𝑆 𝑦) √∑(𝑃𝑂 𝑦,𝑚−𝐴𝑃𝑂 𝑦) 2 ∑(𝐿𝑆 𝑦,𝑚−𝐴𝐿𝑆 𝑦) 2 (8) where 𝑃𝑂𝑦,𝑚 –power outage for a particular year and particular month; 𝐴𝑃𝑂𝑦 –average power output for corresponding year; 𝐿𝑆 𝑦,𝑚 –Lightning strike for a particular year and particular month. The result is presented in Table 2. 3. RESULTS AND ANALYSIS Results obtained from evaluation of C-G lightning st rike in study location and correlation with power outages on 11-132 kV network are as in Figures 3 to 9 and Table 2. Figure 3 presents monthly RLFs of zones Z1 to Z3 respectively. Figures 4 to 6 present the monthly probabilities of LS in the three mentioned zones respectively. Analogically, Figures 7 to 9 present the monthly and annual LS averages for the same zones. Figure 3. Obtained Monthly RLFs for Zones 1 to 3, Lagos State, southwest coast, Nigeria Figure 3 values for zone Z1 show that LS events can be expected throughout the year. However, the intensity varies: 0-5% of annual total of LS is expected in 5 months of every year: January to March; August to September; and December. These include dry season and rain break months for the region. More LS events are expected April, July, and November. Figure 3 further shows that RLF variation patterns for Z2 and Z3 are similar to that of Z1 but vary in magnitudes. Also, the peak for Z1 comes a month earlier. The highest magnitude is in June; while for the other zones it can be expected in both May and June. Figure 4 to 6 presents monthly probabilities of three categories of LS frequencies: LS>0; LS>1; and LS>2. It is notable in Figure 4 that for zone Z1, the probability of LS event exceeding twice in February, March, August, and September, is nil. Figure 6 shows that zone Z3 has the highest probabilities of higher (>2) LS frequencies for all months. 0.00 0.05 0.10 0.15 0.20 0.25 JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC Rel.Freq month Rel.Freq_zI Rel.Freq_zII Rel.Freq_zIII
  • 6. IJECE ISSN: 2088-8708  Modeling of Lightning Strike Events, and it's Correlational with Power Outages .... (Melodi A.O.) 3267 Figure 4. Monthly Probabilities of LS occurring at least once (LS>0); twice (L>1); and thrice LS>2) in Zone Z1 Figure 5. Probability of LS occurring at least once (LS>0); twice (L>1); and thrice LS>2) in in Zone Z2 Figure 6. Probability of LS occurring at least once (LS>0); twice (L>1); and thrice LS>2) in in Zone Z3 Figure 7 to 9 show that: for zone Z1, ALSm can range from 1 to 7 events per month, with peak expected in June; for zone Z2, ALSm can range from 1 to 6 events, with peak expected in June, July, and September; and for zone Z3, ALSm can range from 4 to 22 events, with peak expected in June and October. Annualy, ALSy can have the following monthly ranges: (11, 27) events, (11,31) events, and (81, 145) events for zones Z1, Z2, and Z3 0.00 0.20 0.40 0.60 0.80 1.00 Probability Months P(LS>2) P(LS>1) P(LS>0) 0.00 0.20 0.40 0.60 0.80 1.00 Probability Months P(LS>2) P(LS>1) P(LS>0) 0.00 0.50 1.00 Probability Months P(LS>2) P(LS>1) P(LS>0)
  • 7.  ISSN: 2088-8708 IJECE Vol. 7, No. 6, December 2017 : 3262 – 3270 3268 respectively. These values ascertained that lightning intensity varies from one location to another location. The seasonality should be considered when planning annual maintenance strategies of protective installations. Figure 7. Monthly Average LS`` strike in Zone Z1 Figure 8. Monthly Average LS strike in Zone Z2 Figure 9. Monthly Average LS strike in Zone Z3 19.1 27.4 10.91.7 0.8 1.5 2.8 6.1 6.5 4.7 0.8 1.0 5.2 2.3 0.6 -1.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 0 5 10 15 20 25 30 jan feb mar apr may jun jul aug sep oct nov dec Year LightningStrike Months Yr. av. Yr. max(av.) Yr. min(av.) Monthly av. monthly min(av.) Monthly max(av.) 20.9 30.5 11.2 0.7 1.6 1.5 2.4 4.3 6.0 6.1 1.4 6.0 3.9 2.0 0.5 -1.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 0 5 10 15 20 25 30 35 jan feb mar apr may jun jul aug sep oct nov dec Year LightningFreq. Months Yr. av. Yr. max(av.) Yr. min(av.) Monthly av. monthly min(av.) Monthly max(av.) 113.1 145.1 81.2 3.6 9.0 14.7 14.8 19.0 20.5 11.5 6.4 12.5 21.6 15.2 5.9 0.0 5.0 10.0 15.0 20.0 25.0 0 20 40 60 80 100 120 140 160 jan feb mar apr may jun jul aug sep oct nov dec Year LightningFreq. Months Yr. av. Yr. max(av.) Yr. min(av.) Monthly av. monthly min(av.) Monthly max(av.)
