2. Contents
• LED Lighting
• D75 Lighting
• Theatrical
Lighting
• Control Systems
• Switches
• Automatic shades
• 2014 NYCECC
3. Objectives
1. How are we doing? What NGL tells us about the
performance and quality of SCA Luminaires
2. Toward better educational environment for Autistic
Classroom
3. Design code compliant 2014 New York State and
NYC Energy Codes Energy Code
4. Design code compliant Lighting Control relay panel
solutions for automatic sweep off controls.
7. Lights – D75 Classroom
• Current Design • Q335
LED
-Completely indirect (100% up light)
-45W
-Dimmable
-Soft Light (30K)
-Wide Distribution (no hot spots above the
fixture)
-Flicker Free
Regular Classroom
18. Lights – Theatrical Spotlights
• Current Design • Q335
Tungsten
-Adjustable lens beam and spot
-585W – 10,000 Lumens
-Needs different “gels” to add different
colors
-Dimmable via line voltage dimming
-$300
LED
-Adjustable lens beam and spot
-150W – 8,000 Lumens
-Individually programmable with multiple
colors
-Dimmable via low voltage dimming
-$1000
19. Lights – Theatrical Border Lights
• Current Design • Q335
Incandescent
-Fixed lens
-75W per lamp x 4 lamps
-Needs different “gels” to add different colors
-Dimmable via line voltage dimming
-$300/4 lamps fixture
LED
-Adjustable lens beam and spot
-150W
-Individually programmable with multiple colors
-Dimmable via low voltage dimming
-$1000
-Reduced number of fixtures
22. Control System – Classroom
• Current Design
-2 momentary switches
-2 power packs
-one or more vacancy sensor
-lamp “a” and lamp “b”
controlled separately
-no daylight harvesting
- No dimming
-$500
• Poor light quality (over/under-lit areas)!
o Overlighting wastes money!
o Underlighting compromises safety!
• No dimming – creates jarring shifts in light levels!
• Circuit-level controls not granular enough for
savings or performance requirements!
24. Control System – Classroom
• Q335
• Automatic assessment of ambient light!
• Gradual (imperceptible) adjustment!
• No jarring shifts in light levels!
• Consistent light levels across facility!
• No under-lit/over-lit areas!
-one dimming switches
-one controller for two or four
classrooms
-one or more vacancy sensor
-entire fixture work as one unit
-daylight harvesting
-smooth dimming
-$500
25. Ceiling Motion Sensor + Power Pack + Manual on Switch
• Manual On – Auto Off
• Manual off switch
4 Walls 1 Door up to 900 sq ft
Occupancy Sensor Switch – Line Voltage
• Manual On – Auto Off
• Manual off switch
4 Walls 1 Door up to 3 Light fixtures
Areas controlled by an occupant-
sensing device (O.S.Space)
26. 1. Three rows of fixtures
2. Dimming switching
3. Vacancy sensing
4. Day light harvesting
5. Automatic Shade
D75 Classroom
27. Control System - Relay Panel
• Current Design • Q335
36 Circuit Relay Panel
-One relay per each circuit in the lighting
panel
-$1500
24 Circuit Relay Panel
-Selected circuits from the lighting panel.
-Selected circuits from the receptacle panel.
-$1000
28.
29. Control System - Theatrical Panel
• Current Design • Q335
24 Circuit Dimmer Panel
-Contains dimmer and relay circuits
-DMX cable connect from panel to each
fixture
-$24000
12 Circuit Relay Panel
-Contains only relay circuits
-DMX or 0-10V cable connect from panel to
each fixture.
-$3000
30.
31. Switches
• Current Design • Q335
Two Gang Low Voltage Switch
-on/off
-two per classroom
-Each switch controls one lamp in row of
fixtures
-Switches communicate with local sensors
in room
-$150
One Gang Low Voltage Dimmer Switch
-on/off, up/down and preset
-one per classroom
-Switch controls dimming of all fixtures in room
with a preset level set in the middle
-Switch communicates with local control panel
connected to local sensors in room.
-$175
33. C402.3.1
Building Envelope Requirements
C402.3.1 Maximum area.
The vertical fenestration area (not including opaque doors
and opaque spandrel panels) shall not exceed 30 percent of
the gross above-grade wall area.
C402.3.1.1 Increased vertical fenestration area with
daylighting controls.
In Climate Zones 1 through 6, a maximum of 40 percent
of the gross above-grade wall area shall be permitted to be
vertical fenestration, provided:
1. No less than 50 percent of the conditioned floor area is
within a daylight zone;
2. Automatic daylighting controls are
installed in daylight zones; and
3. Visible transmittance (VT) of vertical fenestration is
greater than or equal to 1.1 times solar heat gain coefficient
(SHGC).
< 30% Glazing
IECC 2012 – C402.3.1
◘ Prescriptive:
30% Max OR
40% Max when
▫ >50% Conditioned floor
area in daylight zone
▫ Automatic daylighting
control installed
▫ Certain VT requirements
34. Section 8.4.2
Power - Automatic Receptacle Control
IECC 2012
◘ No requirements
STD. 90.1 – 8.4.2
◘ Mandatory:
50% in offices (private and
open) and computer
classrooms
New York State & NYC
PRECRIPTIVE rather than
mandatory
Section 8.4.2 Power stipulates automatic control
of 50% of receptacles installed in private offices,
open offices and computer classrooms, including
receptacles installed in modular partitions.
50% Switched Load
35. C405.2.2.1
Automatic time switch control devices.
• Automatic time switch controls shall be installed to control lighting in
all areas of the building. ( Except where you have Occ
Sensors )
Many walls
Many doors
Up to 5000 sq ft per zone
36. C405.2.2.3
Daylight zone control.
• Switched separately from non-daylit zones
• Up to 2500 sq ft per zone
• Manual controls are acceptable
C405.2.2.3.1 Manual daylighting controls.
Manual controls shall be installed in daylight zones unless automatic controls are
installed in accordance with C405.2.2.3.2 Automatic daylighting controls.
(C405.2.2.3.2 Continuous dimming or multilevel switching)
37. 505.2.2.1
Light Reduction Controls
IECC 2012
◘ Three Categories:
1. Dimming device controlled
space (reduced illumination
by at least 50%)
2. Occupant- sensing devise
controlled space.
3. Automatic time switch
controlled space
(corridor/lobbies, storerooms
and restrooms)
>50% Reduced illumination
1
2
3