  • 8. IJECE ISSN: 2088-8708  Modeling of Lightning Strike Events, and it's Correlational with Power Outages .... (Melodi A.O.) 3269 Generally, these values and analyses, depicted by Figures 4 to 10, indicate that C-G LS intensity is significant in the study location and adequate measures should be developed to curtail them for the power installations. This justifies a need to investigate the adequacy of existing LPS installations. Table 2 shows that correlation between C-G LF and power outage duration in zone Z1 (Ikorodu) is: weakly positive for 11kV installations (0.08-0.39); strong and positive for 33kV installations (0.45-0.85); and moderately positive for 132 kV installations (0.3-0.55, in 2012). These values generally show that the relationships between LS and PO are positive linear relationships, being strongest in 33 and 132kV systems. In addition, Table 3 shows that the correlation outcome between C-G LF and outage frequency is equally significant for 33 kV and 132 kV installations. This observation indicates that the existing lightning protective schemes are unreliable and validates a need to evaluate the active efficiency of existing lightning protection schemes on the PDNs in the coastal area, and by extension, Nigeria. Table 2. Correlation for C-G LF and Power Outage Events Duration on 11kV, 33kV and 132kV Systems, 2010-2012 System Correlation Coeffiscients p-values (at alpha = 0.05) Correlation Status and Significance 2010 2011 2012 2010 2011 2012 11kV 0.08 0.23 0.39 0.79664 0.46975 0.21227 weak & insignificant (,,) 33kV 0.45 0.85 0.70 0.13789 0.00050 0.01148 strong positive & significant (,2011,2012) 132kV 0.30 0.47 0.55 0.34148 0.12582 0.06498 moderate positive & insignificant (,,) Table 3. Correlation for C-G LF and Power Outage Events Frequency on 11kV, 33kV and 132kV Systems, 2010-2012 System Correlation Coeffiscients p-values (at alpha = 0.05) Correlation Status and Significance 2010 2011 2012 2010 2011 2012 11kV - - - - - - No data available 33kV 0.93 0.54 0.70 0.000012 0.072539 0.011680 Strong positive & significant(2010,,2012) 132kV 0.36 0.62 0.68 0.252851 0.031330 0.015534 Moderate positive & significant(,2011,2012) 4. CONCLUSION The focus of this paper has been on obtaining model quantitative values and patterns for C-G LS events useful for system design, planning, and maintenance schedules; and to establish a possible correlation with incessant power outages in the specified coastal region, which should be factored-in in the critical search for power outage mitigating measures in present Nigeria systems. From the analyses of the results, it is ascertained that lightning strikes vary from one location or zone to the other. LS events are significantly intense in the studied region and contribute to power outage at 11-132kV installations. Model range values of C-G LS events is (11,145) events per month. 33 kV and 132 kV installations have the highest correlation of outage with LS events in the region. 11kV installations are weakly correlated, indicating that other factors are more salient contributors to outages at this level. Graphical and numerical models of C-G LS events are provided for application in planned LPS installation and maintenance for Nigerian southwest coast. This correlation analyses of lightning events and power outages in 11-132kV networks along Nigerian coast establish the degree of lightning disturbances on power availability and by implication, insight into the effectiveness or adequacy of existing lightning protection scheme in the system. REFERENCES [1] R. Kithil, “Fundamentals of Lightning Protection,” National Lightning Safety Institute (NLSI), 2010. [2] S. N. Nikolovski, et al., “Frequency and Time Response of Power Plant Grounding System Exposed to Lightning Strike,” International Journal of Electrical and Computer Engineering, vol/issue: VI(2), pp. 512-525, 2016. [3] B. S. Ronald, “Consulting on lightning damage or injury, Ph.D Thesis,” 2011. [4] C. E. Dick, “An Analysis of the impact and predictability of lightning strikes in Tallahassee, Florida,” 2011. [5] A. I. Mowete and M. A. K. Adelabu, “Assessment of lightning and other electromagnetic disturbances along the coast of south west Nigeria,” XIX-th International Conference on Electromagnetic, pp. 200-203, 2009. [6] V. Cooray, “The Lightning Flash,” IEE Power and Energy, vol. 34, pp. 574-579, 2003. [7] B. R. P. da Rocha, et al., “Lightning Characteristics Time Distribution over Four Locations in Eastern Amazonia,” in IX International Symposium on Lightning Protection (IX SIPDA), Foz do Iguaçu (Brazil), 2007. [8] J. O. Adepitan and F. O. Ogunsanwo, “Investigating the Relationship between some Thunderstorm Parameters and Ground Flash Density,” The Pacific Journal of Science and Technology, vol/issue: 13(2), pp. 148-150, 2012. [9] C. L. Wooi, et al., “Statistical Analysis on Preliminary Breakdown Pulses of Positive Cloud-to-Ground Lightning in Malaysia,” International Journal of Electrical and Computer Engineering, vol/issue: VI(2), pp. 844-850, 2016.
  • 9.  ISSN: 2088-8708 IJECE Vol. 7, No. 6, December 2017 : 3262 – 3270 3270 [10] F. A. Auditore, “Refurbishment and Upgrading Design Options-lightning Mast VersusOverhead Sheilding Conductor,” in EEA Conference, 2009. [11] S. Yakoyama, “Lightning Detection and LightningProtection of Power System in Japan Panel Paper,” in IEEE PES Transmission and Distribution, Asia Pacific Yakohama, 2002. [12] Geology.com, “World Lightning Map,” 2013. [13] O. Leke and E. Gbenga, “Effects of Global Economy on Spatial Structure of Ikeja, Lagos,” in Department of Urban and Regional Planning, Faculty of Environmental Sciences, University of Lagos, Akoka., Lagos, 2013. [14] I. O. Megbowon and T. O. Oyebisi, “A Reliability Assessment of South West Transmission Lines of the Nigerian National Grid,” FUTAJEET, vol/issue: IV(1), pp. 17-22, 2005. [15] G. Keller and B. Warrack, “Statistics for Management and Economics,” Pacific Grove, USA, Thompson Learning Inc, pp. 832, 2003.